Upload
habib
View
233
Download
0
Embed Size (px)
Citation preview
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
1/68
ROI-S04188-052E021212
P ASOLINK
N ETWORK
MANAGEMENT
S YSTEM
Engineering Manua(PASOLINK Version)
NEC CorporationCopyright 2002
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
2/68
ROI-S04188
Restricted Right Legends.All rights are reserved. No part of this document may be copied,reproduced, or translated to another language without the prior written consent of NECCorporation. The information contained in this material is subject to change without notice.
NEC CorporationTokyo, JAPAN
Copyright Notices. Copyright 2002 NEC Corporation, all right reserved.
Reproduction, adaptation, or translation of this material without prior written permission isprohibited, expected as allowed under the copyright laws.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
3/68
ROI-S04188
PNMS Engineering manual- i -
CONTENTS
1 INTRODUCTION 1
2 SYSTEM OVERVIEW 2
3 SYSTEM COMPONENTS 3
3.1 PNMS-CENTRAL SITE COMPUTER SYSTEM ..........................................................................3
3.2 PNMT - PASOLI NK NETWORK MANAGEMENTTERMINAL .................................................3
3.3 PMC- PASOLINK MANAGEMENT CARD .............................................................................3
4 PHYSICAL INTERFACE 8
4.1 PNMS..................................................................................................................................8
4.2 PNMT..................................................................................................................................9
4.3 PM CARD .............................................................................................................................9
5 PNMS COMMUNICATION INTERAFCE 10
6 NETWORK SIZING RULE 11
7 PNMS IP ADDRESSING 14
7.1 SIMPLETRUNK L INE NETWORK (SERIAL INTERFACE) .......................................................14
7.2 SIMPLETRUNK L INE NETWORK (LAN INTERFACE)............................................................16
7.3 MULTI SUB-BRANCH NETWORK .........................................................................................19
7.4 PNMS IP ADDRESSING SUMMARY ....................................................................................22
7.5 IP ADDRESS REQUIREMENT F OR CUSTOMER......................................................................23
7.6 MAXIMUM NUMBER OF IP ADDRESS...................................................................................24
8 INTEROPERABILI TY WITH OTHER NETWORK 25
8.1 CONNECTION AVAILABILITY ...............................................................................................25
8.2 POINT TO POINT CONNECTION ...........................................................................................26
8.3 POINT TO MULTI-POINT CONNECTION ...............................................................................27
9 TYPI CAL CONFI GURATION 28
9.1 MULTI-CLUSTER NETWORK (1) -DEDICATED LEASED L INE (SERIAL INTERFACE)- ............28
9.2 MULTI-CLUSTER NETWORK (2) DEDICATED LEASED L INE (LAN INTERFACE)-..............29
9.3 MULTI-CLUSTER NETWORK (3) PSTN (SERIAL INTERFACE)- ..........................................29
9.4 MULTI-CLUSTER NETWORK (4) PSTN (LAN INTERFACE)-..............................................30
9.5 MULTI-CLUSTER NETWORK (5) IP NETWORK (LAN INTERFACE)- ..................................30
9.6 CPM REDUCTION SOLUTION ..............................................................................................31
10 PNMS RELIABILI TY 34
10.1 COLD STAND-BY PNMS PRINCIPLE ..................................................................................34
10.2. BACK UP PNMS DATA (UNIX VERSION ONLY) ...............................................................34
10.3 PARALLEL PNMS .............................................................................................................34
11 NETWORK CONFIGURATION WORK 36
11.1 PNMS FOR WINDOWS.......................................................................................................36
11.2 PNMS FOR UNIX.............................................................................................................44
12 RELATED EQUIPMENT FOR PNMS 52
12.1 HYB CONVERTER .............................................................................................................52
12.2. MANAGEMENT INTERFACE UNIT (MI U) ..........................................................................5312.3 PNMS CABL E .................................................................................................................54
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
4/68
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
5/68
ROI-S04188
PNMS Engineering manual- 1 -
1. INTRODUCTION
This document is developed as a guideline to help to ensure a high degree of accuracy,completeness and uniformity in the system design of a PNMS (PASOLINK NetworkManagement System).
NECs PASOLINK system can be remotely monitored and controlled by the optional PNMT(PASOLINK Network Management Terminal) and the PNMS*.
In order to use these systems, each IDU needs to be equipped with the optional PMC(PASOLINK Management Card). The PNMT software is installed in the Windows95/98/NT/2000 based portable PC and connected to SV (marked as LA) port at 9.6/19.2kbpsasynchronous mode. PNMT can login to a PMC and monitor and control any PASOLINKremotely in the network. Therefore the PNMT is used mainly for maintenance purpose. Forcontinuous network monitoring, PNMS is required. All PASOLINKs under the PNMS arealways accessible.
To facilitate the system design, this guide describes the PNMS and its components, with
emphasis on the capability of each component and the connections that makes thecommunication of network management system possible. It is also includes the procedure forPASOLINK network system design, the architecture, the interpretation of a radio network tothe system, determination of the communication paths, and consideration of systemexpansion. In addition, this guide gives some examples of System design, the drawings forcabling of components and the PMC (PASOLINK Management Card) naming andaddressing scheme are the topics of relating to the detailed PNMS system configuration.
*PNMS and PNMT is not mandatory requirement s for the operation of PASOLINK network.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
6/68
ROI-S04188
PNMS Engineering manual- 2 -
2. SYSTEM OVERVIEW
NEC designed PASOLINK Network Management System (PNMS) which enablesremote monitoring and control of a radio network. The NEC PNMS is a sophisticatedsupervisory tool for transmission equipment and allows operator to perform remotesystem monitor alarms, control NE configuration parameters and display event loggingand performance data in either UNIX or Microsoft Windows platform.
Figure 2.1 shows a typical PNMS application. The system consists of a central computer(PNMS Computer) and a number of remote data processing nodes called PM card. Itsupervises and controls PASOLINK transmission equipments.
In the following sections the functions and the usage of each component are described inmore detail.
PNMSPNMT
ID U
RS-232C, 19.2kbps
RS-232C,19.2kbps
Digital Service Channel, 9.6kbps
PM
CARD
Operation Center
Concept of NMS for PASOLINKConcept of NMS for PASOLINK
Figure 2-1 Typical PNMS Application
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
7/68
ROI-S04188
PNMS Engineering manual- 3 -
3. SYSTEM COMPONENTS
3.1 PNMS-Central Site Computer System
The Central Site Computer is the central operator interface and database, from which system
operators manage the PASOLINK network. It receives data from the network via PM Card,stores it, and displays it to the operator in a variety of formats. It accepts command requestfrom the operators and sends them to the on-site equipment for execution. Two types ofPNMS can be proposed in accordance with Customers Network size. One is PNMS onWindows NT/2000 (supporting up to 500NEs) and the other is PNMS on UNIX OS(supporting up to 1,000NEs).
3.2 PNMT - PASOLINK Network Management Terminal
The PNMT (PASOLINK Network Management Terminal) is a portable computer fitted withNEC's PMNT software, which is used, as an on-site maintenance tool by technicians. Itconnects directly to the LA port of PASOLINK to upgrade the configuration and software. It is
also used to provide local/remote data display and control capabilities similar to those ofPNMS.
The PNMT function can also be run on the PNMS to provide configuration and applicationsoftware upgrade for PM Card from a central point.
The PNMT runs in the Windows 95/98/NT/2000 environment and makes extensive use of theuser friendly Windows Graphical User Interface (GUI). It cannot only interrogate individualPMCs but also monitors the network (subnetwork). It means that the PNMT user can makeconnections to remote PMC from any node within a PASOLINK subnetwork. A PASOLINKsubnetwork is defined as a collection of PMC nodes headed by Central PM CARD. Sub PMCard and Remote PM Card nodes are other node types which can be part of a PASOLINK
subnetwork. This PASOLINK subnetwork is called PASOLINK CPM Cluster in later section.Note that the PNMT is an optional component of the PNMS system.
3.3 PMC- PASOLINK Management Card
PM Cards are located at each site in the monitored network to collect alarm and statusinformation from PASOLINK and to control that equipment in response to commands fromthe central site operator. The PMC primary tasks are to control and acquire data fromPASOLINK at remote location and transfer this data back to the central site. The PM card isdesigned as plug-in modules.
3.3.1 SNMP Agent Function
- PM Cards is functioned as a SNMP agent, which detects alarm and status changes inmonitored equipment, and sends of change notifications to PNMS
- PM Card retains the MIB data and transmit a response to SNMP GET commands fromPNMS and PNMT.
- Execution of SNMP SET message commands received from PNMS/PNMT and transmita control command to the alarm control portion (ALM CONT) in the IDU.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
8/68
ROI-S04188
PNMS Engineering manual- 4 -
3.3.2 Collecting Performance Monitor Data
- Performance measurement is equivalent to ITU-T G.826 standard.*
* The measurement is by the total value of performance monitoring data of RF portion, not theperformance monitoring data of every 2MB traffic as stated in ITU-T G.826.
- The following performance parameters are measured.
- Erred Second Ratio (ESR)- Severely Erred Second Ratio (SESR)- Unavailable Seconds Ratio (UASR)- Background Block Error Ratio (BBER)- Out of Frame Seconds (OFS) only for PASOLINK-S
Stored period in PM Card
There are two types of performance data files, one is every 15 minutes data file and the otheris every day data file.
PASOLINK-S : per 15 minutes data : 4 daysper day data : 7 days
PASOLINK : per 15 minutes data : 7 daysper day data : 7 days
- Performance Monitor file format
Performance monitor file is Binary format in PM Card (This file is stored in PNMS/PNMT asASCII format.). It can be converted to the desirable format by the customer.
