RP-AADC-LVAC-BS - POC1ABBREF615CT Ratio 2700:1IEC - Normal InversePickup = 0.95 (0.3 - 5 xCT Sec)Time Dial = 0.153x = 0.945 s, 5x = 0.642 s, 8x = 0.495 s
250A-MCCBSiemens 3VL3VL3725Size = 250 AmpsThermal Trip = 100%Magnetic Trip = Fixed
10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K
Amps X 100 LVAC-AADC-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.415)
10K.5 1 10 100 1K3 5 30 50 300 500 3K 5K
Amps X 100 LVAC-AADC-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.415)
1K
.01
.1
1
10
100
.03
.05
.3
.5
3
5
30
50
300
500
Sec
onds
1K
.01
.1
1
10
100
.03
.05
.3
.5
3
5
30
50
300
500
Seconds
ETAP Star 12.5.0C
N7733-ZAKHER CASE:4.2
Project: 220/33/11kV Zakher GridLocation: Zakher Area of Al AinContract: N7733Engineer: JMFilename: C:\ETAP 1250\N7733\N7733.OTI
Date: 21-01-2016 SN: LARSENTRN2Rev: BaseFault: PhaseCircuit: LVACB/S,MCCB250A