Upload
duongtuyen
View
216
Download
0
Embed Size (px)
Citation preview
BACNET MS/TPBACNET MS/TPTopics:1 – Network Requirements2 – Device Addressing3 – Power Supply Requirements4 – System Architecture5 – BACnet Objects & Services6 – Labwork
Topics:1 – Network Requirements2 – Device Addressing3 – Power Supply Requirements4 – System Architecture5 – BACnet Objects & Services6 – Labwork
1
BACnet MS/TP
2
3 – Power Supply Requirements
When you’ve completed this presentation on EC-gfxProgram Basics, click on the “QUIZ” button below to take a short quiz. Then click the brown “NEXT MODULE” arrow below to advance to the next e-module – Module X: Module Name.
Click to review Instructions >
EST: 45:00
4 – System Architecture
1 – Network Requirements
2 – Device Addressing
CONTINUE
5 – BACnet Objects & Services
6 – Labwork
7 – Project Conversion
8 – Troubleshooting Issues
BACnet MS/TP
Navigation Instructions
3
Select any button on the main menu to navigate to the topic of choice.
When done with that topic, look for the red “BACK TO MENU” arrow to return to this menu.
BACK TO MENU
At any time during a topic, you may click on the blue “BACK TO MENU” arrow at the bottom to return to the main menu.
BACK TO MENU
BACnet MS/TP
Navigation Instructions
4
MORE INFORMATION LINKS: Select these links whenever prompted to view examples and additional info.
You will see instructions in this box regarding what to click and what you will see.
Hysteresis
Limit / Linear
ADDITIONAL MENU LINKS: Select these links whenever prompted to obtain more information on a specific topic.
BACK TO TOOLBOX
ADDITIONAL NAVIGATION LINKS: Select these links to navigate from sub-topics back up to the topic level.
QUIZ LINKS: Select these links to test your knowledge at the end of each module.
NEXT MODULE LINKS: Select this link when you’ve completed the current module and wish to advance to the next module.
NEXT MODULE
In some cases, there may be
semi-transparent green highlighted areas like this that are hyperlinked.
BACnet MS/TP
Icons
Right-click2
MOUSE ICONS: Where needed when describing different processes, the following mouse icons are used to define whether to use left-, double- or right-click mouse options.
Double left-clickLeft-click
STEPS ICONS: Indicate ordered steps of a procedure. 1 2 3
The “drag-and-drop” method is only one of several methods to bring proxy points into the station’s database.
NOTE ICON: Where needed when describing different concepts, a note icon will provide additional information.
NETWORK REQUIREMENTS TOPIC 1
BACNET MS/TPBACNET MS/TP
BACK TO MENU
Topology
Wiring
Device Load
Baud Rate
Topology
Wiring
Device Load
Baud Rate
CHAPTER 2
BACnet Integration in EC-Net-AX
BACnet network design review– Topology and wiring
– Addressing
– Power supply
Commission an EC-BOS review
BCP BACnet Network driver
BACnet MS/TP Communication Port
Device MS/TP MAC addressing
Discovering devices
Device Instance number (ID) strategy
PC connection with BACnet IP to MS/TP adaptor
7BACK TO MENU
MS/TP Network Topology
BACnet MS/TP Network Topology
8
4,000 ft / 50 devices
(Recommended)
Data Transmission Protocol
MS/TP (RS-485)
Architecture Type Daisy Chain
Number of device per segment
255 max (128 masters + 128 slaves) 50 recommended
Network Length 1220 meters (4000 ft) max
BACK TO MENU
MS/TP Network Wiring
BACnet MS/TP Network Wiring
9
Cable Type Shielded twisted pair (STP) (DC approved #07CBL-BACnet)
Wiring Data Bus is Polarity SensitiveShield wire is continue on the entire lengthConnect shield wire to building ground on one end only
End-Of-Line 120 Ohms resistor on each end of the segment- Jumper on ECB Controllers- External resistor on EC-BOS and ECB-Stat
Bias 510 Ohms per wireMinimum of one, maximum of two sets per segmentProvided by built-in EOL (internal jumper EOL)
BACK TO MENU
MS/TP Network Load
All Distech Controls’ devices are categorized as Masters and rated as ⅛ load
Other may have different network load ratings (for example, ¼, ½, or full load)
If a segment contains dissimilar device load ratings, the device with the highest load rating is the one that sets the limit for the maximum number of devices for that data bus segment
For example, you plan to put the following devices on one data bus segment:
10
The solution for the above example is to create two data bus segments connected together by a repeater and then split up the devices between the data bus segments.
