Powerware 5125 (9910-P33) UPSInstallation Guide for IBM Applications®

®

Page 2: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

IBM, pSeries, AIX, xSeries, AS/400, OS/400, and RS/6000 are registered trademarks and iSeries, OpenPower, andi5/OS are trademarks of International Business Machines Corp.Powerware and LanSafe are registered trademarks and X-Slot and ConnectUPS are trademarks of Eaton PowerQuality Corporation.Microsoft and Windows are registered trademarks of Microsoft Corporation.Linux is a registered trademark of Linus Torvalds.Burndy is a registered trademark of Framatone Connectors International.

ECopyright 2001–2005 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may bereproduced in any way without the express written approval of Eaton Corporation.

Page 3: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

Special SymbolsThe following are examples of symbols used on the UPS or accessories to alert you to importantinformation:

RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and theassociated warning should be observed.

CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual foradditional information, such as important operating and maintenanceinstructions.

This symbol indicates that you should not discard the UPS or the UPS batteriesin the trash. This product contains sealed, lead-acid batteries and must bedisposed of properly. For more information, contact your local recycling/reuse orhazardous waste center.

This symbol indicates that you should not discard waste electrical or electronicequipment (WEEE) in the trash. For proper disposal, contact your localrecycling/reuse or hazardous waste center.

Page 4: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

This page intentionally left blank.

Page 5: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C i

Table of Contents

1 Installation 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Parts List 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UPS Internal Battery Connection 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Setup and Installation 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tools Required 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rack-Mount Setup 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

EBM Installation 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UPS Installation 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Remote Emergency Power-off Installation 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power Connections and Startup 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Load Segments 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 Operation 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Turning the UPS On 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Starting the UPS on Battery 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Turning the UPS Off 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating Modes 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Normal Mode 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Battery Mode 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Bypass Mode 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Standby Mode 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Configuration Mode 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 Communication 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Single-Port Card 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Communication Options 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

i5 Interface Overview 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

iSeries or AS/400 Interface Overview 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

i5, iSeries, or AS/400 and Serial Server Interface Overview 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Serial (TTY) Interface Overview 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

p5 or pSeries with Logical Partitions Interface Overview 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4 Service and Support 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 6: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

TABLE OF CONTENTS

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev Cii

This page intentionally left blank.

Page 7: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 1

Chapter 1 Installation

Parts List

Table 1. P33 Base Configuration

Quantity IBM MN IBM FC IBM PN Eaton PN Description

1 P33 — 21P7219 05147155-3901 P33 UPS 3000 VA, 2700W

1 — — 21P7229 05147532-3901 P33 Accessory Kit

Table 2. P33 Application Matrix

IBMMN IBM FC IBM PN Eaton PN DescriptionQuantity forp5/pSeries®

Rack Worldwide

Quantity fori5/iSeriest

Rack Worldwide

— 53P1963 103002841-3901 Left Rail (2U device)

— 6630 53P1964 103002842-3901 Right Rail (2U device) 1 each per P33 UPS

— 53P1965 103002843-3901 Rail Hardware Kit

p

— 29361 97P3886 103003564 Relay Interface Card andCable (7.6m/25 ft) Kit

— 1

— 29742 39J2590 103004770-3901 7188 and/or 9188 PDU to UPSPower Cord (1.2m/4 ft)

1 per P33 UPS

Varies Varies Varies Varies UPS Input Power Cord 1 per P33 UPS

1Maximum: One FC 2934, 2936, or 2939 per P33 UPS.2 For use with 7188 or 9188 PDU.

Page 8: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C2

Table 3. P33 Options Matrix

IBMMN IBM FC IBM PN Eaton PN DescriptionQuantity for

p5/pSeries RackWorldwide

Quantity fori5/iSeries RackWorldwide

— 29341 53P4619 103002974-5501 -X Web/SNMPCard2 KitConnectUPSt Min: 0, Max: 1 —

— 29391 39J2627 103004741-5501 Relay-Serial Card and CableKit

— Min: 0, Max: 1

— 2938 38P9307 103003637-3901 Powerware EnvironmentalMonitoring Probe (EMP) andCAT 5 Cable (1.8m/6 ft) Kit

Min: 0, Max: 1Co-requisite:

FC 2934

— 6607 21P7221 05147156-3901 Extended Battery Module(EBM)

Min: 0, Max: 4

— — 53P0865 05147533-3901 EBM Accessory Kit 1 per FC 6607

— 53P1963 103002841-3901 Left Rail (2U Device)

— 6630 53P1964 103002842-3901 Right Rail (2U Device) 1 each per FC 6607

— 53P1965 103002843-3901 Rail Hardware Kit

p

— 2916 04N7025 05146401-3901 120V Convenience PDU3(for modems, etc.)

