EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE ABSORPTION CHILLER KAMARUL ARIFFIN BIN IDRIS UNIVERSITI MALAYSIA PAHANG (UMP)

EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

Embed Size (px)

Citation preview

Page 1: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

ABSORPTION CHILLER

KAMARUL ARIFFIN BIN IDRIS

UNIVERSITI MALAYSIA PAHANG (UMP)

Page 2: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

“I declare that I have read this thesis and in my opinion this thesis is adequate in terms

of scope and quality for the purpose awarding a Bachelor’s Degree of Chemical

Engineering (Gas Technology).”

Signature : ........................................................

Supervisor’s Name : Associate Professor Zulkafli Bin Hassan

Date : ...........................................................

Page 3: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE
Page 4: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

i

EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

ABSORPTION CHILLER

KAMARUL ARIFFIN BIN IDRIS

A thesis submitted in fulfilment of the

Requirement for the award of the degree of

Bachelor of Chemical Engineering

(Gas Technology)

Faculty of Chemical and Natural Resources Engineering

University Malaysia Pahang (UMP)

MAY, 2008

Page 5: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

ii

I declare that this thesis entitled ‘Effect of ammonia/water ratio in the performance

absorption chillers’ is the results of my own research except as cited in the references.

The thesis has not been accepted for any degree and is not concurrently submitted

candidature of any other degree.

Signature : ………………………………………

Name : Kamarul Ariffin Bin Idris

Date : 16 May 2008

Page 6: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

iii

Special dedicated to my beloved father, mother and my whole family members

Page 7: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

iv

ACKNOWLEDGEMENT

I owe this thesis to a number of people who has contributed directly and

indirectly to the successful completion of the thesis. Firstly, I would like to thank my

supervisor, Associate Professor Zulkafli Bin Hassan for giving me the opportunity to

work on this interesting project. Their many words of wisdom, scientific insight and

shape criticism, and high ethical standards are especially valuable for the implementation

of this work. I am also grateful for their patience in correcting my thesis and for keeping

the pressure on me to finish the thesis within the time frame.

Further gratitude goes to all our FKKSA lecturers and staff who offer tips, advice

and endless cooperation in this project. To who was involved, you all deserved a sincere

Thank You from me. My fellow postgraduate students should also be recognized for their

support. My sincere appreciation also extends to all my colleagues and others who have

provided assistance at various occasions. Their views and tips are useful indeed.

Unfortunately, it is not possible to list all of them in this limited space. I am grateful to

all my family members.

Page 8: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

v

ABSTRACT

The main objective of this study is to determine the coefficient of performance

(COP) for absorption chillers. By using a reversible Carnot cycle process the optimum

coefficient of performance (COP) and ammonia/water ratio are obtained. Gas Absorption

Refrigeration Unit (Model: RF 10) is a complete laboratory bench top unit for the

demonstration and analyze the performance on effect of ammonia/water ratio in

performance for absorption chillers. In this experiment the refrigerant is anhydrous

ammonia and the absorber is water. The ammonia/water ratios used are in the range of

5% to 30% ammonia in water base on volume percentage in the solution. Assuming the

absorption unit has complete cycle and stable system after 8 hours and the performance

of the absorption chillers unit is constant for each experiment the value of coefficient of

performance COP is calculated for each hour depending on the refrigerant/absorber ratio.

Then, the graph for value of coefficient of performance (COP) verses time (hour) is

plotted and analyzed. The COP increased with increasing generator temperature and with

decreasing absorber and condenser temperatures for all the systems. Also, the lowest

temperature at the evaporator is important in order to control the temperature for all the

system cycle that affects the value of COP in absorption chillers. In conclusion, the

optimum ammonia/water ratios that obtained in this experiment are 30% ammonia purity

with 2.97 coefficient of performance.

