SUBMITTAL TRANSMITTAL CONTRACTOR’S REVIEW STAMP A/E REVIEW STAMP SUBMITTAL DATA Project Dallas Park & Rec Dept Admin Offices Location 10031 E. Northwest Highway Dallas, TX 75238 General Contractor DENCO CONSTRUCTION SPECIALISTS Trade Concrete Items Submitted Concrete Mix Design Supplier Red-Mix Concrete Phone 817-980-4543 Substitutions and Deviations Remarks I CERTIFY THAT THE ABOVE ITEM DESCRIBED IN THE ATTACHED SUBMITTAL COMPLIES WITH THE CONTRACT DOCUMENTS EXCEPT AS NOTED ABOVE. Shawnee Hallmark 972-226-2609 ext. 108 6-18-18 NAME (TRADE) PHONE NO. DATE Review Comments: DENCO CONSTRUCTION SPECIALISTS SHOP DRAWING AND SUBMITTAL REVIEW JOB NO. DPA-030000 DATE 6-18-18 REVIEWER Shawnee Hallmark Corrections or comments made relative to submittals during this review do not relieve the subcontractor from compliance with the requirements of the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information given in the contract documents. The subcontractor is responsible for conforming and correlating all quantities and dimensions, selecting fabrication processes and techniques of construction, coordinating his work with that of other trades and performing his work in a safe and satisfactory manner. THIS REVIEW DOES NOT INDICATE NOR IMPLY ANY APPROVAL OF CHANGES TO TIME OR CHANGES IN COSTS

SUBMITTAL TRANSMITTAL

  • Upload
    others

  • View
    20

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SUBMITTAL TRANSMITTAL

SUBMITTAL TRANSMITTAL

CONTRACTOR’S REVIEW STAMP A/E REVIEW STAMP

SUBMITTAL DATA Project Dallas Park & Rec Dept Admin Offices Location 10031 E. Northwest Highway Dallas, TX 75238 General Contractor DENCO CONSTRUCTION SPECIALISTS Trade Concrete Items Submitted Concrete Mix Design Supplier Red-Mix Concrete Phone 817-980-4543 Substitutions and Deviations Remarks I CERTIFY THAT THE ABOVE ITEM DESCRIBED IN THE ATTACHED SUBMITTAL COMPLIES WITH THE CONTRACT DOCUMENTS EXCEPT AS NOTED ABOVE. Shawnee Hallmark 972-226-2609 ext. 108 6-18-18 NAME (TRADE) PHONE NO. DATE Review Comments:

DENCO CONSTRUCTION SPECIALISTS SHOP DRAWING AND SUBMITTAL REVIEW

JOB NO. DPA-030000

DATE 6-18-18

REVIEWER Shawnee Hallmark

Corrections or comments made relative to submittals during this review do not relieve the subcontractor from compliance with the requirements of the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information given in the contract documents. The subcontractor is responsible for conforming and correlating all quantities and dimensions, selecting fabrication processes and techniques of construction, coordinating his work with that of other trades and performing his work in a safe and satisfactory manner. THIS REVIEW DOES NOT INDICATE NOR IMPLY ANY APPROVAL

OF CHANGES TO TIME OR CHANGES IN COSTS

dbechtel
Stamp
dbechtel
Text Box
X
dbechtel
Text Box
DJB
dbechtel
Text Box
07/17/18
Page 2: SUBMITTAL TRANSMITTAL

T H E N E W R E S O U R C E F O R T H E C O N S T R U C T I O N I N D U S T R Y

Redi-Mix Concrete, L.LC a US Concrete Company The Technical Service Department 331 North Main St. Euless, TX 76039 Office: (817) 835-4100 [email protected] www.us-concrete.com

June 18, 2018 To: Denco Construction Project: Dallas Park & Rec Office Renovations RE: Submittal Provisions