BACK TO MENU
MS/TP Network Baud Rate
By default, the Distech BACnet controllers have their BAUD rate set to AUTO
The recommended baud rate for Distech Controls’ devices is 38.4 kbps
All devices on the data bus must be set to the same baud rate
Therefore, the chosen baud rate must be supported by all devices connected to the data bus
11
Baud Rate Support: from 9.6 to 76.8 kbpsRecommended: 38.4 kbpsDefault setting on ECB controllers: AUTO
Most devices will have a settings AUTO. This is the preferred setting for a controller. However, at least one controller on the BACnet MS/TP network data bus must have its BAUD rate set. The preference is to set the building controller’s BAUD rate (if present). e.g. on an EC-BOS.
BACK TO MENU
MS/TP Network Baud Rate
When the Baud rate is set to AUTO, the controller cannot initiate any communication until it has detected the baud rate of the BACnet MS/TP network
If all controllers on the BACnet MS/TP network are set to AUTO, then all controllers will not communicate
Setting the BAUD rate on at least one controller is required, which will set the BAUD rate for all other controllers on the data bus
Setting the BAUD rate on ECB controllers is performed with the EC-Smart-VueGeneral Configuration Menu (See Hardware Installation Guide)
12BACK TO MENU
DEVICE ADDRESSING TOPIC 2
BACNET MS/TPBACNET MS/TP
BACK TO MENU
Device Addressing / Best Practices
14
Device Instance (ID) Number
Bus Master Device Settings
Device MAC Addressing
Device Addressing Overview
Device Numbering System
BACK TO MENU
Device Addressing Overview
Each device connected to the BACnet MS/TP data bus is identified by a:
– MAC address
– Device Instance number
– Network number
The MS/TP Device MAC Address uniquely identifies a device on an MS/TP Network segment (identified by a Network Number). Devices on another MS/TP Network segment (identified by a different Network Number) can have the same MAC Address. The MAC Address is any number between 0 and 127 for Master devices, and 128 to 254 for Slave devices.
Address 255 is a wild card for broadcasts.
15
Addressing Both the MAC Address and the Device Instance must be set for each device and are essential for proper BACnet LAN operation
BACK TO MENU
Device Addressing Overview
The BACnet Device Instance (or Device ID) uniquely identifies a device across the complete BACnet internetwork. The Device Instance may be any number between 0 and 4194302. It is with the Device Instance that messages are exchanged between BACnet devices.
Unlike a MAC Address, a Device Instance cannot be reused elsewhere in the BACnet internetwork (it must be unique).
The BACnet Network Number is any number between 1 and 65534. A network number identifies a LAN for routing purposes. Each BACnet MS/TP Network will have a Network Number, and each BACnet IP Network will also have a Network Number.
16
Addressing Both the MAC Address and the Device Instance must be set for each device and are essential for proper BACnet LAN operation
BACK TO MENU
MS/TP Device MAC Address
Reserve some MAC Addresses for common commissioning and maintenance tasks.
– Reserve MAC 0 for the Building Controller MS/TP port
– Reserve MAC 1 for a portable router, so it can be temporarily connected without conflicting with other devices already connected to the data bus.
Avoid gaps in the MAC address sequence.
The physical order is unimportant.