Page 9: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

vi

ABSTRAK

Tujuan utama penyelidikan ini ialah untuk menentukan nilai akan prestasi yang

alat penyerapan kesejukan. Dengan menggunakan proses yang dapat berbalik Carnot

jumlah maksimum nilai akan prestasi dan nisbah ammonia/air dapat diketahui. Selain itu,

unit gas penyerapan kesejukan (Model RF 10) ialah alat makmal yang sesuai digunakan

untuk menunjukkan dan menganalisis kesan nisbah ammonia/air kepada alat penyerapan

kesejukan. Dalam penyelidikan ini ammonia bertidak sebagai bahan penyejuk manakala

air sebagai bahan penyerap. Nisbah ammonia dan air yang digunakan adalah diantara 5%

hingga 30% ketulenan ammonia mengikut peratusan isipadu larutan. Tambahan pula,

dengan beraggapan alat penyerapan membuat kitaran lengkap dan sistem yang stabil

selepas 8 jam serta, prestasi alat penyerapan kesejukan sama pada setiap penyelidikan

nilai akan prestasi dapat dikira pada setiap satu jam yang bergantung pada nisbah bahan

penyejuk dan bahan penyerap. Kemudian, graf nilai akan prestasi melawan masa (jam)

dilukis dan dianalisis. Nilai akan prestasi akan meningkat sekiranaya suhu alat

pembangkit tenaga bertambah serta penurunan suhu pada alat penyerap dan alat

kondensasi. Juga, suhu yang rendah pada alat penyerap penting untuk mengawal suhu

pada keseluruhan sistem yang mempengaruhi nilai untuk prestasi alat penyerapan

kesejukan. Sebagai kesimpulan, jumlah maksimum nilai untuk prestasi nisbah

ammonia/air adalah pada 30% ketulenan ammonia dalam larutan dengan nilai 2.97 nilai

untuk prestasi.