3.3.3 Collecting Event Log Data- Hold event log of changed MIB data. The following events are logged.
- Status change- Alarm occurrence- Alarm recovery- Control initiation- Parameter change
- Up to 300 event logs are stored.(The old event logs will be erased as the new event is logged.)
- Event log file format
Events log file is ASCII format. It can be converted to the desirable format by the customer.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
9/68
ROI-S04188
PNMS Engineering manual- 5 -
3.3.4 Configuration File
- Hold information of PASOLINK logical network. There are three kinds of file as follows.
(1) ME Configuration file : Common file
- Setting Auxiliary input and output
- Threshold value of Performance Monitor data
(2) System Configuration file : As per PM card
- NE name and PM Card type
- IP address of each port of PM card, Communication speed
- Opposite IP address
(3) Network Configuration file : As per PM card
- Sub network name
- IP address and PM Card type in the Sub network
3.3.5 PMC Operating Modes
Depending on the size, a network can normally be divided into a number of sub-networks. Todistribute the traffic load we normally define one of the PMC as master and the rest as slavesthrough discrete design. As introduced in above, we also call a master a Central PMC (CPM),a sub-master a Sub-Central PMC (SCPM) and similarly, a slave a Remote PMC (RPM).
The Roles of CPM, SCPM and RPM and their rule are explained, 1. Basic function of PMC,2. Sizing rule of PMC, 3. Adoption Criteria of SCPM, and 4. Positioning of SCPM
1. Basic function of PMC
The PM Cards (PMC) operational mode is based on Master/Slave polling concept. Thenetwork consists of a Central site PM Card (CPM), a possibly Sub-central site PMC (SCPM)and a Remote Site PMC (RPM) installed with an individual software functioning as CPM,SCPM and RPM.
Even though there is no difference in the hardware design, the PMC will be playing differentroles according to the installed software in a network management system as follows;
(1) Master mode (CPM):
To get information from the remote sites and to generate reports to the Central Computer(PNMS). The CPM may act as a terminal unit; which processes and then transfers all thephysical information of equipment, which is directly connected to the CPM. In addition,CPM is connected to PNMS via a dedicated serial communications link, and passesmessages received from RPMCs to the PNMS for display.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
10/68
ROI-S04188
PNMS Engineering manual- 6 -
(2) Sub-Master mode (Sub-Central PMC, SCPM): The SCPM has two operating functions:
Master and gateway function which performs the same activity as a CPM acting as agateway between CPM and RPM and routing the messages from CPM to RPM andback.
Terminal unit function that acts as a stand-alone data acquisition and control unitwhich processes and then transfers all the physical information of equipment which isdirectly connected to the SCPM. This function is the same as that of RPM (SlaveMode).
(3) Slave Mode (RPM):
RPM is a stand-alone data acquisition and control unit. It monitors and controlsequipment at some remote location. Its prime task is to monitor and control and transferdata back to the central site.
2. Sizing Rule of PMC
The sizing restriction of PMC is specified as follows:
(1) CPM-RPM Configuration:
In the case of CPM-RPM configuration, one CPM can handle up to13 RPM(s). Toincrease the number of RPM to more than 14, another CPM is required.
OnePNMS can handle up to 32 CPMs. (The detailed network sizing rule is described inSECTION 6.)
Therefore in case of regional PNMS-CPM-RPM configuration, one PNMS can handlemax. 416 RPM(s) (32CPMX13RPM=416).
(2) CPM-SCPM-RPM Configuration:
In case more than 416 RPM(s) are required to be handled by one PNMS, SCPM is used.
One SCPM can handle up to 13RPM (S)
One CPM can handle up to 31 or 30 SCPM(s). (Refer section 6)
Therefore, if SCPM is used, the number of RPM which can be handled by one PNMS isincreased more than 416 RPMs.
As a rule of thumb, SCPM is used in order to increase the network size that can besupervised by PNMS.
By using the SCPM, one CPM associated with 31 SCPMs can handle up to 416 NEs(SCPMs and RPMs). This can result in a network configuration with the optimal number ofCPM(s) within one PNMS coverage.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
11/68
ROI-S04188
PNMS Engineering manual- 7 -
(3) Adoption Criteria SCPM
As basic rule, if the number of RPM becomes 10, a SCPM is assigned on the head of thegroup of RPM(s) then connected to CPM. As mentioned before, additional 3 RPM(S) maybe connected in the maximum case . However this possibility is reserved for futureexpansion. (Of course, if no future expansion is sure, up to 13 RPM(S) may be connected
from initial stage.)
(4) Rule of SCPM
SCPM is considered as a kind of RPM with enhanced function such as Sub-masterin order to expand the network size. Therefore, depends on the network configuration,there is a case that RPM may be applicable and there is a case that SCPM should beapplied. In other word, SCPM NE is NE which may be selected as RPM or SCPMdepends on the actual network configuration.
3.3.6 CPM/SCPM/RPM Role Change Function
When the PM card founds an interruption of polling signal from the upper PM card, this PM
card can function as CPM. Several PM cards do the role change. The PM card cease rolechange when receiving a polling signal from its upper PM card. During role change, an alarmis indicated but role change status cannot be viewed on the PNMS.
Example 1
If there is a link fault between RPM3 and 4, RPM4 will role change to CPM.
Example 2
If there is an equipment fault in RPM4, RPM5 will role change to CPM.
CPM1 RPM2 RPM3 RPM4 RPM5 RPM6 RPM7
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
12/68
ROI-S04188
PNMS Engineering manual- 8 -
4. PHYSICAL INTERFACE
Summary of physical interface of each equipment is described below.
Figure 4-1 Available Physical Interface
PNMS
CPM
PNMT
SCPM
RPMRS-232C9.6/19.2kbps
Async.
(For Windows NT)
10Base T
(For Windows NT and Unix)
RS-232C/V.11
9.6/19.2kbps
Async.
or
LAN(10Base-T)
(NMS port)
RS-485
or
RS232C
9.6kbps
Async.
(NMS port)
RS-232C(COM port)
RS-232C (LA port) RS-232C (LA port)
DSC (9.6kbps) internal connection10 Base-T
For upper management system
RS-485
or
RS232C
9.6kbps
Async.
(NMS port)
4.1 PNMS
4.1.1 Serial InterfaceFunctional : RS232C
Electrical : V.24
Mechanical : DB 9 PIN
Communication rate : 9.6/19.2 kbps (Asynchronous)
4.1.2 LAN Interface
Interface : Ethernet (100/10 BaseT)
Connector type : RJ-45
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
13/68
ROI-S04188
PNMS Engineering manual- 9 -
4.2 PNMT
Functional : RS232C
Electrical : V.24
Mechanical : DB 9 PINCommunication rate : 9.6/19.2 kbps (Asynchronous)
4.3 PM Card
4.3.1 LA Port
Functional : RS232C
Electrical : V.24
Mechanical : DB 15 PIN
Communication rate : 9.6/19.2 kbps (Asynchronous)
4.3.2 NMS Port
Functional
for PNMS connection : RS232C/RS422/LAN(10Base-T)
for Back to Back connection : RS232C/RS485
Electrical : V.24/V.11(for RS232C/RS422/RS485)
Mechanical : DB 15 PIN
Communication rate
for PNMS connection : 9.6/19.2 kbps (Asynchronous) (for RS232C/RS422)
for Back to Back connection : 9.6kbps (Asynchronous)
LA portNMS port
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
14/68
ROI-S04188
PNMS Engineering manual- 10 -
5. PNMS COMMUNICATION INTERAFCE
The interface condition between PNMS and NEs (CPM,SCPM,RPM) is summarized in Figure5.1 (Serial interface) and Figure5.2 (LAN interface). The physical interface at PNMSHardware is RS232C or 10baseT interface. The physical interface at CPM for PNMSconnection is RS-232C (9.6/19.2kbps, Async.). The physical interface at CPM, SCPM and
RPM for back to back connection is RS-232C or RS-485 (9.6kbps, Async.). And the choice ofthe physical interface at CPM,SCPM and RPM should be done by the PNMS software.
Serial Interface between PNMS (Windows) and CPM
Figure5-1 PNMS Communication Architecture (Serial Interface)
RPM
-1
SCPM
-2
SNMP/TFTPSNMP/TFTPSNMP/TFTPAP
RS-232C/485
9.6kbps Async.
RS-232C/485
9.6kbps Async.
RS-232C
19.2kbps Async.
Physical*
HDLC/NRMHDLC/NRMPPPData Link
IPIPIPNetwork
UDPUDPUDPTransport
SCPM-RPMCPM-SCPMPNMS-CPM
CPM
RPM
-3
-4
*The converter will
be required for
other interfaces.
LAN Interface between PNMS (Windows and UNIX) and CPM
Figure 5-2 PNMS Communication Architecture
RPM
-1
SCPM
-2
SNMP/TFTPSNMP/TFTPSNMP/TFTPSNMP/TFTPAP
RS-232C/485
9.6kbps Async.
RS-232C/485
9.6kbps Async.
RS-232C
19.2kbps Async.
10baseTPhysical*
HDLC/NRMHDLC/NRMPPPEthernetData Link
IPIPIPIPNetwork
UDPUDPUDPUDPTransport
SCPM-RPMCPM-SCPMROUTER-CPMPNMS-ROUTER
CPM
RPM
-3
-4
RR IPNetwork
*The converter will
be required forother interfaces.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
15/68
ROI-S04188
PNMS Engineering manual- 11 -
6. NETWORK SIZING RULE
The following network sizing restriction is applied when NEC PASOLINK supervisory networkhierarchy is configured.
