EC-SMART-VUE EC-SMART-VUE Topics: 1 – Model Comparison & Features 2 – Smart-Vue Sub-Network 3 – Scenes, Values & Conditions Topics: 1 – Model Comparison & Features 2 – Smart-Vue Sub-Network 3 – Scenes, Values & Conditions 1 EC-SMART-VUE 2 2 – Smart-Vue Subnetwork When you’ve completed this presentation on EC-gfxProgram Basics, click on the “QUIZ” button below to take a short quiz. Then click the brown “NEXT MODULE” arrow below to advance to the next e-module – Module 3: Distech Controllers. Click to review Instructions > EST: 60:00 3 – Scenes, Values & Conditions 1 – Model Comparison & Features CONTINUE 4 – Labwork

6001-54.2 SLIDES PRE EC-Smart-Vue Lab15 - tech.ct …tech.ct-supply.com/Training Material/Newer6001_TrainingMaterials...Limit / Linear ADDITIONAL MENU LINKS: ... Motion CO2 It has

Embed Size (px)

Citation preview

EC-SMART-VUEEC-SMART-VUE

Topics:

1 – Model Comparison & Features

2 – Smart-Vue Sub-Network

3 – Scenes, Values & Conditions

Topics:

1 – Model Comparison & Features

2 – Smart-Vue Sub-Network

3 – Scenes, Values & Conditions

1

EC-SMART-VUE

2

2 – Smart-Vue Subnetwork

When you’ve completed this presentation on EC-gfxProgram Basics, click on the “QUIZ” button below to take a short quiz. Then click the brown “NEXT MODULE” arrow below to advance to the next e-module – Module 3: Distech Controllers.

Click to review Instructions >

EST: 60:00

3 – Scenes, Values & Conditions

1 – Model Comparison & Features

CONTINUE

4 – Labwork

EC-Smart-Vue

Navigation Instructions

3

Select any button on the main menu to navigate to the topic of choice.

When done with that topic, look for the red “BACK TO MENU” arrow to return to this menu.

BACK TO MENU

At any time during a topic, you may click on the blue “BACK TO MENU” arrow at the bottom to return to the main menu.

BACK TO MENU

EC-Smart-Vue

Navigation Instructions

4

MORE INFORMATION LINKS: Select these links whenever prompted to view examples and additional info.

You will see instructions in this box regarding what to click and what you will see.

Hysteresis

Limit / Linear

ADDITIONAL MENU LINKS: Select these links whenever prompted to obtain more information on a specific topic.

BACK TO TOOLBOX

ADDITIONAL NAVIGATION LINKS: Select these links to navigate from sub-topics back up to the topic level.

QUIZ LINKS: Select these links to test your knowledge at the end of each module.

NEXT MODULE LINKS: Select this link when you’ve completed the current module and wish to advance to the next module.

NEXT MODULE

In some cases, there may be

semi-transparent green highlighted areas like this that are hyperlinked.

EC-Smart-Vue

Icons

Right-click2

MOUSE ICONS: Where needed when describing different processes, the following mouse icons are used to define whether to use left-, double- or right-click mouse options.

Double left-clickLeft-click

STEPS ICONS: Indicate ordered steps of a procedure. 1 2 3

The “drag-and-drop” method is only one of several methods to bring proxy points into the station’s database.

NOTE ICON: Where needed when describing different concepts, a note icon will provide additional information.

MODEL COMPARISON / FEATURESTOPIC 1

EC-SMART-VUEEC-SMART-VUE

BACK TO MENU

Model Comparison Chart

Icon Placement

Eco-Vue Icons

Smart-Vue Uses

Model Comparison Chart

Icon Placement

Eco-Vue Icons

Smart-Vue Uses

EC-Smart-Vue 4-in-1 Series

7BACK TO MENU

EC-Smart-Vue – Model Comparison

8

EC-Smart-Vue interfaces with the ECY/ECB/ECL series controller and is a 4-in-1 sensor (CHM model):

Temperature Relative humidity Motion CO2

It has a customizable LCD readout and graphically indicates energy consumption using the ECO-Vue leaf pattern.