Page 10: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

vii

TABLE OF CONTENTS

CHAPTER TITTLE PAGE

TITLE PAGE i

DECLARATION OF ORIGINALITY

AND EXCLUSIVENESS ii

DECLARATION iii

ACKNOWLEGEMENT iv

ABSTRACT v

ABSTRAK vi

TABLE OF CONTENT vii

LIST OF SYMBOLS ix

LIST OF ABBREVIATION x

LIST OF FIGURES xi

LIST OF TABLE xii

1 INTRODUCTION

1.1 Background of study 1

1.2 Problem statement 2

1.3 Objective of study 3

1.4 Scope of research work 3

2 LITERATURE REVIEW

2.1 Introduction 4

2.3 Problem with ammonia/water absorption 4

chiller

2.2 Improvement absorption process 5

Page 11: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

viii

2.3 Refrigerant and absorber study 10

2.4 Application 12

3 ABSORPTION CHILLER SYSTEMS

3.1 Background 14

3.2 General description 15

3.3 Type of absorption chillers 17

2.3.1 Double effect absorption chillers 17

2.3.2 Triple effect absorption chillers 19

2.3.3 Hybrid system absorption chillers 20

3.4 Lithium bromide/water absorption chiller 20

3.5 Ammonia/water absorption chiller 22

3.5.1 Availability and costing 22

3.5.2 Thermodynamic properties 23

3.5.3 Heat transfer coefficient (W/m.K) 23

3.5.4 Advantages of the system 24

3.5.5 Disadvantages of the system 26

3.6 The previous work in improving COP for 26

absorption chiller unit

3.6.1 Heat integration 27

3.6.2 Additive 27

3.6.3 Solar Application 27

3.7 Environmental issues 28

3.8 Efficiency 30

4 METHODOLOGY

4.1 Introduction 32

4.2 Overall experimental work 32

4.3 Sample preparation 34

4.4 Purging and refilling procedures 34

4.5 Experimental procedures 38

Page 12: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

ix

4.5.1 Start-Up Procedures 38

4.5.2 Troubleshooting procedures 39

4.5.3 Shut-Off Procedures 39

4.5.4 Maintenance Procedures 39

4.5.5 Data collection 40

4.6 Method of analysis 42

5 RESULTS AND DISCUSSION

5.1 Result 43

5.2 Discussion 46

6 CONCLUSION AND RECOMMENDATION

6.1 Conclusion 48

6.2 Recommendation 49

REFERENCES 50-53

Appendices 54-68

Page 13: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

x

LIST OF SYMBOLS

g - Gram

L - Liters

ml - Milliliters

Q - Heat transfer

S.G. - Standard gravity

T - Temperature

W - Work

η - Efficiency

Page 14: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

xi

LIST OF ABBREVIATION

COP - Coefficient of performance

CFC - Chlorofluorocarbon

CHP - Combine Heat Power

DCC - Double condenser couple

HFMAE - Hollow fiber membranes absorber heat exchanger

PHEFFA - Plate heat exchanger falling film type absorber

DACM - Diffusion absorption cooling machine

VAR - Vapor absorption refrigeration

CGS - Co-generation systems

HFC - Hydro fluorocarbons

HCFC - Hydro chlorofluorocarbons

ODP - Ozone depleting potential

GWP - Global warming potential

Page 15: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

xii

LIST OF FIGURE

FIGURE NO. TITLE PAGE

3.1 Faraday’s experimental apparatus 15

3.2 Process flow diagram for the gas absorption refrigeration system 16

3.3 Double effect absorption refrigerant system 18

3.4 Triple effect absorption refrigerant system 19

3.5 Diagram of two-shell lithium bromide/water absorption chiller 21

4.1 Flow chart of overall experimental work 33

4.2 Apparatus for purging and refilling ammonia solution in 35

absorption vessel

4.3 Absorption chiller position for purging existing solution 36

4.4 Absorption chiller position for refilling procedure 37

4.5 Ammonia solution pour to absorption vessel 37

4.6 Temperature indicator of absorption chiller unit 40

4.7 Front view of absorption chiller system 42

5.1 Graph cooling box temperature oC vs. ammonia purity (%) 44

5.2 Graph coefficient of performance vs. time (hour) 46

D1 Back view of absorption chiller system 68

D2 Figure D2: Open and close refilling point 68

Page 16: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

xiii

LIST OF TABLE

TABLE NO. TITLE PAGE

3.1 Ammonia refrigerant requires a smaller displacement compressor 23

for the same output compared to other refrigerants

3.2 Heat Transfer Coefficients (W/m2 K) of ammonia and HCFC 22 24

3.3 Ozone Depletion Potential (ODP) and Global Warming Potential 29

(GWP) of Common Refrigerants (Wang 2001)

4.1 Total volume ammonium hydroxide (30%) needed in preparation 35

500 ml sample solution

4.2: Temperature (oC) each indicator for ammonium hydroxide (5%) 41

5.1 Ammonia purity (%) and cooling temperature (oC) 43

5.2 Coefficient of Performance (COP) values for each 44

ammonia purity (%)

C1 COP for 5% ammonia purity 63

C2 COP for 10% ammonia purity 64

C3 COP for 15% ammonia purity 64

C4 COP for 20% ammonia purity 65

C5: COP for 25% ammonia purity 65

C6: COP for 30% ammonia purity 66

Page 17: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

1

CHAPTER 1

INTRODUCTION

1.1 Background of study

The absorption cycle is a process by which refrigeration effect is produced

through the use of two fluids and some quantity of heat input, rather than electrical input

as in the more familiar vapor compression cycle. Both vapor compression and absorption

refrigeration cycles accomplish the removal of heat through the evaporation of a

refrigerant at a low pressure and the rejection of heat through the condensation of the

refrigerant at a higher pressure. The method of creating the pressure difference and

circulating the refrigerant is the primary difference between the two cycles. The vapor

compression cycle employs a mechanical compressor to create the pressure differences

necessary to circulate the refrigerant. In the absorption system, a secondary fluid or

absorbent is used to circulate the refrigerant. Because the temperature requirements for

the cycle fall into the low-to-moderate temperature range, and there is significant

potential for electrical energy savings, absorption would seem to be a good prospect for

geothermal application. [1]

Absorption machines are commercially available today in two basic

configurations. For applications above 32oF (primarily air conditioning), the cycle uses

lithium bromide as the absorbent and water as the refrigerant. For applications below

