AMST1 GB EN 9711A

ReznorOctober 03

AS1

Warm Air HeaterControl Panel

Page 2: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

I N D E X

1. Introduction

2. Technical Data

3. Specifications

4. Siting

5. Installation

6. Description and Method of Operation

7. Setting of Time Switches

8. Commissioning and Testing

9. Handling Over to the User

10. Wiring Diagram

2

Page 3: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

1. INTRODUCTION

The control panel is designed for use with a single Reznor warm air unit heater. Thecontroller comprises of an electronic time clock, air sensing thermostat and frost protectionthermostat, a Heat/Vent/Off switch – giving ‘fan only’ operation on air heaters and ‘heatingoff’ facilities (except for frost protection for use during holidays etc.), LockoutIndication/Reset switch and a Clock override function.

Note : Lockout Indication/Reset optional connection for use with automatic ignition unitsonly.

2. TECHNICAL DATA (Dimensions)

3

Page 4: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

3. SPECIFICATIONS

3.1 General

Electrical Supply Requirement 240V 50Hz, Fuse 3AHeat/Vent Switch Loading 240V ac 10A (resistive) 3A (inductive)Ambient Temperature Range -5 to 55°COperating Temperature Range 0-30°CThermostat Loading 240V ac 10A(resistive) 2.5A (inductive)Power Indicator Red LEDRun Indicator Amber LED

3.2 Time Switch

Display 7mm LCDProgram Instructions 16 (8 on / 8 off)Shortest Switching Time 1 MinuteBattery Back Up Battery Life Up to Five YearsOverride Constant on, Constant off, soft

Override

4. SITING

4.1 Temperature Sensing

The selection of the correct position for the control panel is particularly important. The unitmust be fitted at a point, which will be generally representative of the heated area.Draughty areas, or areas subjected to direct heat (e.g from the sun, radiators, heateroutlets etc.) or areas where the air movement is relatively stagnant (e.g recesses) are allpositions to be avoided when siting the unit. Ideally, units should be mounted 1.5m fromthe floor.

5. INSTALLATION

IMPORTANT

The structure onto which the controller is mounted must be stable and vibration free.

5.1 Mounting

a) Remove the two cover securing screws on the front of the unit and swing open thedoor away from the base.

b) Offer the unit up to the intended mounting position and mark the location of the topkeyhole slots.

c) For fixing into wood, drill pilot hole to suit No. 8 screws. On masonary, drill hole(No.10) to accept the wall plugs. If the unit is to be fitted to metalwork, use a 5.5mmdrill.

d) Mount the base panel using No. 8 x 1¼” round-headed screws. On metalwork, useM5 machine nuts and bolts or similar.

e) Re-position unit and repeat for remaining two holes.

4

Page 5: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

5.2 Electrical Connections

IMPORTANTWiring external to the unit must be installed in accordance with current I.E.E. Regulationsand any local regulations that apply. Wiring should be contained in conduit, entry for whichis provided on the top right of the enclosure.

Heat/Vent circuits are volt free. The use of the Summer Vent operation is optional andrequires a single wire from terminal 3 in the controller to the heater.

The use of the remote lockout reset (where applicable) is optional and requires a wire fromterminal 4 to the heater. This is a return neutral.

It is important to note that it is not acceptable to provide the main supply to the heater viathe controller. Complete the external wiring in not less than 1.5mm² cable.

NOTE: The mains supply to the controller should be taken from the heater.

CAUTION

a) Insulation test of site wiring must be carried out prior to making connections to aunit. Do not use a Megger once a unit is connected.

b) For continuity test, use only a low voltage instrument e.g Avonmeter set to OHMSrange.

6. DESCRIPTION AND METHOD OF OPERATION

6.1 Heat/Off/Vent

a) In HEAT position, the air heater(s) will operate under control of the time clock andthermostat.

b) In VENT position, the main fan of the heater will run continuously; the temperaturesensing control circuit being immobilised.

c) With the switch in the centre position the heating would be OFF except for frostprotection (for use during holidays etc).

6.2 Thermostats

a) Frost (night set-back) Thermostat

The frost (night set-back) thermostat should be set low (0°C - 5°C) and operatesoutside clock settings.

b) Day Thermostat

The day thermostat is set to the desired occupancy temperature and operatesduring clock settings.

