Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

  • Upload
    vodat

  • View
    216

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

Vission Control Manual

Page 2: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

2

Page 3: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

3

Important Note

Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC.Specifically check for proper voltage and that the neutral is grounded at the source. An equipment groundshould also be run to the panel.

*See Wiring Instructions and Diagrams before proceeding.

Before start-up you need to enter all system values and options, see section on Setpoint Values.

“Before powering the Vission control panel down”, it is a good idea to Backup Control Settings to insurethat all previously changed setpoints have been properly saved. See section on saving changes. After back-ing up the setpoints DO NOT power down the Vission panel for at least 1 minute. This will allow adequatetime for all setpoints to be properly saved.

Note: The screen shots depicted in this manual represent the screens corresponding toVission program version # 2.4.41, the current version at time of printing. In our effortto continuously improve the functionality and ease-of-use of the Vission Micro-con-troller, the look of some screens may differ slightly than the representations shownhere.

Equipment Indentification Numbers:

Vilter Order Number: __________________________Serial Number: _____________Vilter Order Number: __________________________Serial Number: _____________Vilter Order Number: __________________________Serial Number: _____________

Page 4: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

4

Page 5: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

5

Important Note ............................................................................................................ 3STANDARD VILTER WARRANTY STATEMENT ............................................. 6Operational Flow Chart ............................................................................................. 8Operational Flow Chart (cont.) ................................................................................. 9Wiring Instructions ................................................................................................... 11Wiring Instructions For Vission Only ..................................................................... 12Wiring Diagram For Vission Only .......................................................................... 20Main Screen ............................................................................................................... 22Set Up Screen............................................................................................................. 23Version Screen ........................................................................................................... 25Maintenance Screen ................................................................................................. 26Menu Screen .............................................................................................................. 28Common Buttons ....................................................................................................... 29Compressor Control ................................................................................................. 30Additional Compressor Controls ............................................................................ 32Compressor Alarm and Trip .................................................................................... 35Compressor Setpoints and Alarms.......................................................................... 37Miscellaneous Screens (Condenser Control) ........................................................ 41Compressor Sequencing (Max 5 Compressors) .................................................... 43Vilter Only Screen ..................................................................................................... 47Diagnostics Force Output ........................................................................................ 48Instrument Calibration ............................................................................................. 49Calibration Procedure of Optical Actuators.......................................................... 51Installation Instructions For Replacement Of Optical Actuator......................... 54Slide Valve Actuator Troubleshooting Guide ......................................................... 55Slide Wiring Diagram for Models Vission VSM-91 To VSS-601 ........................ 59Slide Wiring Diagram for Models Vission VSS-751 To VSS-1801 ..................... 60Command Shaft Rotation and Travel ..................................................................... 61Calibration For Earlier Style Mechanical Gearmotor/Potentiometers ............. 62Trend Chart ............................................................................................................... 64Data Select Screen .................................................................................................... 65Event List ................................................................................................................... 66Trouble Shooting Flowchart (Vission Only) .......................................................... 68

Table of Contents

Page 6: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

6

Safety Failure Message ............................................................................................ 70Supressor Kit Installation ........................................................................................ 73Flash Card Installation Instructions ....................................................................... 74Back Light Installation Instructions ....................................................................... 76System Setpoints Alarms and Trips Work Sheet .................................................. 80System Control Limit Values Work Sheet .............................................................. 81System Timer Values................................................................................................. 82Spare Parts ................................................................................................................ 84Modifications for Analog Board (Vission/Vantage after July 2003) ................... 85Danfoss Liquid Injection Valves .............................................................................. 87Who to Contact ......................................................................................................... 88

Page 7: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

7

STANDARD VILTER WARRANTYSTATEMENT

Seller warrants the products it manufactures to be free from defects in material and workmanship for a period of eighteen

(18) months from the date of shipment from Seller s manufacturing plant or twelve (12) months from date of installation at

the initial end users location, whichever occurs first. In addition, Seller provides the following extended warranties: (a)

three (3) years from the date of shipment on single screw compressor internal rotating parts, (b) two (2) years from the

date of shipment on reciprocating compressors and single screw and reciprocating compressor parts, and (c) two (2)

years on all other parts on a single screw compressor unit. Such warranties do not apply to ordinary wear and tear.

Seller does not warrant that the product complies with any particular law or regulation not explicitly set forth in the

specifications, and Buyer is responsible for ensuring that the product contains all features necessary to safely perform

in Buyers and its customers plants and operations. Buyer must notify Seller of any warranty claim within ten (10) days

after such claim arises, otherwise Buyer waives all rights to such claim. Products supplied by Seller, which are manufac-

tured by others, are not warranted by Seller, but rather Seller merely passes through the manufacturers warranty to

Buyer.

SELLER EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER EXPRESS OR IMPLIED, INCLUDING

THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

Unless otherwise agreed in writing, Buyers sole remedy for breach of warranty is, at Sellers option, the repair of the

defect, the correction of the service, or the providing a replacement part FOB Sellers office. Seller will not be responsible

for costs of dismantling, lost refrigerant, reassembling, or transporting the product. Further, Seller will not be liable for

any other direct, indirect, consequential, incidental, or special damages arising out of a breach of warranty. THESE

WARRANTY REMEDIES ARE EXCLUSIVE AND ALL OTHER WARRANTY REMEDIES ARE EXCLUDED. Products

or parts for which a warranty claim is made are to be returned transportation prepaid to Sellers factory. Any improper

use, corrosion, neglect, accident, operation beyond rated capacity, substitution of parts not approved by Seller, or any

alteration or repair by others which, in Sellers judgement, adversely affects the Product, shall void all warranties and

warranty obligations. Further, Seller shall not be liable under the above warranties should Buyer be in default of its

payment obligations to Seller under this Agreement or any credit agreement.

Page 8: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

8

Operational Flow Chart

Page 9: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

9

Operational Flow Chart (cont.)

Page 10: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

10

Page 11: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

11

Wiring Instructions

Page 12: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

12

Wiring Instructions For Vission Only

5-1= Main Power to Panel5-2= Heater #1 power5-5= Heater #2 Power

Page 13: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

13

Wiring Instructions For Vission Only

CON7

CON6

CON5

CON4

CON3

CON2

CON1

CON1

CON2

CON3

CON4

CON5

2-12-22-32-42-52-62-72-82-92-103-1 "N"3-23-33-43-5 "N"3-63-73-83-93-104-14-24-34-44-54-64-74-84-94-105-15-25-35-45-55-65-75-85-95-10

CON6

CON7

6-16-26-36-46-56-66-76-86-96-107-17-27-37-47-57-67-77-87-97-10

1-11-2 Safety1-31-41-51-6 "1-71-81-91-10

View Inside Of Vission Panel

Lug

Mandatory Wiring

Step #2

Motor Starter Contactor Connection

The contact to the pull in the motor starter contactor is a drycontact, place a "HOT" wire from the starter circuit on 7-1.Place the wire to energize the starter contactor on 7-2.

Page 14: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

14

Wiring Instructions For Vission Only

CON7

CON6

CON5

CON4

CON3

CON2

CON1

CON1

CON2

CON3

CON4

CON5

2-12-22-32-42-52-62-72-82-92-103-1 "N"3-23-33-43-5 "N"3-63-73-83-93-104-14-24-34-44-54-64-74-84-94-105-15-25-35-45-55-65-75-85-95-10

CON6

CON7

6-16-26-36-46-56-66-76-86-96-107-17-27-37-47-57-67-77-87-97-10

1-11-2 Safety1-31-41-51-6 "1-71-81-91-10

View Inside Of Vission Panel

Mandatory Wiring

Step #3

Motor Starter Auxilary Contact

"HOT" to 4-5Wire to energize to 1-1

Page 15: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

15

Wiring Instructions For Vission Only

CON7

CON6

CON5

CON4

CON3

CON2

CON1

CON1

CON2

CON3

CON4

CON5

2-12-22-32-42-52-62-72-82-92-103-1 "N"3-23-33-43-5 "N"3-63-73-83-93-104-14-24-34-44-54-64-74-84-94-105-15-25-35-45-55-65-75-85-95-10

CON6

CON7

6-16-26-36-46-56-66-76-86-96-107-17-27-37-47-57-67-77-87-97-10

1-11-2 Safety1-31-41-51-6 "1-71-81-91-10

View Inside Of Vission Panel

Mandatory Wiring

Step #4

Oil Pump Starter Connection

"HOT" to 6-1Wire to energize on 6-2

Page 16: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

16

Wiring Instructions For Vission Only

CON7

CON6

CON5

CON4

CON3

CON2

CON1

CON1

CON2

CON3

CON4

CON5

2-12-22-32-42-52-62-72-82-92-103-1 "N"3-23-33-43-5 "N"3-63-73-83-93-104-14-24-34-44-54-64-74-84-94-105-15-25-35-45-55-65-75-85-95-10

CON6

CON7

6-16-26-36-46-56-66-76-86-96-107-17-27-37-47-57-67-77-87-97-10

1-11-2 Safety1-31-41-51-6 "1-71-81-91-10

View Inside Of Vission Panel

Lug

Optional Wiring

Step #5

Auxiliary / Safety Wiring

A determination by the user is to be made if this option willbe used. If it is not used, insure that a jumper is installedbetween L 2-1 and 1-2If this option is used, remove the jumper 2-1 to 1-2 andplace the high level cutout (typically, other cutouts or an E-stopcould be used) common wire on 2-1 and the normally closedwire to 1-2.

Page 17: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

17

Wiring Instructions For Vission Only

CON7

CON6

CON5

CON4

CON3

CON2

CON1

CON1

CON2

CON3

CON4

CON5

2-12-22-32-42-52-62-72-82-92-103-1 "N"3-23-33-43-5 "N"3-63-73-83-93-104-14-24-34-44-54-64-74-84-94-105-15-25-35-45-55-65-75-85-95-10

CON6

CON7

6-16-26-36-46-56-66-76-86-96-107-17-27-37-47-57-67-77-87-97-10

1-11-2 Safety1-31-41-51-6 "1-71-81-91-10

View Inside Of Vission Panel

Lug

Optional Wiring

Step #6

Remote Start Wiring

A determination by the user is to be made if this option willbe used. If it is not used, insure that a jumper is installedbetween L 2-1 and 1-5.If this option is used, remove the jumper 2-1 to 1-5 andplace the dry remote start contact common wire on 2-1and the normally open wire to 1-5.

Page 18: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

18

Wiring Instructions For Vission Only

CON7

CON6

CON5

CON4

CON3

CON2

CON1

CON1

CON2

CON3

CON4

CON5

2-12-22-32-42-52-62-72-82-92-103-1 "N"3-23-33-43-5 "N"3-63-73-83-93-104-14-24-34-44-54-64-74-84-94-105-15-25-35-45-55-65-75-85-95-10

CON6

CON7

6-16-26-36-46-56-66-76-86-96-107-17-27-37-47-57-67-77-87-97-10

1-11-2 Safety1-31-41-51-6 "1-71-81-91-10

View Inside Of Vission Panel

Lug

Optional Wiring

Step #7

Setpoint #1/#2 Selection Wiring

A determination by the user is to be made if this option willbe used. This optional input does not need to be closed forthe compressor to run no jumper is required. If this option isto be used, Place the dry contact common wire on L 2-7 andnormally open on 1-3

Page 19: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

19

Note Page

Page 20: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

20

Wiring Diagram ForVission Only

Page 21: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

21

Wiring Diagram ForVission Only

Page 22: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

22

Main Screen

This Screen contains buttons to navigateto setpoint, setup and maintenance screens.