Min: 0, Max: 1

1Maximum: One FC 2934, 2936, or 2939 per P33 UPS.2 ConnectUPS-X Web/SNMP Card required if implementing Logical Partitions (LPARs) on p5 or pSeries.3 Powered from rack PDU receptacle (10A type).

Table 4. P33 Accessory Kit (21P7229)

Quantity Eaton PN Description

1 164201383 Powerware 5125 Two-in-One UPS (2400–3000 VA) User’s Guide

1 164201356 Powerware 5125 (9910-P33) Installation Guide for IBM Applications

3 60420055 IEC 320-C13 to C14, 10A Equipment Power Cords (1.8m/6 ft)

1 Bag — Cord Retention Clips

1 05146745 Software Suite CD

1 124102022-002 UPS to Server Communication Cable (DB-9 to DB-9, 1.8m/6 ft)

Page 9: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 3

Table 5. EBM Accessory Kit (53P0865)

Quantity Eaton PN Description

1 164201358 Powerware 5125 (9910-P33) EBM Installation Guide for IBM Applications

1 152600834 EBM Cable

UPS Internal Battery Connection

NOTE Check the battery recharge date on the shipping carton label. If the date has expired

and the batteries were never recharged, do not use the UPS. Contact your service

representative.

To ensure proper battery operation before installing the UPS:

1. Verify that the UPS is off and unplugged.

2. Remove the packing material (see Figure 1).

Figure 1. Removing Packing Material

3. Connect the internal battery connector (see Figure 2).

NOTE A small amount of arcing may occur when connecting the batteries. This is normal

and does not damage the unit or present any safety concern.

Page 10: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C4

Figure 2. Connecting the Internal Battery Connector

4. Install the UPS front cover (see Figure 3).

Figure 3. Installing the Front Cover

Setup and InstallationThe P33 UPS can be purchased separately or factory-installed in an IBMiSeries or pSeries rack.

NOTE If the UPS is pre-installed in an IBM pSeries (RS/6000) system, continue to “EBM

Installation” on page 6 or “UPS Installation” on page 7.

Tools RequiredTo assemble the components, the following tools may be needed:

S Medium flat-bladed screwdriver

S #2 Phillips screwdriver

Page 11: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 5

Rack-Mount SetupThe UPS can be installed in 19-inch racks and needs only 2U of valuablerack space.

CAUTIONThe UPS and EBM are heavy. A minimum of two people are required to lift the cabinets into

the rack.

NOTE Fixed mounting rails are required for each UPS and EBM cabinet. If fixed rails are

not already installed in your rack, contact your local IBM representative to order a rail kit(s). If

you are installing the UPS in a non-IBM rack, contact your Powerware representative.

To install the UPS in a rack:

1. Place the UPS on a flat, stable surface with the front of the UPSfacing toward you.

2. Attach the supplied mounting handles to the mounting brackets andsecure with the supplied screws (see Figure 4).

3. If installing optional EBMs, repeat Steps 1 and 2 for each cabinet.

Mounting Handle

MountingBracket

Figure 4. Installing the Mounting Handles

NOTE The UPS and EBMs MUST be installed at the bottom of the rack. If placed in a rack

with existing equipment, the rack must be reconfigured to allow the UPS installation at the

bottom of the rack.

NOTE The EBMs must be installed below the UPS as shown in Figure 5.

4. Slide the UPS and any optional EBMs into the rack.

5. Secure the units to the rack according to the rail kit instructions.

Page 12: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C6

UPS

OptionalEBMs

Figure 5. Rack-Mount UPS with EBMs

EBM Installation

NOTE Up to four EBMs may be connected to the UPS. If there are two UPSs in a rack, up to

two EBMs may be connected to each UPS.

To install an optional EBM(s):

1. Verify that all battery circuit breakers are in the OFF (O) position(see Figure 6).

2. Plug the EBM cable(s) into the battery connectors as shown inFigure 6. Up to four EBMs may be connected to the UPS.

3. Continue to the following section, “UPS Installation.”

Battery Circuit Breaker

UPS Battery

Connector

EBMCable

Power CordCommunication Port

EBM BatteryConnectors

REPO Port

OutputReceptacles

Circuit BreakersInput Connector

ON OFF

Figure 6. Typical EBM Installation

Page 13: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 7

UPS Installation

NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to

your equipment and void your warranty.

To install the UPS:

1. If you are installing power management software, connect yourcomputer to the UPS communication port or optional X-Slott card(see Table 10 on page 26). For the communication port, use onlythe serial cable supplied in the P33 accessory kit.

2. If your rack has conductors for grounding or bonding of ungroundedmetal parts, connect the ground cable (not included) to the groundbonding screw.