5

Page 6: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

7. SETTING OF DIGITAL TIME SWITCH

Fig. 2 Time Switch

7.1 General

The timer enables 8 ON and 8 OFF switch selections to be made automatically by settingthe day, time of day and selecting the ON and OFF periods required. Features include asoft override function and a permanent ON override or permanent OFF override functions.

7.2 Access to the Program Dial for Time Setting

To gain access to the program dial for time setting, remove the clear plastic cover by liftingoff.

7.3 Setting Day of Week and Time of Day (refer to Fig 2).

To prepare the module for programming, clear the memory by pressing the button marked‘R’. Slide the ‘RUN’ button to the left marked ‘ ’. Press the ‘Day’ button until the blacktriangle indicates the current day of the week. Use the ‘HR’ and ‘MIN’ buttons to set thehours and minutes to the actual time.

Rapid selection can be achieved by continuously holding down the HR or MIN buttons.Slide the ‘RUN’ button back to the centre position.

7.4 Planning a Program

A program is a pair of ON/OFF settings, which will dictate when the heater will switch ON orOFF. Up to 8 ON/OFF settings may be programmed. Odd numbers are program ‘ON’ andindicated by a ‘ ’, even numbers are program ‘OFF’.

Multiple days can be programmed by continuous depressing of the ‘DAY’ button. Thesesettings can be individual days, Monday to Friday, Monday to Saturday, Monday to Sundayor Saturday and Sunday only.

To program slide the ‘RUN’ button to the right marked ‘p’. Using the ‘DAY’ ‘HR’ and ‘MIN’buttons, set the first ON program. Depress the button ‘p’ (situated to the left of the daybutton) to confirm the setting and program 2 will appear. Set the OFF program time andday(s).

Continue until programs are complete. Slide the ‘RUN’ button back to the centre position(there is no need to go through all non-used programs). The clock settings and programsettings are not complete.

6

Page 7: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

7.5 Manual Override

Under normal circumstances the ‘AUTO’ button will be the centre position. There are threefacilities for override.

1. CONSTANT ON Slide the auto button to the left indicated ‘I’. The air heater(s) will operate in a constant on state but de-

pendent on stat temperature.

2. CONSTANT OFF Slide the Auto button to the right indicated ‘O’. The air heaters will not operate unless in a frost condi-

tion.

3. SOFT OVERRIDE Depress button ‘ ’ at any time during a cycle. This willchange the current status to it’s opposite i.e. On to Off.

8. COMMISSIONING AND TESTING

NOTE

Ensure that all external electrical connections have been made and that a mains electricalsupply is provided to the unit.

8.1 Functional Tests

After setting the clock, carry out the following checks :

a) Ensure Heat/Vent switch is set to ‘HEAT’.

b) Set clock program constant override to position ’I’.

c) Turn Day thermostat control clockwise until ‘Heater On’ indicator lights. This willoccur once the thermostat setting exceeds the ambient space temperature.

d) Slide clock programming constant override to position ‘O’. ‘Heater ON’ indicatorextinguishers. Turn ‘Frost’ thermostat clockwise until ‘Heater ON’ indicator lights.Turn ‘Frost’ thermostat anti-clockwise until ‘Heater ON’ indicator extinguishes.

e) Slide clock program override to ‘AUTO’. Press soft override button marked ‘ ’.This will be displayed to LED. ‘Heater ON’ indicator lights. Turn the day thermostatto a low setting. ‘Heater ON’ indicator extinguishes. Press soft override button -‘ ’ disappears from LED.

f) Set ‘HEAT/VENT’ switch to ‘VENT’. Check that the heater fan operates but that theburner is not lit and that ‘Heater On’ indicator does not illuminate.

g) Adjust thermostats (and switch settings on clock) to clients’ requirements. Ensurethat any clock override(s) are re-set to appropriate position to suit program.

7

Page 8: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

9. HANDING OVER TO THE USER

Explain the principles involved in setting up the time switch and demonstrate the operationof the unit.

9.1 Normal Automatic Operation

The clock should indicate the correct current time and day of the week. The ‘Heating ON’indicator will be illuminated when the thermostat is calling for heat and the clock switchingstatus is ‘ON’ (or in ‘constant ON’ or soft override ‘ON’).

9.2 Frost Protection Operation

During the ‘OFF’ periods, the heater will operate when the temperature falls below the frostthermostat setting.