Enclosed you will find the necessary submittal documents for the referenced project above for your review. Redi-Mix’s strength guarantee per ASTM C94 will not be effective unless the field sampling has been done per the latest revisions of ASTM C172 and ASTM C31 and the laboratory testing fully complies with ASTM C39 and ASTM C1077. Redi-Mix will also guarantee the strength performance of the mix designs submitted for a concrete temperature between 55°F and 95°F provided the design plastic properties are not exceeded and the concrete is placed within 90 minutes of batch time. This concrete temperature range shall not supersede any more restrictive temperature specification. All concrete should be placed and cured with the appropriate ACI guidelines and recommendations for hot and cold weather concreting. Redi-Mix cannot be responsible for non-conformance of strength if cylinders are not cured per ACI 301, section 1.6.3.2.d. Hot weather concreting practices will require the purchaser to order ice and/or chilled water to meet concrete temperature specifications. The purchaser shall be responsible for precautions taken against excessive wind, heat and low humidity per ACI 305 guidelines. The purchaser shall assume responsibility for any concrete defects related to the finishing process (cracking, scaling, dusting, delamination, discoloration, etc.), which is beyond Redi-Mix’s control. This includes proper preparation, compaction and wetting of subgrade as well as proper spacing and depth of joints and rebar. During periods of cold weather, all concrete surfaces should be protected from freezing for at least the first 24 hours after placement to allow the concrete to attain a compressive strength of 500 psi. Should the purchaser elect not to order temperature control measures, the purchaser shall then assume all liability for costs associated with rejected concrete due to non-compliant concrete temperature. According to ACI 304.2R Section 4.2.1 “Placing Concrete by Pumping Methods”, the inside diameter of the hose should be a minimum of 3 times the maximum angular aggregate size of the concrete. (ASTM C33 allows #57LS to have up to 5% retained on the 1” sieve). It is recommended to minimize or eliminate the free fall of concrete to avoid loss of air content. Depending on boom configurations, alterations to the mix design may be required. With regard to pumped concrete, the various boom configurations, length of hose, line reductions and free fall distance are beyond Redi-Mix’s control and we therefore cannot be responsible for loss of air content or any costs associated with either rejected fresh concrete or the removal and replacement of hardened concrete due to non-compliant air content resulting from this or from placing concrete outside of the slump range specified on the mix design. We thank you for allowing us to submit these documents for your review. Please copy Redi-Mix with the approved submittal. The approved submittal allows Redi-Mix to review any notes, comments or exceptions made by the engineer or owner relating to the specification. Failure to notify us prior to first placement shall constitute acceptance of the submitted mix designs and submittal provisions. Please order by mix number when scheduling concrete delivery. We request that Redi-Mix be added to the list of names receiving copies of testing laboratory information for this project. ASTM C94 entitles a manufacturer to receive copies of all test reports when strength of concrete is used as a basis for acceptance. This information is another tool for Redi-Mix to review and monitor the quality and performance of the concrete product delivered. In the event of limited material availability, substitution of a similar performing material may be required. All substituted materials will meet the appropriate ASTM requirements. In order to maintain the required mix volume, weights of individual materials may be varied to accommodate different material specific gravities. Material certifications for substituted materials are available upon request. The information within this submittal is confidential and the exclusive property of Redi-Mix. It shall not be disseminated to third parties without written permission from Redi-Mix Concrete.

Please contact Technical Services with any questions at (817) 835-4077.

Respectfully,

Daniel Jeray Technical Services Manager

Page 3: SUBMITTAL TRANSMITTAL

136 / 236

Ash Grove, MidlothianASTM C150 Type l/ll Cement

Fly Ash Direct, WelshASTM C618 Class C Fly Ash

ASTM C33 No. 57 LS

Redi-Mix ConcreteASTM C33 Fine Aggregate

Mix Number: 10G11524

.1 301

3 75

31850

30-7

30

BASF MasterPolyheed997/MasterPozzolith322ASTM C494 A & D NRWR

ASTM C94 Water

lb

lb

lb

oz/cwt

Specified Slump 4 Specified Air Percent: 4.5 +/- 1.5%+/- 1"

1.53

0.44

10.82

4.00

1515

1.08

Material Source QuantityVol (ft^3)

ASTM C260 Air Entrainment BASF MasterAir AE90/*Fritz SuperAir Plus oz/cwt

lb

gal

9.12

Total Volume: 27.00

0-4

Vulcan, North Troy

Plant No.:

Project: Dallas Park & Rec Office RenovationsUsage: Sidewalks

Wet Unit Weight: 147.8 lb/ft^3

Notes: Please make sure that [email protected] is on the list to receive break reports. Admixtures may be adjusted, depending on ambient conditions, at time of placement. *Air Entrainment may be adjusted using Fritz Super Air Plus

Design w/(c+p) ratio: 0.66

The use of an EF Technology mix design will reduce the amount of CO2 entering the atmosphere, thereby reducing potential global warming. "Your Project, Our World"

an EF Technology Mix DesignStrength: 2000Description: 4 SK 20% C-ASH NR/NA

psi @ 28 days

Saturated Surface Dry Weights Per Cubic Yard

Customer: Denco Construction

Date: 6/18/2018

Redi-Mix Concrete, L.P. A US-Concrete Company 331 N. Main St Euless, TX 76039 Technical Service: (817)-835-4187 Dispatch: (817) 835-4020 E-mail: [email protected] www.us-concrete.com

T H E N E W R E S O U R C E F O R T H E C O N S T R U C T I O N I N D U S T R Y

This mix has been designed to meet the requirements of this project based on the information sent to Redi-mix Concrete. It is the responsibility of the purchaser to determine whether this mix design meets project specifications and is appropriate for the anticipated environment conditions. The specified strength guarantee per ASTM C94 will not be effective unless field sampling has been done per ASTM C172 and ASTM C31 and the laboratory fully complies with ASTM C39 and ASTM C1077. In the event of limited material avaliability, substitution of a similar performing material may be required. All substituted materials will meet the appropriate ASTM requirements. In order to maintain the required mix volume, weights of individual materials may be varied to accommodate different material specific gravities. Material certifications for substituted materials are avaliable upon request.

All Redi-Mix Concrete mix designs are proprietary and confidential. The information contained in this submittal is only intended for parties associated with this project to validate the mix design materials, properties and its performance. Use of this submittal for other purposes without permission or consent from Redi-Mix Concrete is strictly prohibited.

dbechtel
Callout
NOT FOR STRUCTURAL USE
Page 4: SUBMITTAL TRANSMITTAL

1480

2953

4186

1990

3702

5137

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

6000

2.5 3 3.5 4 4.5 5 5.5

Com

pres

sive

Str

engt

h

Sacks

ACI 318 3 Point Curve20% C-Ash 57LS Air Entrained

Represents Mix# 10G11524

7-day

28-day

Linear (7-day)

Linear (28-day)

Linear (F'CR = 3000)

Page 5: SUBMITTAL TRANSMITTAL

136 / 236

Ash Grove, MidlothianASTM C150 Type l/ll Cement

Fly Ash Direct, WelshASTM C618 Class C Fly Ash

ASTM C33 No. 57 LS

Redi-Mix ConcreteASTM C33 Fine Aggregate

Mix Number: 10J11524

.1 376

3 94

31850

30-7

30

BASF MasterPolyheed997/MasterPozzolith322ASTM C494 A & D NRWR

ASTM C94 Water

lb

lb

lb

oz/cwt

Specified Slump 4 Specified Air Percent: 4.5 +/- 1.5%+/- 1"

1.91

0.55

10.82

4.00

1433

1.08

Material Source QuantityVol (ft^3)

ASTM C260 Air Entrainment BASF MasterAir AE90/*Fritz SuperAir Plus oz/cwt

lb

gal

8.63

Total Volume: 27.00

0-4

Vulcan, North Troy

Plant No.:

Project: Dallas Park & Rec Office RenovationsUsage: Paving

Wet Unit Weight: 148.2 lb/ft^3

Notes: Please make sure that [email protected] is on the list to receive break reports. Admixtures may be adjusted, depending on ambient conditions, at time of placement. *Air Entrainment may be adjusted using Fritz Super Air Plus