Restriction in this layer Restriction of Number of NE in thislayer
PNMS(UNIX)(10,000NE type)
Maximum number of CPMs =192(1)
Maximum number of NE (CPM +SCPM + RPM) s = 10,000(5)
PNMS (UNIX)(1,000NE type)
Maximum number of CPMs = 32 Maximum number of NE (CPM +SCPM + RPM) s = 1,000
Maximum number of CPMs = 16(Serial Interface)
PNMS (NT)
Maximum number of CPMs = 32(LAN Interface)
Maximum number of NE (CPM +SCPM + RPM) s = 500
CPM Maximum number of SCPMs =
31(2)
Maximum number of SCPMs(when CPM is in Dual Master
mode) = 30(3)
Maximum number of directlyconnected SCPMs with one CPM
= 13(4)
Maximum number of NE (SCPM +
RPM) = 416
SCPM Maximum number of (SCPM(5)
+
RPM)s = 13
Maximum number of NE (SCPM +
RPM)s = 13(6)
Table6-1: Network Sizing Rule (Theoretical, Number of NE)
(1) Maximum number of CPMs for Central type PNMS is recommended to be less than100 due to PNMS hardware performance limitation even if theoretical value is 192 asindicated in the Table 6.1
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
16/68
ROI-S04188
PNMS Engineering manual- 12 -
(2) The diagram below demonstrates the restriction per CPM
(3) In case that the two(2) physical Subnets connection is required to CPM as shownbelow, the CPM is regarded as Dual master mode.
PNMS
Subnet1
SCPM1 SCPM2
Subnet2 Subnet3
Subnet32
SCPM31
Subnet N
SCPM N-1
Subnet N+1
SCPM N
Figure 6.1
Maximum number of subnet is 32 under a CPM.
Therefore maximum number of SCPM is 31.
: RPM
: CPM
: SCPM
PNMS
SCPM3
Subnet4
Subnet32
SCPM30
Subnet N+1
SCPM N-1
Subnet N+2
SCPM N
Subnet 3
Figure 6.2 CPM (Dual Master mode)
Maximum number of subnet is 32. In case of dual CPM configuration,
maximum number of SCPM is 30.
Dual Master
SCPM2
Subnet2 Subnet1
SCPM N+1
Radio SectionBack to back connection
: RPM
: CPM
: SCPM
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
17/68
ROI-S04188
PNMS Engineering manual- 13 -
(4) The diagram below demonstrate this restriction on the CPM layer.
(5) Maximum number of NEs is set to 10,000, assuming there are 10 regional PNMS (10Regional PNMS x 1000NEs).
(6) SCPM is within the sub network of the master SCPM. For example in Figure 6.1,SCPM2 is within the SCPM1 sub network. SCPM1 is the master SCPM of SCPM2.
PNMS
Figure 6.3
Maximum number of SCPM per CPM
: 31 or 30(Dual Master)
Maximum number of directly connected
SCPM with CPM is13.
(CPM and SCPM issame subnetwork)
: RPM
: CPM
: SCPM
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
18/68
ROI-S04188
PNMS Engineering manual- 14 -
7. PNMS IP ADDRESSING
PNMS identifies each NE with IP address (IP v4). IP addressing scheme and requirement isdescribed with typical network.
7.1 Simple Trunk Line Network (Serial Interface)
To explain IP addressing of PNMS, Typical network example (simple Trunk line) is shown(Figure 7.1). Serial interface is assumed for the interface between PNMS (Windows) andCPM in this figure.
PNMS(Windows)
PNMS
1
3
Remote Site-A
4 5
Remote Site-B
6 7
Remote Site-C
8
Remote Site-D
2
: RPM
RS232C
19.2/9.6kbps, Async
2
Figure7.1 Typical Network Example (Simple trunk line [Physical Model])
1 : CPM
Figure 7.2 shows a logical network of Figure7.1 and IP address assignment example. Todemonstrate connection of each NE with PNMS, 2 sub-networks, PNMS and CPMsub-network (A) and PASOLINK CPM cluster network (B) are defined.
1
CPM
2
RPM
4
RPM
5
RPM
6
RPM
7
RPM
8
RPM
3
RPM
PNMS
Central Site
172.20.100.1
172.20.100.2
172.20.101.2
172.20.101.3
172.20.101.6
172.20.101.4172.20.101.5 172.20.101.7
172.20.101.8
172.20.101.1
Subnet-B (PASOLINK CPM cluster)
Subnet-A (PNMS-CPM Subnetwork)
Figure7.2 Typical Network Example (Simple trunk line [Logical Model])
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
19/68
ROI-S04188
PNMS Engineering manual- 15 -
7.1.1 IP Addressing Scheme for PNMS-CPM Subnetwork
CPM NMS port and PC PNMS serial port must be located in the same sub network as shownFigure7.2. In this figure, the CPM is connected to PNMS through RS-232C interface and PPPencapsulation. The CPM NMS port IP address acts as the gateway to its PASOLINK cluster.For example, CPM passes an IP packet from PNMS with 172.20.101.3 to the destination NE.
For this PNMS and CPM sub-network (A), PNMS uses a subnet mask of 255.255.255.252.(fixed). One PNMSCPM sub network includes 4 IP addresses accordingly. However 2 IPaddresses are not available because one is assigned for network address, the other isreserved for broadcast address.
7.1. 2 IP Addressing Scheme for PASOLINK CPM Cluster
This section shows the IP addressing scheme in PASOLINK CPM cluster (B). PNMS uses aSubnet mask of 255.255.255.240. (fixed) for this sub-network. Therefore one sub-network inCPM cluster has 16 IP addresses. However available IP addresses for Remote PM Card(RPM) are 13 as shown in section 6 Network sizing rule. It is because one is assigned fornetwork address, the other is reserved for broadcast address, in addition one IP address is
assigned for CPM.
For reference assigned IP address and available IP address of each sub-network are shownin following table.
Subnet-B : 172.20.101. 0 15 (Assigned IP Address): 172.20.101. 1 14 (Available IP Address)
Table7.1 Example for IP address planing in each Subnet
Subnet-A : 172.20.100. 0 3 (Assigned IP Address)
172.20.100. 1 2 (Available IP Address)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
20/68
ROI-S04188
PNMS Engineering manual- 16 -
7.2 Simple Trunk Line network (LAN Interface)
Figure7.3 shows typical network example (simple Trunk line) with LAN interface through IPnetwork between PNMS and CPM.
PNMS
1
3
Remote Site-A
4 5
Remote Site-B
6 7
Remote Site-C
8
Remote Site-D
2
: RPM
RS232C
19.2/9.6kbps, Async
2
1 : CPM
R : Router
Figure7.3 Typical Network Example (Simple trunk line [Physical Model])
IP
Network
R R
Figure 7.4 shows a logical network of Figure7.3 and IP address assignment example. Todemonstrate connection of each NE with PNMS, 2 sub-networks, Router and CPMsub-network and PASOLINK CPM cluster network are defined.
1
CPM
2RPM
4RPM
5RPM
6RPM
7RPM
8RPM
3RPM
PNMS
Central Site
172.20.100.1
172.20.100.2
172.20.101.2
172.20.101.3
172.20.101.6
172.20.101.4
172.20.101.5 172.20.101.7
172.20.101.8
172.20.101.1
Subnet-B (PASOLINK CPM cluster)
R
Subnet-A (Router-CPM Subnetwork)
RIP
Network
Figure7.4 Typical Network Example (Simple trunk line [Logical Model])
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
21/68
ROI-S04188
PNMS Engineering manual- 17 -
7.2.1 IP Addressing Scheme for Router-CPM Subnetwork
CPM NMS port and the Router Serial port must be located in the same sub network as shownFigure 7.4. In this figure, the CPM is connected to the router (R) and must be added to the IProute of the said router. The interface is RS-232C and PPP encapsulation. The CPM NMSport IP address is added to the IP route table of the router and acts as the gateway to the
PASOLINK CPM cluster. For example, an IP packet with 172.20.101.3 is sent to the IPnetwork, the router passes this to the CPM NMS port and then the CPM passes it to thedestination NE, which is the recipient of the packet as shown in Figure 7.4.
For this Router and CPM sub-network, PNMS uses a subnet mask of 255.255.255.252(fixed). One RouterCPM sub network includes 4 IP addresses accordingly. However only 2IP addresses are not available because one is assigned for network address, the other isreserved for broadcast address.
. To allocate plural CPMs and Router ports in the future in this sub-network for networkexpansion as shown Figure 7.5, the Class C sub-network (for example 172.20.100.**) isrecommended.
1
CPM
12
RPM
PNMS
Subnet-D (PASOLINK CPM cluster)
RIP
Network
Figure7.5 Typical Network Example (Multi-branch network [Logical Model])
R
13
RPM
18
RPM
3
CPM
32
RPM
38
RPM
33
RPM
22
RPM
28
RPM
23
RPM
2
CPM
Subnet-A (Router-CPM subnetwork) Subnet-B
Subnet-C
Subnet-E
Subnet-F
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
22/68
ROI-S04188
PNMS Engineering manual- 18 -
7.2.2 IP Addressing Scheme for PASOLINK CPM Cluster
Refer to section 7.1.2.
For reference assigned IP address and available IP address of each sub-network are shownin Table 7.2 for Figure 7.4 and Table 7.3 for Figure 7.5
Subnet-B : 172.20.101. 0 15 (Assigned IP Address)
: 172.20.101. 1 14 (Available IP Address)
Table7.2 Example for IP address planing in each Subnet for Figure 7.4
Subnet-A : 172.20.100. 0 3 (Assigned IP Address)
172.20.100. 1 2 (Available IP Address)
Subnet-B : 172.20.100. 4 7 (Assigned IP Address)
: 172.20.100. 5 6 (Available IP Address)
Table7.3 Example for IP address planing in each Subnet for Figure 7.5
Subnet-A : 172.20.100. 0 3 (Assigned IP Address)
172.20.100. 1 2 (Available IP Address)
Subnet-C : 172.20.100. 8 11 (Assigned IP Address)
: 172.20.100. 1213 (Available IP Address)
Subnet-D : 172.20.101. 015 (Assigned IP Address)
: 172.20.101. 1 14 (Available IP Address)
Subnet-E : 172.20.101. 1631 (Assigned IP Address)
: 172.20.101. 1730 (Available IP Address)
Subnet-F : 172.20.101. 3247 (Assigned IP Address)
@@@@@ : 172. 20.101.3346 (Available IP Address)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
23/68
ROI-S04188
PNMS Engineering manual- 19 -
7.3 Multi Sub-Branch Network
Figure7.6 shows typical network example (Multi sub-branch network). In this figure serialinterface between PNMS and Router is assumed.
