July 2016 Model JP3 Across the Line Start Jockey Pump Controller Technical Data Submittal Document Contents: • Data Sheets • Dimensional Data • Wiring Schematics • Field Connections Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package. Project: Customer: Engineer: Pump Manufacturer:

Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

Embed Size (px)

Citation preview

Page 1: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

July 2016

Model JP3Across the Line Start

Jockey Pump Controller

Technical Data Submittal Document

Contents:• Data Sheets • Dimensional Data• Wiring Schematics• Field Connections

Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.

Project: Customer: Engineer: Pump Manufacturer:

Page 2: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

Technical Data Model JP3 Jockey Pump Controller

July 2016 2

Listing

Underwriters Laboratory (UL) UL508A - Industrial Pump ControllersCSA CSA C22.2 No. 14 Industrial Control EquipmentNew York City Accepted for use in the City of New York by the Department of BuildingsSeismic Certification See page 4 for detailsOptional□ CE Mark Various EN, IEC & CEE directives and standards

Enclosure

Protection Rating□ Standard: NEMA 2 (IP31)Optional□ NEMA 12□ NEMA 3□ NEMA 3R□ NEMA 4

Accessories• Wall mounting lugs ( x4)

□ NEMA 4X-304 sst painted□ NEMA 4X-304 sst brushed finish□ NEMA 4X-316 sst painted□ NEMA 4X-316 sst brushed finish

Paint Specifications• Red RAL3002• Powder coating• Glossy textured finish

Starting Method: Full Voltage Across the line (Direct on line)Typical Voltage Applied at Start: 100%Inrush Current: 6 x normal load currentStarting Torque: 100%Motor Type: Across the line (Direct on line)No. of Contactors: 1 at 100% of horsepowerMin. ampacity of motor conductors: 3 at 125% x 100% of Full load Current (FLC)

JP1

JP2

M

M

M

JP3

Page 3: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

Technical Data Model JP3 Jockey Pump Controller

July 2016 3

Fuseless Motor Starter

• Main disconnect – rotary type - door interlocked• Thermo-magnetic motor protector• Contactor

Control Circuit • 24V.AC

iPD+ Operator Interface

• Solid state controls• All adjustments on door front• Navigation pushbuttons

Pressure Sensing• Pressure transducer for fresh water application stainless steel construction• Rated for 0-600psi working pressure• Pressure sensing line connection ¼” Male NPT

Visual Indications

• Manual motor start/run LED• Automatic motor start/run LED• Motor overload• Pressure reading

• Start pressure• Stop pressure• System pressure

• System pressure diagnostic LED’s• Green: system pressure at or above stop pressure• Yellow: system pressure between start and stop pressure• Red: system pressure at or below start pressure

• AUTO mode• OFF mode

Timers• Minimum run timer (off delay)• Delay start timer (on delay)• Visual countdown

Counters • Pump start counter• Elapsed timer meter (hours / non-resettable)

Operators • OFF-AUTO pushbutton• Start and Stop pushbutton

Operation

Automatic Start Start on pressure drop

Manual Start Start pushbutton

Stopping Stop pushbutton

Timers Field adjustable & visual countdown

• Minimum run timer (off delay)• Delay start timer (on delay)

Page 4: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

Technical Data Model JP3 Jockey Pump Controller

July 2016 4

0.1

1.0

10.0

0.1 1.0 10.0

Spe

ctra

l Res

pons

e A

ccel

erat

ion

(g)

Frequency, f (Hz)

RRS for Nonstructural Components Testing

Horiz. Level 1 Vert. Level 1

Seismic Certification

Seismic Certification Company

TRU Compliance, LLCA Tobalski Watkins Affiliate TWEI Project No.: 15014

Mounting details Rigid wall mounting

Seismic Information

Building Code

Test Criteria

Seismic Parameters SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

IBC 2015, CBC 2016

ICC-ES

AC156

ASCE 7-10 Chapter 13

2.0 1.0 1.5 3.20 2.40 1.33 0.53

3.2 0.0 1.5 3.20 1.28 2.13 0.85

Notes:• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016. • OSHPD Special Seismic Certification Preapproval (OSP)

Page 5: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

Technical Data Model JP3 Jockey Pump Controller

July 2016 5

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

A4 Elapsed time meter (time totalizer)

