Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
PackagedChillerReport:DoNotEdit;
Unit Information
Tag Name: EFR-1
Model Number: 30RB090
Condenser Type: Air Cooled Compressor Type: Scroll
Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 2 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Capacity Control Steps: 4 Minimum Capacity: 22.0 % Shipping Weight: 6590 lb Operating Weight: 6855 lb Unit Length: 142 in Unit Width: 89 in Unit Height: 90 in Minimum Outdoor Operating Temp: 32 °F Chiller Pressure Drop: 11.6 ft wg
Performance Information
Cooling Capacity: 90.8 Tons Total Compressor Power: 80.7 kW Total Fan Motor Power: 13.8 kW Pump Power: 8.79 kW Total Unit Power (without pump): 94.5 kW Total Unit Power (with pump): 103.3 kW Efficiency (without pump): 11.52 EER Evaporator Information Fluid Type: Fresh Water Fouling Factor: 0.00010 (hr-sqft-F)/BTU Leaving Temperature: 44.0 °F Entering Temperature: 54.0 °F Fluid Flow: 217.1 gpm Condenser Information
Altitude: 3116 ft Number of Fans: 6
Total Condenser Fan Air Flow: 74400 CFM Entering Air Temperature: 86.0 °F
Accessories and Installed Options
Al Fin/Cu Tube, Pre-Coat Dual Pump, 15 HP w/ VFD
Single Point Coil Trim Panels Electrical Information Unit Voltage: 208/230-3-60 V-Ph-Hz Connection Type: Single Point Minimum Voltage: 187 Volts Maximum Voltage: 253 Volts
Electrical Electrical Amps Circuit 1 Circuit 2
MCA 470.3 ---
MOCP 500.0 ---
ICF 925.7 ---
Rec Fuse Size 500.0 ---
Packaged Chiller Builder NACO 3.49m Page 1 of 16
8/20/2019 Submittal Chillers
2/16
Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Integrated Pump Information Dynamic Head At Pump: 131.0 ft Dynamic Head External To Chiller: 119.5 ft
Packaged Chiller Builder NACO 3.49m Page 2 of 16
8/20/2019 Submittal Chillers
3/16
Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Integrated Part Load Value (AHRI) IPLV: 13.68 EER
Unit Performance
Percent of Full Load Capacity, % 100 75 50 25
Percent of Full Load Power, % 100.0 61.3 35.9 16.4
Unloading Sequence B B B B
Cooling Capacity, Tons 86.3 64.7 43.2 21.6
Total Unit Power, kW 101.1 62.0 36.3 16.5
Efficiency, EER 10.25 12.54 14.28 15.67Evaporator Data
Fluid Entering Temperature, °F 54.0 51.5 49.0 46.5
Fluid Leaving Temperature, °F 44.0 44.0 44.0 44.0
Fluid Flow Rate, gpm 207.2 207.2 207.2 207.2
Fouling Factor, (hr-sqft-F)/BTU 0.0001 0.0001 0.0001 0.0001Condenser Data
Entering Air Temperature, °F 95.0 80.0 65.0 55.0
All performance efficiency data are without pump.Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle CertificationProgram, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRIDirectory at www.ahridirectory.org.
Packaged Chiller Builder NACO 3.49m Page 3 of 16
8/20/2019 Submittal Chillers
4/16
Detailed Performance Summary For EFR-1Project: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Unit Parameters Tag Name: EFR-1
Model Number: 30RB090
Condenser Type: Air Cooled
Compressor Type: Scroll
Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 2
Manufacturing Source: Charlotte, NC USA
Refrigerant: R410A
Shipping Weight: 6590 lb Operating Weight: 6855 lb Unit Length: 142 in Unit Width: 89 in Unit Height: 90 in
1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground (See Note 3)
Accessories and Installed Options Al Fin/Cu Tube, Pre-Coat Dual Pump, 15 HP w/ VFD
Single Point Coil Trim Panels
Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 37 68 80 87 93 97 93 89 80 100
75% Load 36 72 80 87 93 97 92 89 80 100
50% Load 37 68 80 87 93 97 92 88 79 100
25% Load 31 64 75 81 87 90 87 83 72 94
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input fordimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall100% Load 9 40 52 59 65 69 65 61 52 72
75% Load 8 44 52 59 65 69 64 61 51 72
50% Load 9 40 52 58 64 69 64 60 51 72
25% Load 3 36 47 53 58 62 59 54 44 65
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft 2 - Horizontal Distance From Chiller to Receiver = 30.0 ft 3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49m Page 4 of 16
