6
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy™ Uninterruptible Power Supply LP 33 Series / 10 – 20 – 30 – 40 – 50 – 60 kVA 208 VAC UL – Series 0 Date of issue: 05/15/2007 LPS33U_030-040_UPS_GE_01 LPS33U_050-060_UPS_GE_01 LP 33 Series / 10 & 20 kVA LP 33 Series / 30 & 40 kVA LP 33 Series / 50 & 60 kVA GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44 www.gedigitalenergy.com GE imagination at work

Technical Data Sheets - Powerware

  • Upload
    others

  • View
    15

  • Download
    0

Embed Size (px)

Citation preview

GE Consumer & Industrial Power Protection

Technical Data Sheets Digital Energy™ Uninterruptible Power Supply LP 33 Series / 10 – 20 – 30 – 40 – 50 – 60 kVA 208 VAC UL – Series 0 Date of issue: 05/15/2007

LPS33U_030-040_UPS_GE_01

Dig ital EnergyT M

LP S erie s

LPS33U_050-060_UPS_GE_01

Dig ital E nergyT M

LP S eries

LP 33 Series / 10 & 20 kVA LP 33 Series / 30 & 40 kVA LP 33 Series / 50 & 60 kVA GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44

www.gedigitalenergy.com

GE imagination at work

Modifications reserved Page 2/6 TDS_LPS_33U_10K_60K_0US_V010.doc Technical Data Sheets LP 33 Series 10-20-30-40-50-60 kVA

GENERAL DATA Topology VFI, double conversion Nominal output apparent power kVA 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA Power factor (output) PF 0.8 lag. 0.9 lag. Nominal output active power kW 8 16 24 32 45 54 Overall efficiency at 100% load in VFI mode % 90.0 90.0 90.6 90.5 90.2 90.0 Overall efficiency at 100% load in ECO mode % 98.0 98.0 99.0 99.0 98.0 98.0 Heat dissipation at 100% load in VFI mode, nominal PF and charged battery kW 0.89 1.78 2.49 3.36 4.89 6.00

Cooling air (77°F...86°F / 25°C...30°C) CFM 154 308 431 582 847 1040 Audible noise level dB(A) 50 55 61 62 65 65 Battery type Valve regulated lead-acid (VRLA)

Operating temperature range UPS: 32°F ÷ 104°F (0°C ÷ 40°C) Battery: 68°F ÷ 77°F 20°C ÷ 25°C) recommended

Storage temperature range -13°F ÷ 131°F (-25°C ÷ +55°C) Storage time of the battery without recharge at 68°F (20°C) Max. 6 months Relative humidity Max. 95% (non-condensing) Max. altitude without power derating Power derating (according to IEC 62040-3)

3300 ft 5000 ft: 95% / 6500 ft: 91% / 8200 ft: 86% / 9800 ft: 82%

Protection degree IP 20 (IEC 60529) and NEMA-PE-1 Safety Standards UL 1778, IEC 62040, ISO 9001 EMC FCC Class A, IEC 62040-2 Class A Electrostatic discharge immunity 4kV contact / 8kV air discharge Internal protection All live parts shrouded Enclosure Metal sheet and castors

Transport 10 & 20 kVA: Packaging suitable for handling by forklift 30 to 60 kVA: Cabinet and packaging suitable for handling by forklift

Color RAL 9003 (white)

Installation 10 & 20 kVA: Minimum distance from the wall 2 inches (5 cm) 30 to 60 kVA: Can be positioned against a wall and floor

Service access Front and top External cable connections Front Bottom conduit access Cooling Forced to top by internal blower

Paralleling (RPA version) Up to 4 units in parallel for redundancy or capacity in RPAconfiguration (optional)

RECTIFIER Rectifier bridge Three phase, over temperature protection

Standard input voltage

Nominal: 3 x 208 + N 10 & 20 kVA: -25% ÷ +20% 30 & 40 kVA: -20% ÷ +15% 50 & 60 kVA: -15% ÷ +10%

Input frequency 60 Hz +/-10% Input power factor >0.98 lag.