REPO PortIEC 320-C19 Receptacle

Battery Connector

16A, IEC 320-C20Input ConnectorCommunication Port IEC 320-C13 Receptacles

X-Slot CommunicationBay

CircuitBreakersGround Bonding Screw

Figure 7. UPS Rear View

3. If an emergency power-off (disconnect) switch is required by localcodes, see the following section, “Remote Emergency Power-offInstallation” to install the REPO switch before powering on theUPS.

4. Continue to “Power Connections and Startup” on page 9.

Page 14: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C8

Remote Emergency Power-off InstallationThe P33 includes a REPO port that allows power to be switched off atthe UPS output receptacles from a customer-supplied switch in aremote location.

The REPO feature shuts down the protected equipment immediatelyand does not follow the orderly shutdown procedure initiated by anypower management software.

Any devices that are operating on battery power are also shut downimmediately. When the REPO switch is reset, the equipment will notreturn to battery power until the UPS is manually restarted.

If the Off button is pressed after the REPO is activated, the UPSremains in Standby mode when restarted until the On button ispressed.

WARNINGThe REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be

separated from any hazardous voltage circuits by reinforced insulation.

CAUTIONTo ensure the UPS stops supplying power to the load during any mode of operation, the

input power must be disconnected from the UPS when the emergency power-off function is

activated.

NOTE The REPO function activates when the REPO contacts close.

NOTE If the REPO function is not needed, the REPO connector must remain installed in the

REPO port on the UPS rear panel.

NOTE For Europe, the emergency switch requirements are detailed in Harmonized

document HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety,

Chapter 46: Isolation and Switching.”

To install the REPO switch:

1. Verify that the UPS is off and unplugged.

2. Remove the REPO connector from the REPO port on the UPS rearpanel.

Page 15: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 9

3. Connect isolated, normally-open, dry contacts (rated to handle60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum)across the REPO device to Pin 1 and Pin 2 (see Figure 8).Use stranded, non-shielded wiring, size 0.75 mm2–0.5 mm2

(18–20 AWG).

NOTE A separate contact must simultaneously cause UPS input AC power to be removed.

4. Reconnect the REPO connector to the REPO port.

Pin 1 Pin 2

Figure 8. REPO Connector

5. Verify that the externally-connected REPO switch is not activated toenable power to the UPS output receptacles.

6. Plug in the UPS and start the UPS by pressing the On button.

7. Activate the external REPO switch to test the REPO function.

8. De-activate the external REPO switch and restart the UPS.

Power Connections and StartupThe device power cord connection(s) determines if the setup canprovide dual-redundant power to the protected device(s). See Figure 9for a non-redundant powered device; Figure 10 shows a dual-redundantpowered device.

Legend (Figure 9 and Figure 10)

1 UPS to utility (mains) power cord

2 PDU to UPS power cord

3 PDU to utility (mains) power cord

Page 16: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C10

UPS

PDU

Mains 1 2

Figure 9. Connecting One PDU (Non-Redundant) to UPS

Mains1 2 3

TVSS Protected orSecond UPSUPS

PDU

Mains

PDU

Figure 10. Connecting Two PDUs (Dual-Redundant) to UPS

1. If you are installing a UPS and non-redundant power to the device(s)is desired, plug the PDU power cord into the UPS output receptacle(see Figure 9) using the supplied power cord.

If you are installing a UPS and dual-redundant power to thedevice(s) is desired, two PDUs are required. Plug the first PDUpower cord into the UPS output receptacle (see Figure 10) usingthe supplied power cord. Then plug the second (redundant) PDUpower cord into a non-UPS protected output receptacle (mains) orinto a second UPS.

NOTE The redundant power source must be protected with Transient Voltage Surge

Suppression (TVSS).

2. Insert the supplied cord retention clips by each output receptaclethat will be used (see Figure 11).

Page 17: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 11

Figure 11. Attaching the Cord Retention Clips

3. Plug the equipment to be protected into the appropriate UPS outputreceptacles (see page 15 for more information on load segments).

Table 6. Plug Types Supported

IBM Plug Type Description Quantity Supported

— IEC 320-C14 9

— IEC 320-C20 1

NOTE DO NOT protect laser printers with the UPS because of the exceptionally high

power requirements of the heating elements.

NOTE To prevent an overload alarm, verify that the total equipment ratings do not exceed

the UPS capacity.

4. Bend and twist the cord retention clips around the equipmentpower cords to secure the cord connections (see Figure 11).

5. If you installed an optional EBM(s), remove the breaker tie from allbattery circuit breakers.

Switch all battery circuit breakers to the ON ( ) position.