MAC Addresses should be used as shown in the following table.
17BACK TO MENU
Setting MS/TP Device MAC Address
ECB devices:
– The MAC address can be changed using EC-Smart-Vue (all DIP switches need to be at 0 position)
– The MAC address can also be changed using DIPswitches on ECB-203 and higher series (device power cycle is required after)
ECB-STAT: On the LCD interface menu
EC-BOS: Using EC-NetAX Pro, MstpPort / Link Properties
18
Tool Kit All technicians should have an EC-Smart-Vue in their tool kit
Ex. MAC: 2+16+64 = 82
BACK TO MENU
MS/TP Bus Master – Device Settings
In a typical BACnet Network, the Network interface card used to access the MS/TP bus is called the Bus Master. In recommended architectures, the EC-BOS MS/TP Port is the Bus Master Device.
There are 4 configurations that are required on the Bus Master Device:
– Baud Rate
– MS/TP Address (MAC Address)
– Max Master
– Max Info Frames
19BACK TO MENU
MS/TP Bus Master – Baud Rate & MAC
The Baud Rate Usually set in the Bus Master (EC-BOS) and will be the only reference if all
devices on the network are set to AUTO. All devices on the network need to have the same Baud rate manually set or AUTO
– 38.4 kbps is the recommended Baud rate setting in the EC-BOS
– AUTO is the default and recommended setting for all ECB controllers
The MS/TP Address Or MAC Address for the Bus Master (EC-BOS) is set to 0 (it’s the default value)
20BACK TO MENU
MS/TP Bus Master – Max Master
MS/TP Network: Bus Master Device (Building Controller) To prevent the passing of the token to unused MAC Addresses situated after
the final Master device, the Max Master must be set in each Master Device.
About the Max Master Property By default, the Max Master for the MS/TP Bus is set to 127 in the EC-BOS
In practice, the actual number of devices connected to a data bus is far less. This gap unnecessarily slows-down the data bus.
Set the Max Master in the EC-BOS to the highest Master device’s MAC Address to optimize the efficiency of the data bus (reserve 3 to 5 more for spares)
21BACK TO MENU
MS/TP Bus Master – Max Info Frames
MS/TP Network: Bus Master Device (Building Controller)Max Info Frames is set to 20 (default) in the EC-BOS – may be increased as needed
Once a device has the token, it can make a number of information requests to other devices on the BACnet internetwork. The maximum number of requests is limited by the Max Info Frames property.
22
Device Type Info Frames Reason
ECB-STAT 1 Thermostats
ECB-VAV series 5 Terminal units controllers don’t have many requests
ECB-203 (and above) 5 System unit controllers have more requests
EC-BOS 20 Building Controllers have most requests
Ordinary BACnet MS/TP devices should have the Max Info Frames properties set to between 1 and 5. The Bus Master (EC-BOS) should have the Max Info Frames property set to about 20.
BACK TO MENU
BACnet Device Instance Number (ID)
Default Numbering System for Distech Controls’ controllers By default, controllers from Distech Controls automatically self-assign a Device
Instance number generated from the MAC Address assigned to the controller during installation.
The Device Instance number is calculated as follows, where 364 is Distech Controls BACnet manufacturer ID:
– Default Device Instance number = 364 X 1000 + MAC Address
This Numbering system is sufficient for a BACnet network that has only one MS/TP Network on only one Building Controller (EC-BOS).
Examples:
23
MAC Address Default Numbering System Default Device Instance Number
3 364000 + 3 364003
20 364000 + 20 364020
123 364000 + 123 364123
BACK TO MENU
BACnet Device Instance NumberFor Larger BACnet Networks
24
For larger BACnet networks that have more than one building controller, set the MAC addresses, Device Instance numbers and Network numbers manually according to a good well thought-out network planning scheme.