Central Site
PNMS
(Windows)
1
4
Remote Site-A
5 6
Remote Site-B
Remote Site-C
14
Remote Site-D
3
10 9
12 1113
Remote Site-E
Remote Site-F
Remote Site-G
7
82
RS232C
19.2/9.6kbps, Async
RS485
9.6kbps, Async
Figure 7.6 Typical Network Example (Multi sub-branches network[Physical Model])
: RPM3
1 : CPM
2 : SCPM
Figure 7.7 shows a logical network of Figure7.6 and IP address assignment example. Todemonstrate connection of each NE with PNMS, 3 sub-networks, PNMS and CPMsub-network (A) and PASOLINK CPM cluster network (B and C) are defined.
1
CPM
2
SCPM
4
RPM
5
RPM
6
RPM
7
RPM
8
RPM
3
RPM
PNMS
Central Site 14
RPM
11
RPM
10
RPM
9
RP M
12
RPM
13
RPM
172.20.100.1
172.20.100.2
172.20.101.2
172.20.101.3
172. 20.101.6
172.20.101.4
172.20.101.5
172.20.101.7
172. 20.101.8
172.20.101.9
Subnet-B(PASOLINK CPM cluster)
Subnet-C
172.20.101.17
172.20.101.18172.20.101. 19172.20.101. 20172.120.101. 21
172.20.101. 22
Subnet-A(Router-CPM Subnetwork)
172.20.101.1
Figure 7.7 Typical Network Example (Multi sub-branches network[Logical Model])
7.3.1 IP Addressing Scheme for PNMS-CPM Subnetwork
Refer to section 7.1.1.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
24/68
ROI-S04188
PNMS Engineering manual- 20 -
7.3.2 IP Addressing Scheme for PASOLINK CPM Cluster
PNMS uses a Subnet mask of 255.255.255.240. (fixed) for this sub-network. Therefore onesub-network in CPM cluster has 16 IP addresses. Depending on the size, a network cannormally be divided into a number of sub-networks to distribute the traffic load. Each subnetwork can accommodate 16 IP addresses. Available IP addresses for Remote PM Card
(RPM) are 13.
In Figure7.6, Subnet-B is assigned from 172.20.101.0 to 172.20.101.15. (16 IP Addresses)However 172.20.101.0 and 172.20.101.15 is not available because 172.20.101.0. is subnetwork address and 172.20.101.15 is reserved for broadcast address. In addition one IPaddress is assigned on Central PM Card. Therefore 13 IP addresses (for 13 RPMs) areavailable in Subnet-B (same as for all other sub network).
In addition IP address for next sub-network (Subnet-C) shall be assigned from172.20.101.16. (172.20.101.17 to172.20.101.30 is available), even if Subnet-B has less than13 NEs (for example only one NE), Subnet-C is started to assign from 172.20.101.17.
One CPM cluster can include maximum 32 sub-networks as explained in Section 6.
Therefore one CPM cluster can accommodate maximum 512 IP addresses(16 IP address x32 sub-networks) . This maximum 512 consecutive IP addresses are reserved in PNMS. Two(2) class C sub-networks (for example, 172.20.101.** and 172.20.102.**) are required toassure the 512 IP Addresses.
For reference assigned IP address and available IP address of each sub-network are shownin Table 7.4.
Subnet-B : 172.20.101. 0 15 (Assigned IP Address)
: 172.20.101. 1 14 (Available IP Address)
Subnet-C : 172.20.101.16 31 (Assigned IP Address)
172.20.101. 17 30 (Available IP Address)
Table 7.4 Exam ple for IP address planing in each Subnet
Subnet-A : 172.20.100. 0 3 (Assigned IP Address)
172.20.100. 1 2 (Available IP Address)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
25/68
ROI-S04188
PNMS Engineering manual- 21 -
7.3.3 Example of IP Addressing for Multi Sub-Branch Network
Figure7.8 show the example of IP address assignment for CPM cluster with 8 sub-network
RPM SCPM
CPMSCPMRPMRPMRPM
RPM SCPMRPM
RPM SCPM172.18. 0.1
RPM SCPMRPMRPM
RPM SCPM
172.18.0.18
172.18.0.2
172.18.0.33
172.18.0.34
172.18.0.65
172.18. 0. 36
172.18.0. 35
172.18.0.78
172.18. 0.66
172.18.0. 49172.18.0. 50172.18. 0.51172.18.0.62
172.18.0.81172.18.0.83
172.18.0. 94
172.18.0.82
172.18.0.97
172.18. 0. 113
171.18.0. 110
172.18.0.126
B
CD
E
F
G
H
172.18.0. 37
172.18. 0.67
PNMS
Figure 7.8 Network Example (IP address Scheme)
172.18.2.2
172.18.2.1
172.18.0.17
A
I
Router and CPM
subnetwork
R
Table 7.5 shows assigned IP addresses and available IP addresses of each sub network ofthis multi sub-branch network.
Subnet-C : 172.18.0. 1631 (Assigned IP Address)
: 172.18.0. 17 30 (Available IP Address)
Subnet-D : 172.18.0. 3247 (Assigned IP Address)
: 172.18.0. 3346 (Available IP Address)
Subnet-E : 172.18.0. 4863 (Assigned IP Address)
: 172.18.0. 4962 (Available IP Address)
Subnet-F : 172.18.0. 6479 (Assigned IP Address)
@@@@@ : 172. 18.0. 65
78 (Available IP Address)Subnet-G : 172.18.0.8095 (Assigned IP Address)
: 172.18.0.8194 (Available IP Address)
Subnet-H : 172.18.0.96111 (Assigned IP Address)
: 172.18.0.97110 (Available IP Address)
Table 7.5 : Example for IP address planning in each Subnet
Subnet-A : 172.18.2. 1 (Router Serial IP Address)
: 172.18.2. 2 (CPM NMS port IP Address)
Subnet-B : 172.18.0. 015 (Assigned IP Address)
: 172.18.0. 1 14 (Available IP Address)
Subnet-I : 172.18.0.112127 (Assigned IP Address)
: 172.18.0.113126 (Available IP Address)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
26/68
ROI-S04188
PNMS Engineering manual- 22 -
7.4 PNMS IP Addressing Summary
Figure 7.9 (Serial Interface) and Figure 7.10 (LAN interface) describe the summary of PNMSIP addressing scheme
Figure 7.9 IP address Scheme for PNMS (Serial interface between PNMS and CPM)
Subnet Mask is 255.255.255.240
(11111111.11111111.11111111.11110000)
Number of assigned address is 16.
All 1s and 0s are reserved.
Therefore 14 address are available
for each network.The last 8 bit is also used as a HDLC
address for polling.
The CPM and SCPM works as a router to
routing the packets among the networks.
Subnet Mask is 255.255.255.252
(11111111.11111111.11111111.11111100)
Number of assigned address is 4.
All 1s and 0s are reserved.
Therefore 2 address are available.
CPM
SCPM
SCPMSCPM
RPMRPM
RPM
PNMS (Windows)
R
Subnet Mask is 255.255.255.240
(11111111.11111111.11111111.11110000)
Number of assigned address is 16.
All 1s and 0s are reserved.
Therefore 14 address are available
for each network.
The last 8 bit is also used as a HDLC
address for polling.
The CPM and SCPM works as a router to
routing the packets among the networks.
Subnet Mask is 255.255.255.252
(11111111.11111111.11111111.11111100)
Number of assigned address is 4.
All 1s and 0s are reserved.
Therefore 2 address are available.
CPM
SCPM
SCPMSCPM
RPMRPM
RPM
R
IP
Network
Figure7.10 IP address Scheme for PNMS (LAN interface between PNMS and CPM)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
27/68
ROI-S04188
PNMS Engineering manual- 23 -
7.5 IP Address Requirement for Customer
During the Network Design phase, following IP address must be required in order for eachNEs to connect to the PNMS.
1) RouterCPM sub-network
IP address for Router Serial port
IP address for CPM NMS port (Provision of one class C sub-network isrecommended for multiple Routers in future for expansion)
2) PASOLINK CPM cluster network
CPM cluster sub-network Address for each NE
(Two class C sub networks are required for maximum 512 IP addresses)
3) Others
IP address for the PNMS
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
28/68
ROI-S04188
PNMS Engineering manual- 24 -
7.6 Maximum Number of IP Address
When the PASOLINK network is configured according to the sizing rule, the theoreticalnumber of IP address is calculated as shown in following Table 7.6.
Layer
Theoretical absolute maximumnumber of IP address for NECPASOLINK CPM cluster subnetwork
Theoretical absolute maximum numberof IP address for Router-CPM subnetwork
PNMS (UNIX)(10,000NE Type)
98,304(This type PNMS has up to192 CPMs and each CPM can haveup to 32 subnets and each subnethas a maximum of 16 addresses;therefore total = 192 x (32 subnets x16)) =98,304).
384 (Maximum number of CPMs is 192,two IP addresses are required (RouterSerial IP address and CPM PNMS portIP address).
