58
Model 3095MV Multivariable Pressure Transmitters EN ¢00810-0100-4716y¤ 00810-0100-4716 Rev. BA 7/01

Model 3095MV Multivariable Pressure Transmitters ZYcj ... · 1-2 EN Rosemount Inc MODELS COVERED This manual provides basic installation, commissioning, and troubleshooting information

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Model 3095MV™ Multivariable™ Pressure Transmitters EN

¢00810-0100-4716y¤00810-0100-4716

Rev. BA7/01

Product Discontinued

a

EN

Section 1: IntroductionOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Models Covered. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

Section 2 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Section 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Section 4 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Section 5 Reference Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Typical Setup Overview for the Model 3095 MV Transmitter. . 1-4

Section 2: CommissioningOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

Warnings () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Before We Get Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Setting the Loop to Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2Typical Setup for the Model 3095 MV Transmitter . . . . . . . . . . 2-2

Section 3: InstallationOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1

Warnings () . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6

Mounting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6Housing Rotation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8

Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10

Failure Mode Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12Failure Mode Alarm vs. Saturation Output Values . . . . . . . 3-12

Section 4: TroubleshootingOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1

1

ENRosemount Inc

Section 5: Reference DataOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Transmitter Range and Sensor Limits . . . . . . . . . . . . . . . . . . . . 5-1Bolt Identification and Installation . . . . . . . . . . . . . . . . . . . . . . . 5-4Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5

MV Engineering Assistant (EA) Reference Section 1Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Connecting to a Personal Computer . . . . . . . . . . . . . . . . . . . . . . A-1

Launching MV Engineering Assistant . . . . . . . . . . . . . . . . . . A-3Toolbar for MV Engineering Assistant. . . . . . . . . . . . . . . . . . A-6Menu Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6Installing the HART Modem. . . . . . . . . . . . . . . . . . . . . . . . . . A-7Import old .mfl file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8

HART Communicator 1Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

2

Model 3095MV MultivariablePressue Transmitters

.

.

.

.

.

Rosemount and its logotype are registered trademarks of Rosemount Inc.Coplanar, Multivariable (MV), and Tri-Loop are trademarks of Rosemount Inc. PlantWeb is a registered trademark of the Fisher-Rosemount companies.HART is a registered trademark of the HART Communications Foundation.Hastelloy and Hastelloy C are registered trademarks of Haynes International.Microsoft and Windows are registered trademarks of Microsoft, Inc.Annubar is a registered trademark of Dieterich Standard Inc.V–Cone is a registered trademark of McCrometer, Inc.Photo Cover: 3095b29b.

NOTICE

Read the complete product manual before installing, operating, or servicing the Model 3095MV. Failure to comply with safe transmitter installation and operating practices can cause severe injury or death.

The information contained in this abbreviated field manual is intended only as an aid for skilled users who possess complete product manuals and are already familiar with the installation and operation of the Model 3095MV.

Please contact your nearest Fisher-Rosemount location for additional information or assistance regarding safe installation and operation of the Model 3095MV.

FIELD ENMANUAL

Rosemount Inc.8200 Market BoulevardChanhassen, MN 55317 USATel 1-800-999-9307Fax (952) 949-7001© 2001 Rosemount, Inc.

Fisher-Rosemount satisfies all obligations coming from legislation to harmonize product requirements in the European Union.

Product documentation available at...www.rosemount.com

SECTION EN

1 Introduction

Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-3Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-4Typical Setup Overview for the Model 3095 MV Transmitter . . . . . . page 1-4

OVERVIEWThis section outlines the models covered and the organization of this manual.

The following performance limitations may inhibit efficient or safe operation. Critical applications should have appropriate diagnostic and backup systems in place.

Pressure transmitters contain an internal fill fluid. It is used to transmit the process pressure through the isolating diaphragms to the pressure sensing element. In rare cases, oil leak paths in oil-filled pressure transmitters can be created. Possible causes include: physical damage to the isolator diaphragms, process fluid freezing, isolator corrosion due to an incompatible process fluid, etc.

A transmitter with an oil fill fluid leak can continue to perform normally for a period of time. Sustained oil loss will eventually cause one or more of the operating parameters to exceed published specifications while a small drift in operating point output continues. Symptoms of advanced oil loss and other unrelated problems include:

• Sustained drift rate in true zero and span or operating point output or both

• Sluggish response to increasing or decreasing pressure or both

• Limited output rate or very nonlinear output or both

• Change in output process noise

• Noticeable drift in operating point output

• Abrupt increase in drift rate of true zero or span or both

• Unstable output

• Output saturated high or low

1-1

ENRosemount Inc

MODELS COVEREDThis manual provides basic installation, commissioning, and troubleshooting information for the Rosemount® Model 3095 MV Mass Flow Pressure Transmitter.

USING THIS MANUALThis field manual is designed to assist in basic installation and operation of Model 3095 Family of Multivariable Transmitters. For more detailed information, refer to the Model 3095 product manual (document number 00809-0100-4716).

Section 2 CommissioningSteps of common commissioning tasks and compensated flow setup

Section 3 InstallationA flowchart and steps outlining installation procedures, as well as mechanical and electrical considerations

Section 4 TroubleshootingBasic troubleshooting techniques for common diagnostic messages associated with the transmitter, the Engineering Assistant (EA), and the communicator

Section 5 Reference DataRange and sensor limits, EA tables, a typical model structure, and bolt torque specifications for Model 3095 transmitters

AppendicesEA software information and installation diagrams, screens, menu trees, and fast key sequences for the HART Communicator

1-2

ENRosemount Inc

309

5-3

095A

08

B, 3

051

-30

31B

05A

FEATURESThe latest line of Rosemount Model 3095 MV Multivariable pressure transmitters and LCD meters feature physical and software enhancements for additional functionality and increased ease of use.

HousingTerminal Block

O-ring

Cover

Housing Locking Screw

RTD Connector

Process Adapter O-ring

Electronics Board

Nameplate

Module O-ring

Sensor Module

Drain/Vent Valve

Flange Adapter O-ring

OptionalFlange Adapters

Bolts

Coplanar Flange

CertificationLabel

1-3

ENRosemount Inc

TYPICAL INSTALLATIONFigure 1-1 illustrates a typical Model 3095 MV flow installation. Major components of the Model 3095 MV system and the Model 3095 MV Multivariable transmitter are identified below.

Figure 1-1. Typical Model 3095 MV Flow Installation

TYPICAL SETUP OVERVIEW FOR THE MODEL 3095 MV TRANSMITTERThe Model 3095 MV Mass Flow Transmitter is configured with the MV Engineering Assistant and the Model 275 HART Communicator, or AMS. The following steps are described in detail in “Commissioning” on page 2-1 and“Installation” on page 3-1.

Step 1: Setup Compensated Flow for Model 3095 MV Mass Flow Transmitter

Step 2: Send Configuration to Model 3095 MV Mass Flow Transmitter

Step 3: Test Calculation

Step 4: Configuration: Range, Assign, and Map Process Variables

Step 5: Field Installation

Step 6: Perform Field Calibration

Model 3095 MV Mass Flow

RTD Cable

RTD Assembly

Process Connections

RTD Connector

3095

/DA

TA

E2

2A

1-4

SECTION EN

2 Commissioning

Before We Get Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2Setting the Loop to Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2Typical Setup for the Model 3095 MV Transmitter . . . . . . . . . . . . . . page 2-2

OVERVIEWThis section summarizes the Model 3095 MV transmitter commissioning procedure in steps 1-4.

SAFETY MESSAGESProcedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

Warnings ( )

Explosions can result in death or serious injury.

• Do not remove the transmitter covers in explosive environments when thecircuit is live.

• Both transmitter covers must be fully engaged to meetexplosion-proof requirements.

• Before connecting a communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.

Electrical shock can result in death or serious injury.

• Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.

2-1

ENRosemount Inc

BEFORE WE GET STARTEDDepending on the system ordered, the Model 3095 MV is shipped in as many as three containers:

Model 3095 MV

This box contains the Model 3095 MV transmitter. If ordered, this package also contains an RTD cable and optional mounting hardware.