Status information on the compressor, oil pump,oil heater and run mode.

Start/Stop buttons.

Hour meter.

Motor amperage.

Refrigerant.

Real time compressorand package operating conditions.

Volume and Capacity Slide locations.

The Main Screen

This screen has been designed to givethe operator an overall view of all operatingparameters affecting the compressor pack-age. This screen should always be displayedwhen maintenance items and setpoint itemsare not being performed. The date on thescreen is updated every ½ second. Statusinformation such as Alarms and Trips aredisplayed on the screen.

Page 23: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

23

From the Main screen, touch the Setup but-ton. After entering an authorized user namepassword, the screen pictured below will ap-pear.

·Operator Name – This is the same list thatappears in the login dialog. Names in this listcan be selected for deletion. To change aname or password, you delete the name andenter a new name/password pair. TheVILTER operator name cannot be deleted.Emergency passwords provided by a Vilterrepresentative for the VILTER name aregood only on the date for which they areissued. They are intended to permit navi-gation to this screen for setup or repair ofthis list.

·Language – The user screens can be seenin English, French, and Spanish, depending on the option selected. Some text willstill display in English even when anotherlanguage is selected.

·Pressure Units – Select units of measurefor pressure readings. Choices are psi, kgcm2 and kPa. This section only, affectspressures displayed on main screen. On allother screens, units are displayed in psi. Onthe main screen with psi selected, negativegauge pressures will display as inches ofmercury vacuum with the unit “Hg. Onother screens, negative numbers are scaledas “psi”.

·Temperature Units – Select units of measure for temperature. Choices are Fahrenheit or Celsius.

·Refrigerant – The choice R717 (Ammonia).

Set Up Screen

Touch Here

Page 24: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

24

Set Up Screen

· Anti-Recycle – The operator can select fromthe following AntiRecycle options: True, Ac-cumulative, Modified, or Hot Starts. Theseselect the strategy used to prevent excessivestart/stop cycles of the compressor. Timersand counters used to enforce anti-recyclingare adjusted and monitored in the Compres-sor Timer Settings screen, reached from theMenu screen. Help for the Timer Settingsscreen explains how the different settings andstrategies operate.

· Compressor Control Via – Operator canchoose the method or mode of compressorcontrol. This determines which measured vari-able is used in making loading (capacity con-trol) decisions. The choice selected here de-termines which setpoints are made availablefor adjustment on the Compressor ControlSetpoints screen.

· Delete Operator – Operator can choose todelete operator names from the authorized op-erator listing. A name in the list is selected bytouching it. The selected name will be deletedfrom the list when this button is pushed. Ifyou delete all the names (besides VILTER), besure you add at least one before leaving thisscreen.

· Add Operator – The button opens a dialogfor entry of a new name/password pair. Noth-ing (leaving the password text box blank) is alegal password. The password is not ob-scured as it is typed in, so untrusted partiesshould not be permitted to view the screenduring entry. The password is not confirmedwith a repeat entry, so verify it visually beforepressing okay. Up to 25 name/password pairscan be added. The Operator Name list box willacquire a scroll bar when it fills.

·Slide Non-Movement – Alarm enable and dis-able buttons permit selecting whether an alarmshould be generated when failure of slides tomove is detected.

· Setpoint #1 Oil Pump #2 Oil Pump – Forsingle stage and high stage operation, parttime or normal oil pump fuction are used. Theoil pump shuts off after discharge pressurehas risen sufficiently to drive oil injection. Oilpump operating mode is independentlysettable for setpoint groups # 1 and # 2.

· Modbus Slave Network Address – When mul-tiple MicroControllers are connected on aModbus Network, each controller must havea unique address from the otherMicroControllers on the network. Duplicatenode addresses are not allowed. The nodeaddress of each Vission is determined throughthe SETUP menu. The MicroController thatwill initiate all conversation on the networkMUST be defined as node 100 (this is definedas the “master” node). All other node num-bers should be in the range of 101 through174.

This must be set when the extra special port(Com4) is used to control or monitor the com-pressor via Modbus. It also must be set whenthe multi-compressor sequencing feature isused. Even though Ethernet is used for thecomms, this address establishes thecompressor’s identity and role in the sequenc-ing logic.

· Reset After Power Fail – When Auto is se-lected, the compressor will attempt to restarton powering up if it was running in ‘Auto’when powered down and enabling conditionsare met. When ‘Manual’ is selected, the com-pressor powers up into the ‘Stop’ mode andan explicit command to run is required froman operator or comms channel.

· Min Run Capacity – When enabled, the Mini-mum Run Capacity setting on the AdditionCompressor Setpoints screen operates as de-scribed in the help for that screen. Whenmultiple compressor sequencing is used, se-lecting Disable here does not interfere withuse of the Min Run Capacity setting in the se-quencing logic.

Page 25: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

25

Set Up Screen

Press Log on/Save Button and the above screen will appear. When altering setpoints, log on is necessary. Selectappropriate user name and enter password to change setpoints. This screen is also used to backup and save setpointsby pressing (Backup Settings).

After performing a “Back up Setting” operation, DO NOT power down the Vission/Vantage panel for atleast 1minute. This will allow adequate time to insure all setpoints have been properly stored.

Log On, Off,or Save Changes

Version Screen

To View if a customized program has been installed in your unit, go to the main screen and press VERSION, ascreen will appear with the program version and the make model of the unit.

Page 26: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

26

From the Main screen touch the Maintenance button.

“Service Item Required” message indicates that the compressor runtime hours has accumulated to a value - or apoint- where service Maintenance is required.

>From the main screen, press the “Maintenance” button. A chart will be shown to indicate what service is required- based on the number of hours the compressor has run.

After the all required service work has been accomplished, press the “Service” button located on the Maintenancescreen. A “Services Completed” screen will appear. Press on each service that has been completed. A “check” willappear next to each item that has been pressed. When all required services have been completed, and the appropriatebox has been checked in the “Services Completed” screen, then the “Service Item Required” message will disappearon the main screen.

Note: All of the service items listed for that interval must be checked before the “Servicing Item Required” messagewill disappear.

Touch Here

Maintenance Screen

Page 27: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

27

The Service Button from the Maintenance Screen will bring you to this screen.

When entering service items that were completed, make sure to check all items that are listed to be done at thatservice interval.

Maintenance Screen

This screen shows the chart of routine maintenance to be performed on the machine at hourly intervals from 200 hoursto 120,000 hours.

Page 28: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

28

At the bottom of the Main screen touch theMenu button to bring up the screen shown inFigure below.

Use this screen to navigate to the other setpointscreens contained within the program. Eachscreen has a help button to describe the func-tion of the screen.

Menu Screen

Touch Here

Page 29: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

29

A. Common Buttons

There are several buttons that are common for all menu screens:

· Return to Menu – This button always returns you to the Menu screen

· Logon To Edit – The user is allowed to view data at all screen levels but cannot edit data until a login hasoccurred. In order to logon, press the arrow next to user name, select user then press the abc button, the key padscreen will appear. Enter your password and hit OK.

· Set – To change a value, the operator must first press the SET button and then the text field of the value they wantto modify. A number pad will pop up for ease in entry.

· Help – This screen will provide more information to the user about the operation of the microprocessor.

Common Buttons

Page 30: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

30

These screens enable the operator to view andadjust settings that affect compressor control.

From the Setup screen, the operator can choosethe method or mode of compressor control:

Compressor Control ViaSuction PressureProcess TemperatureDischarge Pressure

Once the method is chosen, the appropriatesetpoints are then displayed on the Compres-sor Control Setpoints screen.

The compressor will decide when to increaseor decrease capacity by comparing the con-trolled variable to the setpoints. The maxi-mum on time and minimum off time settingsfor slide actuator motors can be used to reducehunting or improve response time. The de-

fault settings of 3 and 20 seconds respectively, pro-vide good operation over a wide range of condi-tions.

Also on this screen, the following buttons are dis-played:

· Event List – Provides a chronological event list-ing.

· Chart – Provides a line graph showing processvalues over a range of time.

· Auto – Places the capacity slides into automaticmode. In automatic mode, the capacity slidemoves according to control setpoint informa-tion.

· Manual – Places the capacity slides into manualmode. In manual mode, the capacity slidemoves based on input from the operator.

Compressor Control

Level 1 Access – Compressor Control Setpoints

From the Menu screen , press the Compressor Control setpoints button. The compressor control setpoints screenwill be shown.

Page 31: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

31

Setpoints on this screen:

· Suction Pressure On/Off – The compressorwill automatically cycle ON and OFF at thesetpoints entered. Suction Pressure On/Offcontrol is only active if the Compressor Con-trol Via Suction Pressure option is selectedon the Setup screen. If a compressor shut-down is desired on a suction pressure dropand a manual reset is required, set the OFFvalue below the Low Suction Pressure SafetyTrip value. This will shut down the unit anda reset will be required to restart it.

· Suction Pressure Capacity Increase – Thecapacity of the compressor will increase whensuction pressure is at or above the IncreaseON setpoint, and the increase “off” timer hascycled. Capacity will continue to increaseuntil the Suction Pressure Capacity IncreaseOFF setpoint is reached. If closer systemcontrol is desired, set the ON and OFFsetpoints at the same values. This will es-sentially eliminate any differential betweenthe ON and OFF setpoints.

· Suction Pressure Capacity Decrease – Thecapacity of the compressor will decreasewhen suction pressure is at or below the ONsetpoint, and the decrease “off” timer hascycled. Capacity will continue to decreaseuntil the Suction Pressure Capacity DecreaseOFF setpoint is reached. If closer systemcontrol is desired, set the ON and OFFsetpoints at the same values. This will es-sentially eliminate any differential betweenthe ON and OFF setpoints. While this set-ting is only available for adjustment on theControl Setpoints screen when the Compres-sor Control Via Suction Pressure option isselected on the Setup screen, it has an over-ride effect when control is via process tem-perature as described below.

· Capacity Control °F On/Off – The compres-sor will automatically cycle ON and OFF atthe setpoints entered. Capacity Control °FOn/Off is only active if the Compressor Con-trol via Process Temperature option is se-lected on the Setup screen. If compressorshutdown is desired on a process tempera-ture drop and a manual reset is required, setthe OFF value below the Low Control Tem-

perature safety trip value. This will shut downthe unit and a reset will be required to restartit.

· Capacity Control °F Increase – The capac-ity of the compressor will increase when pro-cess temperature is at or above the ONsetpoint, and the increase “off” timer hascycled. Capacity will continue to increase untilthe Capacity Control °F Increase OFF setpointis reached. If closer system control is desired,set the ON and OFF setpoints at the same val-ues. This will essentially eliminate any differ-ential between the ON and OFF setpoints.Process temperature control of the capacity isactive only if the Compressor Control Via Pro-cess Temperature option is selected on theSetup screen.

· Process Temperature Control – Provides fora Suction Pressure Override feature. If thesuction pressure should drop below the Suc-tion Pressure Capacity Decrease OFF setpoint,the Suction Pressure Capacity Decrease OFFsetpoint will override the Capacity Control °FIncrease and prevent the compressor capac-ity from increasing (loading). If the suctionpressure should continue to decrease belowthe Suction Pressure Capacity Decrease ONsetpoint, the compressor capacity will beforced to decrease until the suction pressureis just above the Suction Pressure CapacityDecrease ON setpoint. This will help stabilizethe suction pressure, allowing for the processtemperature to be gradually pulled down. TheSuction Pressure Capacity Decrease ON andOFF setpoints can be viewed or adjusted bytemporarily selecting “Processor Control ViaSuction Pressure” on the Setup screen.