Input current distortion (THDI) 10 & 20 kVA: <8% 30 to 60 kVA: <10%

Output voltage tolerance +/- 1% Battery ripple current Max. 5% of the battery capacity [Ah], expressed in A Battery charging characteristic IU (DIN 41773), T° compensated floating voltage

Battery charging current limit 10 & 20 kVA: settable in 3 steps 30 to 60 kVA: settable by parameter

Input power data kVA 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA Nominal input at inverter nominal load, and charged battery Current (A) 25.2 50.4 75.1 100 141 170

KVA 9.1 18.1 27.0 36.1 50.9 61.2 kW 8.9 17.8 26.5 35.4 49.9 60.0 Max. input power at inverter nominal load and max. battery recharge current (programmable) Current (A) 27.4 54.7 87.3 113 155 183

KVA 9.9 19.7 31.4 40.5 55.6 65.9 kW 9.7 19.3 30.8 39.7 54.5 64.6 Max. battery charging current (programmable) A 2.4 4.8 15.0 15.0 16.0 16.0 Battery boostcharge Yes (selectable)

Modifications reserved Page 3/6 TDS_LPS_33U_10K_60K_0US_V010.doc Technical Data Sheets LP 33 Series 10-20-30-40-50-60 kVA

BATTERY Battery type Standard: Valve regulated lead-acid (VRLA) Number of blocks and battery capacity See battery table on page 5 and 6 Float voltage at 20°C 2 x 164 VDC Min. discharge voltage (programmable) 2 x 118 VDC Recharge time 6 ÷ 8 hours Automatic and manual battery test Standard Common battery in parallel system Up to 4 units (only for 30 to 60 kVA) Battery power data kVA 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA DC power at full load and nominal PF kW 8. 9 17.8 26.5 35.4 49.9 60.0 Max discharge current at 100% load and nominal PF A 38 75 112 150 211 254 Matching battery cabinets See optional features on page 4

INVERTER Nominal output power at PF=0.6 ... 0.8 lag. / 0.6 ... 0.9 lag. 10 to 40 kVA / 50 & 60 kVA Nominal output voltage (on site programmable) 3 x 208V+ N Inverter bridge IGBT technology Output waveform Sine wave Output voltage tolerance: - static ................................................................................................................ +/- 1% - dynamic (at load step 0 – 100 – 0%) ................................................. +/- 1% - recovery time to +/-1% ........................................................................... <3 ms

10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA - output voltage THD for 100% linear load ....................................... <2% <2% <1.5% <1.5% <2% <2% - output voltage THD for 100% non-linear load (EN 50091) <3% Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3% Output frequency 60 Hz Output frequency tolerance: - free-running ................................................................................................. +/- 0.1% - with mains synchronisation adjustable to...................................... +/- 4% Phase displacement: - at 100% balanced load ........................................................................... 120°: +/- 1% - at 100% unbalanced load...................................................................... 120°: +/- 2% Overload capability (at nominal PF) 125% - 10 minutes, 150% - 1 minute

Short-circuit characteristic Electronic short-circuit protection, current limit to 2.2 times In for 100 ms

10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA Nominal output current at full load 28A 56A 83A 111A 139A 167A Crest factor >3:1

BYPASS

Input connection - Common input (Rectifier & Bypass) - Dual input (optional)

Primary components

- Thyristors (SSM – Static Switch module) - Electromechanical contactors (backfeed protection) on

bypass and inverter - 2 manual switches for maintenance bypass

Voltage limits for inverter/bypass load transfers +/- 15% 200% for 2 Minutes

Overload on bypass 2000% for ½ cycle, non repetitive

INTERFACING

Potential free contacts - 4 (Utility failure, General alarm, Stop operation, load on utility) - 28 user settable signals

Serial channel RS232 (on Delta 9 pin connector) Standard EPO (Emergency Power Off) Standard

Extended Customer Interface Card (optional) - EMERGENCY POWER OFF (n/c contact, customer supplied) - 6 potential free alarm contacts - 2 auxiliary contacts (one default configured as Genset)

Note: all indicated values are typical. Variations may be found from one unit to another.

Modifications reserved Page 4/6 TDS_LPS_33U_10K_60K_0US_V010.doc Technical Data Sheets LP 33 Series 10-20-30-40-50-60 kVA

FRONT PANEL CONTROLS, SIGNALS AND ALARMS

LP 33 Series 10 & 20 kVA

LP 33 Series 30 & 40 & 50 & 60 kVA

LCD SCREEN

Shows the UPS data system data, events messages and UPS setting. The data is displayed on 4 rows, 20 characters each, allowing the operator to select between English, German, French, Spanish, Italian, Finnish or Polish language.

CONTROL PANEL

Metering Electrical parameters, operating statistics and information screens.

Alarm Events (alarms, messages, commands, handling, etc.) and resets general alarm / buzzer.

Menu Settings, LED-test and commands.

+ Scroll to following screen.

- Scroll to previous screen.

Enter Confirms the selected command.