8/20/2019 Submittal Chillers
5/16
Detailed Performance Summary For EFR-1 OP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
PackagedChillerReport:DoNotEdit;
Unit Information
Tag Name: EFR-1 OP MCHX
Model Number: 30RB090
Condenser Type: Air Cooled Compressor Type: Scroll
Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 2 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Capacity Control Steps: 4 Minimum Capacity: 22.0 % Shipping Weight: 6107 lb Operating Weight: 6372 lb Unit Length: 142 in Unit Width: 89 in Unit Height: 90 in Minimum Outdoor Operating Temp: 32 °F Chiller Pressure Drop: 11.6 ft wg
Performance Information
Cooling Capacity: 91.1 Tons Total Compressor Power: 80.2 kW Total Fan Motor Power: 13.8 kW Pump Power: 8.80 kW Total Unit Power (without pump): 94.1 kW Total Unit Power (with pump): 102.9 kW Efficiency (without pump): 11.61 EER Evaporator Information Fluid Type: Fresh Water Fouling Factor: 0.00010 (hr-sqft-F)/BTU Leaving Temperature: 44.0 °F Entering Temperature: 54.0 °F Fluid Flow: 217.8 gpm Condenser Information
Altitude: 3116 ft Number of Fans: 6
Total Condenser Fan Air Flow: 74400 CFM Entering Air Temperature: 86.0 °F
Accessories and Installed Options
Micro Channel Dual Pump, 15 HP w/ VFD
Single Point Coil Trim Panels Electrical Information Unit Voltage: 208/230-3-60 V-Ph-Hz Connection Type: Single Point Minimum Voltage: 187 Volts Maximum Voltage: 253 Volts
Electrical Electrical Amps Circuit 1 Circuit 2
MCA 470.3 ---
MOCP 500.0 ---
ICF 925.7 ---
Rec Fuse Size 500.0 ---
Packaged Chiller Builder NACO 3.49m Page 5 of
8/20/2019 Submittal Chillers
6/16
Detailed Performance Summary For EFR-1 OP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Integrated Pump Information Dynamic Head At Pump: 131.0 ft Dynamic Head External To Chiller: 119.3 ft
Packaged Chiller Builder NACO 3.49m Page 6 of
8/20/2019 Submittal Chillers
7/16
8/20/2019 Submittal Chillers
8/16
Detailed Performance Summary For EFR-1 OP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Unit Parameters Tag Name: EFR-1 OP MCHX
Model Number: 30RB090
Condenser Type: Air Cooled
Compressor Type: Scroll
Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 2
Manufacturing Source: Charlotte, NC USA
Refrigerant: R410A
Shipping Weight: 6107 lb Operating Weight: 6372 lb Unit Length: 142 in Unit Width: 89 in Unit Height: 90 in
1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground (See Note 3)
Accessories and Installed Options Micro Channel Dual Pump, 15 HP w/ VFD
Single Point Coil Trim Panels
Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 37 68 80 87 93 97 93 89 80 100
75% Load 36 72 80 87 93 97 92 89 80 100
50% Load 37 68 80 87 93 97 92 88 79 100
25% Load 31 64 75 81 87 90 87 83 72 94
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input fordimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall100% Load 9 40 52 59 65 69 65 61 52 72
75% Load 8 44 52 59 65 69 64 61 51 72
50% Load 9 40 52 58 64 69 64 60 51 72
25% Load 3 36 47 53 58 62 59 54 44 65
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft 2 - Horizontal Distance From Chiller to Receiver = 30.0 ft 3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49m Page 8 of
8/20/2019 Submittal Chillers
9/16
Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
PackagedChillerReport:DoNotEdit;
Unit Information
Tag Name: EFR-1 OP 30RAP
Model Number: 30RAP090
Condenser Type: Air Cooled Compressor Type: Scroll
Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Capacity Control Steps: 6 Minimum Capacity: 17.0 % Shipping Weight: 4663 lb Operating Weight: 4763 lb Unit Length: 151 in Unit Width: 88 in Unit Height: 78 in Minimum Outdoor Operating Temp: 32 °F Chiller Pressure Drop*: 26.5 ft wg
*Use Chiller Pressure Drop for sizing pumps. This valueincludes losses due to chiller piping, fittings, 40 mesh factorysupplied strainer and BPHX. Performance Information
Cooling Capacity: 87.8 Tons Total Compressor Power: 84.2 kW Total Fan Motor Power: 8.61 kW Pump Power: 8.71 kW Total Unit Power (without pump): 92.8 kW Total Unit Power (with pump): 101.5 kW Efficiency (without pump): 11.35 EER Evaporator Information Fluid Type: Fresh Water
