44
Rev 2.1 ‐1‐ January 9, 2018 Simple Dew Point Control – Aspen Plus v10 Steps are presented to set up a simulation in Aspen Plus v8.8 to model a simple dew point control system consisting of: Gas chiller Flash separator Liquid stabilizer with gas recycle & compression Product gas compression Simple propane refrigeration loop When the simulation is set up the overall PFD should look like the figure to the right. Basis A gas plant is processing 100 MMscfd (dry basis) to produce a spec pipeline gas as well as a pipeline raw mix liquid product (Y Grade). The following are known conditions for the feedstock and specification for the products: The composition of the feed gas is shown in the following table. The gas enters the plant at 400 psia & 120°F. The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf dry gas. The produced pipeline gas should have a gross heating value between 905 to 1050 Btu/scf 1 & a hydrocarbon dew point no higher than 15°F. The produced pipeline gas should be delivered to the pipeline at 1000 psia and no higher than 120°F. The produced liquids shall be exported via pipeline & stabilized to have a TVP (true vapor pressure) @ 100°F no greater than 103 psia. Component Mol% N2 0.357 CO2 0.194 C1 80.980 C2 13.238 C3 3.438 i‐C4 0.431 n‐C4 0.742 i‐C5 0.199 n‐C5 0.156 n‐C6 0.163 n‐C7 0.065 n‐C8 0.026 n‐C9 0.010 A propane refrigeration loop will be used to provide the chilling duty. The condenser will operate at 120°F. The minimum approach temperature within the chiller will be 10°F. Air coolers will be used to cool gases & liquids to 120°F. Create new simulation file When running under Windows 10 you can start the program from Start, the all programs list, Aspen Plus, Aspen Plus V10. When the program opens choose the new button. there are several templates 1 If the gross heating value spec cannot be achieved set the chilled separator to the lowest reasonable temperature when using a simple propane chilling loop, ‐30°F.

Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

  • Upload
    others

  • View
    3

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐1‐ January9,2018

SimpleDewPointControl–AspenPlusv10StepsarepresentedtosetupasimulationinAspenPlusv8.8tomodelasimpledewpointcontrolsystemconsistingof:

Gaschiller Flashseparator Liquidstabilizerwithgas

recycle&compression Productgascompression Simplepropane

refrigerationloopWhenthesimulationissetuptheoverallPFDshouldlooklikethefiguretotheright.BasisAgasplantisprocessing100MMscfd(drybasis)toproduceaspecpipelinegasaswellasapipelinerawmixliquidproduct(YGrade).Thefollowingareknownconditionsforthefeedstockandspecificationfortheproducts:

Thecompositionofthefeedgasisshowninthefollowingtable.

Thegasenterstheplantat400psia&120°F. Thegasisnearlysaturatedwithwaterattheinlet

conditions,48lbwaterperMMscfdrygas. Theproducedpipelinegasshouldhaveagrossheating

valuebetween905to1050Btu/scf1&ahydrocarbondewpointnohigherthan15°F.

Theproducedpipelinegasshouldbedeliveredtothepipelineat1000psiaandnohigherthan120°F.

Theproducedliquidsshallbeexportedviapipeline&stabilizedtohaveaTVP(truevaporpressure)@100°Fnogreaterthan103psia.

Component Mol%N2 0.357CO2 0.194C1 80.980C2 13.238C3 3.438i‐C4 0.431n‐C4 0.742i‐C5 0.199n‐C5 0.156n‐C6 0.163n‐C7 0.065n‐C8 0.026n‐C9 0.010

Apropanerefrigerationloopwillbeusedtoprovidethechillingduty.Thecondenserwill

operateat120°F.Theminimumapproachtemperaturewithinthechillerwillbe10°F. Aircoolerswillbeusedtocoolgases&liquidsto120°F.

CreatenewsimulationfileWhenrunningunderWindows10youcanstarttheprogramfromStart,theallprogramslist,AspenPlus,AspenPlusV10.Whentheprogramopenschoosethenewbutton.thereareseveraltemplates

1Ifthegrossheatingvaluespeccannotbeachievedsetthechilledseparatortothelowestreasonabletemperaturewhenusingasimplepropanechillingloop,‐30°F.