8

Page 9: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

10. WIRING DIAGRAM

NL

34

51

2F

E

G

G. '

HEA

T O

N' L

AMP

CO

MM

ON

(HEA

T/VE

NT)

VEN

TILA

TIO

N C

ON

TRO

L C

IRC

UIT

LOC

KOU

T R

ESET

*LO

CKO

UT

IND

ICAT

ION

*

BR BL O R W Y BR BK

BRBKOBK

BL

BL

BLBL

BL

BR

O

G

BR

YR

BRBK

W

G

BKBRYBL R

W

OBR

- BLA

CK

- YEL

LOW

- BR

OW

N

- RED

- WH

ITE

- OR

ANG

E

- BR

OW

N- B

LUE

G- G

REY

KEY

:

AS1

WIR

ING

DIA

GR

AM

H. F

USE

C

F. 'M

AIN

S O

N' L

AMP

E. L

OC

KOU

T R

ESET

SW

ITC

H

D. H

EAT/

VEN

T/FR

OST

SW

ITC

H

A. T

IME

SWIT

CH

C. F

RO

ST S

TAT

B. R

OO

M S

TAT

VEN

T

DH

EAT

A

1 32

H

2 128 4 37

1 32

B

HEA

TER

CO

NTR

OL

CIR

CU

IT

CO

NST

ANT

FAN

*N

EUTR

ALLI

VE

IMPORTANT WARNING :

WHEN A POWER VENTER FLUE FAN UNIT IS SUPPLIED, DO NOT WIRE AS SHOWN ABOVEBUT USE WIRING CONNECTIONS SHOWN IN INSTRUCTIONS SUPPLIED WITH VENTER.

9

Page 10: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

AMST1 GB EN 9711A

The following pages are a selection of interconnection wiring detailsbetween the heater and the AS1 control panel.

Please refer to the table below to find which interconnection diagramyou need to use.

If the wiring diagram number you need is not listed, please consult theReznor Technical Department.

Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring.

Heater Model Type Heater Wiring DiagramNumber

Refer to InterconnectionDrawing Number

UL and X1000 Series A16---60A, B or C Z16X600AX1000R (Reflex) Series V16---60A Z16X600AUL and X1000 Series A16---61D or E Z16X600AUL and X1000 Series A16—360A or B Z16X300AUL and X1000 Series A16—361D Z16X300A

UA, B & C Series 30000E EMA05-1XA, B, D & E Series 30001E & 30001E/1 EMA05-1XA, B, D & E Series 30001EM EMA05-1XA, B, D & E Series 30002E, /1 & /2 EMA05-1XA, B, D & E Series 30005E & /1 EMA05-1

C4000 Series U16—1A Z16C300AUDSA Series (V3) B16—1B Z16V300B

T2000 & RPV2000 Series C16—61A, B or C Z16T300AT2000 Series C16—61A, B or C Z16T300AUCA Series I16—50A Z16X600AUPA Series H16---1A Z16V300B

10

Page 11: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

546551

14

1

123N 17

2 5 6 9 10

11 30 24

109

Heater terminals

Controls terminals

6542

(* - When aReznor controlpanel is notused)

1 or 3 Phase PermanentMains Supply

Reznor UKTel: 01303 259141Fax: 01303 850002e-mail: [email protected]

Drawing No:Z16X600A-UK

Room

/Duct

thermostat

Fan only facility

Thermistor Room or Duct Sensor

757473

51

J3

J2

4

J2J1 J3

Euroventer 90-6

55

J2J1

76

J3

Other Controls*AS1 Energymizor Mk3

External Controls

52

Heater Wiring For:X1000 & UCA SeriesPermanent PilotSingle Stage

Date: 22.10.03 3 Phase415v 50Hz

1 Phase240v 50Hz

MainsIsolator

Power Supply

J2J1

9 10 12

15

1

2

L1

L2

L3

N

Euroventer 90-6

Notes:1. Remove l ink wires shown dotted.2. Retain/insert l ink wires shown sol id.3. Terminals shown may not be in numerical order. Unused terminals may not be shown at al l.4. 1 Phase supply cable 2.5mm minimum.5. 3 Phase supply cable dependant upon motor rating.6. Controls cables 0.75mm for up to 200 metre run.7. Energymizor Sensor cable 0.25mm (screened)8. Master/s lave cable 0.1mm, bel l wire type (no screen necessary)9. Electrical isolator must be installed within 1 metre of the appliance10. Fuse rating must be suffic iently s ized to handle heater & motor loadings.11. If in doubt contact the Technical Department on T: 01303 259141* Remove only when instal ling a Euroventer