MV Engineering Assistant Software Package (Accessory)

The complete MV Engineering Assistant (EA) software package includes installation software, one HART modem, and cables. The EA software is used to fully configure the Model 3095 MV Mass Flow Transmitter. EA components may be ordered separately.

RTD Assembly (Optional)

This box contains the optional Series 68 or Series 78 RTD Assembly, and the Sensor Wiring Instruction Sheet.

SETTING THE LOOP TO MANUALWhenever you are preparing to send or request data that would disrupt the loop, or change the output of the transmitter, you will have to set your process application loop to manual. The EA, Model 275 HART Communicator, or AMS will prompt you to set the loop to manual when necessary. Acknowledging this prompter does not set the loop to manual. It is only a reminder; you have to set the loop to manual as a separate operation.

TYPICAL SETUP FOR THE MODEL 3095 MV TRANSMITTERThe Model 3095 MV Mass Flow Transmitter can only be fully configured with MV Engineering Assistant or AMS 5.0 with MV Engineering Assistant SNAP ON. A Model 275 HART Communicator, or AMS, can be used for some configuration.

Before proceeding, launch the MV Engineering Assistant Software Appendix A: MV Engineering Assistant (EA) Reference Section

Step 1: Setup Compensated Flow for the Model 3095 MV Mass Flow

After installing the EA software, setup can be completed in the office with the configuration saved. The following EA screen references can be viewed in Appendix A. In “Reference Data” on page 5-1, Table 5-6 shows the liquid and gas database in the EA, and Table 5-7 shows Primary Element Options.

2-2

ENRosemount Inc

NOTEFiles previously created in EA 4.0 will have an .mfl extension. Files created in EA 5.0 or newer will have a .mv extension. Old files can be imported into the current EA software, see “Import old .mfl file” on page A-8.

Natural Gas ConfigurationGross characterization is a simplified method that is acceptable for a narrow range of pressure, temperature, and gas configuration. Detail characterization calculates all pressure, temperature, and gas composition ranges, for which the American Gas Association (A.G.A.) computes compressibility factors. Table 5-8 in Section 5 Reference Data, identifies the acceptable ranges for both of these characterization methods.

Table 2-2. Typical Natural Gas Configuration Screen Sequence

Table 2-1. Typical Configuration Setup Screen Sequences for Liquid, Gas, and Steam

TypeMain Flow Screen(Figure A-20)

Screen 2 (Figure A-21)

Screen 3 (Figure A-22)

Screen 4 (Figure A-23

Screen 5 (Figure A-24

Liquid Choose:1. Database or Custom2. If custom:Enter field name

Choose:1. Primary element2. Sizing information

Operating Standard Condition1. Enter operating conditions

Density/Compressibility & Viscosity

Flow Setup Complete

Gas

Steam Select: Saturated or Super-heated

Main Flow Screen (Figure A-20)

Screen 3 (Figure A-25-A-27)

Screen 2 (Figure A-21)

Screen 4 (Figure A-22)

Screen 5 (Figure A-23)

Screen 6 (Figure A-24)

Choose:1. Natural Gas2. Method desire

Detail Char. Enter Mole% (Must = 100%)

Choose:1. Primary element

2. Sizing information

Operating Standard Condition

1. Enter operating conditions

Density/ Compressibility & Viscosity

Flow Setup Complete

Gross #1 Char. Enter valid ranges: Mole%, density, heating value

Gross #2 Char.Enter valid ranges: Mole% and density

2-3

ENRosemount Inc

Step 2: Send Flow Configuration to Model 3095 MV Mass Flow Transmitter

1. Power up the transmitter. The MV Engineering Assistant allows user to send or save configuration data. Steps for connecting the EA to the transmitter, as well as the EA menu structure, are available in Appendix A: MV Engineering Assistant (EA) Reference Section.

2. Send the Flow Configuration information to the transmitter.a. EA: Select Configure > Configure Flow to send the configuration.b. Step through the Flow Configuration wizard.c. Check Send Flow Configuration to transmitter.

NOTEWhen the information is sent, all previous transmitter information will be overwritten.

Step 3: Test Calculation

The test calculations screen provides a method for viewing the Model 3095 MV mass flow calculations for the current process variables. Optionally, the system administrator can enter process variable values, then view the calculation results.

NOTESince the test calculation procedure actually changes flow and output values during the test, the control loops should be put into manual mode and taken out of flow totalization mode for the duration of the test.

The test calculation results displayed by this screen are calculated in the attached transmitter, not the EA. Also, the calculation update time for this screen is not indicative of the actual transmitter update rate. (The Model 3095 MV sensor update rate is nine times per second.)

1. Display the Test Calculation screen. The initial values indicate current process variable readings.EA: Select Transmitter > Test Calculation

2. Enter values and units for Differential Pressure, Static Pressure, and Process Temperature process variables and units.

NOTEStatic Pressure has to be entered in absolute units, not gauge units.

3. Select the Calculate button. After a short delay, the results box is populated with calculation results.

4. If desired, the Mass Flow Rate, Density, and Viscosity results can be displayed in different units.

5. When finished with your test calculations, select Exit.

2-4

ENRosemount Inc

Step 4: ConfigurationMV Engineering Assistant, AMS, or Model 275 are used to configure the Model 3095 MV Mass Flow Transmitter.

1. Power up the transmitter.2. Communicate with the transmitter. A transmitter icon should appear.

3.Review the configuration data: Transmitter model, Type, Range, Date, Minimum span, Units, 4 and 20 mA points, Output (linear/square root), Damping, Alarm (High/Low), etc. AMS: Select Configuration Properties4.Assign process variables.AMS: Select Assignments > Change PV/SV/TV/QV Assignment

a.Select desired Assign Variables, step though the wizard, then verify output order.

b.Set the range values and units.5.Perform Sensor Trim.AMS: Select Calibrate > Sensor Trim

a.Trim Gauge Pressure (GP) Offset (Zero).b.Trim Gauge Pressure (GP) Slope (Span).c.Trim Differential Pressure (DP) Offset (Zero).d.Trim Differential Pressure (DP) Slope (Span).

6.(Optional) Perform Slope Trim.

NOTEFor Absolute Pressure (AP) Sensor: if open to atmosphere, reading should reflect atmospheric pressure (roughly 12-15 psi (0,8-1,0 bar), NOT zero. A slope (span) trim function may be performed as a maintenance procedure only if necessary.

7.Select RTD Mode.AMS: Select RTD Config> Process Temperature Mode

a.Select Normal PT Mode using RTD or b.Select Fixed PT Mode for 3095 MV Mass Flow (Not

using RTD).c.Backup DT

8.(Optional) Perform RTD Trim.AMS: Select Calibrate > Sensor Trim > Temp Sens Trim

a.Trim Process Temperature (PT) Offset (Zero).b.Trim Process Temperature (PT) Slope (Span).

9.(Optional) Adjust Damping to smooth out noisy process measurement. Select desired variable and value.AMS: Select Configuration Properties > Process Input

HART Keys1, 3, 4

1, 1, 5

1, 2, 2, 1

1, 1, 5

1, 4, 2, 2

1, 2, 2, 1, 4

1, 4, 2, 5

2-5

ENRosemount Inc

2-6

SECTION EN

3 Installation

Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-6Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-9Failure Mode Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-12

OVERVIEWThis section contains safety messages, an installation flowchart (see Figure 3-2 on Page 3-2), and final steps 5 and 6. Also, basic mechanical and electrical considerations guide you through a successful installation. For more detailed information, refer to the Model 3095 MV Multivariable product manual (document number 00809-0100-4716).

SAFETY MESSAGESProcedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

Warnings ( )

Explosions can result in death or serious injury.

• Do not remove the transmitter covers in explosive environments when thecircuit is live.

• Both transmitter covers must be fully engaged to meetexplosion-proof requirements.

• Before connecting a communicator in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.