6. Plug the detachable UPS power cord into the input connector onthe UPS rear panel.

Page 18: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C12

7. Plug the UPS power cord into a power outlet.

All front panel indicators flash briefly and then only the indicatorflashes, indicating the UPS is in Standby mode with the equipmentoffline. If the alarm beeps or a UPS alarm indicator stays on, refer to“Troubleshooting” in the Powerware 5125 Two-in-One UPS(2400–3000 VA) User’s Guide.

8. Press and hold the On button until you hear the UPS beep(approximately one second).

The indicator illuminates solid and the load level indicatorsdisplay the percentage of load being applied to the UPS. The UPS isnow in Normal mode and supplying power to your equipment.

NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is

recommended that the batteries charge for 24 hours after installation or long-term storage.

NOTE If you installed power management software and optional EBMs, ensure maximum

battery runtime by using the ERM configuration tool on the Software Suite CD.

NOTE If more than two EBMs are installed, an external battery charger is recommended

for faster recharge times.

If you have questions about implementing non- or dual-redundant power,the following options are available:

S www.oem.powerware.com/ibm-ups/pdf/nemadiagm.pdf orwww.oem.powerware.com/ibm-ups/pdf/iecdiagm.pdf

S Submit your question to “Ask the Expert” atwww.oem.powerware.com/ibm-ups/

S Submit your question to our FAQ database atwww.oem.powerware.com/IBM_faq/afmmain.asp

S Contact the IBM office or Business Partner servicing your account

Page 19: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 13

Table 7. Typical Power Connections

Item Description

1 IEC 320-C19

2 IEC 320-C20

3 Burndy® UTG Receptacle

4 Burndy UTG Plug

5 Country-Specific UPS power (mains) cord

Amperage IBM FC IBM PN Plug Type Supplier Description

30A 2975 39J2591 12 Eaton IEC 320-C19 to NEMA L6-30P, 2.4m/8 ft with inputbreaker

32A 2976 39J2633 46 Eaton IEC 320-C19 to IEC-309 (P+N+G) 32A, 4.3m/14 ftwith input breaker

20A 9860 14F1553 11 IBM IEC 320-C19 to NEMA L6-20P, 4.3m/14 ft

20A 9861 07H0095 11 IBM IEC 320-C19 to NEMA L6-20P, 4.3m/14 ft

16A 9866 14F1554 18 IBM IEC 320-C19 to CEE 7 VII, 4.3m/14 ft

16A 9867 14F1557 22 IBM IEC 320-C19 to SABS 164 BS 546, 4.3m/14 ft

16A 9868 14F1560 25 IBM IEC 320-C19 to CEI 23-16, 4.3m/14 ft

16A 9871 14F1555 46 IBM IEC 320-C19 to IEC-309 (P+N+G) 16A, 4.3m/14 ft

16A 9872 14F1561 32 IBM IEC 320-C19 to SII 32-1971, 4.3m/14 ft

16A 9874 14F1559 54 IBM IEC 320-C19 to SAA-AS 3112, 4.3m/14 ft

16A 9875 36L8885 64 IBM IEC 320-C19 to IEC 60083-A5, 4.3m/14 ft

6 PDU to UPS power cord

IBM FC IBM PN Plug Type Supplier Description

2974 39J2590 — Eaton Burndy UTG to IEC 320-C20 PDU Power Cord,1.8m/6 ft

7 PDU to utility (mains) power cord*

IBM FC IBM PN Plug Type Supplier Description

6654 25R2555 12 IBM Burndy to NEMA L6-30P, 4.3m/14 ft

6655 25R2557 40 IBM Burndy to RS 3750, 4.3m/14 ft

6656 25R2553 46 IBM Burndy to IEC-309 (P+N+G) 32A, 4.3m/14 ft

6657 25R2558 PDL IBM Burndy to PDL, 4.3m/14 ft

6658 25R2559 KP IBM Burndy to KP, 4.3m/14 ft

8 IEC 320-C13

* Other power cords are supported by the PDU. Power cords shown are similar in voltage and amperage to the UPS.

Page 20: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C14

NOTE P33 supports: PDU types 5160, 7176, or 9176 with FC 9851; PDU types 5161, 7177,

or 9177 with FC 9855.

NOTE P33 does not support iSeries PDU 5162, IEC-309 (3P+N+G) 16A.

NOTE P33 has a maximum output capacity of 2700 watts even though IBM PDU 7188 or

9188 can support higher power output. Plan accordingly.