Temperature

Relative Humidity H)

Motion (M)

Carbon dioxide (C)

Scenes: rolling, quick edit, menu

ECO-Vue leaf: energy consumption

Advanced menu options

EC-Smart-Vue – Icon Placement

9

EC-Smart-Vue LCD screen with ICONS

Configurable through EC-gfxProgram

UnitsUnits

OccupancyOccupancyFanFan

ClockClock

BACK TO MENU

EC-Smart-Vue – Icon Placement

10BACK TO MENU

EC-Smart-Vue – ECO-Vue Icon

11BACK TO MENU

EC-Smart-Vue Uses

12

MAC Address

Baud Rate

Flow Balance

VAV Box Configuration

Device ID

Subnet

Configurable through EC-gfxProgram > >

Commissioning Tool > > > >

Scenes: rolling, quick edit, menu

Advanced menu optionsAdvanced menu options

Customizable Icons

BACK TO MENU

EC-Smart-Vue: A Commissioning Tool

13

EC-Smart-Vue can also be used as a commissioning tool to:

Set the MAC Address, Baud Rate, Subnet or Device ID for BACnet ECB-series and ECB-VAV-series controllers

Flow balance VAV controllers

Configure VAV box configurations for VAV controller pre-loaded applications

MAC Address

Baud Rate

Flow Balance

VAV Box Configuration

Device ID

Subnet

BACK TO MENU

EC-Smart-Vue: A Commissioning Tool

EC-Smart-Vue as a Commissioning tool for all ECB controllers. Once connected to an ECB controller, the EC-Smart-Vue can be used to perform commissioning tasks:

14

Setting ECB controller’s MAC address: Set all DIP switch to 0 (apply to ECB-203 and over)

Use the Gen Conf menu to access the MAC ADDRESS

Setting ECB controller’s Baud rate: The default Baud rate for all ECB controllers is set to AUTO

(recommended)

The Bus Master (EC-BOS) should be the reference Baud rate (if present)

Otherwise, set the Baud rate on one controller on the bus by using the Gen Conf menu to access the BAUD RATE

Accessing the BACnet MS/TP LAN: The EC-Smart-Vue Sub-Network cable also brings the

BACnet MS/TP Network to the sensor for installation and maintenance purposes

The LAN is made available at the communications jack (stereo jack)

BACK TO MENU

SMART-VUE SUBNETWORKTOPIC 2

EC-SMART-VUEEC-SMART-VUE

BACK TO MENU

Overview

Description

Subnet ID

Overview

Description

Subnet ID

Sub-Network Overview

16BACK TO MENU

Sub-Network Description

The Sub-Network on the ECL and ECB lines of controllers is used to communicate with communicating peripherals made by Distech Controls like:

– EC-Smart-Vue

– ECx I/O modules

17

The Sub-Network works with RS-485 transceivers, that makes the wiring and addressing methods very similar to the BACnet MS/TP bus, but it is NOT part of the BACnet Network.

Sub-Network: Subnet ID

Setting the EC-Smart-Vue Subnet ID (Subnet MAC Address) The default Subnet ID for an EC-Smart-Vue is set to 1

Keep default Subnet ID of 1 if there is only one EC-Smart-Vue connected to the controller

If you have more then 1 EC-Smart-Vue on the Sub-Network, change the Subnet ID on each one to a unique number as follows:

18

1. Connect the EC-Smart-Vue to the controller. Wait for the Bell icon and the number 1 to flash on the display

2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display

3. Use the down button to set the number to 9995 (this is the default password)

4. Use the Menu button to select SUBNET ID. The current controller’s Subnet ID is shown

5. Use the up and down buttons to set the controller’s Subnet ID

6. Press the Menu button once to validate and save your selection

7. Press and hold the Menu button for 5 seconds to exit the configuration menu.

BACK TO MENU

SCENES, VALUES & CONDITIONSTOPIC 3

EC-SMART-VUEEC-SMART-VUE

BACK TO MENU

Main Rolling Scenes

Quick Edit Scenes

Menu Scenes

Local & Global Values

Conditions

Enumerations

Icons

Main Rolling Scenes

Quick Edit Scenes

Menu Scenes

Local & Global Values

Conditions

Enumerations

Icons

EC-Smart-Vue: Main Rolling Scenes

20

Standard Scenes Custom Scenes

96 Scenes are available.

Display Values and Information

Some Standard Scenes are already configured

Display Space Temp

Display Relative Humidity

BACK TO MENU

EC-Smart-Vue: Quick Edit/Menu Scenes

21

Quick Edit Scenes: Scene that is displayed when an

arrow key is pressed

Used to Edit a value (typically the Temperature setpoint)

Menu Scenes: Scenes that are displayed when

the menu button is pressed

Advance to the next Scene each time the menu button is pressed

Used to Edit or View many other values

BACK TO MENU

EC-Smart-Vue: Advanced Menu Scenes

22

Scenes that are displayed when the menu button is held for 5 sec

Must provide the default password of 9995.