Electrical shock can result in death or serious injury.

• Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.

3-1

ENRosemount Inc

Figure 3-2. Model 3095 MV Installation Flowchart

B

B

START

A

B

Review Rosemount

drawing 03095-1025/03095-1024

See Rosemount drawings 03095-

1020 or 03095-1021

HazardousLocation?

Non-IncendiveLocation?

Unpack Model 3095 MV

Review the Model 3095 MV

Manual

BenchConfigure?

BENCH CONFIGURE

Connect Bench Power

Supply

Connect Personal

Computer/275

Perform Compensated

Flow Setup

(Optl.) Perform Bench Config/

Calibration Tasks

FIELD INSTALLATION

Review Installation

Considerations

Mount Transmitter

Make Process Connections

DONE

Yes

Yes

No

No

Yes

No

Field CalibrationTasks

Configured?NoPerform

Configuration Tasks

Yes

Checkfor

Leaks

(Optional) Install RTD Assembly

A

3-2

ENRosemount Inc

309

5-C

AB

LEC

ON

Step 5: Field Installation

1. Mount transmitter.a. Mount in desired location; install flange or flange/adapter bolts finger

tight.b. Torque bolts to initial torque vale using a cross pattern (see Table 3-3).

When installing the transmitter to one mounting bracket, torque bolts to 125 in-lb. (169 N-m).

2. Connect transmitter to the process.3. (Optional) Install Series 68 or Series 78 RTD assembly.

a. Mount RTD in desired location.b. Connect RTD cable to Model 3095MV RTD connector. First, fully engage

the black cable connector, then tighten the cable adapter until metal contacts metal (see Figure 3-3).

Figure 3-3. RTD Cable Connection with Armored Shielded Cable

c. (Optional) If using armored, shielded cable, install the cable compression seal, as illustrated in Figure 3-4, and use a pliers to tighten the cap onto the compression fitting.

Figure 3-4. Armored Shielded Cable Compression Seal Connection

Table 3-3. Torque Cross Patterns

Bolt Material Initial Value Final Value

Carbon Steel (CS) 300 in-lb (407 N-m) 650 in-lb (881 N-m)

Stainless Steel (SST) 150 in-lb (203 N-m) 300 in-lb (407 N-m)

First, fully engage the black cable connector.

Second, tighten the cable adapter until metal contacts metal.

Third, tighten the strain relief clamp. 30

95/

067

AB

, 06

8AB

, 069

AB

WasherCap

¾- to ½-in. NPT Adapter

Compression Fitting Bushing

FittingCompression

Cap

Non-conductive Rubber Bushing

Screw to RTDConnection Head

On Transmitter

NOTE: Shielded cable is intended for use in conduit.

Connect to RTD Cable

3-3

ENRosemount Inc

d. Make all necessary wiring connections inside the RTD Flat Connection Head (see Sensor Wiring Instructions included with RTD).

4. Check all process penetrations for leaks.5. Make field wiring connection as shown in Figure 3-10 on Page 3-10,

Connections provide both power and signal wiring.See “Electrical Considerations” on page 3-9.

a. Remove cover on FIELD TERMINALS side of electronics housing.b. Connect positive lead to terminal marked "+SIG" or "+PWR;" remember

to use minimum of 250 ohms in loop.c. Connect negative lead to terminal marked "-".d. Plug and seal unused conduit connections on housing to avoid moisture

accumulation in terminal side.6. Ground transmitter case according to national and local electrical codes.7. (Optional) Install field wiring grounding.8. Replace cover.

Step 6: Perform Field CalibrationTo correct mounting position effect, field zero the Model 3095 MV after installing and filling of impulse lines.

1. Establish communication. 2.Trim DP Offset (Zero).AMS: Select Calibrate > Sensor Trim > DP Sens Trim

3.Trim SP Offset (Zero). (AP, GP)AMS: Select Calibrate > Sensor Trim > GP Sensor Trim

HART Keys1, 2, 2, 1,1

1, 2, 2, 1, 2

3-4

ENRosemount Inc

NOTEFor Absolute Pressure (AP) Sensor: If open to atmosphere, reading should be at atmospheric pressure (roughly 12-15 psi (0,8-1,0 bar), NOT zero.

Use a barometer that is three times as accurate as the model 3095MV AP sensor.

4.(Optional) Connect Tri-Loop. Make all necessary wiring connections, as explained in the Tri-Loop manual (p/n 00809-0100-4754). Remember: the transmitter must be set up for Burst Mode. The Tri-Loop must be in multidrop mode to configure.AMS: Select Configuration Properties > HART > Burst Mode

While in burst mode, select Process vars/Crnt(HART command 3)

5.Perform a Loop Test.AMS: Select Diagnostics and Test > Loop Test6.(Optional) Perform Analog Output Trim. This adjusts analog output to match the plant standard or control loop.AMS: Select Calibrate > D/A Trim

1, 4, 1, 2, 4, 2

1, 4, 1, 2, 4, 1

1, 2, 1, 1

1, 2, 2, 2

3-5

ENRosemount Inc

MECHANICAL CONSIDERATIONS

Mounting Brackets The Model 3095 MV transmitter weighs 6.0 lbs (2,7 kg) without additional options. Optional mounting brackets allow you to mount the transmitter to a panel, a wall, or a 2-inch pipe.

Figure 3-5. Mounting Configurations Using a Mounting Bracket

7.07(180)

309

5-3

095K

04

B, 3

095

K0

4B

, 30

95J0

4BPanel Mount

Pipe Mount

3.5(90)

6.25(159)

6.15(156)

2.8(71)

2.8(71)

4.3(110)

4.7(120)

3-6

ENRosemount Inc

Housing RotationYou can rotate the electronics housing up to 180 degrees (left or right) to improve field access to the two compartments or to better view the optional LCD meter. To rotate the housing, release the housing rotation set screw and turn the housing not more than 180 degrees from the orientation shown in Figure 3-6. Do not rotate the housing more than 180 degrees in either direction. Over-rotation will sever the electrical connection between the sensor module and the electronics module, and will void the warranty.

Figure 3-6. Model 3095 MV Standard Housing Orientation.

30

95M

V0

1.tif

3-7

ENRosemount Inc

309

5-3

095B

03

B, D

03B

, A0

3A.

3051

-303

1B0

3B

Mounting RequirementsRefer to Figure 3-7 for examples of the following mounting configurations:Liquid Flow Measurement

• place taps to the side of the line to prevent sediment deposits on the transmitter’s process isolators

• mount the transmitter beside or below the taps so gases can vent into the process line

• mount drain/vent valve upward to allow gases to ventGas Flow Measurement

• place taps in the top or side of the line• mount the transmitter beside or above the taps so liquid will drain into the

process lineSteam Flow Measurement

• place taps to the side of the line• mount the transmitter below the taps to ensure that the impulse piping will

stay filled with condensate• fill impulse lines with water to prevent the steam from contacting the

transmitter directly and to ensure accurate measurement start-up

NOTE In steam or other elevated temperature services, it is important that temperatures at the coplanar process flanges not exceed 250 °F (121 °C) for transmitters with silicone fill or 185 °F (85 °C) for inert fill. In vacuum service, these temperature limits are reduced to 220 °F (104 °C) for silicone fill and 160 °F (71 °C) for inert fill.

Figure 3-7. Transmitter Installation ExamplesGAS SERVICE

LIQUID SERVICE

STEAM SERVICE

Flow

Flow

Flow

Flow

3-8

ENRosemount Inc

ELECTRICAL CONSIDERATIONS

Power Supply

4–20 mA Transmitters

The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance and signal leads, and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included. Refer to Figure 3-8 for power supply load limitations.

NOTEIf a single power supply is used to power more than one Model 3095 MV Transmitter, the power supply used and the circuitry common to the transmitters should not have more than 20 ohms of impedance at 1200 Hz.

A resistance of at least 250 ohms must exist between the communicator and the power supply for communications.

Figure 3-8. Power Supply Requirements.