Fouling Factor: 0.00010 (hr-sqft-F)/BTU Leaving Temperature: 44.0 °F Entering Temperature: 54.0 °F Fluid Flow: 209.9 gpm Evaporator Pressure Drop*: 12.2 ft wg *Refer to Chiller Pressure Drop for sizing pumps. Condenser Information
Altitude: 3116 ft Number of Fans: 6
Total Condenser Fan Air Flow: 61500 CFM Entering Air Temperature: 86.0 °F
Accessories and Installed Options
Al Fin/Cu Tube, Pre-Coat Value Sound
Dual Pump, 15 HP w/ VFD Single Point Electrical Information Unit Voltage: 208/230-3-60 V-Ph-Hz Connection Type: Single Point
Electrical Electrical Amps Circuit 1 Circuit 2
MCA 425.1 ---
MOCP 450.0 ---
ICF 695.3 ---
Rec Fuse Size 450.0 ---
Packaged Chiller Builder NACO 3.49m Page 9 of 16
8/20/2019 Submittal Chillers
10/16
Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Integrated Pump Information Dynamic Head At Pump: 132.0 ft Dynamic Head External To Chiller: 105.6 ft
Packaged Chiller Builder NACO 3.49m Page 10 of 16
8/20/2019 Submittal Chillers
11/16
Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Integrated Part Load Value (AHRI) IPLV: 15.07 EER
Unit Performance
Percent of Full Load Capacity, % 100 75 50 25
Percent of Full Load Power, % 100.0 54.4 32.8 13.8
Unloading Sequence A A A A
Cooling Capacity, Tons 84.0 63.0 42.0 21.0
Total Unit Power, kW 99.8 54.3 32.8 13.7
Efficiency, EER 10.09 13.91 15.38 18.34Evaporator Data
Fluid Entering Temperature, °F 54.0 51.5 49.0 46.5
Fluid Leaving Temperature, °F 44.0 44.0 44.0 44.0
Fluid Flow Rate, gpm 201.5 201.5 201.5 201.5
Fouling Factor, (hr-sqft-F)/BTU 0.0001 0.0001 0.0001 0.0001Condenser Data
Entering Air Temperature, °F 95.0 80.0 65.0 55.0
For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8
degrees higher.
All performance efficiency data are without pump.Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle CertificationProgram, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRIDirectory at www.ahridirectory.org.
Packaged Chiller Builder NACO 3.49m Page 11 of 16
8/20/2019 Submittal Chillers
12/16
Detailed Performance Summary For EFR-1 OP 30RAPProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Unit Parameters Tag Name: EFR-1 OP 30RAP
Model Number: 30RAP090
Condenser Type: Air Cooled
Compressor Type: Scroll
Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 1
Manufacturing Source: Charlotte, NC USA
Refrigerant: R410A
Shipping Weight: 4663 lb Operating Weight: 4763 lb Unit Length: 151 in Unit Width: 88 in Unit Height: 78 in
1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground (See Note 3)
Accessories and Installed Options Al Fin/Cu Tube, Pre-Coat Value Sound Dual Pump, 15 HP w/ VFD Single Point
Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 42 75 82 88 94 95 93 89 84 100
75% Load 42 75 82 88 94 95 92 89 84 100
50% Load 41 74 81 88 93 94 91 88 83 99
25% Load 40 73 80 87 92 93 90 87 82 98
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 14 47 54 60 66 67 64 61 56 72
75% Load 14 47 54 60 66 66 64 61 56 72
50% Load 13 46 53 59 65 66 63 60 55 71
25% Load 12 45 52 58 64 65 62 59 54 70
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft 2 - Horizontal Distance From Chiller to Receiver = 30.0 ft 3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49m Page 12 of 16
8/20/2019 Submittal Chillers
13/16
Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
PackagedChillerReport:DoNotEdit;
Unit Information
Tag Name: EFR-1 OP 30RAP MCHX
Model Number: 30RAP090
Condenser Type: Air Cooled Compressor Type: Scroll
Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 1 Manufacturing Source: Charlotte, NC USA Refrigerant: R410A Capacity Control Steps: 6 Minimum Capacity: 17.0 % Shipping Weight: 4310 lb Operating Weight: 4411 lb Unit Length: 151 in Unit Width: 88 in Unit Height: 78 in Minimum Outdoor Operating Temp: 32 °F Chiller Pressure Drop*: 26.6 ft wg