Page 2: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐2‐ January9,2018

thatcanbechosen.SelecttheGasProcessingoptionintheleft‐handcolumn&chosetheGasProcessingwithEnglishUnitstemplate.PressCreate.

SaveasyougoOneofthethingsyou’llwanttodoistosaveyourfilesasyougo.ThefirsttimeyougototheSaveAsoptionyou’llhaveseveralformatsfromwhichtochoose.ThereareadvantagestosaveastheAspenPlusBackup(BKP)format–thefilestendtobesmaller&lesslikelytobecomecorrupted.Forthisproblemlet’susethename“SimpleDewPointControlV10.”

DefinetheComponents&thePropertyModelsSpecifycomponents,fluidpropertypackages,&crudeoilassaysThefirststepistoaddasetofpurechemicalspeciestorepresentthegas&waterphases.WhenyouopenanewfilethedefaultscreenshouldbetheComponent‐Specificationsform.(Ifnot,press

Page 3: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐3‐ January9,2018

theSpecificationsitemunderComponentsintheleft‐handcolumn.)Wwillwanttoaddthefollowingpurecomponents:water,nitrogen,carbondioxide,methane,ethane,propane,i‐butane,n‐butane,i‐pentane,n‐pentane,n‐hexane,nheptane,n‐octane,&n‐nonane.OneofthedirectwaystodothisistopressFind&usethesearchformtofindthedesiredcomponents.ThefollowingformsshowasearchforH2O;keyphrasescanbeusedwiththeEqualsorContainsoptionstofindallcomponents.Foreachsucceedingcompoundyouwillbeaskedtoreplaceoneofthecompoundsoraddtothelist;chooseaddtothelist.

Page 4: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐4‐ January9,2018

Whenyoustartaddingtheothercomponentsyouhaveanextraquestiontoanswer,whethertoaddorreplacethecurrentcomponent.YouwillprobablywanttochooseAdduntilyou’veaddedallofyourcomponents.Therearevarioustricksforfindinggroupsofcompounds.Forexample,bysearchingforn‐Alkanesthatcontain“ethane”youcangetthelighthydrocarbons.Youcanselect&addallasagroup.

Page 5: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐5‐ January9,2018

Afterfindingallofthecomponentsyoushouldhavealistthatlookssimilartothefollowingform.

Page 6: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐6‐ January9,2018

AspenPluswillretrieveinformationabouteachcomponent&alsocreateaComponentIDforthissimulation.YouarefreetochangetheseIDstomatchyourpersonaldesires.Forexample,youcanchangetheIDforMETHA‐01toC1bydoublingclickingonthattextitem;afterchangingthetextvalue&pressingenterAspenPluswillverifythatyouwanttoRenamethecomponent&replacethatcomponentwithsomethingelse.Thiscanbedoneforallofthecomponentstocreate(IMHO)morereasonableIDs.

Page 7: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐7‐ January9,2018

Anotherissueistheorderthatthecomponentsmayhavebeenextracted.Ihaveapersonalpreferenceforalistintheorderofwater,lightgascomponents,&thenthehydrocarbonsinincreasingcarbonnumberorder.Thisisnotthecurrentorder.YoucanchangetheorderbypressingtheReorderbutton&thenusingtheup&downarrowstoputcomponentsinyourpreferredorder.

Thenextstepwouldnormallybetopickafluidpropertypackage.However,whenwechosetheGasProcessingoptionwhenwecreatedthesimulationthePeng‐Robinsonequationofstatemethodwaschosenasthedefault.WecanseethisbyselectingMethods&Specificationsintheleft‐handcolumn.NoticethattheBaseMethodisPENG‐ROB.Wewillkeepthisdefaultselection.