· Capacity Control °F Decrease – The capac-ity of the compressor will decrease when theprocess temperature is at or below the ONsetpoint and the decrease “off” timer hascycled. Capacity will continue to decreaseuntil the Capacity Control °F Decrease OFFsetpoint is reached. If closer system controlis desired, set the ON and OFF setpoints atthe same values. This will essentially elimi-nate any differential between the ON and OFF

Compressor Control

Page 32: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

32

· High Discharge Pressure UnloadingSetpoints 1&2 – Active in Suction Pressure orProcess Temperature Capacity Control mode.These setpoints limit the compressor fromloading at high discharge pressure conditions.They override the Suction Pressure or ProcessTemperature Capacity Control setpoints. Thecapacity of the compressor will decrease whenthe discharge pressure is at or above the ONset point. When the OFF setpoint is reached,the compressor will stop from unloading anyfurther.

· Motor Amp. Load Limit Setpoints 1&2 – Thiscontrol limit is the motor full load current drawand the maximum current draw. This control

limit will only prevent the compressor fromloading and does not shut down the compres-sor if the maximum current draw setpoint isexceeded. The actual values entered maydepend on particular circumstances. Thefunction of the setpoint is as follows:

If the motor is operating at the full load am-perage (FLA) setting, the compressor is pre-vented from loading. If the motor amps ex-ceed the MAX setpoint, the compressor isforced to unload until the current is at 1.0625times above the FLA setting. If the motorbeing used has a service factor below 1.0625,use a value for the FLA that is 10% lowerthan the MAX value.

Additional Compressor Controls

Page 33: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

33

· Oil Separator Heater Temperature – This con-trol limit determines when the oil separatorheater is energized. A decrease in oil separatortemperature below the ONsetpoint energizes theoil separator heater. On an increase in oil sepa-rator temperature above the OFF setpoint, theoil heater is de-energized.

· Oil Pump Restart – To determine the ON andOFF values for the pressure ratios, take the ab-solute discharge pressure (PSIA), and divide itby the absolute suction pressure (PSIA). If thepressure ratio is below the ON setpoint value,the oil pump will restart and stay on until thepressure ratio increases above the OFF setpoint.This enables a high stage compressor with a parttime oil pump to temporarily operate under con-ditions requiring a full time oil pump.

EXAMPLE: To calculate the OFF value, ifthe absolute discharge pressure is 200 PSIA andthe desired absolute suction pressure of the cut-out point is 67 PSIA, the discharge pressure isdivided by the suction pressure. The result is aOFF value of approximately 3.0. This wouldthen be entered for the OFF pressure. Nowdetermine the ON value, take the absolute dis-charge pressure (200 PSIA) and divide this bythe desired absolute suction pressure (71 PSIA).This results in a ON valve of 2.8.

· Capacity Slide Adjustment Range – This con-trol limit determines the capacity range the Ca-pacity Slide Adjustment factor will be active.The factor will be active from 0% capacity andwill be deactivated when the OFFsetpoint isreached. On a decrease in capacity below theON set point, the factor will be active.

· Minimum Run Capacity – The Minimum RunCapacity is the minimum capacity the compres-sor will be allowed to run at. When the com-pressor is started, it will be loaded to the Mini-mum Run Capacity control setpoint minus 5%.This is done to prevent the capacity control fromhunting if the load is not great enough to keepthe compressor capacity at the Minimum Run

Capacity setpoint. On a call for unloading, thecompressor will unload until it reaches the Mini-mum Run Capacity control setpoint. It will re-main there until the suction pressure reduces andthe compressor cycles off on the Suction Pres-sure On/Off control setpoint.

Volume Slide Adjustment Factor – This value isnormally zero (0) and will not require changing.However, if the system operating conditions showthe volume ratio is not at the optimum value forthe system, this value can be adjusted up or downto permit the most efficient positioning of the vol-ume slide valves. To determine the value to enter,first ensure that the system is in a steady operatingstate and place the volume side in manual. NOTE:The volume position setting and increase the vol-ume side position slowly until the lowest amper-age level is achieved. If the amperage level risesinstead of falls, decrease the volume slide posi-tion until the lowest amperage is achieved. Recordthe differential from the original position. This willthen be adjustment factor to enter for our system.NOTE: Negative numbers can be used for thissetting. This setpoint is active on a drop in capac-ity below the Capacity Slide Adjustment Rangecut-in (ON) setting. The adjustment is disabledwhen capacity rises above the Adjustment RangeOFF setting. Normally, the “ON-Off” set pointsshould both be set at 100%, so the volume sideadjustment factor will be applied over the full rangeof 0 to 100%

· Economizer Solenoid – This control limit deter-mines when the economizer solenoid is energized.When the percentage of compressor capacity re-duces below the Economizer Solenoid OFFsetpoint, the solenoid is energized.

· Current Transformer Ratio – The value enteredmust agree with the Current Transformer Ratioon the current transformer being used. The cur-rent transformer is mounted in the compressor mo-tor conduit box. The ratio is stated as the ratio ofmeasured current to a nominal full scale currentin the secondary of 5 amps; only the first of theseis entered. For example, if the ratio reads 250/5,enter 250.

Compressor Control

Page 34: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

34

· Low Suction Pressure Load Limit – Active in Dis-charge Pressure Capacity Control mode only. Thesesetpoints limit the compressor from loading at lowsuction pressure conditions. They override the dis-charge pressure capacity control setpoints. Whenthe OFF setpoint is reached (at or below setpoint),the compressor will not be allowed to load any fur-ther. If the suction pressure continues to fall, thecapacity of the compressor will decrease when thesuction pressure is at or below the ON set point. Itwill stop decreasing when the suction pressure risesto a point that is just below the ON set point.

Page 35: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

35

Compressor Alarm and Trip

· Low Suction Pressure Setpoints 1&2 – Thisis the low suction pressure safety. This safetyis active in both temperature and pressurecontrol modes. An alarm or trip will be ac-tive on a drop in suction pressure below thesetpoint value.

· High Discharge Pressure Setpoints 1&2This is the high discharge pressure safety.The alarm or trip will be active on a rise indischarge pressure above the setpoint value.

Low Oil Separator Temperature – This isthe lowest allowable oil separator tempera-ture. The compressor will not be allowed torun if the Oil Separator Temperature is be-low the trip setting. After the compressorstarts, the alarm or trip will be active if theoil temperature in the separator drops belowthe setpoint value.

· High Discharge Temperature – This is thehigh discharge temperature safety. The alarmor trip will be active if the discharge tempera-ture should rise above the setpoint value.

· Low Oil Separator Start Temperature – Thisis the starting low oil separator temperaturesafety. The compressor is prevented fromstarting or running if the oil in the separator isbelow the trip value. After a time delay (OilSeparator Temperature Safety Changeover),this safety is deactivated and the Lo Oil Sepa-rator Run Temperature is the active setpoint.

· Low Oil Separator Run Temperature – Thisis the running low oil separator temperaturesafety. After a time delay (Oil Separator Tem-perature Safety Changeover), the Lo Oil Sepa-rator Start Temperature is bypassed and LoOil Separator Run Temperature is the active

Page 36: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

36

setpoint. The alarm or trip will be active ifthe oil temperature of the separator drops be-low the setpoint value.

· Low Oil Injection Temperature – This is thelow oil injection safety. The alarm or trip willbe active if oil injection temperature dropsbelow setpoint value after a time delay (OilInjection Temperature Safety Changeover).

· High Oil Injection Temperature – This is thehigh oil injection temperature safety. Thealarm or trip will be active on a rise in oil in-jection temperature above the setpoint value.

· Low Control Temperature – This is the lowcontrol temperature safety. This safety is ac-tive when process temperature control hasbeen selected in the Setup screen. An alarmor trip will be active on a drop in process tem-perature below the setpoint value.

· High Control Temperature – This is the highcontrol temperature safety. This safety is ac-tive when the temperature control has beenselected in the Setup screen. An alarm willbe active on an increase in process tempera-ture above the setpoint value.

Compressor Alarm and Trip

Page 37: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

37

Compressor Setpoints and Alarms

· Prelube Oil Pressure – If the oil pressure doesnot rise above the reset setting for a time exceed-ing the Minimum Compressor Prelube Time andthe pump runs longer than the Prelube Pump TimeLimit, an alarm or trip will occur. These timelimits are set on the Compressor Timer Setpointsscreen. Prelube oil pressure is defined as theamount that the oil pump drives manifold pres-sure above the discharge pressure.

· Low Oil Pressure – This is the running oil pres-sure safety. An alarm or trip will be active if theoil pressure should drop below the setpoint value.This occurs once the Oil Pressure Bypass timerhas expired. The time limit is set on the Com-pressor Timer Setpoints screen. For the singlescrew compressor, oil pressure is defined as mani-fold pressure minus suction pressure.

· High Filter Differential Pressure Start – Thissafety setpoint is active when the compressor isin the start cycle. An alarm or trip will be activeif the filter inlet pressure exceeds the filter out-let pressure by the setpoint value.

· High Filter Differential Pressure Run – Thissafety setpoint is active when the compressor isin the run cycle. An alarm or trip will be activeif the filter inlet pressure exceeds the filter out-let pressure by the setpoint value.

· High Motor Amps – This safety setpoint is ac-tive after the Volume Decrease At Start Timerexpires. This timer is not user settable, and instandard applications, is 15 seconds. A trip willoccur if the motor amperage exceeds the safetysetpoint value. The setpoint should be set at125% of the motor full load amperage.

Page 38: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

38

· Capacity Decrease At Start – At compressor startup,the capacity motor is held at minimum position forthis time period. After the timer expires, the slide isfree to move in accordance to the system demands.

· Compressor Starter Auxiliary Contact Bypass – Thistimer is used to bypass the motor amperage input atstart. After the timer times out, the program deter-mines if the motor starter has pulled in by testing theamperage channel. If the program determines thatthe starter did not “pull in”, then the compressor willfail on “Motor Starter Fail” message.

· Volume Slide Adjustment Timer – This timer de-termines the intervals the volume slide is adjusted.If the volume slide is between 2½% & 7% awayfrom the desired volume ratio, the motor is pulsedonce toward the desired volume. If the volumeslide is more than 7% away from the desired value,the volume slide motor is continuously energizeduntil the valve is within 2½% of the desired value.If the actual position is within 2½% of the desiredvalue, no adjustment will be made.

Compressor Timer Setpoints

To change a timer setting,you must “Logon to Edit”

first. Push the “Set”button then push on thetimer setpoint value youwish to change. After thesetpoint is changed, press

the “Refresh” button.This will refresh the

“Current” window, whichshows the elapsed time of

the timers.

Page 39: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

39

· Minimum Compressor Prelube Timer – This is thelength of time the oil pump will run after establish-ing the Prelube Oil Pressure, to prime oil circuitbefore starting the compressor.

· Oil Pressure Bypass At Compressor Start – Thistimer bypasses the Low Oil Pressure limits. Thetimer starts when the compressor starts. After thetimer has cycled, the Low Oil Pressure setpoint isactive.

· Prelube Oil Pump Time Limit – This timer puts alimit on how long the prelube oil pump is allowedto run without establishing the Prelube Oil Pres-sure.

· Filter Differential Pressure Safety Changeover –This timer bypasses the Hi Run Filter DifferentialPressure setting during start, to allow the Hi StartFilter Differential Pressure to protect against HighFilter Differential during start. After the timer hascycled, the Hi Run Differential Pressure Safety isactive.