BACK TO MENU
Device Instance Numbering System
Numbering System for MAC Addresses, Device Instance and Network Numbers Distech recommends the following scheme, as it reuses the MAC Address and Network Number in the Device Instance number to make it easier to implement:
25
Discover Make sure to add only the devices connected to the MS/TP port of the specific EC-BOS being configured. Using this numbering system will greatly help to identify those devices that should be added to a given EC-BOS.
BACK TO MENU
Device Instance Numbering System Example
26BACK TO MENU
POWER SUPPLY REQUIREMENTS TOPIC 3
BACNET MS/TPBACNET MS/TP
BACK TO MENU
Power Supply Requirements
Power Supply Wiring
Power Supply Ground Lift
Typical Wiring Diagram
28BACK TO MENU
Power Supply Wiring
24V Power Supply wiring The 24V COM terminal of all devices must be connected to the Electrical System Ground.
Without this signal reference, transceivers may interpret the voltage levels of the differential data signals incorrectly, and this may result in data transmission errors.
All Distech devices use the 24V COM terminal as the signal reference point for the data bus. That wire must be connected to the Electrical System Ground at the power supply. This ensures that the 24V COM terminals of all devices in the building are at the same potential
Mechanical ground is unacceptable: Do not use a pipe, conduit or duct work for a ground
For inter-building connections, it is recommended to use a BACnet/IP or Fox network connection.
29BACK TO MENU
Power Supply Ground Lift
Avoid Ground Lift Ground lift is caused by wire resistance causing voltage drop on the power
wire run.
Because the 24V COM terminal is the signal reference point for the data bus, a ground lift would offsets that reference and affect the transceiver’s valid data levels.
If the ground lift (voltage drop) is more than 7 volts, there is a risk of data corruption and offline events due to the device being incapable of correctly reading data signals.
30BACK TO MENU
Power Supply Ground Lift
Techniques to Reduce Ground Lift Power wiring runs should not be too long, nor have too many devices
connected to it.
Use the instructions in the Hardware installation guide for limitations info.
Always use a transformer with 100VA power or less.
Power 5 devices or less with one 100VA transformer.
Use a wire with a gage of 18 or less for the power run.
When the total load of a number of device requires more than 100 VA, use two or more transformers.
Maintain consistent polarity when connecting controllers and peripherals to the power run.
The 24V COM terminal of the transformer must be connected to the building’s ground.
31BACK TO MENU
SYSTEM ARCHITECTURE TOPIC 4
BACNET MS/TPBACNET MS/TP
BACK TO MENU
Typical Wiring Diagram
Device BACnet MS/TP LAN and Power Wiring Diagram
33BACK TO MENU
Medium-to-Large Building Architecture
34BACK TO MENU
Peer-to-Peer Architecture
True Peer-to-Peer
Typical architecture for very small projects
No building controller required
Any device is able to Initiate data transfer
Data sharing from one to many
Local network connection required for engineering
35BACK TO MENU
BACnet IP to MS/TP Network Adaptor
Used to connect a computer (typically a laptop) to a BACnet MS/TP network
Internal Web server for configurations and diagnostics
Optically isolated MS/TP port
Supplied by a USB port (USB port is strictly used to power the unit)
3.5mm Stereo jack quick connect to MS/TP bus
Applications– Commissioning
– Configuring
– Engineering
– Troubleshooting
36
Adaptor Use the adaptor in Peer-to-Peer architecturesAlso when no IP connection to the BAS is accessible