Page 8: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐8‐ January9,2018

TheremaystillbeitemstobeaddressedbeforewecanentertheSimulationsection(youcantellthisifthereisa symbolintheleft‐handcolumn).Tofindoutwhatneedstobedoneclickthe button.YoumaygetaformthatallowsustomodifyvaluesforthePeng‐Robinsonbinaryinteractioncoefficients.Ifyougetthis,donotchangeanyofthevalues.

Page 9: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐9‐ January9,2018

Nowwhenyoupressthe (Next)buttontheprogramshouldshowyouthatyoucangoontothenextstep.SelectGototheSimulationenvironment&pressOK.Setup&SolvetheFlowsheetGasChilling&SeparationWhenyouactivatethesimulationenvironment&you’llseeablankflowsheet.Wewillwanttocreateafeedstream&attachittoaHeater.Theoutletwillbeattachedtoathree‐phaseflashseparator.

EnsurethatthemodelPaletteisvisible.Ifitisnot,presstheViewtab&clickModelPalette.AshortcutkeyistopressF10.

Placethefollowingunitsontheflowsheet:

AHeater,COMBINE.(Youmaywanttochooseoneofthesquaresforitsiconinsteadofaheatexchanger).

AnHeater,CHILLER AFlash3separator,COLDSEP.

AsshownintheBFDabove,connecttheunitswithmassstreamsDRYFEED,FEEDWATR,WETFEED,CHILLED,COLDVAP,COLDLIQ,&COLDWATRaswellastheHeatstreamQ‐CHILLR.(Rememberthatstreamnamescanonlybe8charactersinlength&willalwaysbecapitalized.)

Page 10: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐10‐ January9,2018

Double‐clickontheDRYFEEDstreamtoopenuptheentryformstospecifycomposition&conditions.EnsurethattheFlashTypeisTemperature&Pressure.EntertheflowratewithaMolebasis&usetheMMscfdunits.UseMole‐fracforthecomposition(drybasis,i.e.,nowater);youdonotneedtomakesurethenumbersaddto1,theprogramwillnormalizeasappropriate.WewanttodothesamethingforthewaterportionofthefeedrepresentedbythestreamFEEDWATR.Double‐clickontheFEEDWATRstreamtoopenuptheentryformsforthisstream.Enter4,800lb/dayusingtheMassbasis(torepresentthe48lb/MMscfwatercontent).Enterthepressure&thetemperature.SincethisispurewateryoucanspecifythecompositioneitherusingMass‐FracorMole‐Frac.

Page 11: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐11‐ January9,2018

WemixtogethertheseparateDRYFEED&FEEDWATRstreamstodefinethewetfeedtothegasplant.NormallywewoulddothiswithaMixeroperation,butinsteadwe’regoingtodoitwithaHeatertobeabletospecifytheactualtemperatureofthewetfeed.Double‐clickonCOMBINEtoopentheinputform.Specifythe120°FoutletTemperature.SpecifythePressureas400psia(wecouldhavespecifiedazerotodenoteazeropressuredropbutspecifyingtheactualpressuregivesusasinglepointofcontrolfortheinletpressure).PulldowntheValidphaseslist&chooseVapor‐Liquid‐FreeWater.Wenowwanttomodelthegassideofthechiller.Wewillultimatelyuseadifferentoperationtomodelboththeprocess&coolantsidesoftheexchanger,butherewe’lljustmodeltheprocessfeedsidewithaHeater.Double‐clickonCHILLER.FornowspecifythePressureas0psia(tosignifyazeropressuredrop).PulldowntheValidphaseslist&chooseVapor‐Liquid‐FreeWater.Fornowlet’sspecifytheoutletTemperatureas15°F(thespecvalueforthedewpointoftheproducedgasinthepipeline).Finally,let’sspecifytheoperationforthecoldseparator.Double‐clickonCOLDSEP.SettheFlashTypeasDuty&Pressure.SpecifythePressureas0psia(tosignifyazeropressuredrop)&theDutyas0MMBtu/hr(tosignifyadiabaticoperation).PressingNextshowsthatalloftherequiredspecificationshavebeenmade.PressOKtorunthesimulation.AtabfortheControlPanelshouldopenup&indicatethatthesimulationhasrunsuccessfully.(NoticethatthereisawarningconcerningthenumberofphasesintheCOMBINEblock;sincenofreewatershouldformfromthisoperationthiscanbeignored.)