· Low Oil Separator Level Bypass Timer – This timerbypasses the low oil level switch for momentarydrops in the oil level. If the switch is still openafter the Low Oil Separator Level Bypass Timerhas timed out, the compressor will be shut downand an alarm will be displayed. This timer is avail-able if the unit is equipped with a low oil separatorfloat switch. The oil level switch is standard on allliquid injection units and optional on all others.

· Auto Restart After Power Failure – This timerforces the microprocessor to wait for the set timeperiod after a power failure before starting the com-pressor unit. By staggering the time settings, thecompressors can be allowed to start automatically,one at a time, after a power failure. This preventsexcessive loads on the power system that could becaused by all of the equipment coming online at thesame time. The Power-Up Auto Start operator op-tion must be selected on the Setup screen for thisoption to be active.

· Oil Separator Temperature Safety Changeover– This timer allows Low Oil Separator StartTemperature Safety setpoint to protect the com-pressor against cold oil during starting. Afterthe timer has cycled, the Low Oil Separator RunTemperature is then active.

· Low Oil Injection Temperature Bypass – Thistimer bypasses the Low Oil Injection Tempera-ture Safety Setpoint during start-up. After thetimer cycles, the Low Oil Injection Tempera-ture Safety is set.

· Hot Starts / Hr Counter – This counter countscompressor starts. After every start, a one-hourtimer is reset and starts timing. If the timer timesout, the hot starts counter is reset. When thecounter reaches it’s preset value, it will not al-low another compressor start until the one-hourtimer times out and resets the counter. In otherwords, the hot starts counter will be reset whenthe time between compressor starts total onehour. This counter allows repetitive compres-sor starts, but once the counter has reached itsset point, it requires a one-hour window betweencompressor starts in order for the counter to bereset.

· True Anti-Recycle Timer – Once the compres-sor turns off, the timer will keep the compres-sor off for the setting of True Anti-RecycleTimer. This timer is used to prevent short cy-cling of the compressor.

· Accumulative Anti-Recycle Timer – This timeralso forces a specified time between compres-sor starts. When the compressor starts, the timerresets then starts timing and accumulates run-ning time. Once the compressor shuts down, itwill not be allowed to restart for the remainderof the time left on the Accumulative Anti-Re-cycle Timer. Unlike the True Anti-RecycleTimer, if the compressor has run for a time pe-riod that exceeds the setpoint of the Accumula-tive Anti-Recycle Timer, then when the com-pressor shuts down, it will be allowed to restartimmediately.

Compressor Timer Setpoints

Page 40: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

40

Compressor Timer Setpoints

The compressor restart options (Hot Starts orAnti-Recycle Timers) are selected from theSetup screen. One additional Anti-RecycleTimer that can be selected from the Setup screenis the Modified Anti-Recycle Timer.

· Modified Anti-Recycle Timer – Normally, thisanti-recycle timer will function as a True Anti-Recycle Timer. However, if the operator pressesthe stop button, or if a failure occurs, the anti-recycle timer switches functions and acts as anaccumulative type anti-recycle timer. It will al-low the compressor to restart when the accumu-lated runtime and the present off time meets orexceeds the setting of this timer.

Page 41: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

41

Miscellaneous Screens (Condenser Control)

This screen is designed for customized functions only, thus maybe placed as a view only screen.

Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit.

To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screenwill appear with the program version and the make model of the unit.

Page 42: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

42

Miscellaneous Screens (Motor Speed)

This screen is designed for customized functions only, thus maybe placed as a view only screen.

Note: Changing variables on this screen will not have any effect unless you have a customized program for your unit.

To View if a customized program has been installed in your unit, go to the main screen and press VERSION, a screenwill appear with the program version and the make model of the unit.

Page 43: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

43

Compressor Sequencing (Max 5 Compressors)

From the Main Menu (press sequencing), this screen will appear. You must clear the IPAddress beforeentering a new one.

Page 44: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

44

This screen allows the operator to setup a sequenc-ing network. Currently, the MicroController is ca-pable of sequencing 5 compressors. In order for aMicroController to participate on the network, it musthave a unique address from the other Controllers onthe network. Duplicate node addresses are not al-lowed. The node address of each is done throughthe Setup menu.

The MicroController which will initiate all conver-sation on the network MUST be defined as node 100.This is defined as the “master” node. All other nodenumbers should be in the range of 101 through 174.

Ethernet Peer To Peer – In addition to havingunique node addresses, all compressors on theEthernet network must have unique IP addressesand unique names. These are entered from theIP Address/Name screen, accessed from theVILTER ONLY screen. The Ethernet IP ad-dresses of each of the five compressors listedare required to be:

Equipment: Ethernet IP AddressCmp#1: 10.8.0.73Cmp#2: 10.8.0.74Cmp#3: 10.8.0.75Cmp#4: 10.8.0.76Cmp#5: 10.8.0.77

Note: IP addresses must be set prior tothemicrocontrollers being connected together.

The Compressor Sequencing screen only needs tobe setup on the “Master” node. The elements of thisscreen are:

· Equipment – Allows the operator to select thesize of each compressor. This information isused to make sequencing decisions based on theCFM of the compressor. A valid size MUST bechosen for a compressor to participate in se-quencing. This field also allows the operator tochange the name of each of the five compres-sors listed.

Note: Sequencing and Remote/Start-Stop can NOT fuction at the same time- Sequencing will over-rideremote start/stop!

Compressor Sequencing (Max 5 Compressors)

Page 45: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

45

· Node – These node address fields tell the se-quencing algorithm which the MicroControllerwill be participating in the sequencing net-work. Input the node addresses of each Con-troller, participating on the network, in thesefields.

NOTE:

The node addresses for each panel are defined andentered under the Setup screen at each individualpanel.

· Central Off/On Buttons – These buttons in-dicate whether the compressor has been se-lected to operate under Central Control. Ifthe button reads “On”, the compressor will beincluded in the Central Control System. If thebutton reads “Off”, the compressor will notbe included in the Central Control system.Pushing once on the button will toggle thebutton between “Off” and “On”.

· Priority – The Priority fields are used to as-sign the compressor priority for Central Con-trol. The lower the priority number, the greaterthe priority of the compressor. Priority #1compressor is the highest priority compres-sor. Compressors with higher priority num-bers will be lag compressors. A compressorwith a priority of 1 will be considered the“lead” compressor. The suction pressure ofpriority #1 compressor is used to control thesystem pressure.

·Step – This field sets the amount of capacitychange that will occur when a compressor isloading or unloading.

NOTE:

Because of the method used to position the slidevalve, and the method used to determine whenthe slide valve position is “close enough” to thetarget value, the step value should never be lessthan 5%.

· Min Cap – The Minimum Capacity is the lowestcapacity, in percentages, that this compressor isallowed to reach during operation. If the systemneeds to remove additional system capacity, itmay shut a compressor off.

·Max Cap – The Maximum Capacity is the high-est capacity, in percentage, that this compressoris allowed to reach during operation. If the sys-tem needs to increase capacity after this com-pressor has reached its maximum, it may turn onanother compressor.

·Stop Tmr – The Stop Timer (in seconds) is theamount of time the system must hold a compres-sor at minimum capacity before the compressorcan be shut off.

PRESSURE SETPOINTS:

The 7 pressure setpoints are used to control thesystem pressure. With the exception of the Start #1and Start Lag setpoints, all other setpoints must bein decreasing pressures from the previous value.·

Start #1 – The Start #1 pressure setpoint is thesystem pressure at which the Priority 1 compres-sor will be started.

·Start Lag – The Start Lag pressure setpoint willonly start the lag compressor, and only after thelead compressor has reached the Max Cap value,and the Machine Start Timer has timed out. TheLead compressor is normally priority, unless it isnot available to start due to waiting hot starts,safety trips, etc.

·Load Rate 2 – If the system pressure exceedsthe Load Rate 2 pressure setpoint for the timespecified in the Load Rate 2 Timer, Central Con-trol will attempt to increase the capacity of thesystem.

·Load Rate 1 – If the system pressure exceedsthe Load Rate 1 pressure setpoint for the timespecified in the Load Rate 1 Timer, Central Con-trol will attempt to increase the capacity of thesystem.

Compressor Sequencing (Max 5 Compressors)

Page 46: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

46

· Unload Rate 1 – If the system pressure falls be-low the Unload Rate 1 pressure setpoint for thetime specified in the Unload Rate 1 Timer, CentralControl will attempt to decrease the capacity ofthe system.

·Unload Rate 2 – If the system pressure fails be-low the Unload Rate 2 pressure setpoint for thetime specified in the Unload Rate 2 Timer, CentralControl will attempt to decrease the capacity ofthe system.

·Stop – If the system pressure falls below the Stopsetpoint, Central Control will immediately try toshut down the lowest priority lag compressor. Ifthere is only one compressor running, Central Con-trol will shut down.

·CAP Load Timers – These timers are directly re-lated to the setpoint values described above. Thetimers are the minutes and seconds that theCentralControl algorithm will hold before deciding on anaction. The CAP Load Rate Timers are related tothe appropriate Load 1 and 2 increase setpointsdescribed above.

·CAP Unload Timers – The Capacity Unload RateTimers are similar to the timers described above,however, they work to decrease system capacity.The CAP Unload Rate Timers are related to theappropriate Unload Rate 1 and 2 decrease setpointsdescribed previously.

·Machine Start Time – This timer is the time thesystem will wait until another compressor is startedin an attempt to increase capacity.

·Force Priority 1 Compressor On Checkbox -When checked this will override other sequencinglogic and priority 1 compressor will always run.Pressing the box alternating checks and unchecksit.

Compressor Sequencing (Max 5 Compressors)

Page 47: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

47

Vilter Only Screen

WARNING: Settings on these screens should be used only by Vilter represen-tatives or persons acting under their direction. Improper setting may result inloss of vital data and require service NOT covered under warranty.

Page 48: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

48

Diagnostics Force Output

· On/Off – This will turn the force outputs option On/Off. The force outputs that can be modified are as follows:Main Motor Starter, Oil Pump, Economizer Solenoid, Remote Alarm/Trip, Liquid Injection Solenoid, CapacityIncrease Motor, Capacity Decrease Motor, Volume Increase Motor and Volume Decrease Motor. You canchoose the forced output by pressing the down arrow in the control labeled Available Outputs.

Page 49: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

49

Instrument Calibration

The current values reflect the values presently maintained by the system. The user can perform a one-point calibrationby entering an offset value into the respective column. This will automatically adjust the current value and zero out theoffset value. Giving max and min values for a respective current value can perform a two-point calibration. Theprogram will automatically adjust the calibration line to meet those values.

The following items can be calibrated at this screen: Discharge Pressure Transducer, Suction Pressure Transducer,Manifold Pressure, 0-10v Input, Oil Filter Inlet Pressure Transducer, Discharge Temperature RTD, Suction TemperatureRTD, Oil Injection Temperature RTD, Oil Separator RTD, Process Temperature RTD and Motor Amperage.

Page 50: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

50

Instrument Calibration

Instrument calibration menu displays the Input channels that can be calibrated to represent the actual values at thesampling points.

The current values reflect the values presently maintained by the system. The user can perform a one point calibrationby entering an offset value into the respective column. This will automatically adjust the current value and zero out theoffset value.

The following items can be calibrated at this screen: three (3) spare RTDs and two (2) 0-10 volt input.

Page 51: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

51

Calibration Procedure of Optical Actuators

ACTUATOR MOTOR CONTROL MODULECALIBRATION PROCEDURE

1. Disable the Slide Non-Movement Alarm by going to the “Setup” menu on the Vission/ Vantage and choosing “Alarm Disable” for the Slide Non Movement Option.