The first one is the password Scene

Some Standard Scenes already exist:

Edit Subnet ID

Edit MAC Address

Edit Baud Rate

Display Hardware Info

Calibrate Space Temp

Adjust Contrast

BACK TO MENU

EC-Smart-Vue: Values

23

Used to Store data available to and from the EC-Smart-Vue:

30 Local Values

Number and name of Values identical across all the EC-Smart-Vues on the controller

Values within the Local Values are unique for each EC-Smart-Vue

70 Global Values

Names and values are shared across all the EC-Smart-Vues

BACK TO MENU

EC-Smart-Vue: Conditions

24

Used to Hide/Show Scenes

15 Conditions

Number and name of registers identical across all the EC-Smart-Vues on the controller

Values within the conditions are unique for each EC-Smart-Vue

BACK TO MENU

EC-Smart-Vue: Enumerations

25

Used to select options in the Select Enumeration scenes

User can select the numerical Start Value of the enumeration

Total of 127 Strings available for enumerations

Each string up to 16 characters

Texts displayed in the text section of a scene are using Strings out of the 127

Optimization done if the same text is used more than once

BACK TO MENU

EC-Smart-Vue: Icons Selection

26

Used to display any Icon in any Scene

Set by an Icon Value selection

Unit Icons are also use for conversions

BACK TO MENU

EC-Smart-Vue Icons Selection

27BACK TO MENU

EC-Smart-Vue: Communication

28

Local ValuesSmartVue1

ConditionsSmartVue1

Local ValuesSmartVue2

ConditionsSmartVue2

Local ValuesSmartVue3

ConditionsSmartVue3

Global Values

2-way communication

Local and Global Values

Local Conditions

Local Values

Occupied Cool Setpoints

Occupied Heat Setpoints

Global Values

Minimum Airflow Setpoint

VAV application code

BACK TO MENU

EC-Smart-Vue: Conclusion

Fully customizable

Templates are available within the gfxApplications code library

Integrators should always start from a template when configuring the EC-Smart-Vue

96 Scenes are available for display and edit

All Scenes are identical for each EC-Smart-Vue connected to the same controllers.

Conditions and local/global values are used to display different information on different EC-Smart-Vues (e.g., remove a Scene for one or more EC-Smart-Vues)

Integrators should never try to modify the preloaded ECB Series code. If another sequence of operation is needed, start from the gfxApplications library.

29BACK TO MENU

LABWORKTOPIC 4

EC-SMART-VUEEC-SMART-VUE

BACK TO MENU

Main Rolling Scenes

Quick Edit Scenes

Menu Scenes

Main Rolling Scenes

Quick Edit Scenes

Menu Scenes

31

Lab 15: Configuring the EC-Smart-Vue

LAB 15 – 80 minConfiguring the EC-Smart-Vue

OVERVIEW

LAB 15 – 80 minConfiguring the EC-Smart-Vue

OVERVIEW

BACK TO MENU

80:00

Lab 15: Configuring the EC-Smart-Vue

LAB 15A: 5 minConnect the EC-Smart-Vue and Add a Com Sensor blockConnect the EC-Smart-Vue to the ECL-650 via CAT-5.

Replace the Space Temp HWI block with a Com Sensor block.

LAB 15A: 5 minConnect the EC-Smart-Vue and Add a Com Sensor blockConnect the EC-Smart-Vue to the ECL-650 via CAT-5.

Replace the Space Temp HWI block with a Com Sensor block.

LAB 15B: 5 minConfigure the Com Sensor BlockConfigure the Com Sensor block for the model type, time format, and backlight.

LAB 15B: 5 minConfigure the Com Sensor BlockConfigure the Com Sensor block for the model type, time format, and backlight.

LAB 15C: 5 minValidate/Modify a Main Rolling SceneAdd text to an existing main rolling scene and validate that it displays on the LCD screen.

LAB 15C: 5 minValidate/Modify a Main Rolling SceneAdd text to an existing main rolling scene and validate that it displays on the LCD screen.

BACK TO MENU

Lab 15: Configuring the EC-Smart-Vue

LAB 15D: 10 minAdd a stock Main Rolling SceneRelative Humidity, CO2

LAB 15D: 10 minAdd a stock Main Rolling SceneRelative Humidity, CO2

LAB 15E: 10 minAdd a custom Main Rolling SceneOutdoor Air Temp – add as a Global Value – so it can be displayed on multiple EC-Smart-Vue controllers on a network

LAB 15E: 10 minAdd a custom Main Rolling SceneOutdoor Air Temp – add as a Global Value – so it can be displayed on multiple EC-Smart-Vue controllers on a network

LAB 15F: 10 minAdd a Quick Edit SceneSetpoint – add as a Local Value – specific to one EC-Smart-Vue.

LAB 15F: 10 minAdd a Quick Edit SceneSetpoint – add as a Local Value – specific to one EC-Smart-Vue.

BACK TO MENU

Lab 15: Configuring the EC-Smart-Vue

LAB 15G: 20 minAdd a Menu SceneOccupancy – as an Icon Enumeration – person inside/outside of a house. Add as a Local value.

