p30.ppt rev 4.16.04 Powerware 9 Powerware 9 125 125 9910 - P30 9910 - P30 High Performance High Reliability & Availability Flexible & Configurable Advanced Communications

Powerware 9125 9910 - P30

  • Upload
    others

  • View
    16

  • Download
    0

Embed Size (px)

Citation preview

1p30.ppt rev 4.16.04

Powerware 9Powerware 91251259910 - P309910 - P30

High Performance

High Reliability & Availability

Flexible & Configurable

Advanced Communications

2

• Fourth-Generation Online™topology

• Advanced Battery ManagementPlus (ABM Plus™)

• Extended Battery Modules(EBMs)

• Load Segments• Two-in-One form factor• 2U rack-mount height• Hot-swappable batteries• X-Slot™• Power management software

bundle

Product SnapshotPower Rating: 3000VA/2100W Voltage: 120/208-240 VacFrequency: 50/60 Hz (auto-sensing)Configuration: use as rackmount or tower unit

P30 Features

3

P30 Applications

The P64 was specifically designed, engineered andapproved for IBM rack applications• iSeries and AS/400• pSeries and RS/6000• xSeries and other eServers• Storage and networking devices

9910 UPSs are ideal power protection foriSeries family of serversIBM x200IBM p660IBM p640

in rackIBM x220

4

Series 9 Power ProtectionThe P30 provides double-conversion online powerprotection from all 9 of the most common power problemsthat threaten your equipment and data

Power failures High voltage spikes

Power sags Frequency variations

Power surges Switching transients

Brownouts Harmonic distortion

Line noise

5

Utility Load

Internal Automatic Bypass

Battery

AC to DCRectifier

DC to ACInverter

Bi-DirectionalPower Converter

Filtering

• Wide input voltage range– Reduces battery usage– Reserves batteries for power failures--when you

need maximum runtime– Extends UPS service life– Reduces battery replacement costs

• EnergyShare– Under extremely poor utility conditions, P30 takes

power from both the utility and battery– Reduces battery usage– Extends runtime and service life of the battery

P30 Fourth-Generation OnlineTopologyTM

6

Energy Share

EnergyShare range: 120-160V(combined battery and utility)

Battery Power: <120V

Battery Power: >288V

Online voltage regulation: 160-288V

(no battery power needed)

Input Voltage RangeDuring extreme brownouts,the P30 provides an extralevel of protection; the UPS“shares” battery andincoming voltage to continueto provide ±3% of nominalvoltage

7

B CABM® Technology

• Doubles batteryservice life by chargingonly when needed

• Optimizes rechargetime

• Does not trickle chargeand starve the electrolyte

• Intelligent microprocessor controlled -Only true & automatic battery check (periodic, controlleddischarge) for most accurate advanced failure protection

• Sleep Feature - no unnecessary battery “drain”

8

Compact Design

By minimizing the size of the P30, you save rackspace for other equipment such as servers,storage, I/O and networking.

2U

Model shown in white for illustration only.

9

Informative User Interface

On Button(Start-On-Battery)

Overtemperature

Overload

Load Level/Battery LevelBypass Mode

Alarm Silence/Test Button Off Button

Battery Mode

Normal Mode(UPS On)

Site Wiring Fault

Self-Test

ReplaceBattery (ABM)

Note: rotate 90° for cabinet configuration

10

Load Segments

Individual control of two

Load Segments

• Power down sequencing of Load Segments– Extends runtime for critical devices

• Power up sequencing of Load Segments– Orderly power up of connected devices

• Scheduled on/off times– Turn off equipment for security and power conservation

11

No need to shut downyour critical load whenreplacing batteries

Hot-Swappable Batteries

12

2U

One EBM Two EBMs

Add EBMs to extend backup timeIn rack-mount configurations, each EBMoccupies only 2U (3.5 inches) of rack space

Extended Battery Modules

Models shown in white for illustration only.