PNMS (UNIX)
(1,000NE Type)PNMS (Windows)(LAN interface)
16,384 (This type PNMS has up to
32 CPMs and each CPM can haveup to 32 subnet and each subnet hasa maximum of 16 addresses;therefore total = 32 x (32 subnets x16)) = 16,384).
64 (Maximum number of CPMs is 32,
two IP addresses are required (RouterSerial IP address and CPM PNMS portIP address).
PNMS (Windows)(Serial Interface)
8,192 (1 PNMS has up to 16 CPMsand each CPM can have up to 32subnet and each subnet has amaximum of 16 addresses;therefore total = 16 x (32 subnets x16)) = 16,384).
32 (Maximum number of CPMs is 16,two IP addresses are required (RouterSerial IP address and CPM PNMS portIP address).
CPM 512 (1 CPM can have up to 32subnet and each subnet has amaximum of 16 addresses thereforetotal = 32 subnets x 16 = 512).
2 (Router Serial IP address and CPMPNMS port IP address)
SCPM 16 (13 address for the SCPM/RPM*7)
, one for the SCPM*8)
, one forbroadcast address, one for thenetwork address.
-
Table7.6 : Network Sizing Rule (Theoretical, Number of IP address)
Note:The above numbers are theoretical maximum. The practical numbers required are
determined by network capacity and performance requirements by the Customer. For examplethe number of CPMs per PNMS can be optimised to three (3) to cover the maximum 1000 NEsinstead of the above theoretical maximum 32 CPMs by introducing effective mediation devicessuch as MIU (Refer to Section 12.2)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
29/68
ROI-S04188
PNMS Engineering manual- 25 -
8. INTEROPERABILITY WITH OTHER NETWORK
If the network is composed of only PASOLINK, the integration of PNMS will be simple.However in case of the existing customers transmission network, interconnectivities andinteroperability among different manufacturers will have to be confirmed. The purpose of thissection is to allow the PASOLINK supervisory network to managed each heterogeneously
located PASOLINK hop through customers existing transmission network and IP network.
For example, the interconnected equipments could be:
Other transport equipments from manufacturers
Routers such as Cisco
8.1 Connection Availability
Following table is the connection availability between PASOLINK and Other equipment
(other manufacture equipment and NEC equipment other than PASOLINK) of RS485interface.
Point to point Connection Point to multi-point(daisy chain) connection
Otherequipment(RS485)
Otherequipment(RS422)
Otherequipment(RS485)
Otherequipment(RS422)
PASOLINKRS485
PASOLINK(RS485)
Not Available(Note 1)
(Note 2) Not Available(Note 1)
Not Available Available
ProposedSolution
Convert RS422by using HYB CONV
Convert RS422by using HYB CONV
-
Table 8.1 Connection availability
Note.1) Because the method of connecting data signal lines in plural connections in point tomulti-point line is not determined, it is not possible to connect equipment fromdifferent manufacturers unless connection test between PASOLINK and otherequipment is required.
Note.2) Terminal impedance of other manufacture equipment is not clear. Therefore outputlogical condition of other manufacture equipment is not clear in high impedancecondition. In this case it is impossible to connect each other. (Connection test isrequired between PASOLINKand other equipment.)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
30/68
ROI-S04188
PNMS Engineering manual- 26 -
8.2 Point to Point Connection
Figure 8.1 shows the PASOLINK supervisory interface with existing network (dedicated linesuch as DSC) between PNMS and CPM.
PASOLINK CLUSTER
DSC i 19.2/9.6kbps, ASYNCj
Figure 8.1 Interoperability with other manufacture equipment
PNMS
(Windows )
Existing Network (Dedicated line)
RS232C port
(In case of other than RS232C port,
additional converter is required
in accordance with the existing
physical interface
RS-232C19.2/9.6kbps
ASYNC
RS-232C
19.2/9.6kbpsASYNC
DSC i 19.2/9.6 kbps, ASYNCj
LAN
RS-232C
19.2/9.6kbps
ASYNC
Existing Network (Dedicated line)
RS232C port
(In case of other than RS232C port,
additional converter is required
in accordance with the existing
physical interface
PNMS
(UNIX or
Windows )
PASOLINK CLUSTER
R
RS-232C
19.2/9.6kbps
ASYNC
Figure 8.2 show the PASOLINK supervisory interface with existing network (PSTN or IPnetwork) between PNMS and CPM.
MD MD
IP
Network
Figure 8.2 Interoperability with other network
LAN
RS-232C
9.6kbps
ASYNC
RS-232C
9.6kbps
ASYNC
RS-232C
19.2/9.6kbps
ASYNC
PSTN
Continuous connection is needed
PNMS
(UNIX or
Windows)
PNMS
(Windows )
PASOLINK CLUSTER
RR
PASOLINK CLUSTER
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
31/68
ROI-S04188
PNMS Engineering manual- 27 -
Figure 8.3 show the PASOLINK supervisory interface with existing network betweenPASOLINKs.
Figure 8.3 Interoperability with other network (point to point connection)
LAN
RS-232Cor RS-485
19.2/9.6kbps
ASYNC
RS-232C, RS-485
19.2/9.6kbps
ASYNC
RS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
Existing Network (Dedicated line)
19.2/9.6 kbps, ASYNC PNMS
(UNIX or
Windows)
LANRS-232Cor RS-485
19.2/9.6kbps
ASYNC
RS-232C, RS-48519.2/9.6kbps
ASYNC
RS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
PNMS
(UNIX or
Windows)
MD MD
PSTN
Continuous connection is needed
R
R
RS232Cport
(In case of other than RS232C port,
additional converter is requiredin accordance with the physical interface
PASOLINK CLUSTER
PASOLINK CLUSTER
8.3 Point to Multi-Point Connection
Figure 8.4 show the PASOLINK supervisory interface with existing network betweenPASOLINKs (point to multi-point connection). Because of the reason described section 8.1,HYB converter (Refer to section 12.1) is required to combine and divide the supervisionsignal.
Figure 8.4 Interoperability with other network
LANRS232C, RS-485
19.2/9.6kbps
ASYNC
RS-232C, RS-48519.2/9.6kbps
ASYNC
RS-232C19.2/9.6kbps
ASYNC
Existing Network
(Dedicated line)
19.2/9.6 kbps, ASYNC
RS232 or RS422 or RS485 port
(In case of other than RS232C or RS485 or RS485 port,
additional converter is requiredin accordance with the existing physical interface
PNMS
(UNIX orWindows)
H
Y
B
C
O
N
V
H
Y
B
C
O
N
V
R
R :Router
: Existing Network (Dedicated line): RPM
: CPM
PASOLINK CLUSTER
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
32/68
ROI-S04188
PNMS Engineering manual- 28 -
9. TYPICAL CONFIGURATION
The PNMS supports a variety of radio topologies. That is, there are many ways in which theconnections can be made between PNMS, CPM, SCPM and RPM. The system design is toanalyse the network and customer requirement, to decide the PASOLINK networkconfiguration, to estimate the cost and provide customer with some optimised solutions.
Based on the radio network information a PASOLINK network management system can beformed by following steps specified below:
Select PNMS Architecture and decide on the number of PNMS hardware.
Decide that the PASOLINK network configuration based on given radio topology.Divide the monitored network into sub-networks, which is geographically andfunctionally manageable for monitoring and controlling in accordance with section6.Network Sizing rule.
Decide on the PMC operation modes (such as CPM, SCPM, and RPM) and the PMC
Determine the data communication path.
.
9.1 Multi-Cluster Network (1) -Dedicated Leased Line (Serial Interface)-
Figure 9.1 shows a multi-cluster network, monitored and controlled by PNMS through serial(RS232C) interface and dedicated line such as DSC. Multiple connections on centralcomputer are realized by RS232C extension port installed in the PC. 19.2kbps or 9.6kbps(RS232C interface) are required for dedicated leased line or Digital Service Channel.
EEE
Figure 9.1 Multi-branch network through Digital Service Channel
with PNMS Serial interface
PNMS
(Windows)
Extension port (board
inserted into PCI SLOT)
EEEE
RS-232C
19.2/9.6kbps
ASYNCRS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
Existing Network (Dedicated line)
19.2/9.6 kbps, ASYNC
RS232C port
(In case of other than RS232C port,
additional converter is required
in accordance with the existing
physical interface
PASOLINK CLUSTER
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
33/68
ROI-S04188
PNMS Engineering manual- 29 -
9.2 Multi-Cluster Network (2) Dedicated Leased Line (LAN Interface)-
Figure 9.2 shows a multi-cluster network, monitored and controlled by PNMS through LANinterface and dedicated line such as DSC. 19.2kbps or 9.6kbps (RS232C interface) arerequired for Router port of dedicated line or Digital Service Channel .
EEEE
EEEE
RS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
PASOLINK CLUSTER
R
PNMS
(UNIX or
Windows )
Existing Network (Dedicated line)
19.2/9.6 kbps, ASYNC
RS232Cport
(In case of other than RS232C port,
additional converter is required
in accordance with the physical interface
Figure 9.2Multi-branch network through Digital Service Channel
with PNMS Serial interface
RS-232C
19.2/9.6kbps
ASYNC
9.3 Multi-Cluster Network (3) PSTN (Serial Interface)-
Figure9.3 shows a multi-cluster network, monitored and controlled by PNMS through serialinterface and PSTN. RS232C interface (9.6/19.2kbps) are required for Modem.
PNMS(Windows)
MD
MD
MD
MD
MD
MD
MD
MD
EEEE
RS-232C9.6kbps
ASYNC
RS-232C
9.6kbps
ASYNC
Extension port (board
inserted into PCI SLOT)
EEEE
PASOLINK CLUSTER
PSTN
Continuous connection is needed
Figure 9.3 Multi-branch network through PSTN with PNMS Serial interface
PASOLINK CLUSTER
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
34/68
ROI-S04188
PNMS Engineering manual- 30 -
9.4 Multi-Cluster Network (4) PSTN (LAN Interface)-
Figure 9.4 shows a multi-cluster network, monitored and controlled by PNMS through LANinterface and PSTN. RS232C interface (9.6/19.2kbps) are required for Modem.