Design w/(c+p) ratio: 0.53

The use of an EF Technology mix design will reduce the amount of CO2 entering the atmosphere, thereby reducing potential global warming. "Your Project, Our World"

an EF Technology Mix DesignStrength: 3000Description: 5 SK 20% C-ASH NR/NA

psi @ 28 days

Saturated Surface Dry Weights Per Cubic Yard

Customer: Denco Construction

Date: 6/18/2018

Redi-Mix Concrete, L.P. A US-Concrete Company 331 N. Main St Euless, TX 76039 Technical Service: (817)-835-4187 Dispatch: (817) 835-4020 E-mail: [email protected] www.us-concrete.com

T H E N E W R E S O U R C E F O R T H E C O N S T R U C T I O N I N D U S T R Y

This mix has been designed to meet the requirements of this project based on the information sent to Redi-mix Concrete. It is the responsibility of the purchaser to determine whether this mix design meets project specifications and is appropriate for the anticipated environment conditions. The specified strength guarantee per ASTM C94 will not be effective unless field sampling has been done per ASTM C172 and ASTM C31 and the laboratory fully complies with ASTM C39 and ASTM C1077. In the event of limited material avaliability, substitution of a similar performing material may be required. All substituted materials will meet the appropriate ASTM requirements. In order to maintain the required mix volume, weights of individual materials may be varied to accommodate different material specific gravities. Material certifications for substituted materials are avaliable upon request.

All Redi-Mix Concrete mix designs are proprietary and confidential. The information contained in this submittal is only intended for parties associated with this project to validate the mix design materials, properties and its performance. Use of this submittal for other purposes without permission or consent from Redi-Mix Concrete is strictly prohibited.

dbechtel
Callout
IS THIS ALSO USED FOR STRUCTURAL CONCRETE?
Page 6: SUBMITTAL TRANSMITTAL

STRENGTH PERFORMANCEREPORT

REDI-MIX LABORATORY201 WEST EULESS BLVD EULESS, 76040 Tel: 817-835-4077

Period :