*Use Chiller Pressure Drop for sizing pumps. This valueincludes losses due to chiller piping, fittings, 40 mesh factorysupplied strainer and BPHX. Performance Information
Cooling Capacity: 88.1 Tons Total Compressor Power: 83.7 kW Total Fan Motor Power: 8.54 kW Pump Power: 8.72 kW Total Unit Power (without pump): 92.2 kW Total Unit Power (with pump): 101.0 kW Efficiency (without pump): 11.46 EER Evaporator Information Fluid Type: Fresh Water
Fouling Factor: 0.00010 (hr-sqft-F)/BTU Leaving Temperature: 44.0 °F Entering Temperature: 54.0 °F Fluid Flow: 210.6 gpm Evaporator Pressure Drop*: 12.3 ft wg *Refer to Chiller Pressure Drop for sizing pumps. Condenser Information
Altitude: 3116 ft Number of Fans: 6
Total Condenser Fan Air Flow: 61500 CFM Entering Air Temperature: 86.0 °F
Accessories and Installed Options
Micro Channel Value Sound
Dual Pump, 15 HP w/ VFD Single Point Electrical Information Unit Voltage: 208/230-3-60 V-Ph-Hz Connection Type: Single Point
Electrical Electrical Amps Circuit 1 Circuit 2
MCA 425.1 ---
MOCP 450.0 ---
ICF 695.3 ---
Rec Fuse Size 450.0 ---
Packaged Chiller Builder NACO 3.49m Page 13 of 16
8/20/2019 Submittal Chillers
14/16
Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Integrated Pump Information Dynamic Head At Pump: 131.9 ft Dynamic Head External To Chiller: 105.3 ft
Packaged Chiller Builder NACO 3.49m Page 14 of 16
8/20/2019 Submittal Chillers
15/16
Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Integrated Part Load Value (AHRI) IPLV: 15.14 EER
Unit Performance
Percent of Full Load Capacity, % 100 75 50 25
Percent of Full Load Power, % 100.0 54.5 32.9 13.8
Unloading Sequence A A A A
Cooling Capacity, Tons 84.2 63.1 42.1 21.0
Total Unit Power, kW 99.4 54.2 32.7 13.7
Efficiency, EER 10.17 13.99 15.45 18.40Evaporator Data
Fluid Entering Temperature, °F 54.0 51.5 49.0 46.5
Fluid Leaving Temperature, °F 44.0 44.0 44.0 44.0
Fluid Flow Rate, gpm 202.1 202.1 202.1 202.1
Fouling Factor, (hr-sqft-F)/BTU 0.0001 0.0001 0.0001 0.0001Condenser Data
Entering Air Temperature, °F 95.0 80.0 65.0 55.0
For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8
degrees higher.
All performance efficiency data are without pump. An uncoated Novation condenser coil was selected for this product. This is based on an installed location that must be analyzed and
guidance provided by applications engineering and a non-corrosive localized environment.Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle CertificationProgram, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRIDirectory at www.ahridirectory.org.
Packaged Chiller Builder NACO 3.49m Page 15 of 16
8/20/2019 Submittal Chillers
16/16
Detailed Performance Summary For EFR-1 OP 30RAP MCHXProject: HOTEL DANN BUCARAMANGA 01/07/2016Prepared By: 04:21PM
Unit Parameters Tag Name: EFR-1 OP 30RAP MCHX
Model Number: 30RAP090
Condenser Type: Air Cooled
Compressor Type: Scroll
Chiller Nameplate Voltage: 208/230-3-60 V-Ph-Hz Quantity: 1
Manufacturing Source: Charlotte, NC USA
Refrigerant: R410A
Shipping Weight: 4310 lb Operating Weight: 4411 lb Unit Length: 151 in Unit Width: 88 in Unit Height: 78 in
1 - Chiller Height Above Ground2 - Horizontal Distance From Chiller to Receiver 3 - Receiver Height Above Ground (See Note 3)
Accessories and Installed Options Micro Channel Value Sound Dual Pump, 15 HP w/ VFD Single Point
Acoustic InformationTable 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 42 75 82 88 94 95 93 89 84 100
75% Load 42 75 82 88 94 95 92 89 84 100
50% Load 41 74 81 88 93 94 91 88 83 99
25% Load 40 73 80 87 92 93 90 87 82 98
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 14 47 54 60 66 67 64 61 56 72
75% Load 14 47 54 60 66 66 64 61 56 72
50% Load 13 46 53 59 65 66 63 60 55 71
25% Load 12 45 52 58 64 65 62 59 54 70
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.(2) Chiller is assumed to be a point source on a reflecting plane.(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft 2 - Horizontal Distance From Chiller to Receiver = 30.0 ft 3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49m Page 16 of 16