MD
MD
MD
MD
MD
MD
MD
MD
E
EEE
RS-232C9.6kbps
ASYNC
RS-232C
9.6kbps
ASYNC
E
EEE
PASOLINK CLUSTER
PSTN
Continuous connection is needed
Figure 9.4 Multi-branch network through PSTN with PNMS LAN interface
R
PASOLINK CLUSTER
PNMS
(UNIX or
Windows )
9.5 Multi-Cluster Network (5) IP Network (LAN Interface)-
Figure 9.5 shows a multi-cluster network, monitored and controlled by PNMS through LANinterface and IP network.
IP NETWORK
LAN
RS-232C
19.2/9.6kbps
ASYNC
EEEE
PASOLINK CLUSTER
PASOLINK CLUSTER
Figure 9.5 Multi-branch network through IP network
R
R
R
R
R
PNMS
(UNIX or
Windows )
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
35/68
ROI-S04188
PNMS Engineering manual- 31 -
9.6 CPM Reduction Solution
In accordance with customers network such that many CPM clusters scattered in all over theregion, plural CPMs are required to be monitored and controlled by PNMS as shown inFigure9.6. In such cases the number of the required Router serial port increases inaccordance with the number of CPMs. If the number of NEs within a PASOLINK cluster
managed by a CPM is smaller than 416, it is possible to combine such PASOLINK clusters tooptimise the configuration. To reduce CPMs, 3 solutions are proposed as described infollowing section.
The concept for reducing CPM is shown Figure 9.7. The CPM function is located at PNMSsite. In case that each PASOLINK cluster scattered all over the region and these are neededto be connected through customers DSC, HYB CONV can concentrate this connection atPNMS site. Then single combined signal is connected to CPM.
EEEE
EEEE
RS-232C
19.2/9.6kbps
ASYNC
RS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
PASOLINK CLUSTER
R
PNMS
(UNIX or
Windows)
Existing Network (Dedicated line)
19.2/9.6 kbps, ASYNC
RS232C port
(In case of other than RS232C port,
additional converter is required
in accordance with the physical interface
Figure 9.6 Multi cluster network through Digital Service Channel
: RPM
: CPM
: SCPM
Up to 416 NEs
Up to 416 NEs
Up to 416 NEs
Up to 416 NEs
EEEE
EEEE
RS-232C or RS485
9.6kbps
ASYNC
RS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
PASOLINK CLUSTER
R
PNMS
(UNIX or
Windows)
Existing Network (Dedicated line)
9.6 kbps, ASYNC
RS232C port
(In case of other than RS232C port,
additional converter is requiredin accordance with the physical interface
Figure 9.7 Multi cluster network through Digital Service Channel
CPM
Function
H
Y
B
C
O
N
V
: RPM
: CPM
: SCPM
Up to 416 NEs
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
36/68
ROI-S04188
PNMS Engineering manual- 32 -
9.6.1 Solution 1
This solution is applied for the case of PASOLINK HOP locating at PNMS site as shown inFigure 9.8.
EE
EE
EEEE
RS-232C or RS485 port
9.6kbps
ASYNC
RS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
PASOLINK CLUSTER
R
PNMS
(UNIX or
Windows)
Existing Network (Dedicated line)
9.6 kbps, ASYNC
RS232C port (In case of other than RS232C
port,additional converter is required
in accordance with the physical interface
Figure 9.8 Multi cluster network through Digital Service Channel
H
Y
B
C
O
NV
: RPM
: CPM
: SCPM
Up to 416NEs
9.6.2 Solution 2
This solution is applied for the usage of mediation device (CPM function) locating at PNMS
site. This mediation device is called MIU (Management Interface Unit). (Refer to Section12.2.)
EEEE
EEEE
RS-232Cor RS485
9.6kbps
ASYNC
RS-232C
19.2/9.6kbps
ASYNC
PASOLINK CLUSTER
PASOLINK CLUSTER
R
PNMS
(UNIX or
Windows)
Existing Network (Dedicated line)
9.6 kbps, ASYNC
RS232C port
(In case of other than RS232C port,
additional converter is required
in accordance with the physical interface
Figure 9.9 Multi cluster network through Digital Service Channel
H
Y
B
C
O
N
V
MIU
Up to 416 NEs
: RPM
: CPM
: SCPM
RS-485
9.6kbps
ASYNC
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
37/68
ROI-S04188
PNMS Engineering manual- 33 -
9.6.3 Solution 3
This solution is applied to support plural MIUs at PNMS site. Plural MIUs requires pluralserial ports of Router. This solution reduces the number of the router port.
A multiplexing function is introduced between MIU and Router at PNMS site to reduce the
number of router serial ports as shown Figure 9.10. Multiplexing function is router, which hasplural serial interface.
R
Figure 9.10 Network Architecture
PASOLINK CLUSTER
PNMS
H
Y
B
C
O
N
V
MUX
Function
PASOLINK CLUSTER
H
Y
B
C
O
N
V
PASOLINK CLUSTER
H
Y
B
C
O
N
V
MIU
MIU
MIU
RS-232C
19.2/9.6kbps
ASYNC
: Existing Network (Dedicated line)
Up to 416 NEs
Up to 416 NEs
Up to 416 NEs: RPM
: CPM
: SCPM
RS232C port
(In case of other than RS232C port,additional converter is required
in accordance with the physical interface
RS-232C or RS485 port
9.6kbps
ASYNC
RS-232C or RS485 port
9.6kbps
ASYNC
RS-485
9.6kbpsASYNC
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
38/68
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
39/68
ROI-S04188
PNMS Engineering manual- 35 -
For example, assuming that PNMS-1 is in operation and PNMS-2 is down:
a) Logging data
If alarms occur in PASOLINK network, the alarm log is registered in PNMS-1. However theselogs are not registered in PNMS-2. After PNMS-2 is re-started, the logging data is not
synchronized between PNMS-1 and PNMS-2. In this case Operator is required to downloadthe logging data from PNMS-1and to upload it to PNMS-2 desired directory and re-startPNMS-2, if Operator want to synchronize the logging data of both PNMS.
b) Performance monitor data
PNMS collects performance data stored in all PM Cards in the network once a day.(Collecting time can be set by Operator.) If PNMS-1 collects performance data of all NEs inthe network, PNMS-1 stores performance data of the day. However PNMS-2 does not storethe performance data. Therefore, after PNMS-2 is re-started, the performance data is notsynchronized between PNMS-1 and PNMS-2. In this case Operator is required to downloadthe performance data from PNMS-1 and upload it to PNMS-2 desired directory and re-start
PNMS-2, if Operator want to synchronize the performance data of both PNMSs.
c) Network configuration data
In addition, the network configuration data can be created from either Network Configurationtool (PNMS) and is not automatically transferred to another PNMS regardless whether PNMSis in operation or down. Therefore, in order to synchronize such data between PNMSs,whenever such data is created or changed from one PNMS, Operator shall remake such datain another PNMS to be identical to those in one PNMS accordingly.
PNMS-1 PNMS-2
R
Figure 10.1Parallel PNMS
LAN
Alarm or Event trap Alarm or Event trap
R : Router
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
40/68
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
41/68
ROI-S04188
PNMS Engineering manual- 37 -
3. Create configuration file on PNMS for each PM Card and PNMS by NetworkConfiguration tool.
4. Export configuration file of each PM Card and PNMS to the directory set up in theNetwork Configuration tool.
5. Copy the configuration files of each PM Card from PNMS PC to PNMT and
download them to each PM Card on site using PNMT.
6. Import configuration file for PNMS using Update Network Configuration windowfunction on PNMS.
Figure11.3 Network Example
: RPM
: CPM
: Radio Connection
: Cable Connection
PNMS Site
7. Connect PNMS to CPM and confirm the connection. After that it is possible tomonitor and control each NE.
Figure11.4@Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
: Radio Connection
: Cable Connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
42/68
ROI-S04188
PNMS Engineering manual- 38 -
11.1.2 Modify Network Configuration
11.1.2.1 Example 1 : Add New HOP in Subnet-4
1. Plan to add new HOP in Subnet-4.
Figure 11.5 Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Hop
: Radio Connection
: Cable Connection
2. Decide the new PM Card mode(CPM, SCPM or RPM) (for example Figure 11.7).
3. Create configuration file for new PM card and PNMS by Network Configuration tool.
4. Export configuration file of each PM Card and PNMS to the directory set up in NetworkConfiguration tool.
5. Copy the configuration files of new PM Card from PNMS PC to PNMT and downloadthem to new PM Card by PNMT and install new NE(ODU and IDU) on site.
6. Download the modified configuration files to the existing PM Cards, Master PM Cards(SCPM of new NEs subnetwork and CPM which such SCPM is belonging) and a PMCard which is connecting new HOP physically) from PNMS. Refer to Figure 11.6.(Downloading from PNMT is also available. In this case copy the configuration files foreach NE from PNMS PC to PNMT is required.)
- Master PM Card (Sub-CPM in Subnet-4): Modify Network Configuration file to
recognize the added new HOP. (System Configuration file is not necessary to bemodified.)
- Existing PM card connecting with new HOP physically : Modify SystemConfiguration file to recognize connecting with new HOP. (Although NetworkConfiguration file is also necessary to be modified, the network configuration file isautomatically modified and downloaded from Master PM CARD (CPM or SCPM) tothe RPM under it.)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
43/68
ROI-S04188
PNMS Engineering manual- 39 -
-Other PM Cards in this CPM cluster: Although Network Configuration file isnecessary to be modified, the network configuration file is automatically modifiedand downloaded from Master PM CARD (CPM or SCPM) to each PM Cards underit. (System Configuration file is not necessary to be modified.)