Create additional logic to generate a pulse into the Min On Time block.

LAB 15G: 20 minAdd a Menu SceneOccupancy – as an Icon Enumeration – person inside/outside of a house. Add as a Local value.

Create additional logic to generate a pulse into the Min On Time block.

LAB 15H: 15 minOptional: Add a Menu Scene

Fan Speed – as an Icon Enumeration – using Fan icon.

LAB 15H: 15 minOptional: Add a Menu Scene

Fan Speed – as an Icon Enumeration – using Fan icon.

BACK TO MENU

Lab 15: Configuring the EC-Smart-Vue

LAB 15A: 5 minConnect the EC-Smart-Vue and Add a Com Sensor blockConnect the EC-Smart-Vue to the ECL-650 via CAT-5. Replace the

Space Temp Hardware Input block with a Com Sensor block.

LAB 15A: 5 minConnect the EC-Smart-Vue and Add a Com Sensor blockConnect the EC-Smart-Vue to the ECL-650 via CAT-5. Replace the

Space Temp Hardware Input block with a Com Sensor block.

BACK TO MENU BACK TO SECTIONS

Lab 15: Configuring the EC-Smart-Vue

BACK TO MENU BACK TO SECTIONS

LAB 15B: 5 minConfigure the Com Sensor BlockConfigure the Com Sensor block for the model type, time format, and

backlight.

LAB 15B: 5 minConfigure the Com Sensor BlockConfigure the Com Sensor block for the model type, time format, and

backlight.

Lab 15: Configuring the EC-Smart-Vue

BACK TO MENU BACK TO SECTIONS

LAB 15C: 5 minValidate/Modify a Main Rolling SceneAdd text to an existing main rolling scene and validate that it displays

on the LCD screen.

LAB 15C: 5 minValidate/Modify a Main Rolling SceneAdd text to an existing main rolling scene and validate that it displays

on the LCD screen.

Lab 15: Configuring the EC-Smart-Vue

BACK TO MENU BACK TO SECTIONS

LAB 15D: 10 minAdd a stock Main Rolling SceneRelative Humidity, CO2

LAB 15D: 10 minAdd a stock Main Rolling SceneRelative Humidity, CO2

Lab 15: Configuring the EC-Smart-Vue

BACK TO MENU BACK TO SECTIONS

LAB 15E: 10 minAdd a custom Main Rolling SceneOutdoor Air Temp – add as a Global Value – so it can be displayed on multiple EC-Smart-Vue controllers on a network

LAB 15E: 10 minAdd a custom Main Rolling SceneOutdoor Air Temp – add as a Global Value – so it can be displayed on multiple EC-Smart-Vue controllers on a network

Lab 15: Configuring the EC-Smart-Vue

LAB 15F: 10 minAdd a Quick Edit SceneSetpoint – add as a Local Value – specific to one EC-Smart-Vue.

LAB 15F: 10 minAdd a Quick Edit SceneSetpoint – add as a Local Value – specific to one EC-Smart-Vue.

BACK TO MENU BACK TO SECTIONS

LAB 15G: 20 minAdd a Menu SceneOccupancy – as an Icon Enumeration – person inside/outside of a house. Add as a Local value. Create additional logic to generate a pulse into the Min On Time block.

LAB 15G: 20 minAdd a Menu SceneOccupancy – as an Icon Enumeration – person inside/outside of a house. Add as a Local value. Create additional logic to generate a pulse into the Min On Time block.

Lab 15: Configuring the EC-Smart-Vue

BACK TO MENU BACK TO SECTIONS

15G – Add a Menu Scene

LAB 15G: 20 minAdd a Menu SceneOccupancy – as an Icon Enumeration – person inside/outside of a house. Add as a Local value. Create additional logic to generate a pulse into the Min On Time block.

LAB 15G: 20 minAdd a Menu SceneOccupancy – as an Icon Enumeration – person inside/outside of a house. Add as a Local value. Create additional logic to generate a pulse into the Min On Time block.

BACK TO MENU BACK TO SECTIONS

Smart-Vue: Conclusion

Fully customizable

Templates are available within the gfxApplications code library

Integrators should always start from a template when configuring the EC-Smart-Vue

96 Scenes are available for display and edit

All Scenes are identical for each EC-Smart-Vue connected to the same controllers.

Conditions and local/global values are used to display different information on different EC-Smart-Vues (e.g., remove a Scene for one or more EC-Smart-Vues)

Integrators should never try to modify the preloaded ECB Series code. If another sequence of operation is needed, start from the gfxApplications library.

43BACK TO MENU

BACK TO EC-SMART-VUE

MENU(CLICK HERE)