Page 12: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐12‐ January9,2018

Whataresomeoftheresults?Wecangetanoverviewbypostingsummaryconditionsontheflowsheet.ClickonStreamResultsintheModifytaboftheribbon.SelectTemperature,Pressure,Massflowrate,&Heat/Duty.PressOK.Nowthesenumbersarepostedontheflowsheet.

Page 13: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐13‐ January9,2018

NoticethatallvaluesarecalculatedforthestreamsoutofCOLDSEPareat15°F.Thismeansthatthevaporoutoftheseparator,COLDVAP,isatitsdewpointat15°F.Thismakesthepipeline’sdewpointspec,right?No,notreally.Buthowwouldweknowthis?WecanlookatthephaseenvelopeforCOLDVAPtodetermineifthevaporwillhaveaminimumdewpointtemperatureatallpressuresitislikelytoexperienceinthepipeline.ClickonstreamCOLDVAP;intheribbonundertheHometabselectthepulldownlistStreamAnalysis&selectPTEnvelope.MakesuretheStreamIDisCOLDVAP.PressRunAnalysis.Youwillseeaphasediagramshowingthebubblepoint&dewpointcurves;fromthediagramyoucanseethatthecricondenthermisabout20°F.SelecttheResultsforPTENV‐1intheleft‐handcolumn;fromthetableofvaluesyoucanseethatthehighesttemperature(essentiallythecricondentherm)is19.8°F.Thisoccursat647psia.

Page 14: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐14‐ January9,2018

Page 15: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐15‐ January9,2018

Thepressureatwhichthecricondenthermoccursisverymuchinthepossiblerangeofpipelineoperatingpressures.Sincethegasinthepipelinewillexperiencepressureslowerthantheinlet’s1000psia,itisappropriatetousethecricondenthermasthecontrollingvalueforthisspec.Andsincethetemperatureis20°F,thisgasdoesnotmakethisspec.Fornowwe’llusetrial‐and‐errortodetermineanappropriatetemperatureforthecoldseparator.NotethatifwespecifythetemperatureoutofCHILLERas9°FwegetacricondenthermofCOLDVAPofjustunder15°F.Havewemettheheatingvaluespec?Wecandeterminethisbymakinguseofthebuilt‐innet&grossheatingvalues&addingtothestreamreport.ExpandtheSetupitemintheleft‐handtreestructureoftheSimulationitems.UnderPropertySetscreateaNewsetcalledHEATVALS.Editthatpropertyset&addthepropertiesQVALGRS&QVALNET.(Forreasonstobenotedlater,makesurethatQVALGRSisthefirstinthelist.)

Page 16: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐16‐ January9,2018

Nowwecanrerunthesimulation&lookfortheResultsforCOLDVAP.Gotothebottomofthestreamreport&clickon<addproperties>.TowardthebottomofthelistclickonbothHEATVALSproperties&clickOK.AtthebottomoftheEditStreamPropertyTemplateformpressOK.NowwhenyoulookatthestreamreportforCOLDVAPyou’llseethegross&netheatingvalues.

Page 17: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐17‐ January9,2018

Thebadnewsisthateventhoughthenet&grossheatingvaluesarecalculated&reportedatthebottomofthelistthesevaluesareinmassunits,notthescfmolarunitsthatwereallywant.We’llhavetodosomeunitconversionsusingtheMassflow&Moleflowvalues:

6

hrBtu lb 2423048.9 211179daylb hr

HHVscfMMscf 1098.809

MMscfday

Btu1182.3

scf

Thisvalueistoohigh&willrequiremoreheavyhydrocarbonsberemoved.Butbeforewefocusonthislet’saddadditionalprocessingtostabilizetheliquidformed(sincethiswillinvolverecyclingbacktheevolvedgas).LiquidStabilizationDeterminationofliquid’sTVPvalueThenextstepistodetermineiftheproducedliquidwillmaketheTVPspecof103psia.Let’saddaHeaterTVPCALContoCOLDLIQ&useittodeterminethebubblepointpressureat100°F.SettheVaporfractionto0(tocorrespondtoaliquidfractionofexactly1).