Mix : 10J11524

22 Nov 2016 08 Dec 2017To

3000 Specified Strength

Average Strength

Standard Deviation

Corrected CofV ACI Running Average of 3 Criteria

ACI Standard Deviation Criteria

4690

520

11.1 Yes

Yes

28 Day

Required Strength 3710

Compressive Test Number of Tests 30

Air Content

%

Concrete

Temp

deg F

Slump

in

Air Temp

deg F

7D Str

psi

28D Str

psi

Count

Average

STDEV

COV%

Range Min

Range Max

30 30 30 30 30 30

4.06 80 4.42 72 3660 4690

0.59 10 0.60 14 440 520

14.5 12.1 13.5 19.2 12.0 11.1

3.00 56 3.00 33 2610 3720

5.00 93 5.00 90 4340 5660

Air Content

%

Concrete

Temp

deg F

Slump

in

Air Temp

deg F

7D Str

psi

28D Str

psi

12/8/2017 18000608

12/1/2017 18000125

10/19/2017 17008316

10/12/2017 17008145

9/29/2017 17007354

9/28/2017 17006802

9/22/2017 17007353

9/20/2017 17006633

9/11/2017 17006503

9/5/2017 17006513

8/28/2017 17006104

8/10/2017 17005712

6/13/2017 17005551

6/8/2017 17005545

6/7/2017 17004805

6/6/2017 17004765

6/1/2017 17004203

4/21/201717003853

17003854

4/19/2017 17003852

4/14/2017 17003187

4/8/2017 17003054

3/9/2017 17002991

2/27/2017 17004737

2/23/201717004738

17004739

12/21/2016 17001044

12/15/2016 17001316

12/14/2016 17000390

11/22/2016 17000101

Date Sample

4.00 71 4.00 42 3560 5660

4.20 74 5.00 68 4340 5240

3.50 84 5.00 70 3720 4540

3.70 82 4.00 73 2870 3720

4.50 84 5.00 74 3290 4320

3.30 87 5.00 77 2610 3920

4.00 89 4.00 83 3840 4220

5.00 91 5.00 86 3230 4360

5.00 82 5.00 76 3700 4980

3.00 87 3.50 84 3070 3930

4.50 87 4.75 81 3170 4030

3.50 91 3.00 79 4070 5350

4.20 84 4.75 90 3570 4330

4.20 83 4.75 74 3900 5000

4.20 93 4.50 89 3990 4650

3.80 80 4.50 72 3910 5250

4.60 89 4.00 81 4160 5220

3.10 83 5.00 79 3650 5050

4.30 82 5.00 74 3280 4550

3.70 79 5.00 71 3340 4780

4.10 82 4.00 71 3310 4320

4.50 70 4.00 56 4000 4900

3.60 68 3.50 73 3290 4530

4.40 68 5.00 64 3750 5020

4.10 84 3.50 82 3680 4700

4.70 79 4.00 77 3930 4900

3.00 66 4.00 60 4270 5380

3.40 56 4.75 33 4330 4930

5.00 56 4.00 40 4160 5250

4.80 84 5.00 66 3900 3740

Date : 12/6/2018 Page 1 of

Page 7: SUBMITTAL TRANSMITTAL
Page 8: SUBMITTAL TRANSMITTAL
Page 9: SUBMITTAL TRANSMITTAL
Page 10: SUBMITTAL TRANSMITTAL
Page 11: SUBMITTAL TRANSMITTAL
Page 12: SUBMITTAL TRANSMITTAL
Page 13: SUBMITTAL TRANSMITTAL
Page 14: SUBMITTAL TRANSMITTAL
Page 15: SUBMITTAL TRANSMITTAL

Fritz-Pak Corporation • Mesquite, TX USA • Tel: 214-221-9494 • Fax: 214-349-3182 • www.fritzpak.com

43

ADVANTAGES• Reduces amount of concrete rejected due to low

entrained air content• Super Air Plus is a premeasured dry material and

will not freeze• Easily transported and dispensed• Improves concrete workability• Addition of Super Air Plus will not affect the

water/cement ratio• Entrained air content may be easily adjusted

prior to job site testing• Super Air Plus is packaged in water-soluble Fritz-

Pak inner bags for convenient use at plant or job site.

DESCRIPTIONFritz-Pak Super Air Plus is a dry powdered admix-ture, packaged in patented ready-to-use water-sol-uble bags or in bulk (50 lb bags). Super Air Plus is recommended for all types of air entrained concrete when an increase in entrained air content is neces-sary. Super Air Plus may also be used as a primary air-entraining admixture. Super Air Plus is compat-ible with all standard concrete admixtures.

DIRECTIONS1. If entrained air content is below the specifi ed level,

determine which Air Plus product is required. (See Recommended Dosage Rate).

2. Each Super Air Plus package is double bagged. Remove the protective outer bag and add the water-soluble Fritz-Pak inner bag to plastic concrete. The entire inner bag will easily dissolve.

3. Mix at high speed for 5 to 7 minutes to insure that the Super Air Plus is uniformly dispersed throughout the mix.

4. If entrained air content remains below specifi ed levels, more Super Air Plus may be added.

RECOMMENDED DOSAGE RATE

FOR CONCRETE:

Super Air Plus. For larger increases in entrained air content, use one 8-oz bag (227 g) of Super Air Plus to increase the entrained air content for a full load of concrete by ¾ to 2%. For use as a primary air-entraining admixture, a Super Air Plus dosage rate of 0.25 to 1.25 oz./cwt. (0.15 to 0.80 g/kg) is recom-mended to achieve 5 to 7% entrained air content.

Cementitious content, concrete temperature, ambi-ent temperature or concrete mixes containing ac-celerators, retarders, or special admixtures such as superplasticizers or silica fume may require dosage rates outside the recommended range. Contact your Fritz-Pak distributor with any questions concerning the dosage rates for these products. It is recom-mended that testing be done to determine the suit-ability of Super Air Plus to your mix designs.

FOR ONE YARD TRAILER MIXERS:Use specially packaged product in 4 oz. water-solu-ble bags. (Item #95661).