2. Open the plastic cover of the capacity motor byremoving the four #10 screws. Caution: thereare wires attached to the connector on theplastic cover. Handling the cover too aggres-sively could break the wires.

3. Gently lift the cover and tilt it toward the Turckconnectors. Raise the cover enough to be ableto press the blue calibrate button and be able tosee the red LED on the top of assembly.

4. Press “Menu” on the main screen and then pressthe “Slide Calibration” button, to enter the slidecalibration screen. If you are re-installing a newoptical actuator re-connect the yellow and graycables.

5. Press INC and DEC to move the slide valve andcheck for the correct rotation. See Table 1 forActuator/command shaft rotation specifications.

6. Note: If the increase and decrease buttons donot correspond to increase or decrease shaftrotation, swap the blue and brown wires of the“yellow power cable”. This will reverse therotation of the actuator/command shaft.

* If you are replacing or reinstalling a new optical actuator see: page 63 first.

Page 52: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

52

Calibration Procedure of Optical Actuators

7. Quickly press and release the blue pushbutton on the actuator one time. This placesthe actuator in calibration mode. The redLED will begin flashing rapidly.

8. Note: When the actuator is in calibrationmode, it outputs 0V when the actuator isrunning and 5V when it is still. Thus, asstated earlier, the actuator voltage willfluctuate during calibration. After theactuator has been calibrated, 0V output willcorrespond to the minimum position and 5Vto the maximum position.

9. Note: The “Slide calibration” screen onthe Vission/Vantage has a “Current”window, which displays twice the actuatoroutput voltage. This value, (the % volumeand the % capacity) displayed in the“Current Vol” and Current Cap” Windowsare meaningless until calibration has beencompleted.

10. Use the DEC button on the Vission/Vantagepanel to drive the slide valve to its minimum“mechanical stop” position. Do notcontinue to run the actuator in thisdirection after the slide valve has reachedthe stop. Doing so may cause damage tothe actuator or the slide valve.

Press down on the photochopper shaft todisengage the brake, releasing tensionfrom the motor mount. Use the INCbutton to pulse the actuator to where theslide is just off of the mechanical stopand there is no tension on the motorshaft.

11. Quickly press and release the blue buttonon the actuator again. The red LED willnow flash at a slower rate, indication thatthe minimum slide valve position (zeroposition) has been set.

12. Use the INC button on the Vission/Vantage panel to drive the slide to itsmaximum “mechanical stop” position.Do not continue to run the actuator inthis direction after the slide valve hasreached the stop. Doing so may causedamage to the actuator or the slidevalve. Press down on the photochoppershaft to disengage the brake, releasingtension from the motor mount. Use theDEC button to pulse the actuator towhere the slide is just off of its mechani-cal stop and there is no tension on themotor shaft.

13. Quickly press and release the bluebutton on the actuator one more time.The red LED will stop flashing. Theactuator is now calibrated and knows theminimum and maximum positions of theslide valve it controls. Now the capacityor volume channel of the Vission/Vantage can be calibrated.

14. Use the Dec button to move the actuatortowards its minimum position whilewatching the millivolt readout on theVission/Vantage screen. Discontinuepressing the DEC button when themillivolt reading the “Current” windowabove the “Set Min” button is approxi-mately 500 millivolts.

Remove CoverPress Down OnPhotochopper

Do not touch wires, may cause anelectrical shock!

Page 53: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

53

15. Now use the DEC and INC buttons to positionthe slide valve until a value close to 300millivolts is on the screen. Then, press the “SetMin” button in the capacity or volume slidevalve window to tell the controller that this isthe minimum millivolt position. Note: Thevalue in the “Current Cap” or “Current Vol”window has no meaning right now.

16. Use the INC button to rotate the actuatortowards its maximum position while watchingthe millivolt readout on the controller screen.Discontinue pressing the INC button when themillivolt reading in the “Current” window isapproximately 9200 millivolts (7900 millivoltsfor the 2783J qualified analog boards applies toonly VISSION). You are nearing the mechani-cal stop position.

17. Pulse the INC button to carefully move theslide valve until the millivolt readout “satu-rates”, or stops increasing. This is around 9500millivolts (8400 millivolts for 2783 qualifiedanalog boards applies to only VISSION).Record millivolt maximum reading.

18. Pulse the DEC button until the millivolts juststart to decrease. (This is the point where thechannel drops out of saturation).Adjust millivolt value to 300 millivolts belowrecorded maximum millivolts in step #17.

19. Press the “Set Max” button.

20. Press the “Main” button to complete calibra-tion and exit the “Slide Calibration” screen.The controller will automatically energize theactuator and drive it back to its minimumposition (below 5%) for pre-start-up.

21. Note: Now the “Current Cap” or the “CurrentVol” value will be displayed in the window onthe “Main” screen and the “Slide Calibration”screen.

Calibration Procedure of Optical Actuators

22. Gently lower the plastic cover over thetop of the actuator to where it contacts thebase and o-ring seal. After making surethe cover is seated properly, gentlytighten the four #10 screws. Caution:The plastic cover will crack if thescrews are over tightened.

23. Enable the “Slide Non-MovementAlarm” by going to the “Setup” menu andchoosing “Alarm Enable” for the “SlideNon-Movement Option”.

24. This completes the calibration for thischannel either capacity or volume.Repeat the same procedure to the otherchannel.

Page 54: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

54

Installation Instructions For Replacement Of Optical Actuator

CAUTION: WHEN INSTALLING THEOPTICAL SLIDE MOTOR, LOOSENLOCKING COLLAR BEFORE SLIDINGTHE COLLAR DOWN THE SHAFT. DONOT USE A SCREWDRIVER TO PRYLOCKING COLLAR INTO POSITION.

OVERVIEW

Calibration of an optical slide valve actuator is atwo step process that must be down for each actua-tor installed on the compressor. The steps are as fol-lows.

1. The actuator motor control module,located inside the actuator housing, iscalibrated so that it knows the minimumand maximum rotational positions of theslide valve it controls. The calibrated actuator will output 0 VDC at the minimumposition and 5 VDC at maximum position.

2. After the actuator motor control module hasbeen calibrated for 0-5 Volts, the controlling channel corresponding to the actuatormotor ( either the capacity or volume) hasto be calibrated. This instructs the Vission/Vantage control panel to learn the rotational0% position & rotation 100% position ofthe slide valve travel.

Please Note:Because there is an optical sensor on this motor, DONOT attempt to calibration in direct sunlight.

3. Before appling power to the Vission/Vantage disconnect the gray and yellow cable.

4. Power the Vission/Vantage back on.

5. Refer to Calibration Procedure ofOptical Actuators (page 60-62).

Page 55: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

55

Slide Valve Actuator Troubleshooting Guide

Slide Valve Actuator Theory of Operation

The slide valve actuator is a gear-motor with a posi-tion sensor. The motor is powered in the forward andreverse directions from the main computer in the con-trol panel. The position sensor tells the main com-puter the position of the slide valve. The main com-puter uses the position and process information to de-cide where to move the slide valve next.

The position sensors works by optically counting mo-tor turns. On the shaft of the motor is a small alumi-num “photochopper”. It has a 180 degree fence thatpasses through the slots of two slotted optocouplers.The optocouplers have an infrared light emitting di-ode (LED) on one side of the slot and a phototransistoron the other. The phototransistor behaves as a lightcontrolled switch. When the photochopper fence isblocking the slot, light from the LED is prevented fromreaching the phototransistor and the switch is open.When photochopper fence is not blocking the slot, theswitch is closed.

As the motor turns, the photochopper fence alternatelyblocks and opens the optocoupler slots, generating asequence that the position sensor microcontroller canuse to determine motor position by counting. Becausethe motor is connected to the slide valve by gears,knowing the motor position means knowing the slidevalve position.

During calibration, the position sensor records the highand low count of motor turns. The operator tells theposition sensor when the actuator is at the high or lowposition with the push button. Refer to the calibrationinstructions for the detailed calibration procedure.

The position sensor can get “lost” if the motor is movedwhile the position sensor is not powered. To preventthis, the motor can only be moved electrically whilethe position sensor is powered. When the position sen-sor loses power, power is cut to the motor. A capacitorstores enough energy to keep the position sensor cir-cuitry alive long enough for the motor to come to acomplete stop and then save the motor position to non-volatile EEPROM memory. When power is restored,the saved motor position is read from EEPROMmemory and the actuators resumes normal function

This scheme is not foolproof. If the motor is moved

manually while the power is off or the motor brake hasfailed, allowing the motor to free wheel for too longafter the position sensor looses power, the actuator willbecome lost.

A brake failure can sometimes be detected by the posi-tion sensor. If the motor never stops turning after apower loss, the position sensor detects this, knows itwill be lost, and goes immediately into calibrate modewhen power is restored.

Page 56: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

56

Slide Valve Actuator Troubleshooting Guide

The actuator cannot be cali-brated

The actuator goes into calibra-tion mode spontaneously

The actuator goes into calibra-tion mode every time power isrestored after a power loss

Dirt or debris is blocking one or bothoptocoupler slots

The photochopper fence extends lessthan about half way into theoptocoupler slots

The white calibrate wire in the greyTurck cable is grounded

Dirt and/or condensation on the po-sition sensor boards are causing it tomalfunction

The calibrate button is stuck down

The position sensor has failed

Push button is being held down formore that ¾ second when goingthrough the calibration procedure

The white calibrate wire in the greyTurck cable is grounding intermit-tently

A very strong source of electromag-netic interference (EMI), such as acontactor, is in the vicinity of the ac-tuator or grey cable

There is an intermittent failure of theposition sensor

The motor brake is not working prop-erly (see theory section above.)

Clean the optocoupler slots witha Q-Tip and rubbing alcohol.

Adjust the photochopper so thatthe fence extends further into theoptocoupler slots. Make sure themotor brake operates freely andthe photochopper will not contactthe optocouplers when the shaftis pressed down.

Tape the end of the white wire inthe panel and make sure that itcannot touch metal

Clean the boards with an elec-tronics cleaner or compressed air.

Try to free the stuck button.

Replace the actuator.

Depress the button quickly andthen let go. Each ¾ second thebutton is held down counts asanother press.

Tape the end of the white wire inthe panel and make sure that itcannot touch metal.

Increase the distance between theEMI source and the actuator.

Install additional metal shieldingmaterial between the EMI sourceand the actuator or cable.

Replace the actuator.

Get the motor brake to where itoperates freely and recalibrate.

Replace the actuator

Page 57: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

57

The motor was manually movedwhile the position sensor was notpowered.

The motor brake is not workingproperly

The position sensor’s EEPROMmemory has failed

The photochopper is misalignedwith the slotted optocouplers

The photochopper is positioned toolow on the motor shaft.

A motor bearing has failed

There is a loose connection in thescrew terminal blocks

There is a loose or dirty connectionin the yellow Turck cable

The position sensor has failed

There is a broken motor lead orwinding

The thermal switch has tripped be-cause the motor is overheated

Any of the reasons listed in “Themotor operates in one directiononly”

The command shaft is jammed

Broken gears in the gearmotor

Motor is overheating and the ther-mal switch is tripping

Recalibrate.

Get the motor brake to where it op-erates freely and then recalibrate.

Replace the actuator.

Try to realign or replace the actua-tor.

Adjust the photochopper so that thefence extends further into theoptocoupler slots.

Replace the actuator.

Tighten.

Clean and tighten.

Replace the actuator.

Replace the actuator.

The motor will resume operationwhen it cools. This could be causedby a malfunctioning control panel.Consult the factory.

See above.

Free the command shaft.

Replace the actuator.