BACK TO MENU
BACNET OBJECTS & SERVICES TOPIC 5
BACNET MS/TPBACNET MS/TP
BACK TO MENU
BACnet Specific Objects
38
BACnet Objects
Inputs
Outputs
Values
PID
Schedule
Calendar
Commandable objects usage
Non-commandable objects usage
BACnet Network properties
Alarm properties (B-AAC)
BACK TO MENU
Read Property Services
COV Subscription Services
Receive Broadcast COV
Write Property Services
Send Broadcast COV Services
BACnet Specific Services
39BACK TO MENU
LABWORK TOPIC 6
BACnet MS/TPBACnet MS/TP
BACK TO MENU
LAB 12: Getting Started With BACnet MS/TPLAB 12: Getting Started With BACnet MS/TP
41
Ideal for large control requirements, ranging from 28-points to 76-points(HW inputs/outputs) (support up two ECx-400 extension modules)
Fast-response 32-bit microprocessor for complex data processing, including floating point support and math function execution, such as trigonometric and psychometric calculations
Supports up to 500 network values
Lab 12: Starting With BACnet MS/TP
LAB 12 – 75 minGetting Started With BACnet MS/TP ControllersLAB 12 – 75 minGetting Started With BACnet MS/TP Controllers
BACK TO MENU
40:00
Lab 12: Starting With BACnet MS/TP
42
A. Add BACnet Network
B. Configure the Local Device (EC-BOS)
C. Add & Configure MS/TP Port
D. Set MAC Addresses for BACnet Devices
E. Discover & Add Devices
F. Configure Device IDs for all Devices
G. Configure Max Master
H. Launch EC-gfxProgram / Load a Project
A. Add BACnet Network
B. Configure the Local Device (EC-BOS)
C. Add & Configure MS/TP Port
D. Set MAC Addresses for BACnet Devices
E. Discover & Add Devices
F. Configure Device IDs for all Devices
G. Configure Max Master
H. Launch EC-gfxProgram / Load a Project
BACK TO MENU
43
Lab 12: Starting With BACnet MS/TP
BACK TO MENU
LAB 12A – 3 minCreate a BcpBacnetNetwork on the EC-BOS stationLAB 12A – 3 minCreate a BcpBacnetNetwork on the EC-BOS station
LAB 12B – 2 minConfigure the Local Device (EC-BOS)LAB 12B – 2 minConfigure the Local Device (EC-BOS)
LAB 12C – 10 minAdd & Configure the MSTP PortLAB 12C – 10 minAdd & Configure the MSTP Port
LAB 12D – 10 minSet MAC Address for all BACnet devicesLAB 12D – 10 minSet MAC Address for all BACnet devices
44
Lab 12: Starting With BACnet MS/TP
BACK TO MENU
LAB 12E – 3 minDiscover & Add BACnet devicesLAB 12E – 3 minDiscover & Add BACnet devices
LAB 12F – 5 minConfigure Device IDs for all BACnet devicesLAB 12F – 5 minConfigure Device IDs for all BACnet devices
LAB 12G – 2 minConfigure the Max Master property and communicate to all devices on the BACnet network
LAB 12G – 2 minConfigure the Max Master property and communicate to all devices on the BACnet network
LAB 12H – 5 minLaunch EC-gfxProgram and Load a projectLAB 12H – 5 minLaunch EC-gfxProgram and Load a project
45
From the Distech Controls palette, add the BcpBacnetNetwork driver to your station. Or use the New button in the Driver Manager.
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12A – 3 minAdd a BcpBacnetNetwork on the EC-BOS StationLAB 12A – 3 minAdd a BcpBacnetNetwork on the EC-BOS Station
BACK TO SECTIONS
Lab 12: A – Add a BACnet Network
Add the BcpBacnetNetwork driver to the Drivers container of your EC-BOS station.
BACK TO MENU BACK TO SECTIONS
Lab 12: A – Add a BACnet Network
Driver Manager
New button
Add the BcpBacnetNetwork driver to the Drivers container of your EC-BOS station.
BACK TO MENU BACK TO SECTIONS
1
2
3 4
2
48
On the Local Device’s property sheet, set the Object ID property to a value other than the default of -1.
For the Lab exercise, we will use the last 2 digits of the EC-BOS IP address plus “000” to designate the EC-BOS as the master controller.