Eaton (6) Varies (5)12

PDUIBM

iSeriesor

pSeries 7188 or9188

Device

P332700WUPS

1 2

MainsVaries34

8

8

8

8

8

8

8

8

8

Figure 12. P33 with Non-Redundant Power

Eaton (6) Varies (5)12

PDUIBM

iSeriesor

pSeries 7188 or9188

P332700WUPS

1 234

8

8

8

8

8

8

8

8

8

Device

MainsVaries

PDUIBM

iSeriesor

pSeries 7188 or9188

MainsVaries4 IBM (7)3

Figure 13. P33 with Dual-Redundant Power

Page 21: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 15

Load SegmentsLoad segments are sets of receptacles that can be controlled by powermanagement software, providing an orderly shutdown and startup ofyour equipment. For example, during a power outage, you can keep keypieces of equipment running while you turn off other equipment. Thisfeature allows you to save battery power. See your power managementsoftware manual for details.

NOTE If power management software is not used, the individual load segments cannot be

controlled.

Each UPS has three load segments as shown in Figure 14.

Load Segment 2

Load Segment 3Load Segment 1

Figure 14. UPS Load Segments

Page 22: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

INSTALLATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C16

This page intentionally left blank.

Page 23: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 17

Chapter 2 Operation

This section describes:

S Turning the UPS on and off

S Starting the UPS on battery

S Operating modes

Turning the UPS OnAfter the UPS is connected to a power outlet, it enters Standby mode.To turn on the UPS, press and hold the On button until you hear theUPS beep (approximately one second). The indicator illuminatessolid and the load level indicators display the percentage of load beingapplied to the UPS.

Starting the UPS on Battery

NOTE Before using this feature, the UPS must have been powered by utility power at least

once.

To turn on the UPS without using utility power, press and hold theOn button for at least four seconds. The UPS supplies power to yourequipment and goes into Battery mode.

Turning the UPS OffTo turn off the UPS:

1. Prepare your equipment for shutdown.

2. Press and hold the Off button until the long beep ceases(approximately five seconds). The indicator begins to flash andthe UPS switches to Standby mode (if utility power is available) andremoves power from your equipment.

3. Unplug the UPS.

If you do not unplug the UPS, it remains in Standby mode.

Page 24: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

OPERATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C18

Operating ModesP33’s front panel indicates the UPS status through the UPS indicators.Figure 15 shows the UPS front panel indicators and controls.

On Button

Off Button

Alarm Reset Button

Normal Mode Indicator (Solid Green)Standby Mode Indicator (Flashing Green)

Bypass Mode Indicator (Solid Red) Red

Flashing

Unlit

Green

Indicator Legend

Load Level IndicatorsBattery Mode Indicator

Figure 15. UPS Front Panel

Normal ModeDuring Normal mode, the indicator illuminates and the front paneldisplays the percentage of UPS load capacity being used by theprotected equipment (see Figure 16). The UPS monitors and charges thebatteries as needed and provides power protection to your equipment.

>100%

76–100%

51–75%

26–50%

0–25%

Figure 16. Load Level Indicators

When all of the load level indicators and the indicator are illuminated,power requirements exceed UPS capacity; refer to “Troubleshooting” inthe Powerware 5125 Two-in-One UPS (2400–3000 VA) User’s Guide formore information.

Page 25: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

OPERATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 19

Battery ModeWhen the UPS is operating during a power outage, the alarm beepsonce every five seconds and the + --- indicator illuminates. When theutility power returns, the UPS switches to Normal mode operation whilethe battery recharges.

If battery capacity becomes low while in Battery mode, the + --- indicatorstarts flashing and the alarm becomes continuous. Immediatelycomplete and save your work to prevent data loss and similar difficulties.

When utility power is restored after the UPS shuts down, the UPSautomatically restarts. The indicator flashes until the battery hasrecharged to an acceptable level.

Bypass ModeIn the event of a UPS overload or internal failure, the UPS transfers yourequipment to utility power. Battery mode is not available; however, theutility power continues to be passively filtered by the UPS. The alarmsounds and the indicator illuminates red. The UPS switches toBypass mode when:

S The UPS has an overtemperature condition.

S The UPS has an overload condition of 103 to 110% for 30 seconds.

S The UPS detects a fault in the battery or UPS electronics.

Standby ModeWhen the UPS is turned off and remains plugged into a power outlet,the UPS is in Standby mode. The indicator flashes and the load levelindicators are off, indicating that power is not available to yourequipment. The battery recharges when necessary.

NOTE For 200–240V models, the output receptacles may remain electrically live (up to

100–120V). Unplug the UPS to ensure power is not available to the output receptacles.

Page 26: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

OPERATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C20

Configuration ModeWhen the UPS is in Configuration mode, the front panel indicatorsrepresent the configuration options. Use the control buttons(On button, Off button, and button) to modify the UPSconfiguration. Figure 17 shows the indicators and Table 8 explains thecorresponding options.

1. Press and hold the On button and the button simultaneouslyfor one beep (approximately five seconds). The UPS switches toConfiguration mode.