32oF, an ammonia/water cycle is employed with ammonia as the refrigerant and water as

the absorbent. [1]

Page 18: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

2

Most commercial and industrial refrigeration applications involve process

temperatures of less than 32oF and many are 0oF. As a result, the lithium bromide/water

cycle is no longer able to meet the requirements, because water is used for the

refrigerant. As a result, a fluid which is not subject to freezing at these temperatures is

required. The most common type of absorption cycle employed for these applications is

the water/ammonia cycle. In this case, water is the absorbent and ammonia is the

refrigerant. [2]

Use of water/ammonia equipment in conjunction with geothermal resources for

commercial refrigeration applications is influenced by some of the same considerations

as space cooling applications. Because most commercial and industrial refrigeration

applications occur at temperatures below 32oF, required heat input temperatures must be

at least 230oF. It should also be remembered that the required evaporation temperature is

10 to 15oF below the process temperature. For example, for a +20oF cold storage

application, a 5oF evaporation temperature would be required. [1]

The performance of the absorption chiller define base on efficiencies of

absorption chillers are described in terms of coefficient of performance (COP), which is

defined as the refrigeration effect, divided by the net heat input (in comparable units such

as kBtu). [2]

1.2 Problem statement

Absorption chiller systems have greater resource efficiency than similar

compressor systems and electric system. Only about 5% to 10% of the fuel resource is

lost with an absorption chiller system. Additionally, electricity costs per Btu are typically

three to four times the cost per Btu for electricity, so the cost of a unit of output

(refrigeration) can often be lower with an absorption unit. Utilizing waste heat that would

otherwise be unused greatly increases the cost-effectiveness of the systems, compared to

Page 19: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

3

consuming gas directly. The absorption system is the used of non-ozone depleting and

low global warming potential working fluid pair, the most common of which is

ammonia-water. [2]

The disadvantage of ammonia/water absorption system is the temperature at

evaporator is high compare to compression system and electric system. To ensure the

absorption system can be competitive with compressor system, the effect of

ammonia/water ratio to the temperature at evaporator of absorption chiller is studied and

the efficiency of the system can be improved. Also, the coolest temperature at evaporator

is important in order to control the temperature of the system

1.3 Objective of study

The objectives of this research are to study the effect of ammonia/water ratio to

the coefficient of performance (COP) for absorption chiller system. By calculating the

COP value for every ammonia/water ratio that use in absorption chiller, the optimum

refrigerant/absorbent that give optimum performance and efficiency can be measured.

1.4 Scope of research work

The ammonia/water ratio uses in this study are in the rage of 5% - 30% ammonia

in water based on volume percentage in the solution and the coefficient of performance

(COP) is calculated using a reversible Carnot cycle process of absorption chiller as the

main scope of this research. Gas Absorption Refrigeration Unit (Model: RF 10) is a

complete laboratory bench top unit for the demonstration of gas absorption refrigeration.

The unit is a continuous absorption refrigeration system operated by application of a heat

source either electrically or furnished by fuel gas.

Page 20: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

4

CHAPTER 2

LITERATURE REVIEW

2.1 Introduction

This chapter is explained about all the improvements to the problem of

ammonia/water absorption chiller unit that have been done by other researchers. The

improvement processes are including simulation and experimental study to increase the

performance of main components of the absorption chiller unit. The effect of working

fluids in absorption chiller unit and latest application of the ammonia/water system also

discuss in this chapter.