Tim

e control

Legend:

240v240v

240v

LowVoltage

240vL

1

Slave / Master Connections (If Required)

3123

11

Page 12: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

210546551

284123N

109

14

1

17

2 5 6 9 10

11 30 24 13 16 11

PermanentMains Supply

J5*J5*

11 1213

Thermistor Room or Duct Sensor

757473

4

J2J1

76 2328

Heater terminals

Controls terminals

6542

Reznor UKTel: 01303 259141Fax: 01303 850002e-mail: [email protected]

Drawing No:Z16X300A-UK

Room/Duct

thermostat

Lock-out reset

Fan only facility

9

535455

J5* J5*

J2J2J1

Lock-out lamp

(240v)

Euroventer 90-6

52

Other ControlsAS1 Energymizor Mk3

External Controls

51

2

Heater Specification:X1000HSISingle Stage

Date: 22.5.02 3 Phase415v 50Hz

1 Phase240v 50Hz

MainsIsolator

Power Supply

J2J1

2 11 12 13

1

2

L1

L2

L3

N

Euroventer 90-6

Notes:1. Remove l ink wires shown dotted.2. Retain/insert l ink wires shown solid.3. Terminals shown may not be in numerical order. Unused terminals may not be shown at al l .4. 1 Phase supply cable 2.5mm minimum.5. 3 Phase supply cable dependant upon motor rating.6. Controls cables 0.75mm for up to 200 metre run.7. Energymizor Sensor cable 0.25mm (sc reened)8. Master/s lave cable 0.1mm, bell wire type (no screen necessary )9. Elec trical isolator must be installed within 1 metre of the appliance10. Fuse rating mus t be suffic iently s ized to handle heater & motor loadings .11. If in doubt contact the Technical Department on T: 01303 259141* Remove only when ins tal l ing a Euroventer

Time control

Legend:

240v

240v

240vL

1

3115

240v

LowVoltage Slave / Master

C onnections (If Required)

12

Page 13: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

64121165

14

1

213N 17

2 5 611 12

11 30 24

1211

Heater terminals

Controls terminals

8642

(* - When aReznor controlpanel is notused)

PermanentMains Supply

Reznor UKTel: 01303 259141Fax: 01303 850002e-mail: [email protected]

Drawing No: EMA05-1

24v Room

/Duct

thermostat

Fan only facility

Thermistor Room or Duct Sensor

757473

51

J3

J3

4

J2J1 J2

Euroventer 90-6

54

J1

76

J2

Other Controls*AS1 Energymizor Mk3

External Controls

52

8

3 Phase415v 50Hz

1 Phase240v 50Hz

MainsIsolator

Power Supply

J2J1

6 8 9Heater Type:XA, B, D & E SeriesPermanent PilotSingle Stage

Date: 15.10.03

J3

55

2

53

113

15

1

2

L1

L2

L3

N

Euroventer 90-6

3

Notes:1. Remove link wires shown dotted.2. Retain/insert l ink wires shown sol id.3. Terminals shown may not be in numerical order. Unused terminals may not be shown at al l.4. 1 Phase supply cable 2.5mm minimum.5. 3 Phase supply cable dependant upon motor rating.6. Controls cables 0.75mm for up to 200 metre run.7. Energymizor Sensor cable 0.25mm (screened)8. Master/s lave cable 0.1mm, bell wire type (no screen necessary)9. Electrical isolator must be installed within 1 metre of the appl iance10. Fuse rating must be suffic iently s ized to handle heater & motor loadings.11. If in doubt contact the Technical Department on T: 01303 259141* Remove only when ins tall ing a Euroventer

Tim

e control(240v)

Legend:

240v240v

24/240v

LowVoltage

24/240v

Slave / Master Connections ( If R equired)

3123L

5

13

Page 14: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

210546551

14

1

284123N 17

2 5 6 9 10

11 30 24 13 16 11

109

Heater terminals

Controls terminals

6542

Reznor UKTel: 01303 259141Fax: 01303 850002e-mail: [email protected]

Drawing No:Z16C300A-UK

Room/Duct

thermostat

Lock-out reset

Fan only facility

Thermistor Room or Duct Sensor

9

757473

J2

4

J2J1

Lock-out lamp

(240v)