A5 Motor run alarm contact

A6 Loss of power alarm contact

A7 Overload or short circuit alarm contact

D12 CE Mark c/w externally mounted wetted parts

D13A Externally mounted wetted parts

D14 Export packing for 1 controller

D18 Audible alarm

D19 Anti-condensation heater and thermostat

D20 Anti-condensation heater and humidistat

D21 Tropicalization

D22 Phase reversal / failure pilot light and alarm contact

D23 Controller power healthy pilot light and alarm contact

D24 Pump failure via current sensing relay with pilot light and dry alarm contact

D25 Low zone pump control function

D26 Mid zone pump control function

D27 High zone pump control function

D28 Selector switch in auto alarm contacts

D29 Selector switch in off alarm contacts

D30 Motor heater circuit

D32

Service entrance rated - 100kA short circuit withstand rating:• 120V/1ph (0.5hp max.)• 240V/1ph (1hp max.)• 200V-208V - 60hz (2hp max.)• 220V-240V - 60hz (3hp max.)• 380V-416V - 50hz - 60hz (5hp max.)• 440V-480V - 60hz (5hp max.)

D33

Service entrance rated - 65kA short circuit withstand rating:• 120V/1ph (0.5hp max.)• 240V/1ph (1hp max.)• 200V-208V - 60hz (3hp-15hp max.)• 220V-240V - 60hz (515hp max.)• 380V-416V - 50hz - 60hz (7.5hp - 40hp max.)• 440V-480V - 60hz (7.5hp-40hp max.)

D34 Service entrance rated - 42kA short circuit withstand rating:• 600V - 60hz (7.5hp max.)

L01 Other language and English (bilingual)

L02 French

L03 Spanish

L04 German

L05 Italian

L06 Polish

L07 Romanian

L08 Hungarian

L09 Slovak

L10 Croatian

L11 Czech

L12 Portuguese

L13 Dutch

L14 Russian

L15 Turkish

L16 Swedish

L17 Bulgarian

L18 Thai

L19 Indonesian

L20 Slovenian

L21 Danish

L22 Greek

L23 Arabic

L24 Hebrew

L25 Chinese

Page 6: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

Technical Data Model JP3 Jockey Pump Controller

July 2016 6

iPD+ Operator Interface

1 - Power on LED2 - System status LED3 - Digital display4 - Hand start LED5 - START pushbutton

6 - STOP pushbutton 7 - Auto start LED8 - Navigation keypad9 - ON - OFF pushbutton

AUTOHAND

9

5

6

3 2

1

8

74

Page 7: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

JP3-DI500/EModel

Dimensions

Projection

Standard Internal Layout

Dimensions*Maximum Motor Horsepower

Main Disconnect

- All Dimensions are in Inches [Millimeters]- Use Watertight Conduit and Connector Only.- Protect Equipment Against Drilling Chips.

Notes:

Sensing Line Connection

- Door Swing Equal to Door Width

Across the Line / 3 Phase

Built to the latest edition of the UL 508A & CSA C22.2 No.14 standard

Jockey Pump Controller

- Standard NEMA: NEMA 2- Standard Paint: Textured Red RAL 3002. Manufacturer reserves the right to modify this drawing without notice.

Contact manufacturer for "As Built" drawing.*Dimensions may change depending on option required. Consult Factory for exactdimensions.

Drawing for information only.

:JP3

NYCDpt of Building

Approved

Drawing No.

DD/MM/YYDESCRIPTION

PER QUOTE DRAWING No.

REV.

RatingLabel

DS

ON

OFF

DF C

2-¼" [58]

4-½" [115]

EG

1/4 " M.NPT

A

B

Ø38 "[9] x4

HAND AUTO

G

Y

R

GG

ENCLOSED INDUSTRIAL CONTROL PANEL

Laboratories Inc.

No. AC-XXX

LISTED

Underwriters

CE

PT1

Drawing No.

