Upload
norman-andrews
View
238
Download
17
Embed Size (px)
Citation preview
Systems Solution Marketing GroupIndustrial Automation Business HeadquartersYokogawa Electric Corporation
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
System Integration by SIOSApril 22, 2023
Page 2
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
Other aspects of system integration
Other system integration
Page 3
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
Current solutions for system integration
FIO modules with subsystem communication software– To support Modbus RTU/TCP and other
proprietary popular protocols
GSGW (Generic Subsystem GateWay) station– The GSGW employs the standard OPC
interface and serves as a platform to integrate the CS 3000 operation with subsystems.
– Supports only data accessBoth solutions provide subsystem data integration
Page 4
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
System configuration with GSGW
PRM
GSGW
ENG
FCS
HIS
PLCOPC Server
OPC-DA
Field network
Page 5
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
Requirements for the current GSGW solution
To support A&ERedundant configuration as standardTo increase the data numberEasy engineering– Converting tags from other systems into
CENTUM format, without control logic configuration
R3.06 provides a new system integration interface,
SIOS (System Integration OPC client Station)SIOS is a large-volume, high-performance system
integration station based on OPC.
Page 6
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS outline
What benefit can be provided?– Tighter integration with other control systems.– Not only process data, but alarm and
messages are also integrated.– Excellent integration tool for integration with
competitors’ control systems.
What is the positioning of SIOS?– Communication FIO modules are for
subsystem interface by dedicated driver basis.– GSGW is a subsystem interface by OPC.– SIOS is used for system integration by OPC.
Page 7
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
What is different between GSGW and SIOS?
Functions GSGW SIOS
Data communication
Data collection Available Available
Data setting Available Available
Message handling N/A Available
Capacity 4,000 100,000
Function block Available N/A
Max. number of OPC servers
DA 4 16
A&E N/A 16
Redundancy Tokuchu Standard*
*:Supports only Vnet/IP-based systems (future plan)
Page 8
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS specifications
General specifications– Hardware platform: Generic PC with VI701/VF701– OS: Windows 2003 server* or
Windows XP professional SP2– Software package: LBC2100 system integration
OPC client package– OPC server
• OPC DA2.0 custom interface• OPC A&E1.10 custom interface
– Capacity• 16 OPC servers/SIOS (DA:16, A&E:16)• Data volume: 100,000 data/SIOS
– Performance: approx. 4,000 data/sec. *: For server PC
Page 9
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
System configuration with SIOS
PRM
SIOS
ENG
FCS
HIS
OPC Server
OPC-DA
OPC-A&E
Other System
s
Page 10
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS operation 1
Data access– Data exchange between CENTUM tags and
OPC data by item ID.
Message handling– A&E server alarm and event messages are
converted into CENTUM messages for HIS.– SIOS’s own system alarms are transmitted
to HIS.
Status display– HIS monitors SIOS status and displays it on
the system status window.
Page 11
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS operation 2
Data display on HIS windows – Process data via SIOS displays
• On the standard windows (graphics, trend*, tuning, face plate, process report and group displays).
• A special data display window for SIOS is newly designed.
– A&E messages are displayed on the message monitor window (alarm and historical message).
Message monitor window System configuration window
Page 12
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS operation 3
For digitaldata
For characterdata
Faceplate sample
On SIOS, one OPC data is counted as one tag. – Each data type has special
faceplate for monitoring.– OPC tag from SIOS counted as
CS 3000’s tag.– OPC tag has one data with
data status, and does not have other parameters such as SV,MV,HI,LO.
For analoguedata
Page 13
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS engineering 1
Data configuration for CENTUM– Data generation by browsing OPC data.– Data browsing displays data item names
and A&E alarm filter definitions automatically.
Scope of online loading– OPC server information– Group/data item definitions
• Data update cycle: 500 msec. by default
– SIOS definitions (data cache size)
Page 14
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS engineering 2
Creating a SIOSCreating a SIOS
SIOS definitionSIOS definition
DA Server DA Server definitiondefinition
OPC Group OPC Group definitiondefinition
CENTUM tag CENTUM tag definitiondefinition
Save & LoadSave & Load
Creating a SIOSCreating a SIOS
SIOS definitionSIOS definition
Acquiring OPC Acquiring OPC tag by OPC tag by OPC
browsebrowse
Defining tag by Defining tag by automaticallyautomatically
Save & LoadSave & Load
DA configuration byoffline engineering
Creating a SIOSCreating a SIOS
SIOS definitionSIOS definition
A&E Server A&E Server definitiondefinition
Message filter Message filter definitiondefinition
Save & LoadSave & Load
A&E configurationDA configuration byonline engineering
Page 15
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS engineering 3
Engineering procedure– Create SIOS on the System View.– Add OPC servers and set OPC server
definition items.– Define data assignment.
• For CS 3000, auto data assignment can be done by OPC browse function and auto generation function.
• For other systems, manual data assignment and CSV data import function are provided.
– Download the engineering data to SIOS.
Page 16
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
SIOS engineering 4
Automatic Generation dialog
Main SIOS Engineering dialog
A&E serverDA server
Page 17
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
Future system configuration
PRMENGENG
FFCS-L
HISHIS
OPC Server
Redundant SIOS
Note: Redundant SIOS will support only Vnet/IP and is a future plan.
Other System
s
Page 18
ISD-MASP-S05011Copyright © Yokogawa Electric CorporationFebruary 18, 2005
GOOD SELLING!