INDICATION LED’S

Alarm (red) On: No mains available.

Load supply at risk due to: - Battery empty; - Overtemperature; - Overload. Warning (yellow) Blinking: Alarm not jeopardizing

load supply. Operation (green) On: LOAD ON INVERTER

Blinking: SERVICE REQUIRED

OPTIONS

COMMUNICATION:

1. Advanced SNMP Card

2. GE Power Diagnostics

3. GE Data Protection

4. Modbus RTU Interface

OPTIONS (UPS internally mounted):

1. Extended Customer Interface Card

2. RPA (Redundant Parallel Architecture) to parallel up to 4 units

3. Dual utility input (one for rectifier / one for bypass)

4. EMC filter for dual input (only for 30 – 40 – 50 - 60 kVA)

5. Additional battery charger (only for 10 & 20 kVA)

OPTIONS IN ADDITIONAL CABINETS:

1. Battery cabinet for 30 to 60 kVA

LPS33U_OPT_Cabinet battery_01

Dimensions (WxDxH):

16.93” x 28.55” x 70.95” 430 x 725 x 1802 mm

Weight (empty):

188 lbs 85 Kg

Modifications reserved Page 5/6 TDS_LPS_33U_10K_60K_0US_V010.doc Technical Data Sheets LP 33 Series 10-20-30-40-50-60 kVA

TECHNICAL DATA

LP 33 Series 10 & 20 kVA - WEIGHT

UPS without battery UPS with battery UPS

rating UPS UPS floor loading

UPS with st. shipping

UPS with battery

Floor loading

UPS with standard shipping

10 kVA 180 Kg 397 lbs

408 Kg/m2

84 lbs/sq.ft 195 Kg 430 lbs

*290 - °395 Kg *640 - °871 lbs

*657 - °895 Kg/m2

*135 - °184 lbs/sq.ft *305 - °410Kg *673 - °905lbs

20 kVA 195 Kg 430 lbs

442 Kg/m2

91 lbs/sq.ft 210 Kg 464 lbs

410 Kg (24 Ah) 905 lbs (24 Ah)

929 Kg/m2 (24 Ah)

191 lbs/sq.ft (24 Ah) 425 Kg (24 Ah) 938 lbs (24 Ah)

(*) Battery 12 Ah (°) Battery 24 Ah

LP 33 Series 10 & 20 kVA - BATTERY TABLE

UPS rating

Battery capacity

Autonomy time Cabinet

12 Ah 9 min. 10 kVA

24 Ah (2 x 12 Ah) 26 min. Mounted inside the UPS cabinet (see Weight table)

20 kVA 24 Ah (2 x 12 Ah) 9 min. Mounted inside the UPS cabinet (see Weight table)

LP 33 Series 10 & 20 kVA

1310

mm

566mm780mm

51.5

8"

22.71"30.71"

Battery autonomy time at 100% load and PF=0.8 lag., only with High Rate Battery

LP 33 Series 30 & 40 kVA - WEIGHT

UPS without battery UPS with battery UPS

rating UPS UPS floor loading

UPS with st. shipping

UPS with battery

Floor loading

UPS with stand. shipping

33 Ah 24 blocks

605 Kg 1335 lbs

816 Kg/m2

168 lbs/sq.ft 630 Kg

1390 lbs 33 Ah

48 blocks 860 Kg

1897 lbs 1160 Kg/m

2

238 lbs/sq.ft 885 Kg

1952 lbs 30 kVA

350 Kg 772 lbs

472 Kg/m2

97 lbs/sq.ft 375 Kg 827 lbs

50 Ah 24 blocks

735 Kg 1621 lbs

991 Kg/m2

203 lbs/sq.ft 760 Kg

1676 lbs 33 Ah

24 blocks 625 Kg

1379 lbs 843 Kg/m

2

173 lbs/sq.ft 650 Kg

1434 lbs 33 Ah

48 blocks 880 Kg

1941 lbs 1186 Kg/m

2

243 lbs/sq.ft 905 Kg

1996 lbs 40 kVA

370 Kg 816 lbs

499 Kg/m2

103 lbs/sq.ft 395 Kg 871 lbs

50 Ah 24 blocks

755 Kg 1665 lbs

1018 Kg/m2

209 lbs/sq.ft 780 Kg

1720 lbs

LP 33 Series 30 & 40 kVA - BATTERY TABLE

UPS rating

Battery capacity

Autonomy time Cabinet L

33 Ah (24 blocks) 9 minutes UPS + 1 Battery cabinet 40.55” / 1030mm

2 x 33 Ah (48 blocks) 23 minutes UPS + 1 Battery cabinet 40.55” / 1030mm 50 Ah (24 blocks) 14 minutes UPS + 1 Battery cabinet 40.55” / 1030mm