2000

1100

35.216.511.0

250

Voltage (V dc)

Lo

ad (

Oh

ms)

OperatingRegion

4–20 mA dc

(1) For CSA approval, power supply must not exceed 42.4 V dc.

HART protocol communication requires a loop resistance value between 250–1100 ohms, inclusive. Loop resistance is determined by the voltage level of the external power supply, as described by:Max. Loop Resistance = Power Supply Voltage–11.0

0.022

HART ProtocolConformance

309

5/0

103

B

3-9

ENRosemount Inc

Wiring To make electrical connections, remove the housing cover on the side marked FIELD TERMINALS. Do not remove the instrument covers in explosive atmospheres when the circuit is alive. All power to the transmitter is supplied over the signal wiring. Connect the lead that originates at the positive side of the power supply to the terminal marked “+” and the lead that originates at the negative side of the power supply to the terminal marked “–” (see Figure 3-9). Avoid contact with the leads and the terminals. Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the test connection.

Plug and seal unused conduit connections on the transmitter housing to avoid moisture accumulation in the terminal side of the housing. If you do not seal the unused connections, mount the transmitter with the electrical housing positioned downward for drainage. Install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.

NOTESignal wiring need not be shielded, but use twisted pairs for best results. In order to ensure proper communication, use 24 AWG or larger wire, and do not exceed 5000 feet (1 500 meters).

Figure 3-9. Model 3095 MV Transmitter Terminal Block with External Ground Assembly

305

1-3

031F

02A

External Ground Assembly

3-10

ENRosemount Inc

Wiring Diagrams

The following diagrams show the wiring connections necessary to power a Model 3095 MV transmitter and enable communications with EA or a hand-held communicator. Do not remove the transmitter covers in explosive environments when the circuit is live.

Figure 3-10. 4–20 mA Transmitter Wiring Diagrams

NOTEThe Model 3095 MV Mass Flow Transmitter can only be fully configured with MV Engineering Assistant (EA). EA 5.0 is not compatible with Windows 2000 or later.

1100 RL� 250 �

User-Provided Power Supply

305

1-3

031

F0

2C3

095

-10

06A

03F

User-Provided Power Supply

Modem

Wiring in the Field

Wiring to a Personal Computer1100 � � RL� 250 �

See “Safety Messages” on page -1 for complete warning information.

3-11

ENRosemount Inc

FAILURE MODE ALARMAs part of normal operation, the Model 3095 MV continuously monitors its own operation. This automatic diagnostic routine is a timed series of checks repeated continuously. If the diagnostic routine detects a failure, the transmitter drives its output either below or above specific values depending on the position of the failure mode jumper.

• For 4–20 mA transmitters factory-configured for standard operation, the transmitter drives its output either below 3.75 mA or above 21.75 mA.

The failure mode alarm jumper is located on the front of the electronics board inside the electronics housing cover. The position of this jumper determines whether the output is driven high or low when a failure is detected (see Figure 3-11). If the alarm jumper is not installed, the transmitter will operate normally and the default alarm condition will be high.

Figure 3-11. Write Protect and Alarm Jumpers on the Electronics Board

Failure Mode Alarm vs. Saturation Output ValuesThe failure mode alarm output levels differ from the output values that occur when applied pressure is outside of the range points. When pressure is outside of range points, analog output continues to track the input pressure until reaching the saturation value listed below. The output does not exceed the listed saturation value regardless of the applied pressure. For example, with standard alarm and saturation levels and pressures outside of the 4–20 range points, the output saturates at 3.9 mA or 20.8 mA. When the transmitter diagnostics detect a failure, the analog output is set to a specific alarm value that differs from the saturation value to allow for proper troubleshooting.

Table 3-4. 4–20 mA Transmitter Alarm Values vs. Saturation Values.

Level

STANDARD

Saturation Alarm

Low 3.9 mA � 3.75 mA

High 20.8 mA � 21.75 mA

3095

-029

2A0

1A

3-12

SECTION EN

4 Troubleshooting

OVERVIEWTable 4-5 provides summarized troubleshooting suggestions for the most common operating problems.

NOTEFor a complete list of diagnostic messages, corrective actions, assembly/disassembly, and repair instructions, refer to the Model 3095 MV Multivariable product manual (document number 00809-0100-4716).

Failure to follow safe operating practices can cause death or serious injury. Please review the following safety messages before troubleshooting the Model 3095 MV Transmitter.

• Using improper procedures or parts can affect product performance and the output signal used to control a process. To ensure safe transmitter performance, use only new parts and follow Rosemount documented procedures. Questions regarding these procedures or parts should be directed to the nearest Fisher-Rosemount location.

• Isolate a failed transmitter from its pressure source as soon as possible. Pressure that may be present could cause death or serious injury to personnel if the transmitter is disassembled or ruptures under pressure.

• To avoid explosions, do not remove the instrument cover or make electrical connections in explosive atmospheres when the circuit is live. Make sure the instrument is installed in accordance with intrinsically safe or nonincendive field wiring practice.

• To meet explosion proof requirements, make sure that both transmitter covers are fully engaged.

• To avoid process leaks, use only the O-ring designed to seal with the corresponding flange adapter. Rosemount Inc. supplies two unique styles of O-rings for Rosemount flange adapters: one for Model 3051 flange adapters and another for Model 1151 flange adapters. Each flange adapter is distinguished by its unique groove. Refer to the Spare Parts List PPL 4001 for the numbers of the flange adapters and O-rings designed for the Model 3051 Pressure Transmitter.

4-1

ENRosemount Inc

Table 4-5. Model 3095 Troubleshooting Chart

Symptom Corrective Actions

Milliamp Reading is Zero • Check if Power Polarity is Reversed• Verify Voltage Across Terminals(should be 11 to 55 V dc,165 Vat 250 � for HART protocol)• Check for Bad Diode in Terminal Block• Replace Transmitter Terminal Block

Transmitter not Communicating with Model 275

HART Communicator

• Check Power Supply Voltage at Transmitter (Minimum 11 V)• Check Load Resistance (250 � minimum)• Check if Unit is Addressed Properly• Replace Electronics Board

Milliamp Reading is Low or High • Check Pressure Variable Reading for Saturation• Check if Output is in Alarm Condition• Perform 4–20 mA Output Trim• Replace Electronics Board

No Response toChanges in Applied Pressure

• Check Test Equipment• Check Impulse Piping for Blockage• Check for Disabled Span Adjustment• Check Transmitter Security Jumper• Verify Calibration Settings (4 and 20 mA Points)• Replace Sensor Module

Pressure Variable Reading is Low or High

• Check Impulse Piping for Blockage• Check Test Equipment• Perform Full Sensor Trim• Replace Sensor Module

Pressure VariableReading is Erratic

• Check Impulse Piping for Blockage• Check Damping• Check for EMF Interference• Replace Sensor Module

No Communication between EA Software and the Model 3095 MV

Loop Wiring• HART protocol communication requires a loop resistance value

between 250–1100 ohms, inclusive.• Check for adequate voltage to the transmitter. (If the computer is

connected and 250 ohms resistance is properly in the loop, a power supply voltage of at least 16.5 V dc is required.)

• Check for intermittent shorts, open circuits, and multiple grounds. • Check for capacitance across the load resistor. Capacitance should be

less than 0.1 microfarad. EA Installation• Verify that the install program modified the CONFIG.SYS file. • Verify computer reboot followed EA installation. • Verify correct COMM port selected. • Verify laptop computer is not in low energy mode (certain laptops

disable all COMM ports in low energy mode). • Check if HART driver is loaded and installed.

Cannot launch EA software • Computer name matches must match the host name. Check the computer name by going to the control panel settings on the PC and access the network file. This file will indicate the computer name. Next, to check the host name, enter the protocol tab. Access the TCP/IP Protocol Properties and click the DNS tab. This should indicate the host name. It should be the same as the computer name.