Figure 11.6@Network Example
R
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Hop
: RPM
: CPM
: SCPM
R : Router
: Radio Connection
: Cable Connection
7. Update Network configuration file for PNMS using Update Network Configurationwindow function PNMS. After that it is possible to monitor and control added NE.
Figure 11.7@Network Example
R
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
: RPM
: CPM
: SCPM
R : Router
: Radio Connection
: Cable Connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
44/68
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
45/68
ROI-S04188
PNMS Engineering manual- 41 -
Figure 11.9Network Example
R
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
NewSubnet
: RPM
: CPM
: SCPM
R : Router
: Radio Connection
: Cable Connection
7. Update Network configuration file for PNMS by Update Network Configuration windowfunction on PNMS. After that it is possible to monitor and control added subnetwork.
Figure 11.10 Network Example
R
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
Subnet-6
: RPM
: CPM
: SCPM
R : Router
: Radio Connection
: Cable Connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
46/68
ROI-S04188
PNMS Engineering manual- 42 -
11.1.2.3 Example 3 : Modify Sub-Network Configuration
1. It is planed to be divided Subnet-2 into two subnetworks to consider future expansion.
Figure11.11@Network Example
R
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Subnet
: RPM
: CPM
: SCPM
R : Router
: Radio Connection
: Cable Connection
2. Decide each PM Card mode according to new network configuration as shownFigure11.13.
3. Create configuration file for PM Cards in modified subnetwork and for PNMS by
Network Configuration tool.4. Export configuration file for each PM Card and for PNMS to the director set up in the
Network Configuration tool.
5. Download modified configuration file to associated all NEs in new subnetwork and theMaster NE (CPM which new subnetwork is belonging and all SCPMs in the CPMcluster.) from PNMS. Refer to Figure 11.12. (Downloading from PNMT is also available.In this case copy the configuration files for each NE from PNMS PC to PNMT isrequired.)
- Master PM CARD (CPM) and all SCPM in the CPM cluster : Modify NetworkConfiguration file to be recognized to modification of sub-network configuration
- All NEs in new subnetwork : Modify network configuration file and system
configuration file
- Other PM Card in this CPM Cluster: Although Network Configuration file isnecessary to be modified, the network configuration file is automatically modifiedand downloaded from Master PM CARD (CPM or SCPM) to the PM Card under it.(System Configuration file is not necessary to be modified.)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
47/68
ROI-S04188
PNMS Engineering manual- 43 -
Figure11.12@Network Example
R
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Subnet
: RPM
: CPM
: SCPM
R : Router
: Radio Connection
: Cable Connection
6. Update Network configuration file for PNMS by Update Network Configuration windowfunction on PNMS. After that it is possible to monitor and control modified sub network.
Figure11.13@Network Example
R
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Subnet
: RPM
: CPM
: SCPM
R : Router
: Radio Connection
: Cable Connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
48/68
ROI-S04188
PNMS Engineering manual- 44 -
11.2 PNMS for UNIX
11.2.1 Install PNMS
1. Install PASOLINK hardware.
I f the PASOLINK system exists w ith conf igu rat ion f i le, skip Step 2 throug h Step 6.
Figure11.14 Network Example
: RPM
: CPM
: Radio Connection
: Cable Connection
PNMS Site
: PC for Network configuration tool
2. Decide each PM Card mode (for example Figure 11.15).
Figure11.15 Network Example
: RPM
: CPM
: Radio Connection
: Cable Connection
: SCPM
PNMS Site
: PC for Network configuration tool
3. Create configuration file for each PM Card and for PNMS by Network Configuration
tool on PC.
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
49/68
ROI-S04188
PNMS Engineering manual- 45 -
4. Export configuration file of each PM Card and for PNMS to the directory set up in theNetwork Configuration tool.
5. Copy the configuration files of each PM Card form PC (Network Configuration tool) toPNMT and download them to each PM Card on site using PNMT.
6. Upload the configuration file from PC (Network Configuration tool) to PNMS Work
Station by FTP and import it into PNMS.
Figure11.16 Network Example
: RPM
: CPM
: Radio Connection
: Cable Connection
UploadMap file
: PC for Network configuration tool
7. Connect PNMS to CPM and confirm the connection. After that it is possible to monitor
and control each NE.
Figure11.17@Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
: PC for Network configuration tool
: Radio Connection
: Cable Connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
50/68
ROI-S04188
PNMS Engineering manual- 46 -
11.2.2 Modify Network Configuration
11.2.2.1 Example 1 : Add New HOP in Subnet-4
1. Plan to add new HOP in Subnet-4.
Figure 11.18 Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Hop
: PC for Network configuration tool
2. Decide the new PM Card mode (CPM, SCPM or RPM) (for example Figure 11.20).
3. Create configuration file for new PM card and PNMS by Network Configuration tool.
4. Export configuration file of each PM Card and PNMS to the directory set up in theNetwork Configuration tool.
5. Upload the configuration file of each PM Card and PNMS from PC (Networkconfiguration tool) to PNMS Work Station by FTP and import it into PNMS.
6. Copy the configuration files of new PM Card from PC (Network Configuration tool) toPNMT and download them to new PM Card by PNMT and install new NE (ODU andIDU) on site.
7. Download the modified configuration files to the existing PM Cards, Master PM Cards(SCPM of new NEs subnetwork and CPM which such SCPM is belonging.) and a PMCard which is connecting new HOP physically from PNMS. Refer to Figure 11.19.
(Downloading from PNMT is also available. In this case copy the configuration files foreach NE from PNMS PC to PNMT is required.)
- Master PM Card (Sub-CPM in Subnet-4): Modify Network Configuration file torecognize the added new HOP (System Configuration file is not necessary to bemodified.
- Existing PM card connecting with new HOP physically : Modify SystemConfiguration file to recognize connecting with new HOP (Although NetworkConfiguration file is also necessary to be modified, the network configuration file isautomatically modified and downloaded from Master PM CARD (CPM or SCPM) tothe RPM under it.)
- Other PM Cards in this CPM cluster: Although Network Configuration file isnecessary to be modified, the network configuration file is automatically modified
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
51/68
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
52/68
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
53/68
ROI-S04188
PNMS Engineering manual- 49 -
Figure 11.22 Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
NewSubnet
: PC for Network configuration tool
8. After that it is possible to monitor and control added subnetwork.
Figure 11.23 Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
Subnet-6
: PC for Network configuration tool
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
54/68
ROI-S04188
PNMS Engineering manual- 50 -
11.2.2.3 Example 3 : Modify Sub-Network Configuration
1. It is planed to be divided Subnet-2 into two subnetworks to consider future expansion.
Figure11.24@Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Subnet
: PC for Network configuration tool
2. Decide each PM Card mode according to new network configuration as shownFigure11.26.
3. Create configuration file for PM Cards in modified subnetwork and for PNMS byNetwork Configuration tool.
4. Export configuration file for each PM Card and PNMS to the directory set up in theNetwork Configuration tool.
5. Upload the configuration file for each PM Card and PNMS from PC(NetworkConfiguration tool) to PNMS Work Station by FTP and import it into PNMS.
6. Download modified configuration file to associated all NEs in new subnetwork and theMaster NE (CPM which new subnetwork is belonging and all SCPMs in the CPMcluster) from PNMS. Refer to Figure 11.25. (Downloading from PNMT is also available.In this case copy the configuration files for each NE from PNMS PC to PNMT isrequired.)
- Master PM CARD (CPM) and all SCPM in the CPM cluster : Modify NetworkConfiguration file to be recognized to modification of sub-network configuration
- All NEs in new subnetwork : Modify network configuration file and systemconfiguration file
- Other PM Card in this CPM Cluster: Although Network Configuration file isnecessary to be modified, the network configuration file is automatically modifiedand downloaded from Master PM CARD(CPM or SCPM) to the PM Card under it.(System Configuration file is not necessary to be modified.)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
55/68
ROI-S04188
PNMS Engineering manual- 51 -
Figure11.25@Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Subnet
: PC for Network configuration tool
7. After that it is possible to monitor and control modified sub network.
Figure11.26@Network Example
: RPM
: CPM
: SCPM
R
R : Router
Subnet-1
Subnet-2
Subnet-3
Subnet-4
Subnet-5
New Subnet
: PC for Network configuration tool
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
56/68
ROI-S04188
PNMS Engineering manual- 52 -
12. RELATED EQUIPMENT FOR PNMS
12.1 HYB Converter
The Hybrid converter is designed to convert serial interface, RS232C, RS422 and RS485 andto combine/divide communication signal simultaneously all in one unit. It is used for
transmitting SV signal of PNMS through third party equipment.
It is especially useful for PASOLINK multi-cluster network monitored and controlled by PNMSthrough third party equipment to convert interface and to combine or divide supervisorysignal.
Followings are the features of HYB Converter:
Easy setting Interface, function and transmission speed.-> Selection of interface (RS232C/RS422/RS485), function (interface conversion or
Combine/Divide) and transmission speed (9.6kbps/19.2kbps) is executed by front switch
Interface Conversion function-> For each port, three physical interfaces may be selected: RS232C, RS422 and RS485.Following conversions are available.(1) RS232C form/to RS422(2) RS232C from/to RS485(3) RS422 from/to RS485
Combine/Divide function
-> Provide 7 communicationports, up to 1:6 (Maximum) combine/divide function isavailable
Flexible function Setting-> In accordance with network configuration, flexible function setting is available at port level.
(1) Interface conversion function only(2) Combine/Divide function only(3) Both Conversion and Combine/Divide function
Figure 12.1 shows a example of using HYB converter in PNMS network.