4 x 33 Ah (96 blocks) 52 minutes UPS + 2 Battery cabinets 57.48” / 1460mm

30 kVA

2 x 50 Ah (48 blocks) 37 minutes UPS + 2 Battery cabinets 40.55” / 1030mm 33 Ah (24 blocks) 6 minutes UPS + 1 Battery cabinet 40.55” / 1030mm

2 x 33 Ah (48 blocks) 14 minutes UPS + 1 Battery cabinet 40.55” / 1030mm 50 Ah (24 blocks) 10 minutes UPS + 1 Battery cabinet 40.55” / 1030mm

4 x 33 Ah (96 blocks) 37 minutes UPS + 2 Battery cabinets 57.48” / 1460mm

40 kVA

2 x 50 Ah (48 blocks) 26 minutes UPS + 2 Battery cabinets 57.48” / 1460mm

LP 33 Series 30 & 40 kVA

LPS33U_030-040_UPS dimensions_TDS_01

Digit al EnergyTM

LP Se ries

752mm

1'82

0mm

71.6

6"

29.61"

L600mm23.63"

430mm16.93"

Battery autonomy time at 100% load and PF=0.8 lag., only with High Rate Battery.

Modifications reserved Page 6/6 TDS_LPS_33U_10K_60K_0US_V010.doc Technical Data Sheets LP 33 Series 10-20-30-40-50-60 kVA

LP 33 Series 50 & 60 kVA – WEIGHT STANDARD UPS

UPS without battery UPS with battery UPS

rating UPS UPS floor loading

UPS with st. shipping

UPS with battery

Floor loading

UPS with stand. shipping

50 kVA

60 kVA

460 Kg

1015 lbs 532 Kg/m

2

109 lbs/sq.ft

490 Kg

1081 lbs

33 Ah

48 blocks

970 Kg

2139 lbs 1122 Kg/m

2

230 lbs/sq.ft

1000 Kg

2205 lbs

LP 33 Series 50 & 60 kVA – WEIGHT SINGLE ADDITIONAL BATTERY CABINET

UPS rating Battery capacity Weight Floor loading

2 x 33 Ah (48 blocks) 595 Kg / 1312 lbs 1909 Kg/m2 / 391 lbs/sq.ft 50 kVA

& 60 kVA 50 Ah (24 blocks) 470 Kg / 1037 lbs 1508 Kg/m

2 / 309 lbs/sq.ft

LP 33 Series 50 & 60 kVA - BATTERY TABLE

UPS rating

Battery capacity

Autonomy time Cabinet L

2 x 33 Ah (48 blocks) 9 minutes UPS + 1 Battery cabinet 45.28” / 1150mm 4 x 33 Ah (96 blocks) 24 minutes UPS + 2 Battery cabinet 62.21” / 1580mm 2 x 50 Ah (48 blocks) 16 minutes UPS + 2 Battery cabinet 62.21” / 1580mm 3 x 50 Ah (72 blocks) 29 minutes UPS + 3 Battery cabinet 79.14” / 2010mm

50 kVA

4 x 50 Ah (96 blocks) 36 minutes UPS + 4 Battery cabinets 96.07” / 2440mm 2 x 33 Ah (48 blocks) 8 minutes UPS + 1 Battery cabinet 45.28” / 1150mm 4 x 33 Ah (96 blocks) 18 minutes UPS + 2 Battery cabinet 62.21” / 1580mm 2 x 50 Ah (48 blocks) 13 minutes UPS + 2 Battery cabinet 62.21” / 1580mm 3 x 50 Ah (72 blocks) 23 minutes UPS + 3 Battery cabinet 79.14” / 2010mm

60 kVA

4 x 50 Ah (96 blocks) 33 minutes UPS + 4 Battery cabinet 96.07” / 2440mm

LP 33 Series 50 & 60 kVA

LPS33U_050-060_UPS dimension_TDS_01

Di gi ta l E nergyT M

LP S eries

752mm

1'82

0mm

71.6

6"

29.61"

L720mm28.35"

430mm16.93"

Battery autonomy time at 100% load and PF=0.9 lag., only with High Rate Battery.

UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS

Common input Rectifier & Bypass Dual input Rectifier & Bypass (optional)

IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60634, IEC 61140, IEC 61557)