4-2

SECTION EN

5 Reference Data

Transmitter Range and Sensor Limits . . . . . . . . . . . . . . . . . . . . . . . . page 5-1Bolt Identification and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-4Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-5

OVERVIEWThis section contains the following reference data for the Model 3095 MV family of pressure transmitters:

• Transmitter Range and Sensor Limits• EA tables• Bolt Installation• Ordering Information

TRANSMITTER RANGE AND SENSOR LIMITSModel 3095MV Sensor Limits

(for transmitters with serial numbers less than 40000)Sensor Range LRL– (1)

(1) LRL– is equal to LRV and lower sensor trim limits.

LRL URL URL+(2)

(2) URL+ is equal to URV and upper sensor trim limits.

Flow No limit 0 Op-limits calc(3)

(3) The flow rate when DP=URL+, AP=UOL, and PT=LOL. This value is calculated by the EA.

No limit

DP Range 1 –27.5 inH2O @ 68 °F(–68,5 bar @ 20 °C)

–25 inH2O @ 68 °F(–62,3 bar @ 20 °C)

25 inH2O @ 68 °F(62,3 bar @ 20 °C)

27.5 inH2O @ 68 °F(68,5 bar @ 20 °C)

DP Range 2 –275 inH20 at 68 °F(–685 mbar @ 20 °C)

–250 inH20 at 68 °F(–623 mbar @ 20 °C)

250 inH20 at 68 °F(623 bar @ 20 °C)

275 inH20 at 68 °F(685 bar @ 20 °C)

DP Range 3 –1100 inH20 at 68 °F(–2 740 mbar @ 20 °C)

–1000 inH20 at 68 °F(–2 490 mbar @ 20 °C)

1000 inH20 at 68 °F(2 490 mbar @ 20 °C)

1100 inH20 at 68 °F(2 740 mbar @ 20 °C)

AP Range 3 0 psia(4) (0 bar)

(4) For output board versions below 10, LRL– is 0.45 psia.

0.5 psia (34,5 mbar) 800 psia (55 bar) 880 psia (61 bar)

AP Range 4 0 psia(4) (0 bar) 0.5 psia (34,5 mbar) 3626 psia (250 bar) 3988 psia (275 bar)

GP Range C –0.15 psig (–10 mbar) 0 psig (0 bar) 800 psig (55 bar) 880 psig (61 bar)

GP Range D –0.15 psig (–10 mbar) 0 psig (0 bar) 3626 psig (250 bar) 3988 psig (275 bar)

PT (5)

(5) In the fixed temperature mode, PT range is –459 to 3500 °F (–273 to 1927 °C).

–170 °F (–112 °C) –150 °F (–101 °C) 1500 °F (815 °C) 1550 °F (843 °C)

Sensor Temperature –47 °F (–44 °C) –40 ° F (–40 ° C) 185 °F (85 °C) 200 °F (93.5 °C)

5-1

ENRosemount Inc

Table 5-6. Liquids & Gases in Engineering Assistant AIChE Physical Properties(1)

Table 5-7. Primary Element Options(2)

Acetic AcidAcetoneAcetonitrileAcetyleneAcrylonitrileAir Allyl Alcohol Ammonia Argon BenzeneBenzaldehyde Benzyl Alcohol BiphenylCarbon Dioxide Carbon Monoxide Carbon Tetrachloride ChlorineChlorotrifluoroethylene Chloroprene CycloheptaneCyclohexaneCyclopentaneCyclopentene

CyclopropaneDivinyl Ether EthaneEthanol EthylamineEthylbenzene EthyleneEthylene GlycolEthylene OxideFluoreneFuranHelium–4 Hydrazine HydrogenHydrogen Chloride Hydrogen Cyanide Hydrogen Peroxide Hydrogen Sulfide IsobutaneIsobutene Isobutyl IsopentaneIsoprene

IsopropanolMethane Methanol Methyl AcrylateMethyl Ethyl Ketone Methyl Vinyl Etherm–Chloronitrobenzene m–Dichlorobenzene Neon NeopentaneNitric Acid Nitric Oxide Nitrobenzene NitroethaneNitrogenNitromethane Nitrous Oxide n–Butanen–Butanoln–Butyraldehyden–Butyronitrile n–Decane n–Dodecane n–Heptadecane

n-Heptane n–Hexane n–Octane n–Pentane OxygenPentafluorothanePhenolPropanePropadienePyrene PropyleneStyreneSulfer DioxideToluene Trichloroethylene Vinyl Acetate Vinyl Chloride Vinyl Cyclohexane Water1–Butene 1–Decene1–Decanal1–Decanol 1–Dodecene

1–Dodecanol1–Heptanol 1–Heptene 1–Hexene 1–Hexadecanol 1–Octanol 1–Octene 1–Nonanal1–Nonanol 1–Pentadecanol1–Pentanol 1–Pentene 1–Undecanol 1,2,4–Trichlorobenzene 1,1,2–Trichloroethane 1,1,2,2–Tetrafluoroethane 1,2–Butadiene 1,3–Butadiene 1,3,5–Trichlorobenzene1,4–Dioxane 1,4–Hexadiene 2–Methyl–1–Pentene 2,2–Dimethylbutane

(1) This list is subject to change with out notice.

1195 Integral Orifice 1195 Mass Proplate1195 Mass Proplate, Calibrated Cd1195 Mass Proplate, Cd with BiasAnnubar® Diamond II/Mass ProBar Annubar® Diamond II+/Mass ProBarCalibrated Annubar® Diamond II+/Mass ProBar (2)

Calibrated Annubar® Diamond II/Mass ProBar (2) Nozzle, Long Radius Wall Taps, ASME Nozzle, Long Radius Wall Taps, ISO Nozzle, ISA 1932, ISO Orifice, 2½D & 8D Taps Orifice, Corner Taps, ASME Orifice, Corner Taps, ISOOrifice, D & D/2 Taps, ASMEOrifice, D & D/2 Taps, ISO

Orifice, Flange Taps, AGA3 Orifice, Flange Taps, ASMEOrifice, Flange Taps, ISO Small Bore Orifice, Flange Taps, ASMEVenturi Nozzle, ISO Venturi, Rough Cast/Fabricated Inlet, ASME Venturi, Rough Cast Inlet, ISO Venturi, Machined Inlet, ASME Venturi, Machined Inlet, ISO Venturi, Welded Inlet, ISO

(2) Selecting a primary element from the other list requires additional setup information regarding the primary element. This information should be obtained from the primary element manufacturer or from your own test data. If the calibrated data table is selected, a minimum of two completed rows is required.

Other(2) Primary Element Setup Options

Calibrated Orifice: Flange, Corner or D & D/2 TapsCalibrated Orifice: 2 ½ D & 8D TapsCalibrated NozzleCalibrated Venturi

Constant Cd, Discharge Coefficient or 20 � 2 Calibrated Data Table

Area Averaging Meter Constant K, Flow Coefficient

V–Cone® Constant Cf, Coefficient of Flow

5-2

ENRosemount Inc

Table 5-8. Acceptable Ranges: Gross vs. Detail Characterization Methods

Engineering Assistant VariableGross

MethodDetail

Method

Pressure 0–1200 psia (1)

(1) The Model 3095 MV sensor operating limits may limit the pressure and temperature range.

0–20,000 psia (1)

Temperature 32 to 130 °F (1) –200 to 400 °F (1)

Specific Gravity 0.554–0.87 0.07–1.52

Heating Value 477–1150 BTU/SCF

0–1800BTU/SCF

Mole% Nitrogen 0–50.0 0–100

Mole% Carbon Dioxide 0–30.0 0–100

Mole% Hydrogen Sulfide 0–0.02 0–100

Mole% Water 0–0.05 0–Dew Point

Mole% Helium 0–0.2 0–3.0

Mole% Methane 45.0–100 0–100

Mole% Ethane 0–10.0 0–100

Mole% Propane 0–4.0 0–12

Mole% i-Butane 0–1.0 0–6 (2)

(2) The summation of i-Butane and n-Butane cannot exceed 6 percent.