J2J1

76

Other ControlsAS1 Energymizor Mk3

External Controls

2

Heater Specification:C4000 & RHC4000/8000Single Stage

Date: 3.7.02

2328

3 Phase415v 50Hz

MainsIsolator

Power Supply

J2J1

15

1

2

31

L1

L2

L3

N

1 Phase240v 50Hz

Notes:1. Remove l ink wires shown dotted.2. Retain/insert l ink wires shown solid.3. Terminals shown may not be in numerical order. Unused terminals may not be shown at all.4. 1 Phase supply cable 2.5mm minimum.5. 3 Phase supply cable dependant upon motor rating.6. Controls cables 0.75mm for up to 200 metre run.7. Energymizor Sensor cable 0.25mm (screened)8. Master/s lave cable 0.1mm, bell wire type (no screen necessary)9. Electrical isolator must be installed within 1 metre of the appliance10. Fuse rating must be suffic iently s ized to handle heater & motor loadings.11. If in doubt contact the Technical Department on T: 01303 259141 Tim

e control

Legend:

240v240v

LowVoltage

240vL

1

Slave / Master Connections (If Required)

PermanentMains Supply

14

Page 15: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

Heater terminals

Controls terminals

N10346531

14

1

30

N 4 5 6 9

11 17 23 24 13 16

Room/Duct

thermostat

Lock-out reset

Fan only facility

Thermistor Room or Duct Sensor

Reznor UKTel: 01303 259141Fax: 01303 850002e-mail: [email protected]

Drawing No:Z16V300B-UK

910

757473

3

Lock-out lamp

(240v)

J2J1

76

(* - When aReznor controlpanel is notused)

AS1

J1 J2J'

N 3 4 6 9 10

N 32 1 4 28

Heater Wiring For:UDSA (V3) & UPA SeriesOn/Off Burner Control

Date: 22.10.03 Mains Isolator -Must be installed within1 metre of the appliance

Power Supply

Other Controls *Energymizor Mk3

External Controls

N

2928

L

J2J1

15 31

1 Phase240v 50Hz N

L

J'

Notes:

1. Remove link wires shown dotted.2. Retain/insert l ink wires shown solid.3. Terminals shown may not be in numerical order. Unused terminals may not be shown at al l.4. 1 Phase supply cable 2.5mm minimum.5. Controls cables 0.75mm for up to 200 metre run.6. Energymizor Sensor cable 0.25mm (screened)7. Master/slave cable 0.1mm, bell wire type (no screen necessary)8. Fuse rating must be suffic iently s ized to handle heater & motor loadings.9. If in doubt contact the Technical Department on T: 01303 259141

Legend:

Time control

240v

LowVoltage

240v

Reznor

PermanentMains Supply

Slave / Master Connections ( If Required)

1 5L

L

240v

15

Page 16: AS1 - Boiler Manualsboilermanuals.org.uk/boilers/Reznor/AS1 Installation... · 2012-04-15 · Please ignore the sections showing ‘AS1’ or ‘Other Controls’ wiring. Heater Model

210546551

14

1

284123N 17

2 5 6 9 10

11 30 24 13 16 11

109

Heater terminals

Controls terminals

6542

Reznor UKTel: 01303 259141Fax: 01303 850002e-mail: [email protected]

Drawing No:Z16T300A-UK

Room

/Ducttherm

ostat

Lock-out reset

Fan only facility

Thermistor Room or Duct Sensor

9

75

3 Phase415v 50Hz

MainsIsolator

Power Supply

1

2

L1

L2

7473

J2

4

J2J1

Lock-out lamp

(240v)

J2J1

76

Other ControlsAS1 Energymizor Mk3

23

External Controls

2

Heater Specification:T2000HSISingle Stage

Date: 21.5.02

28

J2J1

3115

Notes:1. Remove link wires shown dotted.2. Retain/insert l ink wires shown sol id.3. Terminals shown may not be in numerical order. Unused terminals may not be shown at al l.4. 1 Phase supply cable 2.5mm minimum.5. 3 Phase supply cable dependant upon motor rating.6. Controls cables 0.75mm for up to 200 metre run.7. Energymizor Sensor cable 0.25mm (screened)8. Master/s lave cable 0.1mm, bell wire type (no screen necessary)9. Elec trical isolator must be ins talled within 1 metre of the appliance10. Fuse rating must be suffic iently s ized to handle heater & motor loadings.11. If in doubt contact the Technical Department on T: 01303 259141

Tim

e control

Legend:

240v240v

LowVoltage

240vL

1

Slave / Master Connections (If Required)

L3

N

1 Phase240v 50Hz

16