The indicators flash briefly and then display the enabled options.

2. Press the On button to scroll through the options. Each time youpress the button, the UPS beeps. The indicator for the selectedoption indicates the current setting; flashing represents disabledoptions (see Figure 17 and Table 8).

Scrolling past the last indicator returns to the first configurationoption.

If you press the On button and nothing happens, the UPS is still inOperation mode. Repeat Step 1 for one beep ONLY to enterConfiguration mode, and then perform Step 2.

3. Press the Off button button ONCE to select the Voltage optionor to toggle the Site Wiring Fault Alarm on or off.

NOTE The UPS exits Configuration mode automatically after two minutes.

4. Press the button to confirm the selection and exit Configurationmode. If you do not press the button, the UPS defaults to theoriginal settings.

Page 27: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

OPERATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 21

4

On Button

Off Button

Alarm Reset Button

Configuration Mode Indicators

Press and hold the On and Alarm Resetbuttons simultaneously to enterConfiguration mode.

1 2Press the On button toscroll to the next option.

3Press the Off button ONCE toselect the option.

Press the Alarm Reset buttonto save the setting and exitConfiguration mode.

Figure 17. Using Configuration Mode

Page 28: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

OPERATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C22

Table 8. Configuration Mode Indicators and Options

Configuration ModeIndicators Option Indicator

Status Explanation

100/200-208VNominal InputVoltage

On Selecting this option changes the nominal input voltage onlow voltage models to 100V and to 200-208V for high voltagemodels.g

Flashing 100/200-208V is disabled; one of the other input voltageoptions is selected.

110/220VNominal InputVoltage

On Selecting this option changes the nominal input voltage onlow voltage models to 110V and to 220V for high voltagemodels.g

Flashing 110/220V is disabled; one of the other input voltage options isselected.

120/230VNominal InputVoltage

On Selecting this option changes the nominal input voltage onlow voltage models to 120V and to 230V for high voltagemodels.g

Flashing 120/230V is disabled; one of the other input voltage options isselected.

127/240VNominal InputVoltage

On* Selecting this option changes the nominal input voltage onlow voltage models to 127V and to 240V for high voltagemodels.*Default for P33.

Flashing 127/240V is disabled; one of the other input voltage options isselected.

Site WiringFault Alarm

On Alarm sounds when the polarity of the outlet is reversed orthe ground connection is missing; have a qualified electricianrepair the outlet wiring.

Flashing* Alarm DOES NOT sound when the polarity of the outlet isreversed or the ground connection is missing.*Site Wiring Fault is not available for 100, 200, or 208V models.

Page 29: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 23

Chapter 3 Communication

This section includes

S Single-Port Card information

S Communication options

Single-Port CardThe P33 is factory-installed with a Single-Port Card, enabling connectionto a PC for power management control.

To establish communication between the UPS and a computer, connectyour computer to the UPS communication port using the suppliedcommunication cable.

When the communication cable is installed, power managementsoftware can exchange data with the UPS. The software polls the UPSfor detailed information on the status of the power environment. If apower emergency occurs, the software initiates the saving of all dataand an orderly shutdown of the equipment.

The cable pins are identified in Figure 18 and the pin functions aredescribed in Table 9.

3

8 79

1

6

245

Figure 18. Communication Port

Page 30: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C24

Table 9. Communication Port Pin Assignment

Pin Number Signal Name Function Direction from the UPS

1 Low Batt Low Battery relay contact Out

2 TxD Transmit to external device Out

3 RxD Receive from external device In

4 DTR PnP (Plug and Play) from external device (tied to Pin 6) In

5 GND Signal common (tied to chassis) —

6 DSR To external device (tied to Pin 4) Out

7 RTS PnP from external device (default) or On Bypass relaycontact (jumper-selectable)

In / Out

8 AC Fail AC Fail relay contact Out

9 Power Source +V (8 to 24 volts DC power) Out

The On-Bypass Relay Contact. You can enable the On-Bypass relay usingthe jumper on the Single-Port Card. The jumper default is disabled. Toenable the On-Bypass relay:

1. Remove the Single-Port Card on the UPS rear panel. Retain thescrews (see Figure 19).

Figure 19. Removing the Single-Port Card

2. Move the J3 jumper to the AS/400® position to enable theOn-Bypass relay as shown in Figure 20.

Page 31: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 25

On-Bypass Relay Jumper(J3)

On-BypassDisabled

On-BypassEnabled

AS/400NORM

Figure 20. On-Bypass Relay Jumper

3. To prevent electrostatic discharge (ESD), place one hand on a metalsurface such as the UPS rear panel.

Align the Single-Port Card with the slot guides and slide the cardinto the slot until it is firmly seated.