Mole% n-Butane 0–1.0 0–6 (2)

Mole% i-Pentane 0–0.3 0–4 (3)

(3) The summation of i-Pentane and n-Pentane cannot exceed 4 percent.

Mole% n-Pentane 0–0.3 0–4 (3)

Mole% n-Hexane 0–0.2 0–Dew Point

Mole% n-Heptane 0–0.2 0–Dew Point

Mole% n-Octane 0–0.2 0–Dew Point

Mole% n-Nonane 0–0.2 0–Dew Point

Mole% n-Decane 0–0.2 0–Dew Point

Mole% Oxygen 0 0–21.0

Mole% Carbon Monoxide 0–3.0 0–3.0

Mole% Hydrogen 0–10.0 0–100

Mole% Argon 0 0–1.0

NOTE: Reference conditions are 14.73 psia (1,0 bar) and 60 °F (15,6 °C) for Gross Method.

5-3

ENRosemount Inc

BOLT IDENTIFICATION AND INSTALLATIONBolts supplied by Rosemount Inc. can be identified by their head markings. Refer to Figure 5-12 to verify that you are using the proper types of bolts.

Figure 5-12. Rosemount Bolt Identification Markings

Table 5-9. Bolt Installation Torque Values

Bolt Material Initial Torque Value Final Torque Value

Carbon Steel (CS) 300 in-lb (34 N-m) 650 in-lb (73 N-m)

Stainless Steel (SST) 150 in-lb (17 N-m) 300 in-lb (34 N-m)

Stainless Steel Head Markings (SST)

B7M

316 B8M

Carbon Steel Head Markings (CS)

316STM316

SW316

316R

305

1 -3

031 I

06A

5-4

ENRosemount Inc

ORDERING INFORMATION Model Product Description

3095M Multivariable Transmitter

Code Output

A 4–20 mA with Digital Signal Based on HART Protocol

Code Differential Pressure Range

1(1)

23

0–25 inH2O (0–62,3 mbar)0–250 inH2O (0–622,7 mbar)0–1000 inH2O (0–2490 mbar)

Code Static Pressure Ranges

34CD

0–8 to 0–800 psia (0–0,55 to 0–55 bar)0–36.26 to 0–3626 psia (0–2,5 to 0–250 bar)0–8 to 0–800 psig (0–0,55 to 0–55 bar) 0–36.26 to 0–3626 psig (0–2,5 to 0–250 bar)

Code Isolator MaterialFill Fluid

AB(2)

J(3)

K(2)

316L SSTSilicone Hastelloy C-276 Silicone 316L SSTInert Hastelloy C-276 Inert

Code Flange Style, Material

ABC

F(4)

J0

Coplanar, CSCoplanar, SSTCoplanar, Hastelloy C Coplanar, SST, non-vented Traditional, SSTNone (Required for Option Code S5)

Code Drain/Vent Material

AC(2)

0

SSTHastelloy C None (Required for Option Code S5)

Code O-ring

1 Glass-filled TFE

5-5

ENRosemount Inc

Code Process Temperature Input (RTD ordered separately)

01234

5(5)

78ABC

D(5)

Fixed Process Temperature (No cable) For EMS Code B/Disable For EMS Code ARTD Input with 12 ft (3,66 m) of Shielded Cable (Intended for use with conduit.)RTD Input with 24 ft (7,32 m) of Shielded Cable (Intended for use with conduit.)RTD Input with 12 ft (3,66 m) of Armored, Shielded CableRTD Input with 24 ft (7,32 m) of Armored, Shielded CableRTD Input with 21 in. (53 cm) of Armored, Shielded Cable RTD Input with 75 ft (22,86 m) of Shielded Cable RTD Input with 75 ft (22,86 m) of Armored, Shielded Cable RTD Input with 12 ft (3,66 m) of CENELEC Flame-proof Cable RTD Input with 24 ft (7,32 m) of CENELEC Flame-proof Cable RTD Input with 75 ft (22,86 m) of CENELEC Flame-proof CableRTD Input with 21 in. (53 cm) of CENELEC Flame-proof Cable(Typically ordered with Approval Code H)

Code Transmitter Housing Material Conduit Entry Size

ABCJKL

Polyurethane-covered Aluminum ½–14 NPTPolyurethane-covered Aluminum M20 � 1.5 (CM20) Polyurethane-covered Aluminum PG 13.5SST ½–14 NPTSST M20 � 1.5 (CM20)SST PG 13.5

Code Terminal Block

AB

StandardWith Integral Transient Protection

Code Meter

01

NoneLCD Meter

Code Bracket

01

None Coplanar SST Flange Bracket for 2-in. Pipe or Panel Mount, SST Bolts

Code Bolts

01N

CS BoltsAustenitic 316 SST Bolts None (Required for Option Code S5)

5-6

ENRosemount Inc

Code Approvals

0ABCD

FGH

None Factory Mutual (FM) Explosion-Proof Approval Factory Mutual (FM) Explosion-Proof Approval and Non-Incendive/Intrinsic Safe ComboCanadian Standards Association (CSA) Explosion-Proof Approval Canadian Standards Association (CSA) Explosion-Proof Approval and Non-Incendive/Intrinsic Safety Approval Combination BASEEFA/CENELEC Intrinsic Safety CertificationBASEEFA Type N CertificationISSeP/CENELEC Flame-proof Certification

Code Enhanced Measurement Solution (EMS)

B Mass Flow and Measured Variables (DP, P, and T)

Code Option MV (Available with Code B: Enhanced Measurement Solution)

C2S4(6)

S5 P1P2Q4

Q8(7)

DF(8)

Custom Flow Configuration (Requires Configuration Data Sheet 00806-0100-4716.) Factory Assembly to Rosemount Primary Element Diamond II+ Annubar or Model 1195 Integral Orifice (Requires corresponding model number–see 00813-0100-4760)Assembly with Model 305 Integral Manifold (Requires integral manifold model number)Hydrostatic Testing Cleaning for Special ServicesInspection Certificate for Calibration Data Material Inspection Certificate per EN 10204 3.1B Plated CSFlange Adapters — Type Determined by Selected Flange Material: SST or Hastelloy C

Typical Model Number3095M A 2 3 A A A 1 3 A B 0 1 1 0 B

(1) Available only with 3 or C sensor modules and A 316L SST/silicone, Isolator/Fill Fluid option.

(2) Meets NACE material recommendations per MR 01–75.

(3) Only available with C or D Gage Sensor Modules.

(4) Requires that Drain/Vent Material Code set to 0 (none).

(5) For use with Annubars with integral RTDs.

(6) With a primary element installed, the maximum operating pressure will be the lesser of either the transmitter orthe primary element.

(7) This option is available for the sensor module housing, Coplanar and Coplanar flange adapters.

(8) Not available with assembly to Model 1195 Integral Orifice Option Code S4.

5-7

ENRosemount Inc

5-8

SECTION EN

A MV Engineering Assistant (EA) Reference Section

OVERVIEWThe MV Engineering Assistant Software package is available with or without the HART modem and connecting cables. The complete Engineering Assistant package contains installation software, one HART modem, and a set of cables for connecting the computer to the Model 3095 MV.

GETTING STARTEDMinimum hardware requirements:

• IBM PC compatible Pentium 150 MHz or above• 32 MB of memory if using Windows 95 or 98; 64 MB of memory if using

Windows NT 4.0• 150 M of hard disk space• 1 CD-ROM drive• Color computer display (VGA or better)• 1 RS232 port• Mouse or other pointing device• HART modem

CONNECTING TO A PERSONAL COMPUTER

Figure A-13. Figure A-14 illustrates how to connect a computer to a Model 3095 MV

Explosions can cause death or serious injury. Before making any computer connections, ensure that the Model 3095 MV area is non-hazardous.

A-1

ENRosemount Inc

Install the Program

1. Place the disk in the CD-ROM drive and run the setup fromWindows 95, 98 or NT.

2. After installing the software, open the MV Engineering Assistant from the program file. The Hart modem installation will automatically launch. Be sure to tun off any other programs that might interfere with the use of the selected Com ports.