This could be caused by a malfunc-tioning control panel. Consult thefactory.

Slide Valve Actuator Troubleshooting Guide

The actuator does not transmitthe correct position after apower loss

There is a rapid clicking noisewhen the motor is operating

The motor operates in one direc-tion only

The motor will not move in ei-ther direction

The motor runs intermittently,several minutes on, several min-utes off

Page 58: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

58

Slide Valve Actuator Troubleshooting Guide

Bad thermal switch

Any of the reasons listed in “The mo-tor will not move in either direction”

Stripped gears inside the gear motoror the armature has come un-pressedfrom the armature shaft

Replace the actuator.

See above.

Replace the actuator.

The motor runs sporadically

The motor runs but output shaftwill not turn

Page 59: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

59

Slide Wiring Diagram for Models Vission VSM-91 To VSS-601

Page 60: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

60

Slide Wiring Diagram for Models Vission VSS-751 To VSS-1801

Page 61: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

61

Command Shaft Rotation and Travel

NOTES:

a) The large gear on the command shaft has 50 teeth. The teeth are counted when moving the command shaft from the minimum stop position tothe maximum stop position.

b) The manual operating shaft on the gear motor should be turned the opposite direction of the desired command shaft rotation.c) The capacity and volume control motors are equipped with a brake, if it is necessary to operate the control motors manually, the brake must be

disengaged. The brake can be disengaged by pushing on the motor shaft on the cone end. The shaft should be centered in its travel. Do notuse excessive force manually operating the motor or damage may result.

COMMAND SHAFT ROTATION NO. OF TURNS / ROTATION ANGLE / SLIDE TRAVELCOMP. CAPACITY VOLUME CAPACITY VOLUMEMODEL INC DEC INC DEC TURNS/ANGLE/TRAVEL TURNS/ANGLE/TRAVELVSR 111 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSR 151 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSR 221 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSR 301 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSS 451 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSS 601 CW CCW CW CCW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSS 751 CCW CW CCW CW 1.09 / 392 / 4.283" 0.63 / 227 / 2.473"VSS 901 CCW CW CCW CW 1.09 / 392 / 4.283" 0.63 / 227 / 2.473"VSS 1051 CCW CW CCW CW 1.22 / 439 / 4.777" 0.74 / 266 / 2.889"VSS 1201 CCW CW CCW CW 1.22 / 439 / 4.777" 0.74 / 266 / 2.889"VSS 1501 CCW CW CCW CW 1.36 / 490 / 5.325" 0.82 / 295 / 3.200"VSS 1801 CCW CW CCW CW 1.36 / 490 / 5.325" 0.82 / 295 / 3.200"VSM 71 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 91 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 101 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 151 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 181 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 201 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 301 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 361 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 401 CW CCW CW CCW 0.80 / 288 / 3.141" 0.45 / 162 / 1.767"VSM 501 CCW CW CCW CW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSM 601 CCW CW CCW CW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"VSM 701 CCW CW CCW CW 0.91 / 328 / 3.568" 0.52 / 187 / 2.045"Note:These refer to the old stlye gear mototrs and DO NOT apply to the optical motors.

Table 1

Page 62: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

62

Calibration For Earlier Style Mechanical Gearmotor/Potentiometers

· Capacity Slide Valve Potentiometer Calibra-tion – Move the capacity slides to their mini-mum position. This can be accomplished byeither electrically actuating the slide valvemotor through the Force Outputs On or bymanually actuating the slide valve motor. Tomanually actuate the motor, release the brakeand turn the hex nut on the gear motor in theproper direction to move the capacity slidesto their minimum position (see Table 1).

IMPORTANTAfter the slide valves have contacted the inter-nal stop, release the tension in the mechanismby actuating the brake and then manually turnthe command shaft back one tooth on the com-mand shaft gear. Failure to do so may result inpremature failure of the gear motor.

Remove one of the ¼” socket head capscrews from the potentiometer bracket,loosen the other and turn the potentiometershaft until a millivolt reading of between 900and 1100 is displayed in the Current windowabove the Set Min button. Mesh the potenti-ometer gear with the command shaft gear andreplace the ¼” socket head cap screw. Themillivolt reading must remain between 900and 1100 millivolts. Without changing thegear mesh, remove one ¼” screw, and applyLoctite #242 to the threads. Reinstall thescrew finger tight, then repeat the procedureon the remaining screw (do not change theorientation of the lockwashers on the screws).The gear lash must be adjusted so there is noside load on the potentiometer shaft. Tightenand torque the ¼” socket head cap screw to16 ft/lbs. Recheck the millivolt reading. Itmust be between 900 and 1100 millivolts. Ifnot, the gear mesh will have to be readjusted.

At this point, press the Set Min button inthe Capacity Slide Valve Potentiometer win-dow. Realize that the Current Cap window

will show a value, but it has no meaning atthis point. Now turn the command shaft tothe fully loaded position. With the slidevalve against the mechanical stop, releasethe tension in the mechanism by actuatingthe brake and manually turn the commandshaft back one tooth on the command shaftgear. This is the maximum millivolt posi-tion. Now press the Set Max button. Cali-bration of the slide is completed AFTERpressing the Main button, to exit the SlideCalibration Screen. Now if you re-enter theSlide Calibration Screen, the correct valuewill be displayed in the Current Cap win-dow and on the Main screen.

· Volume Slide Potentiometer Calibration –Move the volume slides to their minimumposition. This can be accomplished by ei-ther electrically actuating the slide valvemotor through the Slide Calibration ScreenINC and DEC buttons, or by manually actu-ating the slide valve motor. To manuallyactuate the motor, release the brake and turnthe hex nut on the gear motor in the properdirection to move the volume slides to theirminimum position (see Table 1).

IMPORTANTAfter the slide valves have contacted the inter-nal stop, release the tension in the mechanismby actuating the brake and then manually turnthe command shaft back one tooth on the com-mand shaft gear. Failure to do so may result inpremature failure of the gear motor.

Remove one of the ¼” socket head capscrews from the potentiometer bracket andloosen the other. Turn the potentiometershaft until a millivolt reading of between 900and 1100 is displayed. Mesh the potentiom-eter gear with the command shaft gear andreplace the ¼” socket head cap screw. Themillivolt reading must remain between 900

Page 63: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

63

Calibration For Earlier Style Mechanical Gearmotor/Potentiometers

and 1100 millivolts. Without changing the gearmesh, remove one ¼” screw, and apply Loctite#242 to the threads. Reinstall the screw fingertight, then repeat the procedure on the remain-ing screw (do not change the orientation of thelockwashers on the screws). The gear lash mustbe adjusted so there is no side load on the po-tentiometer shaft. Tighten and torque the ¼”socket head cap screw to 16 ft/lbs. Recheckthe millivolt reading. It must be between 900and 1100 millivolts. If not, the gear mesh willhave to be readjusted.

At this point, press the Set Min button in theVolume Slide Valve Potentiometer window.Realize that the Current Vol window will showa value, but it has no meaning at this point.Now turn the command shaft to the fullyloaded position. With the slide valve againstthe mechanical stop, release the tensions inthe mechanism by actuating the brake andmanually turn the command shaft back onetooth on the command shaft gear. This is themaximum millivolt position. Now press theSet Max button. Calibration of the slide iscompleted AFTER pressing the Main button,to exit the Slide Calibration Screen. Now ifyou re-enter the Slide Calibration Screen, thecorrect value will be displayed in the CurrentVol window and on the Main screen.

Upgrading from Old Style GearMotors to Optical Actuators.

Refer to the installation instructions that aresupplied with the new Optical Actuators.(VPN 25972A)

Page 64: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

64

Trend Chart

The trend analysis screen shows recorded data for a logging range of either 60 minutes or 120 hours. Additionally,selections can be made to display segments of the logged data.

To view which selections are being shown hit the data select button.

Note: When the panel is powered down, and powered back up, the “Trend Screen” will default to 120 hours even ifyou have chosen 60 minutes. Trend data is not retained.

Page 65: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

65

Data Select Screen

The user has the ability to select which value they would like to see displayed on the graph. Only four selections canbe chosen at once to view, even though all data is being accumulated.

Page 66: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

66

Event List

Touch Here

From the Menu screen, touch the Event List button. The screen on the next page will appear.

Page 67: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

67

The Event List will give a chronological record of the last 40 events recorded by the controller. These events can befiltered by selecting the Filter box on the upper left of the screen.

Event List

Page 68: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

68

Trouble Shooting Flowchart (Vission Only)

MicroController does not boot up, nolights on any boards.

MicroController appears to bebooted, lights seen on boards and E-stop switch, but no touch screen isevident.

MicroController boots up but all datatemperatures and pressures arezeroed and do not update.

Check to make sure 120VAC is run to “L1” on the Relay board.This is the board on the inside left back of the panel. “L1” isthe fifth connector down from the top and the top terminal.The neutral should be brought to any “N” on the relay board.

Check F1 fuse on relay board.

Check F1 fuse on the power supply, located on the front of thedoor. If all of the above is okay, the power supply may be bad.Check DC voltages on the single board computer interfaceboard, which is the big green board above the power supply.Along the right edge of this board, just above the power sup-ply connector J14, are test points. If proper voltages are notlocated at these test points, the power supply may be faulty.

Check cable connections located on the LCD Inverter board.This board is located inside the door on the LCD touch screenback plane above the single board computer. The connectorwith the pink and white wires, located on the left center of theboard is the power supply to the board. The connector on thetop right of the board with the black wires has the data wires.If these are inserted correctly, the problem could be bad solderjoint on the LCD Inverter board or a component failure.

Check Analog board jumpers J41 & J46. They should be onpins 1 & 2 (center and right pins).

Check the upper DIP switch on the analog board. This identifies the node address of the Analog board. Only switch #1should be on, the rest off.

The MicroController has (2) boards running separate programs.The Analog board located inside the panel on the back rightcalculates pressures, temperatures, amps and monitors inputs.The single board computer requests this data for action anddisplay. The single board computer will instruct the Analogboard to activate outputs or relays as needed. Communication between the boards is RS-485 running at 115200 baud.The cable is basically phone cable with phone jack style connectors. The connector to the single board computer is on thetouch screen back panel and is labeled RS-485 Com2 to Analog Bd. The connector on the Analog board is located on thebottom of the board. There are 2 connectors on the analogboard, either one can be used.

If this cable is open or disconnected, there will be no commu-nications between the boards. The top two green lights on theAnalog board (D10 & D11), located on the bottom left of theboard, will be off. The pressures and temperatures will notupdate. Ensure the cable is plugged in correctly. Try rebootingagain. If the problem persists, try moving the cable on theAnalog board to the other connector. If not successful, try adifferent cable on the Analog board to the other connector onthe board. If not successful, try a different cable. Any phonestyle cord should work. If neither of these help, contact theVilter Home Office.

Page 69: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

69

Trouble Shooting Flowchart (Vission Only)

A bank of pressure or temperaturechannels no longer function.

A pressure channel reads a negativenumber over -140

A temperature channel reads a largenegative value over -400°

Screen Cursor will not retain cali-bration.

There are four fuses on the Analog board that limit thecurrent on the 24VDC to the Analog channels. The fusesare 500 milliamp, located near the power supply connec-tors and brown in color. LEDs next to the fuses give avisual indication of the status of the fuse, however, it isbest to pull the fuse and check them with an ohmmeter. Ifany are blown, find the shorted device that is responsiblefor the blown fuse and replace.

F1 protects the +24VDC supply to the pressure transduc-ers and relays.

F2 protects the –12VDC supply which is subregulated to5VDC required for multiplexers, analog to digital convertsand temperature channels.