4. Secure the Single-Port Card with the screws removed in Step 1.

Page 32: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C26

Communication OptionsIf you want the UPS to communicate with your computer, use Table 10to determine which communication option is correct for your application.

Table 10. Communication Options

Application Software Suite CDand Serial Cable

ConnectUPS-XWeb/SNMP Card Kit

(FC 2934)

Relay InterfaceCard and Cable Kit

(FC 2936)

Relay-Serial Cardand Cable Kit(FC 2939)

IBM i5/iSeries Server — — X —

IBM i5/iSeries Server andSerial Server (Microsoft®Windows®, Linux®, AIX®, orother operating systems)

— — — X

IBM p5/pSeries Server,OpenPowert, or xSeries®Server with Single Serial(TTY) Connection

X — — —

IBM p5/pSeries Server,OpenPower, or xSeriesServer with LPARs and/orNetwork (WebServer)Connection (UPS as anode)

— X — —

Follow the installation instructions with the Software Suite CD or theapplicable card kit. This section shows the communication optionoverviews. For additional information and a current listing of supportedoperating systems, go to www.powerware.com.

Page 33: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 27

i5 Interface OverviewTo connect the UPS to an i5 you need:

S An Eaton-supplied Relay Interface Card and AS/400 interface cable(labeled 05142494), located in the FC 2936 carton labeled “Cable Kitfor IBM iSeries”

S An IBM-supplied UPS interface cable (labeled 1827), included withthe server

Follow the instructions included with the Relay Interface Card and CableKit to install the card and set UPS monitoring functions in i5/OSt.Installation may include removal of an existing X-Slot card from the UPS.

Connect the cables as shown in Figure 21.

AS/400 Interface Cable(labeled 05142494)

UPS Interface Cable(labeled 1827)

UPS

Communication Port

“P1-T1” UPS Port

IBM i5 Server

Relay Interface Card

Figure 21. i5 Interface

Page 34: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C28

iSeries or AS/400 Interface OverviewTo connect the UPS to an iSeries or AS/400 you need:

S An Eaton-supplied Relay Interface Card and AS/400 interface cable(labeled 05142494), located in the FC 2936 carton labeled “Cable Kitfor IBM iSeries”

Follow the instructions included with the Relay Interface Card and CableKit to install the card and set UPS monitoring functions in OS/400®.Installation may include removal of an existing X-Slot card from the UPS.

Connect the cable as shown in Figure 22.

CommunicationPort

“J14” UPS Port(location mayvary by model)

AS/400 Interface Cable(labeled 05142494)

IBM iSeries Server

UPS

Relay Interface Card

Figure 22. iSeries or AS/400 Interface

Page 35: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 29

i5, iSeries, or AS/400 and Serial Server Interface OverviewTo connect the UPS to an i5, iSeries, or AS/400 and a serial server youneed:

S An Eaton-supplied Relay-Serial Card, an AS/400 interface cable(labeled 124902074-030), and a serial interface cable (labeled124102022-003), located in the FC 2939 carton labeled “Cable Kit forIBM iSeries and Windows or AIX/Linux Servers”

S For the i5 only: An IBM-supplied UPS interface cable (labeled 1827),included with the server

S For the serial server only: Powerware LanSafe® Power ManagementSoftware from the Software Suite CD, located in the P33 accessorykit

Follow the instructions included with the Relay-Serial Card and Cable Kitto install the card and set UPS monitoring functions in i5/OS and serial(TTY) server. Installation may include removal of an existing X-Slot cardfrom the UPS.

Follow the software installation instructions contained on the SoftwareSuite CD to install the Powerware LanSafe software.

If you have an i5, connect the cables as shown in Figure 23. Otherwise,see Figure 24 to connect the cables.

AS/400 Interface Cable(labeled 124902074-030)

UPS Interface Cable (labeled 1827)

“P1-T1” UPS Port

IBM i5 Server

Serial Interface Cable(labeled 124102022-003)

UPS

Communication Port

Relay-Serial Card

Serial (TTY)Server

Figure 23. i5 and Serial Server Interface

Page 36: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C30

“J14” UPS Port(location mayvary by model)

IBM iSeries Server

AS/400 Interface Cable(labeled 124902074-030)

Serial Interface Cable(labeled 124102022-003)

Serial (TTY)Server

UPS

Relay-Serial Card

CommunicationPort

Figure 24. iSeries or AS/400 and Serial Server Interface

Page 37: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 31

Serial (TTY) Interface OverviewTo serially (TTY) connect the UPS to a p5, pSeries, RS/6000®,OpenPower or other system you need:

S An Eaton-supplied serial interface cable (labeled 124102022-002),located in the P33 accessory kit

S Powerware LanSafe Power Management Software from theSoftware Suite CD, located in the P33 accessory kit

For p5 installations, you also need:

S An IBM-supplied 2-port Asynchronous EIA adapter (FC 5723) installedon a p5 server (the pSeries does not require an EIA adapter)

S An IBM-supplied maintenance package 5200-05 for AIX 5.2L V5.2(APAR IY66260); or the maintenance package 5300-01 for AIX 5.3LV5.3 (APAR IY62267)

Follow the software installation instructions contained on the SoftwareSuite CD to install the Powerware LanSafe software. Connect the serialcable as shown in Figure 25.