2.2 Problem with ammonia/water absorption chiller

Lazzarin et al. (1996) analyzed of a large amount of data on the failures of

absorption refrigeration machines of the ammonia water type was carried out. The data

derive from the records of a 10-year maintenance contract under which every machine

was installed. The records were computerized for the period 1989-1992, and they refer to

sales starting from 1980 (i.e. to 73 778 machines). The failures are classified, identifying

the most serious (generator and solution pump). The rate of early failures is rather high,

but the failures are generally minor and easily repaired. The production quality was not

constant, with a very bad year in 1984. The failure rate is evaluated for the first 10 years

Page 21: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

5

of life of the equipment. In general terms, one machine in two does not require any

intervention during that period. [7]

2.3 Improvement absorption process

Swinney et al. (2000) published the use of composition with the mixed refrigerant

to achieve a temperature lift has been examined. It has demonstrated theoretically how

this may be achieved by using a series of equilibrium stages with counter current

vapor/liquid contacting. These stages could be arranged in column format. A simple

graphical analysis of the system along the line of a McCabe-Thiele construction for

distillation has been presented for the case of a binary mixture. The possibilities of

integrating the column into a closed cycle have been examined, along with the practical

implications of this in term of energy requirement. Performance is shown to be

comparable to conventional absorption refrigerant unit bearing in mind the possibility of

recovering much lower level heat. The designer has considerable flexibility over the use

of shaft power and recovered low level heat. Like all absorption refrigerant based

systems, the new cycle is best suited to situations where waste heat at low temperature is

readily available. [8]

Ezzine et al. (2004) developed a thermodynamic simulation model of an

ammonia–water double effect, double-generator absorption chiller. The limits of the

various operating parameters are given on the basis of the fundamental data. Simulation

enabled the study of the influence of the various operating parameters on chiller

performance. An analysis of the Second Law of Thermodynamics was applied to

quantify the irreversibility of each component. Results indicate that the absorber, solution

heat exchangers, and condenser have the greatest potential to improve the chiller’s

energy efficiency. Also they indicate that focusing on irreversibility is a more direct way

of analyzing the potential for improving the efficiency of an ammonia–water absorption

chiller. [9]

Page 22: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

6

Matthew (2005) reported a micro channel heat and mass exchanger was tested as

a disrober for application in an ammonia water absorption heat pump in this study. The

experiments were conducted to investigate the effects of solution flow rate, vapor

fraction and glycol/water flow rates on the heat and mass transfer performance. A model

was developed to predict the performance of the heat and mass exchanger on a segmental

basis through the disrober. This model used heat transfer correlations and the heat and

mass transfer analogy to estimate heat and mass fluxes on a segmental basis in the heat

and mass exchanger. A parallel resistance network as well as knowledge of the segmental

heat duty was used to estimate the fraction of wetted tube area in each segment. The

experiments indicated that the solution flow rate has the largest impact on the overall

heat transfer coefficient of the disrober. The overall heat transfer coefficient ranged from

388 to 617 W/m2-K and the solution side heat transfer coefficient ranged from 659 to

1795 W/m2-K over the solution flow rates tested. The segmental analysis of the process

revealed that the wetting ratio of the tubes is a major determining factor in the

performance of the disrober. Previous work on this geometry had shown that wetting

fractions as low as 20-30% were limiting the performance. The model in this study

indicates that the average wetting ratios ranged from 25-69%. This increase in wetting

ratio is most likely due to the new fluid distribution system used in this study. To further

reduce the negative effects of incomplete wetting, it is recommended that the vertical

height of the disrober be limited. By limiting the height of the disrober, and increasing

the horizontal dimensions of the disrober to maintain adequate heat transfer area, the

wetting fractions can be maximized. While increasing the horizontal dimensions of the

heat and mass exchanger will reduce the flow rate per length of tube, the lowered heat

transfer coefficient resulting from the lower Reynolds number will be offset by the

advantages of maintaining a higher wetting ratio over a larger portion of the heat and

mass exchanger. The model also revealed that rectification of the vapor stream occurs in

the upper segments of the disrober. The result of this is a vapor stream with a very high

concentration of ammonia, requiring the actual rectifier to be much smaller than would

otherwise be necessary with a co-flow disrober design. This geometry is ideally suited

for the indirect firing of a disrober, for example, in waste heat recuperation for

cooling.[10]