EXAMPLE: 13000
13 = last 2 digits of BOS IP (10.1.1.113) 000 = MAC address of EC-BOS
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12B – 2 minConfigure the Local Device (EC-BOS)LAB 12B – 2 minConfigure the Local Device (EC-BOS)
BACK TO SECTIONS
Set the Object ID property to a value other than the default of -1.
Use the last 2 digits of the EC-BOS IP address plus “000” to designate the EC-BOS as the master controller.
EXAMPLE: 13000
13 = last 2 digits of BOS IP (10.1.1.113)
000 = MAC address of EC-BOS
Lab 12: B – Configure Local Device
BACK TO MENU BACK TO SECTIONS
Set the Object ID property to a value other than the default of -1.
Use the last 2 digits of the EC-BOS IP address plus “000” to designate the EC-BOS as the master controller.
EXAMPLE: 13000
13 = last 2 digits of BOS IP (10.1.1.113) 000 = MAC address of EC-BOS
Lab 12: B – Configure Local Device
Local Device
Object ID
Property sheet
BACK TO MENU BACK TO SECTIONS
51
From the distechControls palette, add an MSTP port to the BcpBacnetNetwork under BACnet Comm > Network.
Configure the following properties on the MSTP Port’s property sheet:
• Port Name
• Baud Rate
• MS/TP Address (MAC)
• Max Master
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12C – 10 minAdd & Configure the MSTP PortLAB 12C – 10 minAdd & Configure the MSTP Port
BACK TO SECTIONS
Lab 12: C – Add/Configure MS/TP Port
From the distechControls palette, add an MSTP port to the BcpBacnetNetwork under BACnet Comm > Network.
BACK TO MENU BACK TO SECTIONS
Lab 12: C – Add/Configure MS/TP Port
distechControls
MSTP Port
From the distechControls palette, add an MSTP port to the BcpBacnetNetwork under BACnet Comm > Network.
BACK TO MENU BACK TO SECTIONS
BACK TO SECTIONS
Lab 12: C – Add/Configure MS/TP Port
Configure the following properties on the MSTP Port’s property sheet:
• Network Number
• Port Name
• Baud Rate
• MS/TP Address (MAC)
• Enabled
Bacnet Comm > Network > MSTP Port
Property sheet
Set to TRUE
BACK TO MENU
Lab 12: C – Add/Configure MS/TP Port
BACK TO MENU
Configure the following properties on the MSTP Port’s property sheet:
• Network Number• Port Name• Baud Rate• MS/TP Address (MAC)• Enabled
BACK TO SECTIONS
56
Using one of the following methods, set the MAC address and BAUD rate for the BACnet controllers:
• DIP switches
• EC-Smart-Vue
• LCD screen (x50 series)
• Menu button (STAT only)
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12D – 10 minSet MAC Address / Baud Rate for all BACnet devicesLAB 12D – 10 minSet MAC Address / Baud Rate for all BACnet devices
BACK TO SECTIONS
Lab 12: D – Set Device MAC Addresses
BACK TO MENU BACK TO SECTIONS
Using one of the following methods, set the MAC address and BAUD rate for the BACnet controllers:
• DIP switches• EC-Smart-Vue• LCD screen (x50 series)• Menu button (STAT only)
Lab 12: D – Set Device MAC Addresses
The following options are available for setting the MAC address for a programmable BACnet device:
X50 LCD Screen
EC-Smart-Vue
DIP Switches
STAT Menu
Click for more info:
BACK TO MENU BACK TO SECTIONS
BACK TO SET MAC
Lab 12: D – Set Device MAC AddressesDIP Switches
DIP Switches
Binary settings
BACK TO SET MAC
Lab 12: D – Set Device MAC AddressesEC-Smart-Vue
Advanced menu Password = 9995- GEN CFG menu
MAC addressBAUD rate
BACK TO SET MAC
Lab 12: D – Set Device MAC Addressesx50 series Controllers – LCD Screen
Settings Menu
MAC address
BACK TO SET MAC
Lab 12: D – Set Device MAC AddressesSTAT Menu button
Menu button
COM address set?