F3 protects the +12VDC supply, which is subregulated to+5VDC, required for multiplexers, analog to digital con-verters, and temperature channel.

F4 protects the main +5VDC supply required for most ofthe components on the analog board.

If F1 blows, the pressure transducers will produce errone-ous readings and the relays on the relay board will drop out(de-energize). If F2, F3 or F4 blows, all analog readingswill be affected.

This indicates the transducer wiring or transducer is eitheropen or shorted. Check wiring to print.Check fuses F1, F2, F3 and F4 on analog board.

This indicates the RTD wiring or RTD is open. Checkwiring to print.Check fuses F1, F2, F3 & F4 on analogboard.

Calibrate the screen cursor, TWICE, per the instructionsprovided in the manual.

Go to “IP Address” screen and clear IP Address. Re-enterthe same IP address

Go to Change Date/Time and clear both. Re-enterappropriate date and time.

Save changes and backup settings. Power off the panel. Power on the panel.

Verify the screen cursor follows the fingertip correctly.

Page 70: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

70

Safety Failure Message

Suction Pressure SP#1 Fail - This message will appear when the suction pressure falls below thesafety setting of the Lo Suction Pressure Trip Setpoint No.1. Inaddition, this message will appear when the suction pressure readingrises above 300 PSI, indicating an open transducer or bad analogchannel.

Suction Pressure SP#2 Fail - This message will appear when the suction pressure falls below thesafety setting of the Lo Suction Pressure Trip Setpoint No.2. Inaddition, this message will appear when the suction pressure readingrises above 300 PSI, indicating an open transducer.

Discharge Pressure SP#1 Fail – This message will appear when the discharge pressure exceeds thesafety setting of the Hi Dsch Press Trip Setpoint No. 1 . In addition,this message will appear when the discharge pressure reading fallsbelow 30” Hg, indicating a shorted transducer.

Discharge Pressure SP#2 Fail – This message will appear when the discharge pressure exceeds thesafety setting of the Hi Dsch Press Trip Setpoint No. 2 . In addition,this message will appear when the discharge pressure reading fallsbelow 30” Hg, indicating a shorted transducer

Suction Temp Fail – This message will appear when the suction temperature falls below thesafety setting of the Low Suction Temperature Trip setpoint. In addition,this message will appear when the suction temperature rises above 400degrees, indicating an open RTD.

Discharge Temp Fail – This message will appear when the discharge temperature rises abovethe safety setting of the High Discharge Temperature Trip setpoint. Inaddition, this message will appear when the discharge temperature fallsbelow -30 degrees, indicating a shorted RTD.

Oil Separator Start Temp Fail – This message will appear when the Oil Separator Temp is below theLow Oil Separator Start Temp Trip setpoint. In addition this messagewill appear after the Oil Separator Temp Safety Changeover timer timesout and the Oil Separator temperature fails to rise above the Low OilSeparator Start Temp Reset after the compressor is started.

Oil Separator Run Temp Fail – This message will appear when the Oil Separator Temp is below theLow Oil Separator Run Temp Reset setpoint after the Oil SeparatorTemp Safety Changeover timer times out.

Percent Capacity Fail – This message will appear if the percent capacity reading exceeds 300%or goes below –15%.

Page 71: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

71

Safety Failure Message

Percent Volume Fail – This message will appear if the percent volume reading exceeds 300% orgoes below –15%.

Lo Control Temperature Fail – This message will appear when the Process Control Temperature fallsbelow the safety setting of the Lo Control Temperature Trip Setpoint. Inaddition, this message will appear when the Process Control Temperaturerises above 300 degrees F, indicating an open RTD.

Lo Start Oil Pressure Fail – This message will appear with the Prelub Oil Pressure (Manifold minusDischarge) has remained below the Prelub Oil Pressure Reset setpoint.The Prelub Oil Pressure must be above the Prelub Oil Pressure for a timeperiod of the Minimum Compressor Prelub time. It will continue to try todo this for a time period of the Prelub Oil Pump Time Limit. When thePrelub Oil Pressure fails to achieve this, then the failure message willoccur.

Lo Oil Pressure Fail – This message will appear when the Running Oil Pressure (Manifold minusSuction) has remained below the low Oil Pressure Reset setpoint when theOil Pressure Bypass at Compressor Start timer times out. This messagewill also appear when the Runnning Oil Pressure falls below the Low OilPressure trip setpoint after the Oil Pressure Bypass at Compressor Starttimer times out.

Lo Oil Injection Temp Fail – This message will appear when the Oil Injection temperature falls belowthe Low Oil Injection Temperature trip setpoint. This message will alsoappear when the Oil Injection temperature fails to rise above the Low OilInjection Temperature reset setpoint after the Low Oil Injection TempBypass timer times out.

Hi Oil Injection Temp Fail – This message will appear when the Oil Injection temperature rises abovethe High Oil Injection Temperature trip setpoint.

Manifold Pressure Fail – This message will appear with the manifold pressure rises above 300 PSIor falls below 30” Hg.

Filter Inlet Pressure Fail – This message will appear with the manifold pressure rises above 300 PSIor falls below 30” Hg.

Start Filter Diff Press Fail – This message will appear if the Filter Differential pressure rises above theHigh Fltr Diff Press – Start setpoint before the Filter Differential PressureSafety Changeover timer times out.

Page 72: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

72

Safety Failure Message

Run Filter Diff Press Fail – This message will appear if the Filter Differential pressure rises above theHigh Fltr Diff Press – Run setpoint after the Filter Differential PressureSafety Changeover timer times out.

Maximum Amperage Fail – This message will appear if the motor amperage rises above the Hi MotorAmps trip setpoint.

Motor Starter Aux Contact Fail – This message will appear if the Motor Auxiliary contact fails to closebefore the Compressor Starter Auxiliary Contact Bypass timer times out.Refer to wiring diagram.

Auxiliary Safety#1 Input Fail – This message will appear when power is removed from the input modulethat is designated as “Auxiliary #1 Safety” (please refer to your wiringdiagram).

Lo Oil Separator Level Fail – This message may appear when power is removed from the input modulethat is designated as “Lo Separator Oil Level Trip” (please refer to yourwiring diagram). This safety has an associated delay. The associateddelay timer is the Lo Oil Separator Level Bypass Timer. This safety willactivate only after the oil level has been low after the timer times out.

Page 73: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

73

Supressor Kit Installation

Page 74: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

74

Flash Card Installation Instructions

Disconnect the Connector AndRibbon As Shown

Remove (4) Screws, One InEach Corner Of Board

Flip Board Over ToView Flash Card

VANTAGE/VISSION

EMERGENCYSTOP BUTTON

Hit The Emergency Stop BottonLocated In Front Of the Panel

Verify Unit is Shut Down Completely

Verify Lockout Disconnect On Compressor Start.This Ensures Compressor Does Not Start.

Proceed As Follows

Note: Before Powering Down To Replace Flashcard, You MustCopy Down All Setpoints As These Will Need To Be Re-enteredWhen New Flashcard Is Installed.

View Inside Of Door

Page 75: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

75

Flash Card Installation Instructions

Flip Board Back Into Postion

Reconnect Connectors and Ribbons

Secure Board To MountsWith Previously Removed Screws

Press Latch To Release Flashcard

Remove Flashcard And Replace

Note: You Must Re-enterSetpoints And Recalibrate SlideValves.See Section On Setpoint Values And the Section On Optical Actuators.

Page 76: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

76

Back Light Installation Instructions

Flip Board Over

Disconnect RibbonUnplug Connector

Remove (Four) Screws AndTurn Board Over

Remove (Four) NutsRemove Board

Page 77: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

77

Back Light Installation Instructions

Remove Small ScrewAnd Slide Back LightOut As Shown

Slide New Back Light In AndSecure With Previously Removed Screw

Page 78: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

78

Back Light Installation Instructions

Place Board Back Onto Back Of Panel AndSecure With Previously Removed Nuts

Place Board Back Into Postion And Secure

Connect Ribbon And PlugConnector Back In

Page 79: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

79

Transducer Wiring

Page 80: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

80

System Setpoints Alarms and Trips Work Sheet

SAFETY SYSTEM VALUES VALUE LIMITS DEFAULT VALUESSETPOINTS ALARM TRIP RESET ALARM TRIP RESET ALARM TRIP RESET

LO SUCTION TEMP -99/300 -99/300 -99/300 -45 -50 -40

HI DISCHARGE TEMP -30/260 -30/260 -30/260 205 210 200

LO OIL SEP START TEMP 50/200 50/200 50/200 75 70 80

LO OIL SEP RUN TEMP 50/200 50/200 50/200 105 100 110

LO OIL INJECT TEMP 50/160 50/160 50/160 95 90 100

HI OIL INJECT TEMP -99/160 -99/160 -99/160 140 145 135

LO CONTROL TEMP (3) (2) -99/210 -99/210 -99/210 -50 -55 -45

HI CONTROL TEMP (3) (2) -99/210 - - - - - - 100 - - - - - -

LO SUCT PRESSSETPOINT #1 30”/300 30”/300 30”/300 3” 4” 3”SETPOINT #2 30”/300 30”/300 30”/300 1” 2” 1”

HI DISCHARGE PRESSSETPOINT #1 30”/350 30”/350 30”/350 210 220 205SETPOINT #2 30”/350 30”/350 30”/350 220 230 215

PRELUB OIL PRESSURE - - - 4/300 4/300 - - - 4 5

LO OIL PRESSURE (2) 18/300 18/300 18/300 38 35 40

HI START FLTR DIFF PR 30”/50 30”/50 30”/50 50 50 25

HI OIL RUN FILTER DIFF PR(1) 30”/40 30”/40 30”/40 12 15 10

HI AMPS LIMIT (4)(5) 0/1000 0/1000 0/1000 15 15 - - -

NOTES:

(1) If your unit is equipped with new style filters (Vilter Part #3109B or 3110B), the Alarm should be set at 37 psig, Trip at 40 psig and Resetat 35 psig.

(2) For boosters, set Alarm at 28 psig, Trip at 25 psig, Reset at 30 psig.(3) Set Alarm at 60% and Trip at 70% of full load motor nameplate amps. Only if Process Temp Control(4) Set Alarm at 120% and Trip at 125% of full load motor nameplate amps.