Upgrade the MV Engineering Assistant program

1. Place the disk in the CD-ROM drive and run the EAupgrade.exe from Windows 95, 98, or NT. To properly install, the program will first uninstall MV Engineering Assistant from your computer.

2. After uninstall is complete, reboot your computer.3. To install the upgraded program, run the EAupgrade.exe from Windows 95,98,

or NT again.

Connect to Transmitter

1. After installing the EA on your computer, connect the computer to the Model 3095 MV. See Warning above, as well as Figure A-14.

a. Connect one end of the 9-pin to 9-pin cable to the HART communications port on the personal computer.

b. Connect the 9-pin HART modem cable to the 9-pin communications port on the computer.

c. Open the cover above the side marked Field Terminals, and connect the mini-grabbers to the two Model 3095 MV terminals marked COMM.

2. Power up the computer. 3. Select the MV Engineering Assistant from the program menu.4. An AMS Application logon window will appear. 5. If password security is enabled, the Engineering Assistant Privileges Screen

appears.6. The default login name is admin (must be lower case). The password line is

left blank. Select OK.

Explosions can cause death or serious injury. Do not remove the instrument cover in explosive atmospheres with the circuit is live.

A-2

ENRosemount Inc

NOTERefer to “Model 3095 Troubleshooting Chart” on page 4-2 for troubleshooting information.

Figure A-14. Connect to transmitter diagram

Launching MV Engineering Assistant

On-LineIn on-line mode, MV Engineering Assistant communicates directly with the Model 3095MV through AMS. The MV Engineering Assistant is launched from a pop-up menu.

309

5-1

006

A0

3F

User-Provided Power Supply

Modem

1100 � � RL� 250 �

A-3

ENRosemount Inc

Figure A-15. On-line Start Up Menu

1. In AMS Explorer view or AMS Connection view, right click on a Model 3095MV device tag or icon.

2. Select MV Engineering Assistant from the pop-up context menu. The MV Engineering Assistant main window is displayed.

Off-LineIn off-line mode, MV Engineering Assistant does not communicate directly with the Model 3095MV. Instead, the EMS configuration is sent to a Model 3095MV later when MV Engineering Assistant is in on-line mode. In the off-line mode a future device needs to be created in order to launch MV Engineering Assistant.

Figure A-16. Off-Line Start UpO

N-L

INE

_S

TA

RT

UP

OF

F-L

INE

_ST

AR

TU

P

A-4

ENRosemount Inc

To launch MV Engineering Assistant off-line:3. In AMS Explorer view or AMS Device Connection view, left click on Plant

Database to the Area fold.4. Left click on Area to the Unit folder.5. Left click on Unit to the Equipment Module folder. 6. Left click on Equipment Module to the Control Module folder.7. Right click on Control Module to the pop-up context menu.8. Select Add Future Device.9. Select 3095MV Template and click OK.

10. Right click on Future device to pop-up context menu.11. Select MV Engineering Assistant from the pop-up context menu. The MV

Engineering Assistant main window is displayed.

See AMS Help for additional information on Future Device of EA on-line help.

Figure A-17. Future Device

FU

TU

RE

_D

EV

ICE

A-5

ENRosemount Inc

Toolbar for MV Engineering AssistantA fast way to access EA screens is the toolbar shown in Figure A-18. Simply click on the icon to access the screen.

Figure A-18. Model 3095 MV Engineering Assistant Toolbar

Menu CategoriesThe menu bar identifies seven menu categories:

File

The File category contains screens for reading and writing Model 3095 MV configuration files.

View

The View selections determine whether the toolbar and the status bar are displayed.

Configure

The configure category contains the Configure flow wizard. These screens also determine the contents of a configuration file, and are used to define a Compensated Flow measurement solution. Options for security and password can be enabled at this time. Also, old flow configurations may be imported and changing unit preferences.

Transmitter

Sending receiving, configuration, test calculation and privileges are contained in the transmitter category.

Help

The Help selection identifies the current EA software revision and theonline help guide.

Open Config Configure Flow

New Config SaveConfig

Options About

30

95-3

095

MV

/TO

OL

BA

R01Send

Receive

Test Calculation

A-6

ENRosemount Inc

Figure A-19. MV Engineering Assistant Menu Structure

Installing the HART ModemAfter installing the MV Engineering Assistant, the HART modem configuration window automatically appears when the AMS|MV Engineering Assistant is opened. If this window is canceled, the HART modem may be installed manually by following the following procedure.

1. Close AMS. From the Start Menu selectSetting > Control Panel > AMS Configuration

2. Select Add from the AMS Network Configuration window. A "Select AMS Network Component Type" window will open.

3. Select Hart Modem.4. Select Install.5. Step through the Wizard. A prompt will inquire a COM PORT. A typical

default is "COM1".6. Select OK. Close out of the AMS Network Configuration window.7. The configuration change will activate when AMS|MV Engineering

Assistant is launched.

Model 3095 MV Engineering Assistant – UntitledFile View Configure Transmitter Help

New Ctrl + NOpen Ctrl + OSave Ctrl + SSave As...1 filename.mfl Exit

Send Configuration...Receive Configuration...Test CalculationPrivileges

MV Engineering Assistant HelpAbout MV Engineering Assistant

ToolbarStatus Bar

Configure Flow...OptionsImportPreferences...

A-7

ENRosemount Inc

NOTEExit from the program if a Palm Pilot HotSync or any other program is shared with the COMPORT.

Import old .mfl fileThe MV Engineering Assistant will have a new extension of .mv. EA 4.0 or older had a .mfl file extension. Old flow configuration can be imported by completing the following steps.

1. Select Import from the MV Engineering Assistant File menu.2. Navigate to the *.mfl file you wish to import.3. Click Open.4. Open the Flow Wizard from the MV Engineering Assistant File menu and

check Data. You must step through the Flow Wizard or you will not import the file. Either send and/or save the new file.

Figure A-20. Main Flow Setup Screen

EA

A-8

ENRosemount Inc

Figure A-21. For liquid, gas, or steam Primary Element selection and sizing

Figure A-22. Operating and Reference Conditions

PR

IMA

RY

_EL

EM

EN

T_S

EL

EC

T%

26S

IZE

OP

ER

AT

ING

_RE

F_C

ON

DIT

ION

S

A-9

ENRosemount Inc

Figure A-23. Density, Compressibility, and Viscosity Table

Figure A-24. Flow Setup Complete Screen

DE

NS

ITY

_VIS

CO

SIT

Y_

TA

BLE

EA

_C

OM

PL

ET

E

A-10

ENRosemount Inc

Figure A-25. Natural Gas Setup Screen (Detail Characterization)

Figure A-26. Natural Gas Setup Screen (Gross Characterization Method 1)

DE

TA

IL_

CH

AR

GR

OS

S_

MT

H1

A-11

ENRosemount Inc

Figure A-27. Natural Gas Setup Screen (Gross Characterization Method 2)

GR

OS

S_M

TH

2

A-12

ENRosemount Inc

A-13

ENRosemount Inc

A-14

SECTION EN

B HART Communicator

OVERVIEWThe HART Communicator provides communication capabilities for the Model 3095 MV transmitter. The HART Communicator menu tree provides a schematic overview of configuration functions, and the fast key sequences provide direct access to software functions.

Online Menu

The Online menu appears automatically if the HART Communicator is connected to an active loop with an operating transmitter. From the Online menu, press the appropriate key sequence to access the desired function. Follow the on-screen instructions to complete the function.

HART Fast Key Feature

The fast key sequences for the HART Communicator use the following convention for their identification:

1 through 9–Refer to the keys located in the alphanumeric keypad located below the dedicated keypad.

NOTEHART fast key sequences are operational only from the Online menu. To access the Online menu from any other menu, select the HOME (F3) key.