Central Site
PNMS
Remote Cluster-A
3 41 2
Remote Cluster-B
7 8
Remote Cluster-E
5 6
Remote Cluster-C
MM
M
MM
M
M M
M : MODEM / Other Microwave Radio Equipment
2 : PASOLINK
M M : Dedicated leased line / Digital Service Channel
RS232C
19.2/9.6kbps,
Async
RS232C,9.6kbps,
Async
Provide 1:4 Divide/Combine function
: Hybrid Converter
5 6
Remote Cluster-D
M
M
RS232C,9.6kbps,
Async
Figure 12.1 Network example using HYB CONV
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
57/68
ROI-S04188
PNMS Engineering manual- 53 -
12.2. Management Interface Unit (MIU)
12.2.1 Main Feature
MIU provides CPM function and together with HYB Converter it works to concentrateSupervisory signal from each PASOLINK (PM Card), which is scattered in differentplaces as shown Figure 12.2. The detail is also described in section 9.6.
EEEE
EEEE
RS-232 or RS485
9.6kbps
ASYNC
RS-232C
19.2kbps
ASYNC
PASOLINK CLUSTER
PASOLINK CLUSTER
R
PNMS(UNIX or
Windows NT)
Existing Network (Dedicated line)
9.6 kbps, ASYNC
RS232 port
(In case of other than RS232C or RS485 port,
additional converter is required
in accordance with the physical interface
Figure 12.2 Multi cluster network through Digital Service Channel
H
Y
B
C
O
N
V
MIU
RS-4859.6kbps
ASYNC
12.2.2 Interface:
(1) For PNMS: PNMS port
Physical interface : RS232C (V.24) or RS422 (V.11) or LAN(10Base-T)
Connector : DB 15pin
Communication rate : 19.2 kbps (PPP, Asynchronous)
(2) for PNMT : PNMT port
Physical interface : RS232C (V.24)
Connector : DB 15pin
Communication rate : 19.2 kbps (PPP, Asynchronous)
(3) For Back to Back : EXP port
Physical interface : RS485 (V.11)
Connector : RJ 45
Communication rate : 9.6 kbps (Asynchronous)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
58/68
ROI-S04188
PNMS Engineering manual- 54 -
12.3 PNMS CABLE
Following table shows cables for PNMS connection. In accordance with customers networkconfiguration, the selection of suitable cable is required.
Cable Name How to use Pin AssignmentLCT Figure 12.4 Figure 12.5
PNMT Figure 12.6 Figure 12.7
PNMT+LCT Figure 12.8 Figure 12.9
PNMS Figure 12.10,12.11 Figure 12.12
Back to Back (Point to point)
-RS232C Figure 12.13 Figure 12.14
-RS485 Figure 12.13 Figure 12.15
Back to Back (Point to multi-point)
(1) Cascade connection Cable Figure 12.16 Figure 12.17(2) Cascade connection Cable Figure 12.16 Figure 12.18
(3) Terminal connector Figure 12.16 Figure 12.19
PNMS+Back to Back (Point to multi-point)
(1) Cascade connection Cable Figure 12.20 Figure 12.21
(2) Cascade connection Cable Figure 12.20 Figure 12.22
(3) Terminal connector Figure 12.20 Figure 12.23
HYB CONV-PASOLINK (point to point)
-RS232C Figure 12.24 Figure 12.25
-RS422 Figure 12.24 Figure 12.26HYB CONV-PASOLINK (point to multi-point)
(1) Cascade connection Cable Figure 12.27 Figure 12.28
(2) Cascade connection Cable Figure 12.27 Figure 12.29
Table 13.1 Cable List
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
59/68
ROI-S04188
PNMS Engineering manual- 55 -
12.3.1 LCT Cable
PASOLINK
Figure 12.4 LA port - LCT(PC) connection
LA PortNMS Port
Station A Station B
LCT
PASOLINK
Figure12.5 Pin assignment for LA port - LCT(PC) connection
15pin(M)
1
23
45
6
7
89
10
11
1213
14
15
1
23
45
6
7
89
Paso
LAConnector
CD
RDTD
DTRGND
DSR
RTS
CTSRI
PC(LCT)
LCT-TXD
GNDLCT-RXD
LCT-RTSLCT-CTS
GND
PNMT-CTS
PNMT-RTSPNMT-RXD
GND
PNMT-TXD
RS-232C1
23
45
6
7
89
10
11
1213
14
15
1
23
45
6
7
89
9 pin(F)
PC(LCT)
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
60/68
ROI-S04188
PNMS Engineering manual- 56 -
12.3.2 PNMT Cable
PASOLINK
Figure 12.6 LA port - PNMT(PC) connection
LA PortNMS Port
Station A Station B
PNMT
PASOLINK
15pin(M) 9 pin(F)
PC(PNMT)Paso
LA
Connector
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
LCT-TXD
GND
LCT-RXD
LCT-RTS
LCT-CTS
GND
PNMT-CTS
PNMT-RTS
PNMT-RXD
GND
PNMT-TXD
RS-232C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
CD
RD
TD
DTR
GND
DSR
RTS
CTS
RI
PC(PNMT)
1
2
3
4
5
6
7
8
9
Figure 12.7 Pin assignment for LA port PNMT (PC) connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
61/68
ROI-S04188
PNMS Engineering manual- 57 -
12.3.3 PNMT + LCT Cable
PASOLINK
Figure 12.8 LA port - PNMT/LCT(PC) connection
LA PortNMS Port
Station A Station B
PNMT LCTor
PASOLINK
15pin(M) 9 pin(F)
1
2
3
4
5
6
7
89
10
11
12
13
14
15
1
2
3
4
5
6
7
89
PC(PNMT)Paso
LA
Connector
CD
RD
TD
DTR
GND
DSR
RTS
CTSRI
PC(LCT)
LCT-TXD
GND
LCT-RXD
LCT-RTS
LCT-CTS
GND
PNMT-CTS
PNMT-RTS
PNMT-RXD
GND
PNMT-TXD
RS-232C
1
2
3
4
5
6
7
89
10
11
12
13
14
15
1
2
3
4
5
6
7
89
1
2
3
4
5
6
7
8
9
CD
RD
TD
DTR
GND
DSR
RTS
CTS
RI
PC(PNMT)
1
2
3
4
5
6
7
8
9
9 pin(F)
PC(LCT)
Figure 12.9 Pin assignment for LA port PNMT/LCT (PC) connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
62/68
ROI-S04188
PNMS Engineering manual- 58 -
12.3.4 PNMS Cable
PASOLINK PASOLINK
Figure 12.10 NMS port PNMS connection
LA PortNMS Port
[RS232C]
Station A Station B
PNMS (Windows NT only)
CPM RPM
Figure 12.11 NMS port - Router connection
LA PortNMS Port
[RS232C]
Station A Station B
PNMS
In case of connection to Router, physical interface
shall be adjusted by suitable adaptor(s)
RouterLAN
15pin(M)
1
234
5
67
8
91011
12
1314
15
1
23
45
67
8
9
PC(PNMS)Paso NMSConnector
CD
RDTD
DTRGND
DSRRTS
CTS
RI
PC (PNMS)
orRouter
DEBUG-TXD
EMS-TXDEMS-RXD
EMS-RTS
EMS-CTS-GND
DEBUG-RXDNMS-TXDNMS-RXD
NMS-RTSNMS-CTS
RS-232C
1
234
5
67
8
91011
12
1314
15
1
23
45
67
8
9
9 pin(F)
Figure12.12 Pin assignment for NMS port PNMS/Router connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
63/68
ROI-S04188
PNMS Engineering manual- 59 -
12.3.5 Back to Back Cable (Point to Point)
CPM
RPM
RPM
Figure 12.13 Back-to-Back (point to point) connection
NMS Port NMS Port
RPM
15pin(M) 15pin(M)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
DEBUG-TXD
EMS-TXD
EMS-RXD
EMS-RTS
EMS-CTS-
GND
DEBUG-RXD
NMS-TXD
NMS-RXD
NMS-RTS
NMS-CTS
RS-232C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
DEBUG-TXD
EMS-TXD
EMS-RXD
EMS-RTS
EMS-CTS-
GND
DEBUG-RXD
NMS-TXD
NMS-RXD
NMS-RTS
NMS-CTS
RS-232C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Figure12.14 Pin assignment for back to back
(point to point, RS232C) connection
15pin(M) 15p in(M)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
EMS-TXD+
EMS-TXD-
EMS-TXDR
EMS-RXD+
EMS-RXD-
GND
NMS-TXD+
NMS-TXD-
NMS-TXDR
NMS-RXD+
NMS-RXD-
RS-485
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
EMS-TXD+
EMS-TXD-
EMS-TXDR
EMS-RXD+
EMS-RXD-
GND
NMS-TXD+
NMS-TXD-
NMS-TXDR
NMS-RXD+
NMS-RXD-
RS-485
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Figure12.15 Pin assignment for back to back
(point to point, RS485) connection
8/10/2019 PNMS Engineering ROI-S04188-052E (Ver.4).pdf
64/68
ROI-S04188
PNMS Engineering manual- 60 -
12.3.6 Back to Back Cable (Point to Multi-point)
CPM
RPM
RPM
Figure 12.16 Back to Back Cable (point to Multi-point) connection
NMS Port
[RS485]
NMS Port
[RS485]
SCPM
F M
F M
SCPM
RPM
NMS Port
[RS485]
F M
(3)Put on the Termination M at the end of connections
(1) (2) (2)
15pin(M)
15pin(F)
1
2
3
4
5
6
78
9
10
11
12
13
14
15
1
2
3
4
5
6
78
9
10
11
12
13
14
15
EMS-TXD+
EMS-TXD-
EMS-TXDR
EMS-RXD+
EMS-RXD-
GND
NMS-TXD+
NMS-T