FOR MORTARS AND DRY BLENDED PRODUCTS:Super Air Plus can be used as an air entraining agent for the production of mortars and other dry blended materials. Up to 16% air entrainment can be obtained with Super Air Plus. Air contents vary considerably depending on the materials used. Use the following table as a guideline:

DesiredAir

Content

Dosage of Super Air PlusBy weight of

cement

By total weightof blend

5-7% 0.25-1.25 oz/cwt0.15-0.80 g/kg

0.9-4.5 oz/ton28-141 g/MT

7-10% 1.0-4.0 oz/cwt0.63-2.5 g/kg

5.0-12.0 oz/ton156-375 g/MT

10-15% 4.0-6.0 oz/cwt2.5-3.75 g/kg

14.0-22.0 oz/ton438-688 g/MT

COMPATIBILITYSuper Air Plus is compatible with all air-entraining admixtures, calcium chloride and other admixtures. When used with other admixtures, each one must be dispensed separately into the mix.

APPLICABLE STANDARDSSuper Air Plus meets ASTM C-260, AASHTO M-154 & CRD C-13 specifi cations.

PACKAGING• 8-oz. (227 grams) water soluble bag, 60 bags

per case, 35 cases per pallet (item #95664)• 50-lb paper bag, 40 bags per pallet (item

#95667)

SUPER AIR PLUSAIR ENTRAINING ADMIXTURE

Product Bulletin #124

Page 16: SUBMITTAL TRANSMITTAL

Fritz-Pak Corporation • Mesquite, TX USA • Tel: 214-221-9494 • Fax: 214-349-3182 • www.fritzpak.com

44

• 4-oz. water soluble bag, 60 bags per case, 35 cases per pallet (item #95661)

FAQsQ. What does increased air content do to

concrete?A. It increases its durability by making it more

resistant to damage from freezing.

Q. Will it change the set time?A. No, it will not speed or slow the set.

Q. What standards does Super Air Plus meet?A. They meet ASTM C-260, AASHTO M-154 and

CRD C-13 standards.

Q. Will it affect the strength of my concrete?A. It will not signifi cantly change strength, and it

will increase durability.

Q. What is the difference between Super Air Plus and Air Plus?

A. Super Air Plus has twice the concentration of the active ingredient of Air Plus.

Q. Which product should I use, Air Plus or Super Air Plus?

A. Air Plus should be used by concrete producers who have very consistent quality in their supply of raw materials, thus only needing small corrections of air. Concrete producers that have variation in their quality of raw materials normally experience wider fl uctuations in air content and should consider using Super Air Plus.

Q. What is the raw material used in the production of Super Air Plus?

A. Vinsol Resin, a natural air entrainer.

Q. Are these products compatible with synthetic air entrainers?

A. Yes. Additionally the spacing and size of air bubbles is improved when natural air entrainers are used to correct synthetic air entrainers.

Q. Can they be used in dry-blended materials like mortars and stuccos?

A. Yes. See the recommended dosage rate chart.

Q. Are Super Air Plus and Air Plus effective in concrete with fl y ash containing high levels of organic compounds (i.e. high LOI)?

A. Yes. Natural air entrainers are more effective than synthetic air entrainers.

Q. Can I add Super Air Plus or Air Plus to water to make a liquid admixture?

A. No. Some of the components will only dissolve under special conditions of temperature and pH.

Q. How long have the products been in the market?

A. Since 1992.

PRECAUTIONSAll Fritz-Pak Concrete Admixtures should be stored in a dry location, protected from breakage, deterioration and contamination. They are not subject to damage from freezing temperatures.

WARRANTYThe information and recommendations in this publication are, to the best of our knowledge, reliable. Suggestions made concerning uses or applications are only the opinion of Fritz-Pak Corporation and us-ers should make their own tests to determine the suitability of these products for their own particular purposes. Because of numerous factors affecting results, Fritz-Pak Corporation makes no warranty of any kind, expressed or implied, including those of merchantability and fi tness for purpose. Statements herein, therefore, should not be construed as representations or warranties. The responsibility of Fritz-Pak Corporation for claims arising out of breach of warranty, negligence, strict liability, or otherwise are limited to the purchase price of the materials.

U.S. Patents No. 4,961,790 and No. 5,120,367.

© 2009 Fritz-Pak Corporation

AIR ENTRAINING ADMIXTURE

SUPER AIR PLUS

Product Bulletin #124