63
Discover the devices (physical controllers) on your BcpBacnetNetwork.
Add them to the BcpBacnetNetwork in the Database pane.
Rename the device as appropriate with the site’s device naming convention.
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12E – 3 minDiscover & Add BACnet devicesLAB 12E – 3 minDiscover & Add BACnet devices
BACK TO SECTIONS
Lab 12: E – Discover/Add BACnet Devices
BACK TO MENU
Discover the devices (physical controllers) on your BcpBacnetNetwork.
Add them to the BcpBacnetNetwork in the Database pane.
Rename the device as appropriate with the site’s device naming convention.
BACK TO SECTIONS
Lab 12: E – Discover/Add BACnet Devices
BACK TO MENU BACK TO SECTIONS
Discover Pane
Database Pane
66
Select the devices for which you wish to change the Device ID in the Database pane, and click the Change Device ID button.
Set the Device IDs for devices simultaneously for common changes or individually for changes unique to a specific device.
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12F – 5 minConfigure Device IDs for all BACnet devicesLAB 12F – 5 minConfigure Device IDs for all BACnet devices
BACK TO SECTIONS
Lab 12: F – Configure Device IDs
Select the devices for which you wish to change the Device ID in the Database pane, and click the Change Device ID button.
Set the Device IDs for devices simultaneously for common changes or individually for changes unique to a specific device.
BACK TO MENU BACK TO SECTIONS
Lab 12: F – Configure Device IDs
BACK TO MENU BACK TO SECTIONS
Change Device ID
Database Pane
1
2
3 4 5
69
On the MSTP Port Link property sheet, use the MSTP Configuration tool to set the Max Master for all BACnet devices on the network.
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12G – 2 minConfigure the Max Master property and communicate to all devices on the BACnet network
LAB 12G – 2 minConfigure the Max Master property and communicate to all devices on the BACnet network
BACK TO SECTIONS
Lab 12: G – Configure the Max Master
BACK TO MENU BACK TO SECTIONS
On the MSTP Port Link property sheet, use the MSTP Configuration tool to set the Max Master for all BACnet devices on the network.
Lab 12: G – Configure the Max Master
Max Master
MS/TP Configuration tool
BACK TO MENU BACK TO SECTIONS
2 3
4
1
72
Right-click on the Bacnet device and select Launch Wizard.
EC-gfxProgram will load under EC-Net-AX. Validate connectivity with both the EC-BOS and the BACnet controller.
Load a pre-loaded application project from the Code Library.
BACK TO MENU
Lab 12: Starting With BACnet MS/TP
LAB 12H – 5 minLaunch EC-gfxProgram and Load a projectLAB 12H – 5 minLaunch EC-gfxProgram and Load a project
BACK TO SECTIONS
Lab 12: H – Launch GFX and Load a Project
Right-click on the Bacnet device and select Launch Wizard.
EC-gfxProgram will load under EC-Net-AX. Validate connectivity with both the EC-BOS and the BACnet controller.
Load a pre-loaded application project from the Code Library.
BACK TO MENU BACK TO SECTIONS
Lab 12: H – Launch GFX and Load a Project
Launch Wizard
EC-gfxProgram
BACK TO MENU BACK TO SECTIONS
Lab 12: H – Launch GFX and Load a Project
BACK TO MENU BACK TO SECTIONS
Code Library
gfxApplications
23
1
PROJECT CONVERSION TOPIC 7
BACnet MS/TPBACnet MS/TP
BACK TO MENU
Project Conversion
To convert a project engineered in another protocol such as LonWorks, you must convert it to the current protocol – in this case, BACnet. Before conversion, the Error List will display many errors, such as below, because BACnet does not know how to interpret the other protocol’s objects.
77BACK TO MENU
2
Project Conversion
To convert a pre-engineered project to another protocol, use the ConvertProject button in the File menu. The resulting new list of errors should be significantly reduced.