13

Attach EBMs with simple daisy-chain connection

EBM #1

EBM #2

EBM Connection

14

P30 Battery RuntimesBattery Runtime (in minutes)*

Standard (Std)Watts Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs

875 16 57 90 150 2001050 13 55 72 120 1601750 7 28 48 68 882100 5 25 38 54 70Rack Height 2U 4U 6U 8U 10U

* Up to 4 EBMs can be connected to the P30. EBM runtimes include P30 internal batteries. Runtime chart provides typicalinformation. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.

15

P30 Rear Panel

X-Slot Communication Port

Network Transient Protector

Battery Connector

REPO port

(4) IEC-320-C13

IEC-320-C19

IEC-320-C20

16

Network Transient Protector provides protectionfrom “back door” disturbances that travel throughphone/network lines

REPO/Network TransientProtector

Shut down UPS remotely with REPO port;ideal for rack applications

17

• Replace or upgrade the UPS without powering downthe equipment

• Surge Protection in the Absence of UPS electronicsmodule during maintenance

• Individual load segment switched maximize back uptime for critical devices

• Designed to line-up and match the P30

PowerPass

Model shown in white for illustration only.

18

Powerware ExtensionsSoftware for IBM Director

• Seamless UPS and softwareintegration into IBM DirectorNetwork Management System(NMS)

• Real time monitoring,management and alarmnotification of all UPSs in thenetwork: e.g. battery status,battery replacement, load leveland metering information

• Automatically launches LanSafeand ConnectUPS Web/SNMPCard applications from withinDirector

• Available on Powerware web• FREE-OF-CHARGE

19

Powerware Software SuiteThe industry’s most comprehensive software bundle, The PowerwareSoftware Suite, is free and included with every P30.

Software Wizard guides you through softwareselection and installation. In addition to multimediademonstrations, product data sheets, and video clips,the Software Suite contains the following powermanagement software:• LanSafe™ Network UPS shutdown and monitoring

software• PowerVision® (30-day trial version) UPS performance

analysis and monitoring software• Foreseer® (demonstration) facility and data center

management software

Power Management Software

20

Software Application

Powerware Extensions for

Application LanSafe NetWatch IBM Director

Single pSeries (serial/TTY) non-LPAR !

Single pSeries (network) non-LPAR !* !*

Single pSeries (LPAR) !*

Multiple pSeries (non-LPAR) ! !*

Multiple pSeries (LPAR) !*

IBM Director Network Device !*

* Co-requisite FC 2934 ConnectUPS Web/SNMP network card.

Note: UPS for iSeries applications utilize OS/400 UPS monitoring functions.

21

Software Comparison

AmbientEmail/ SSL/SSH1 Temperature

Application Monitoring Shutdown GUI SMTP Security Humidity

LanSafe Yes Yes Yes Yes / Yes No/No No/No

NetWatch - Yes - No/No No/No No/No

ConnectUPS Web/ Yes2 Yes3 Yes Yes / Yes Yes / Yes Yes / Yes4

SNMP Card(FC 2934)1SSL = Secure Sockets Layer. SSH = Secure Shell. 2Via Web Browser, LanSafe or Network Management System (e.g.IBM Director, Tivoli). 3In conjunction with NetWatch software. 4With optional FC 2938 EMP (Environmental MonitoringProbe) device attached.

22

ConnectivityWhat you need by application

Software Solution zSeries iSeries pSeries xSeries Storage Networking

LanSafe ! !

LanSafe and ConnectUPS ! !MultiServer card (IBM FC 2933)

NetWatch and ConnectUPS ! !! ! ! !Web/SNMP card (IBM FC 2934) LPARs

Powerware Extensions for ! ! ! IBM Director

NetWatch ! ! ! ! !

ConnectUPS Relay card andAS/400 cable (IBM FC 2936) !!Use ConnectUPS Web/SNMP/xHub card, IBM FC 2934 to support LPAR (POWER 4 Chip Set) servers. For pSeriesconfigurations, each LPAR needs a network connection and will install Powerware provided NetWatch or LanSafesoftware.

23

P30 Collateral

• Additional information available atwww.oem.powerware.com/ibm-ups– Select your region. Click “Products”, click “9910

Solutions” then click “Powerware pSeries” or“Powerware iSeries”

• Materials available– Data sheet– Application overview chart– Product presentation– Documents (manuals)