FU1 DS

C1 OL1

PT1

XTR

1

DANGER

A X B X C

16"X16"X7-½" 16-½"X16-½" 14"X16-¾"

D X E F X G200-208V10HP20HP

220-240V 380-416V15HP40HP

440-480V20HP60HP

575-600V25HP60HP

10HP30HP

10"X12"X6-½" 10-⅝"X12-⅝" 8"X12-¾"

Enclosure Dimensions Door Dimensions Anchor Dimensions

3 4 5 6 72

G

H

0 1 8

B

C

D

E

F

I

A

3 4 5 6 720 1 8

G

H

I

A

B

C

D

E

F

2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

4 Terminals and dimensions tables updated. Layout modified. 09/10/15 4 Terminals and dimensions tables updated. Layout modified. 09/10/155 Modified Tornatech & Seismic Logo 14/04/16 5 Modified Tornatech & Seismic Logo 14/04/166 Modified J19 Outputs ID 10/06/16 6 Modified J19 Outputs ID 10/06/16

Page 8: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

ModelWiring schematic JP3-WS500/E

Bla

ck

Pressure Sensor

Whi

te

Gre

en

Red

Type 0-50mV

Across the Line / 3 Phase

Built to the latest edition of the UL 508A & CSA C22.2 No.14 standard

Jockey Pump Controller

Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.

- Drawing for information only.

T1

OL1

C1

T2 T3

FU1

X2

X1

XTR1

H1

H2 3

1

L1 L3L2

DS

G

G

3 4 5 6 72

G

H

0 1 8

B

C

D

E

F

I

A

3 4 5 6 720 1 8

G

H

I

A

B

C

D

E

F

2016Copyright © Tornatech Inc.

:JP3

NYCDpt of Building

Approved

Drawing No.

DD/MM/YYDESCRIPTION

PER QUOTE DRAWING No.

REV.

HAND AUTO

G

Y

R

GG

PsI

n-P

sOut

-P

sOut

+P

sIn+

A2

RESET

F5

"IPD+"

J2

J5

J8

J3 J1

J9

OUTPUT ON

RGWB 5 S

A1

G

22 8

24Vac24Vac

J19

3 1

J21IN2

IN1

PT1

C1A1 A2

P1

OL1734 33

9

All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

4 Terminals and dimensions tables updated. Layout modified. 09/10/15 4 Terminals and dimensions tables updated. Layout modified. 09/10/15 4 Terminals and dimensions tables updated. Layout modified. 09/10/155 Modified Tornatech & Seismic Logo 14/04/16 5 Modified Tornatech & Seismic Logo 14/04/16 5 Modified Tornatech & Seismic Logo 14/04/166 Modified J19 Outputs ID 10/06/16 6 Modified J19 Outputs ID 10/06/16 6 Modified J19 Outputs ID 10/06/16

Page 9: Technical Data Submittal Document - Tornatech Inc. · PDF fileJockey Pump Controller Technical Data Submittal Document ... Model JP3 Jockey Pump Controller July 2 ... System status

JP3-TD500/EModel

Line and Motor Terminal Size:JP3

NYCDpt of Building

Approved

Drawing No.

DD/MM/YYDESCRIPTION

PER QUOTE DRAWING No.

REV.Across the Line / 3 Phase

Built to the latest edition of the UL 508A & CSA C22.2 No.14 standard

Jockey Pump ControllerDrawing No.

Line Terminals (L1,L2,L3,GND)Maximum Motor Horsepower

Wire Size Copper Only Torque

Motor Terminals (T1,T2,T3,GND)

Wire Size Ground Copper Only

Bonding GroundIncoming Power

Power Connections and Motor Connections

3 Phase

200-208V10HP #14 AWG - #6 AWG 2 Nm20HP #12 AWG - #1 AWG 6 Nm

200-208V5HP #14 AWG - #10 AWG 1.8 Nm10HP #14 AWG - #6 AWG 2.5 Nm15HP #10 AWG - #3 AWG 5 Nm

220-240V7.5HP

380-416V10HP15HP30HP

440-480V15HP20HP50HP

575-600V20HP25HP50HP

#14 AWG - #2 AWG#6 AWG - #2 AWG

#14 AWG - #2 AWG#12 AWG - #2 AWG#12 AWG - #2 AWG

220-240V10HP30HP

380-416V20HP40HP

440-480V20HP60HP

575-600V25HP60HP

#10 AWG - #2 AWG #12 AWG - #2 AWG11.3 Nm20HP 40HP 60HP 60HP

10HP20HP30HP

Maximum Motor HorsepowerWire Size Copper Only Torque Wire Size Ground Copper Only

M

T1 T2 T3

C1

L2L1DS

L3

3 4 5 6 72

G

H

0 1 8

B

C

D

E

F

I

A

3 4 5 6 720 1 8

G

H

I

A

B

C

D

E

F

2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

4 Terminals and dimensions tables updated. Layout modified. 09/10/155 Modified Tornatech & Seismic Logo 14/04/166 Modified J19 Outputs ID 10/06/16