Page 81: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

81

SYSTEM CONTROL LIMIT VALUES WORKSHEET

CONTROL SYSTEM VALUES VALUE LIMITS DEFAULT VALUESLIMITS CUT IN CUT OUT CUT IN CUTOUT CUT IN CUT OUT

SUCTION PRESSURE ON/OFF (1) SETPOINT #1 30”/150 30”/150 10 6 SETPOINT #2 30”/150 30”/150 15 11SUCT PR CAP INCREASE (1) SETPOINT #1 30”/150 30”/150 20 25 SETPOINT #2 30”/150 30”/150 20 25SUCT PR CAP DECREASE (1) SETPOINT #1 30”/150 30”/150 18 23 SETPOINT #2 30”/150 30”/150 18 23HIGH DSCH PRESS UNLD (1) SETPOINT #1 0/300 0/300 200 190 SETPOINT #2 0/300 0/300 210 200LIQ INJECTION SOLENOID CONTROL ON OFF ON OFFTEMP VIA: OIL INJECTION TEMPERATURE 200°F 50°F 120°F 105°F OIL SEPARATOR TEMPERATURE 200°F 50°F 120°F 105°FOILPMP RESTART (D/S) 1.0/8.0 1.0/8.0 2.8 3.0OIL SEPARATOR HEATER 80/130 80/130 95 105CAP CTRL °F ON/OFF (2) SETPOINT #1 -99/200 -99/200 20 10 SETPOINT #2 -99/200 -99/200 25 15CAP CTRL °F INCR (2) SETPOINT #1 -99/300 -99/300 28 27 SETPOINT #2 -99/300 -99/300 33 32CAP CTRL °F DECR (2) SETPOINT #1 -99/200 -99/200 24 25 SETPOINT #2 -99/200 -99/200 29 30LAG, CAPACITY STEP (3) 0/100 - - - 10 - - -VOL SLIDE ADJ FACTOR -100/100 - - - 0% - - -MINIMUM RUN CAPACITY 10% / 90% - - - 30 - - -LEAD, MAXIMUM CAP FLAG (3) 50/100 50/100 95 90ECONOMIZER SOLENOID 0% / 100% 0% / 100% 80% 75%‘VOL ADJ CAP RANGE 0/100 - - - 100% 100%LOW SUCTION PRESS LOAD LIMIT SETPOINT #1 SETPOINT #2LOW SUCTION PRESSURE LOAD LIMIT ON OFF ON OFF SETPOINT #1 30 35 SETPOINT #2 40 45MOTOR AMPS LOAD LIMIT (4) SETPOINT #1 0/999 0/999 5 10 SETPOINT #2 0/999 0/999 5 10

C/T RATIO C/T RATIO C/T RATIOCURRENT TRANSFORMER (1) 100-1000/AMPS 100/5 AMPS

NOTES:(1) Must be field set.(2) Set only if temperature is used for capacity control.(3) Set only if Lead/Lag option is selected.(4) Set FLA at nameplate amps, MAX at nameplate + service factor.

System Control Limit Values Work Sheet

Page 82: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

82

The values or options in the screen displays shown must be entered before start-up.

SYSTEM CONTROL LIMIT VALUES WORKSHEET

TIMER VALUES SYSTEM VALUES VALUE LIMITS DEFAULT VALUES

AT START CAPACITY DECREASE 0/999 SEC 15 SEC

CAPACITY INCREASE MOTOR ON 0/255 SEC 2 SEC

CAPACITY DECREASE MOTOR ON 0/255 SEC 2 SEC

CMP STARTER AUX CONTACT BYPASS 0/255 SEC 10 SEC

CAP INCREASE MOTOR OFF 0/255 SEC 20 SEC

CAP DECREASE MOTOR OFF 0/255 SEC 10 SEC

VOL SLIDE ADJ TIMER 0/255 SEC 20 SEC

MINIMUM CAP PRELUB TIME 0/255 SEC 5 SEC

RUN CYCLE OIL PRESS BYPASS 0/90 SEC 60 SEC

PRELUB PUMP TIME LIMIT 0/255 SEC 255 SEC

FLTR DIFF PR SAFETY CHANGEOVER 0/999 SEC 60 SEC

LO OIL SEP LEVEL BYPASS TIMER 0/120 SEC 60 SEC

AUTO RESTART AFTER POWER FAIL 1/240 MIN 5 MIN

OIL SEP TEMP SAFETY CHANGEOVER 0/15 MIN 5 MIN

LO OIL INJ TEMP SFTY CHANGEOVER 0/15 MIN 6 MIN

ANTIRECYCLE STRT TIMER (MIN) (1) 0/30 MIN 20 MIN

FORCE START LAG COMP (MIN) (2) 0/60 MIN 30 MIN

HOT STRTS/HR COUNTER (COUNTS) (1) 1/10 COUNTS 3 COUNTS

NOTES:(1) Must be field set.(2) Set only if Lead/Lag option is selected.

System Timer Values

Page 83: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

83

EM

ER

GE

NC

Y

ST

OP

VIS

SIO

Nm

icro

-co

ntro

ller

SU

BP

AN

EL

LA

YO

UT

DO

OR

LA

YO

UT

DE

TA

IL-A

RT

D J

UM

PE

R C

ON

FIG

UR

AT

ION

ST

AN

DA

RD

JU

MP

ER

SE

TT

ING

ST

RA

NS

DU

CE

R J

UM

PE

R C

ON

FIG

UR

AT

ION

ST

AN

DA

RD

JU

MP

ER

SE

TT

ING

S

DE

TA

IL-B

SE

E D

ET

AIL

-B

SE

E D

ET

AIL

-A

INT

ER

NA

L4

-20

mA

EX

TE

RN

AL

4-2

0 m

AR

TD

Page 84: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

84

Spare Parts

PART DESCRIPTION VILTER PART NUMBER QTY.

Analog Board (VISSION PANEL) 3011A 1Analog & Relay Board (VANTAGE PANEL) 3011C1 1Control Relay, 4PDT 3011B1 1Control Relay, DPDT 3011A1 1Control Relay, SPDT 3011Z 1Input Module 2895M (120v) 1Output Module 2895N (120v) 1Output Module Fuse 2895P 1Panel Fuse, ½ Amp 3011V 1Panel Fuse, 10 Amp 3011W 1Panel Fuse, 4 Amp 2895P 1Power Supply 3011K 1Relay Board (VISSION) 3011B 1Pressure Transducer 2783J 1Resistance Temperature Detector 2611G 1Fuse Kit (VISSION PANEL) 3011F 1Fuse Kit (VANTAGE PANEL) 3011F1 1VISSION SBC Sub-Assembly 3011ML 1Modbus Cable 3011X 1VISSION Cable Kit 3011Y 1RTD/Transducer Cable 3122B 1Cable Kit (VANTAGE PANEL) 3011Y1 1Modbus Cable Kit (VANTAGE PANEL) 3011X1 1CORD SET RK4T-4/ 5618Turk 3122B 164m Flashcard 3011FC-1 1Lighted Emergancy Switch 3011H 1Snubbers 3030C 1Supressor Kit KT785 1

*Supplied with 120VAC. input& output modules.

Page 85: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

85

Using Danfoss Transducers with 2783J qualifiedboards

The analog boards used in the Vission and Vantagepanels after July 2003 have been modified to ac-commodate the use of Danfoss transducers (VPN2783J). These analog boards are denoted as “2783Jqualified” boards. The use of 2783J qualified boardswith Danfoss transducers require that scaling fac-tors for the Danfoss pressure transducers be checkedand modified if necessary.

The scale factors for all transducers are located at aspecific Index location in Vission/Vantage database.Refer to Figure 1. This table shows the proper scalefactors for each type of transducer as well as theIndex location of the scaling factor for each trans-ducer.

N660 3950

Value* : The value 3950 shown is the Scale Factor for transducers manufactured by Ametek andSetra. This does NOT include Danfoss transducers. If Danfoss transducers are being used with2783J qualified boards, the “Value” at the Indexes shown above needs to be modified to 4297.The procedure on the next page describes how to modify the scaling factor.

Figure 1. Transducer Index Table and Scale Factors

Vission and Vantage (VSS and SOI units) Vission (VRS units)Transducer Index Value* Transducer Index Value*Suction N658 3950 Suction N658 3950Discharge N659 3950 Discharge N659 3950Man/Filter Out N660 3950 Manifold N660 3950Filter In N661 3950 Filter Inlet N661 3950

Filter Outlet (Retrofit) N664 3950

Vission and Vantage (Cool Compression units) Vantage (Recip)Transducer Index Value* Transducer Index Value*Suction N658 3950 Suction N658 3950Discharge N659 3950 Discharge#1 N659 3950Man/Filter Out N660 3950 Filter Out N660 3950

Filter Inlet N661 3950Discharge#2 N662 3950Oil Manifold N663 3950Crankcase N664 3950

Modifications for Analog Board (Vission/Vantage after July 2003)

Page 86: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

86

The procedure to Change Scale Factors on 2783JQualified Board

1. From the Main Screen, press the Menu button.2. From the Menu Screen, press the Vilter ONLY

screen.3. Logon4. From the Vilter ONLY screen, press the Raw

Data Screen button.You will now see a screen labeled “DataTest”, containing 4 columns, 2 labeled “Index” and 2 labeled “Value”.

5. Press the “Set” button and then press one of theblank boxes under either one of the Index col-umns.

6. A keypad will be displayed. Now type in“N658” (without the quote marks). Press the OKbutton. (Per the table, this is the Index for theSuction Pressure transducer.)

7. You are now returned to the “Data Test” screen.You will see “N658” in the box that you touched,and you will see the value 3950 in the corre-sponding “Value” box. This is the scale factorthat will be changed.

8. Now press the “Set” button again, and press the“Value” box that contains the value 3950. Anumeric keypad will now be visible.

9. Press the Clear button. Now press the buttons4297, followed by pressing the “Enter” button.You will now be returned to the “Data Test”screen, and the Value field that previously con-tained 3950 now contains the Value 4297. Perthe table below, you have now corrected thescaling factor for the Suction Pressure trans-ducer.

10. Continue this process, entering in “Index” val-ues and changing the scaling factors for all trans-ducers. (Reference Figure 1 below.)

11. When completed, press the OK button and re-turn back to the main screen.

12. Now go to the LOGON screen and perform a“BACKUP SETTINGS”. After a minute or so,the new scale factors will be “active”.

13. You may now need to recalibrate your trans-ducers again, as the new scale factors will af-fect the current readings of the transducers. Ifyou have gauges on your system, you can dothis using your gauge readings. When you havecompleted re-calibration of all your transduc-ers, do another “BACKUP SETTINGS”.

Modifications for Analog Board (Vission/Vantage after July 2003)

2895A 3011A Vission 3011C1 Vantage 3011A Vission 3011C1 Vantage(2783J qualified) (2783J qualified)

Ametek Yes Yes Yes Yes YesVPN 2783G

Danfoss No* No No Yes-Rescale Yes-RescaleVPN 2783J

Setra Yes Yes Yes Yes YesVPN 2783K

Table II The acceptable mix of analog boards and transducers.

No* = this combination of board and transducer will result in a very slight scaling error (2 percent error over entire0-300 PSIG range of transducer). Vilter does not recommend using the Danfoss transducer with a 2895A board.

Warning -If a Danfoss Transducer is used with a non-qualified 2783J Analog Board, the transducer will notproperly read pressures over 165 PSIG.

Page 87: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

87

1. Press “Setup”2. Select “Enable” for Liquid Pos. Valve3. Press “OK”4. Press “Vilter Only”, you will be prompted to Log In5. Press “Liquid Inj. Temp Control” then you will see the

screen as in the attached picture “Liquid Inj. Control”,the values you see there are default and can be changedaccording to your application.

Setup Screen

Vilter Only Screen

Liquid Inj. Temp Control Screen

NOTE:

Consult the VSS / VSM / VSR Unit Manual for properDanfoss ICM valve setup procedure.

Danfoss Liquid Injection Valves

Page 88: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

88

If service is required, first contact your equipment distributor or contactA Vilter Technical Service Representative at:

Note: It will be necessary to have your Vilter order number availablewhen contacting Vilter Manufacturing Corporation for service support.

Disclaimer: Specifications are subject to change without notification.

Who to Contact

Vilter Manufacturing LLC5555 South Packard Ave.

PO Box 8904Cudahy, WI 53110-8904

Tel: 414-744-0111Fax: 414-744-1769

e-mail: [email protected]

www.vilter.com

Page 89: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

89

Page 90: Vission Control Manual - Emerson · PDF file3 Important Note Before applying power to the VISSION MicroController panel, all wiring to the panel should be per NEC. Specifically check

Vilter Manufacturing LLC are trademarks of Emerson Electric Co. or one of its affi liated companies.©2011 Emerson Climate Technoligies, Inc. All rights reserved. Printed in the USA.

35391SA Rev 06