Communication Port

Serial Interface Cable(labeled 124102022-006or 152601412-001)

IBM p5 Server

2-Port AsynchronousEIA Adapter(FC 5723)

UPS

Figure 25. Serial (TTY) Interface

Page 38: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

COMMUNICATION

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C32

p5 or pSeries with Logical Partitions Interface OverviewTo connect the UPS to a p5 or pSeries with LPARs you need:

S An Eaton-supplied ConnectUPS-X Web/SNMP Card, located in theFC 2934 carton labeled “ConnectUPS-X Web/SNMP Card Kit”

S NetWatch software from the Software Suite CD, located in the P33accessory kit

S A customer-supplied Ethernet cable

S An available Ethernet port on the server

Follow the instructions included with the ConnectUPS-X Web/SNMPCard Kit to install the card and set UPS monitoring functions. Installationmay include removal of an existing X-Slot card from the UPS.

Follow the software installation instructions contained on the SoftwareSuite CD to install the NetWatch software onto each LPAR.

Connect the Ethernet cable as shown in Figure 26.

Ethernet Cable(customer-supplied)

IBM p5 Server

The server must havean available Ethernet port.

Ethernet Connectors

UPS

ConnectUPS-X Web/SNMP Card

Figure 26. p5 or pSeries with LPARs Interface

Page 39: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C 33

Chapter 4 Service and Support

In the United States and Canada, call 1-800-IBMSERV (1-800-426-7378). InEurope, the Middle East, and Africa (EMEA); Latin America; orAsia-Pacific, call the IBM office that services your account. Please haveyour serial, model, and part number ready when you call (see Figure 27).

For additional information, see the appropriate user’s guide for the UPSor Extended Battery Module (EBM).

(S/N Bar Code 39)

Part Number

S991010L3AAA

(Data: P21P7219)(IBM Part Number Bar Code 39)

Front Panel Label

Rear Panel LabelModel Number

Serial Number

IBM/UPSType-Model/Feature: 9910-P33(P) IBM P/N: 21P7219

(S) Serial Number: 9910-10L3AAA

(2P) EC: xxxxxx

(Serial Number Bar Code 39)(Data: S991010L3AAA)

(Data: xxxxxxxx)(EC Number Bar Code 39)

Assembled in MexicoDate of MFG: YYYYMMDD

Serial Number

Figure 27. Example of IBM Serial Number Labels

CommentsWe welcome your comments about this manual. Please send yourquestions or suggestions for improvements [email protected].

Page 40: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

SERVICE AND SUPPORT

EATON Powerware® 5125 (9910-P33) UPS Installation Guide for IBM® Applications S Rev C34

This page intentionally left blank.

Page 41: Powerware 5125 (9910-P33) UPS Installation Guide …oem.powerware.com/ibm-ups/pdf/p33inst.pdf · 1 05146745 Software Suite CD 1 124102022-002 UPS to ... EATON Powerware® 5125 (9910-P33)

Requesting a Declaration of ConformityUnits that are labeled with a CE mark comply with the following harmonized standards and EU directives:

S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition

S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits93/68/EEC, Amending Directive 73/23/EEC89/336/EEC, Council Directive relating to electromagnetic compatibility92/31/EEC, Amending Directive 89/336/EEC relating to EMC

The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the ECDeclaration of Conformity, contact:

Eaton Power Quality OyKoskelontie 13FIN-02920 EspooFinlandPhone: +358-9-452 661Fax: +358-9-452 665 68

Class A EMC StatementsFCC Part 15NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuantto part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmfulinterference when the equipment is operated in a commercial environment. This equipment generates, uses, andcan radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, maycause harmful interference to radio communications. Operation of this equipment in a residential area is likely tocause harmful interference in which case the user will be required to correct the interference at his ownexpense.

ICES-003

This Class A Interference Causing Equipment meets all requirements of the Canadian Interference CausingEquipment Regulations ICES-003.

Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur duCanada.

EN 50091-2

Some configurations are classified under EN 50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” Forthese configurations, the following applies:

WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference,in which case, the user may be required to take additional measures.

VCCI Notice