78BACK TO MENU
1
Project Conversion
In the case of converting from a Lon project, BACnet does not recognize Network Variables or SNVTs, and so each Network Variable must be replaced with a BACnet Network Value block:
BACK TO MENU
Project Conversion
Each Network Value block must be configured for the following properties:
Network Value Mode
Configuration Type
Service
Device Path
Object
Property
Data Type
Default Value
Poll Interval
BACK TO MENU
Project Conversion
Property ValueNetwork Value Mode Input or Output
Configuration Type Database or Manual
Service For INPUTS:• Read Property• Read Property Multiple• COV Subscription• Receive Broadcast COV
For OUTPUTS:• Write Property• Write Property Multiple• Send Local Broadcast COV• Send Global Broadcast COV
Device Path Select the device from a network tree
Object For INPUTS:
Select the BACnet object from the device that is being received from (and read by) the controller
For OUTPUTS:
Select the BACnet object from the device that is being sent to (and written to) the other controller
BACK TO MENU
Project Conversion
The Project Conversion tool can save you both time and money in allowing you to reuse existing projects engineered in other protocols or devices.
BACK TO MENU
TROUBLESHOOTING ISSUES TOPIC 8
BACnet MS/TPBACnet MS/TP
BACK TO MENU
CHAPTER 6
Troubleshooting Issues
84BACK TO MENU
Troubleshooting Issues- Fault Conditions
85BACK TO MENU
Troubleshooting Issues- Status LED Interpretations
86BACK TO MENU
Troubleshooting Issues- Before Calling Tech Support Verifications
87
Bus EOL termination
Duplicate MACs
Same Baud rate
Incorrect polarity
BACK TO MENU
Troubleshooting Issues- Before Calling Tech Support Verifications
88
MAC address gaps
COV reporting
Non Daisy-chained
Power: not > 5 devices
BACK TO MENU
Troubleshooting Issues- Before Calling Tech Support Verifications
Bus EOL termination
BACK TO MENU BACK TO SUPPORT ISSUES
Troubleshooting Issues- Before Calling Tech Support Verifications
BACK TO MENU BACK TO SUPPORT ISSUES
Duplicate MACs
DIP SwitchesBinary settings
Troubleshooting Issues- Before Calling Tech Support Verifications
BACK TO MENU BACK TO SUPPORT ISSUES
Same Baud rate
Troubleshooting Issues- Before Calling Tech Support Verifications
BACK TO MENU BACK TO SUPPORT ISSUES
Incorrect polarity
Troubleshooting Issues- Before Calling Tech Support Verifications
BACK TO MENU BACK TO SUPPORT ISSUES
Excess COV Reporting
Troubleshooting Issues- Before Calling Tech Support Verifications
BACK TO MENU BACK TO SUPPORT ISSUES
MAC address gaps
Troubleshooting Issues- Before Calling Tech Support Verifications
BACK TO MENU BACK TO SUPPORT ISSUES
Non Daisy-chained
Troubleshooting Issues- Before Calling Tech Support Verifications
BACK TO MENU BACK TO SUPPORT ISSUES
Power: Not > 5 devices
What is the recommended limit for the total number of Distech BACnet devices allowed on a network?
What is the Max Master and why is it important that it be changed from the default setting of 127?
Review Questions
97
What is the MAC address reserved for broadcasts?
How do you set the MAC address of an ECB-VAV or -600 series controller?
When should you set the Max Master for the network?
In what chapters of the Network Guide are the guidelines for Bacnet data bus fundamentals and associated troubleshooting?
BACK TO GETTING STARTED
WITH BACNETMENU
(CLICK HERE)
It’s Quiz Time
It’s time to review what you’ve learned.
Click the QUIZ button to begin.If you wish to review first, click the REVIEW button below.
REVIEW
The QUIZ is still under development.
So click again and we’ll take you to the next module.
NEXT MODULE