Page 23: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

7

Byongjoo Kim, and Jongil Park (2006) proposed paper a lumped-parameter

dynamic model of a single-effect ammonia water absorption chiller is developed based

on the conservation of mass, momentum and energy. Ordinary differential equations are

derived and the constitutive relations are solved numerically. The dynamic two-phase

thermal-hydraulic characteristics and system performance are investigated during the

start-up operation of a 10.5 kW absorption chiller. The parameters considered are the

bulk concentration and the mass of the ammonia water solution filled, the volume of key

components, and the stepwise turn-up and turn-down of the flue gas flow rate during the

primary stage of the start-up period. The time constant decreases as the bulk

concentration of the solution increases. The mass of the solution filled should be small

for rapidly attaining its rated cooling capacity. Larger volume of generator results in a

smaller time constant. Optimum levels on the volume of generator, the bulk

concentration and the mass of the solution filled for attaining the maximum cooling

capacity exists. The best combination of these parameters for the shortest time constant

without damaging the cooling capacity very much is a low mass of the solution of a

stronger concentration contained in a larger generator. However, it is not easy to satisfy

the optimum condition and the time constant is still too large. Therefore a simple and

practical control strategy for markedly decreasing the time constant is a stepwise turn-up

and turn-down of the flue gas flow rate during the primary stage of the start-up period.[11]

Junghui Chen et al. (2006) studied an innovative hybrid absorber heat exchanger

device using hollow fiber membranes (HFMAE) and mathematical simulation has been

conducted for performance study for application to the ammonia water absorption heat

pump. The device utilizes porous fibers for the heat and mass transfers between the

absorption solution phase and the vapor phase, while nonporous fibers are used to

facilitate the heat transfer between the absorption solution phase and the cooling fluid

phase. Application as a solution-cooled absorber, in-depth comparisons of HFMAE and

plate heat exchanger falling film type absorber (PHEFFA) are conducted by simulation.

Internal profiles, including temperature profiles, composition profiles, heat fluxes and

mass fluxes, are established. The comparisons of fluid phase heat and mass transfer

coefficients of both devices reveal that the vast interfacial area feature of HFMAE is the

Page 24: EFFECT OF AMMONIA/WATER RATIO IN THE PERFOMANCE

8

major reason for achieving higher absorption performance. The sensitivity analyses

indicate that the absorption solution phase mass transfer and the vapor phase heat and

mass transfers are major factors affecting the performance of PHEFFA. However, for

HFMAE, the only significant factor is the absorption solution phase mass transfer. The

utilization of HFMAE as the solution-cooled absorber and the water-cooled absorber in a

typical ammonia water absorption chiller is analyzed. The use of HFMAE is

accompanied by the adjustment of sizes of other components. The vase interfacial area of

HFMAE allows the system operation to be more closely approaching the thermodynamic

equilibrium. The energy efficiency is hence improved through the reduction of the flow

rate of circulating lean absorption solution. The flow rate reduction is 43%. The increase

in COP attended is 14.8% and the reduction in overall system energy loss attended is

26.7%. Although the performance of using HFMAE has been investigated in this paper

by mathematical simulation, further confirmation of the feasibility of HFMAE by

experimental study is essential. The applicability of the existing heat transfer and mass

transfer correlations of hollow fiber membrane modules for the condensation or

evaporation of binary mixtures requires further experimental investigation. HFMAE can

also be considered for using as other mass transfer components in the absorption heat

pump, including rectifier and generator. However, due to the polymer material constraint,

the application of HFMAE for rectifier or generator is only feasible when the operating

temperature is lower, such as in the solar-driven systems. [12]

Jakob, and Eicker (2006) published result of solar thermal driven or assisted

absorption cooling machines are gaining increasing importance due the continually

growing demand for air-conditioning in residential houses as well as office and hotel

buildings. Considering these circumstances, the Stuttgart University of Applied Sciences

has developed and set up three single-effect hot-water driven, solar powered diffusion

absorption cooling machine (DACM) each with a design cooling capacity of 2.5kW. The

first prototype showed that the value of COP range from 0.1 to 0.2, and the evaporator

cooling capacity could reach 1.5kW. However, the auxiliary gas circulation of the first

prototype was not high enough, leading to fast saturation of evaporated ammonia. The

second compacted prototype showed stable and continuous temperature and pressure