B-1

ENRosemount Inc

Figure B-28. HART Communicator Menu Tree for Model 3095 MV Mass Flow

Online Menu

1 DP Sensor Range2 SP Sensor Range3 SP Type4 Isolator Material5 Fill Fluid6 Flange Material7 Flange Type8 Drain Vent Matl9 O-Ring Material10 RS Type11 RS Fill Fluid12 RS Isolator Matl13 No of Rmt Seals

1 VIEW PRIMARY VAR. ANALOG 1

2 VIEW SECOND VAR.

3 VIEW TERTIARY VAR.

4 VIEW FOURTH VAR.

5 OUTPUT VAR UNITS

1 Identify Secondary Var.2 Secondary Value3 Change Sec. Var. Assign.

1 Identify Fourth Variable2 Fourth Value3 Change 4th Var. Assign.

1 Primary Var. Units2 Secondary Var. Units3 Tertiary Var. Units4 Fourth Var. Units

1 PROCESS VARIABLES

2 DIAGNOSTICS AND SERVICE

3 BASIC SETUP

4 DETAILED SETUP

5 Review

1 DEVICE SETUP2 PV3 PV AO4 PV LRV5 PV URV

1 Absolute AP2 AP% RANGE3 A014 VIEW FIELD DEV VARS

5 VIEW OUTPUT VARS

1 TEST/STATUS

2 CALIBRATION

1 ANALOG OUTPUT

2 HART OUTPUT

1 Differential Pressure2 Absolute Pressure3 Process Temperature4 Gage Pressure5 Flow Rate6 Flow Total

1 Identify Tertiary Var.2 Tertiary Value3 Change Tert. Var. Assign.

1 SENSOR TRIM

2 ANALOG TRIM

1 DP Unit2 AP Unit3 Process Temp Unit4 GP Unit5 Flow Unit6 Flow Total Unit

1 DP Sensor Trim2 AP Sensor Trim3 GP Sensor Trim4 Temp Sensor Trim

1 OUTPUT CONDITIONING

2 SIGNAL CONDITIONING

3 LCD

4 TOTALIZER

5 SPECIAL UNITS

6 DP LOW FLOW CUTOFF

1 Tag2 Descriptor3 Message4 Date5 Final Assbly No.6 Manufacturer7 Model8 Write Protect9 REVISIONS

1 D/A Trim2 Scaled D/A Trim3 Factory Trim

1 Universal Rev2 Fld Dev Rev3 Software Rev4 Hardware Rev5 Snsr Mod sw Rev6 Snsr Mod hw Rev

1 D/A Trim2 Scaled D/A Trim3 Factory Trim

1 OFF-LINE2 ON-LINE3 FREQUENCY

DEVICE4 UTILITY

1 Tag2 XMTR VAR ENG UNITS3 Range Values

4 DEVICE INFORMATION

5 CONSTRUCTION MATERIALS

1 Identify Primary Variable2 Primary Value3 Primary Range4 A015 Change Prim. Var. Assign.

1 Loop Test2 View Status3 Reset

1 AO Alarm Type2 Loop Test3 ANALOG TRIM

1 Poll Address2 No Request Pream3 No Response Pream4 BURST MODE OPER

1 Burst Option2 Burst Mode3 Xmtr Var Slot Assn

1 CALIBRATION2 RTD Config3 Atm Press Config4 DP Damping

5 XMTR VAR DAMPING

6 XMTR VAR ENG UNITS

1 SENSOR TRIM

2 ANALOG TRIM

1 DP Snsr Trim2 AP Snsr Trim3 GP Snsr Trim4 Temp Snsr Trim

1 D/A Trim2 Scaled D/A Trim3 Factory Trim1 DP Damping

2 AP Damping3 Temp Damping4 GP Damping

1 DP Units2 AP Units3 Temp Units4 GP Units5 Flow Units6 Flow Total Unit

1 Display Period2 Local Display

1 Mode2 Total

1 FLOW

2 TOTAL

1 Base Unit2 Scaling Factor3 Unit String

1 Base Unit2 Scaling Factor3 Unit String

B-2

ENRosemount Inc

Table B-10. HART Fast Key Sequences for the Model 3095 MV Mass Flow Transmitters

Function/Variable Fast Key Sequence

% rnge 1, 1, 2

% rnge 1, 1, 5, 1, 3

4V is 1, 1, 5, 4, 1

AO Alrm typ 1, 4, 1, 1, 1

AO1 1, 1, 3

AO1 3

AP Damping 1, 4, 2, 5, 2

AP Sens Trim 1, 2, 2, 1, 2

AP Units 1, 3, 2, 2

Absolute (AP) 1, 1, 4, 2

Atm Press Cnfg 1, 4, 2, 3

Burst mode 1, 4, 1, 2, 4, 2

Burst option 1, 4, 1, 2, 4, 1

Change PV Assgn 1, 1, 5, 1, 5

Change SV Assgn 1, 1, 5, 2, 3

Change TV Assgn 1, 1, 5, 3, 3

Change 4V Assgn 1, 1, 5, 4, 3

D/A trim 1, 2, 2, 2, 1

DP Low Flow Cutoff 1, 4, 6

DP LRV 4

DP Sens Trim 1, 2, 2, 1, 1

DP Snsr Range 1, 3, 5, 1

DP URV 5

DP unit 1, 3, 2, 1

Date 1, 3, 4, 4

Descriptor 1, 3, 4, 2

Diff pres damp 1, 4, 2, 4

Diff pres 1, 1, 1

B-3

ENRosemount Inc

Function/Variable Fast Key Sequence

Diff pres 2

Drain vent matl 1, 3, 5, 8

Factory Trim 1, 2, 2, 2, 3

Fill fluid 1, 3, 5, 5

Final asmbly num 1, 3, 4, 5

Flange type 1, 3, 5, 7

Fld dev rev 1, 3, 4, 9, 2

Flnge matl 1, 3, 5, 6

Flo rate 1, 1, 4, 5

Flow Rate Special Units 1, 4, 5, 1

Flow Units 1, 3, 2, 5

GP Damping 1, 4, 2, 5, 4

GP Sens Trim 1, 2, 2, 1, 3

GP Units 1, 3, 2, 4

Gage (GP) 1, 1, 4, 4

Hardware rev 1, 3, 4, 9, 4

Isoltr matl 1, 3, 5, 4

LCD Settings 1, 4, 3

Loop test 1, 2, 1, 1

Manufacturer 1, 3, 4, 6

Message 1, 3, 4, 3

Model 1, 3, 4, 7

Num remote seal 1, 3, 5, 13

Num req preams 1, 4, 1, 2, 2

Num resp preams 1, 4, 1, 2, 3

O ring matl 1, 3, 5, 9

PV is 1, 1, 5, 1, 1

Poll addr 1, 4, 1, 2, 1

Process temp unit 1, 3, 2, 3

Process temp 1, 1, 4, 3

B-4

ENRosemount Inc

Function/Variable Fast Key Sequence

RS fill fluid 1, 3, 5, 11

RS isoltr matl 1, 3, 5, 12

RS type 1, 3, 5, 10

RTD Config 1, 4, 2, 2

Range values 1, 3, 3

Reset 1, 2, 1, 3

SP Snsr Range 1, 3, 5, 2

SP Type 1, 3, 5, 3

SV is 1, 1, 5, 2, 1

Scaled D/A trim 1, 2, 2, 2, 2

Snsr module hw rev 1, 3, 4, 9, 6

Snsr module sw rev 1, 3, 4, 9, 5

Software rev 1, 3, 4, 9, 3

Status group 1 1, 6

Totalizer 1, 4, 4

Totalizer Special Units 1, 4, 5, 2

TV is 1, 1, 5, 3, 1

Tag 1, 3, 1

Temp Sens Trim 1, 2, 2, 1, 4

Temp damp 1, 4, 2, 5, 3

Universal rev 1, 3, 4, 9, 1

View status 1, 2, 1, 2

Write protect 1, 3, 4, 8

Xmtr Var Slot Assn 1, 4, 1, 2, 4, 3

B-5

ENRosemount Inc

B-6