Page 18: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐18‐ January9,2018

Runthesimulation.Therearevariouswaystocheckforthecalculatedvaporpressure;let’slookatthestreamResultsforLIQUID.ThisshowsthattheTVPis654psia,muchhigherthanthedesired103psia.Wecanlookatthecompositiontoseetheproblem–theamountofmethaneisroughlythesameastheethane&propane.ThisismuchtoohighforaY‐gradeNGLliquidmix.Howcanweseethemolefractions?Thesearepartofthestreamreport,butyoumayhavetopressthe+signontheMoleFractionsoptiontoexapandthelist.

Page 19: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐19‐ January9,2018

SetuptheStabilizercolumn

Wecanprocessthehigh‐pressureliquidinastrippingcolumntoremovetheselightends.Let’saddtwounitsinbetweenthecoldseparator&theTVPcalculation:

AValve,VLV‐001 APetroFracSTRIPcolumn,STAB.

ConnectwithmaterialstreamsFLSHDLIQ,STABGAS,&STABLIQasshownabove.Double‐clickonVLV‐100.SpecifytheOutletPressureas200psia.Nowlet’sdefinethestabilizingcolumnasa11‐stagecolumnwithakettlereboiler.(Rememberthatthereboilerwillactasthe11thstage,sothereareonly10stagesinthecolumnitself.)Double‐clickonSTAB.Setthenumberofidealstagesto11.SpecifyNone‐TopFeedfortheCondenserbutaKettleastheReboilertype.Weneedgiveanestimatefortherateeitheroutthetoporbottomofthecolumn.Roughly6900lb/hrisbeingfedtothecolumn;if¾ofthisisstrippedoffasvolatilegasthenthebottomsflowshouldbeabout1,500lb/hr.

Page 20: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐20‐ January9,2018

Let’slookattheStreamstab.Theinformationshouldalreadyhavebeenspecifiedfortheproductstreams.Ensurethatthefeedtothecolumngoestothetopstage,1.ByspecifiyingAbove‐Stagethenanyvaporthatmightbecreatedbyflashingthroughtheinletnozzleofthetowerwillnotcontacttheotherfluidsonthetopstagebutratheronlymixwiththevaporfromthetopstage.Let’slookatrunningthetowerat200psiawithanegligiblepressuredrop.Specify200forboththetop&bottomstagepressure.Wecannowrunthesimulation.Lookingattheprocessflowdiagramwecanseethatthecolumnoperateswithatemperatureof416°F.But,theliquidproducedhasaTVPat100°Fofonly3psia(asseenfromtheresultsforTVPCALC).Thisismuchlowerthanitneedstobe.

Page 21: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐21‐ January9,2018

OneofthereasonsforusingaPetroFraccolumnisthatitisrelativelyeasytospecifyoperatingconditionsonthecolumn.Let’sspecific200°Fasthereboilertemperature.SelectDesignSpecificationsintheleft‐handcolumn&presstheNewbutton.SelectStagetemperatureastheType&assignittothereboiler(thelaststage,11).Setthevalueto200(thedefaultunitsbeingusedare°F).OntheVarytabselecttheBottomsFlowRateastheadjustedvariable.Nowwhenwererunthecolumnweseethatthereboilertemperatureis,indeed,200°F,buttheTVPat100°Fis68psia(stilllowerthannecessary).

Wecouldadjustthetower’sdesignspecbytrail‐and‐error,butthatwouldbeinconvenientaswemakeotherchangesthataffectthecolumnoperation.However,wecanaddaflowsheet‐leveldesignspectovarythereboilertemperaturetomakethisspec.SelectDesignSpecsunderFlowsheetingSpecsintheleft‐handcolumn.Createanewspec,DS‐TVP.First,we’lldefinethetargetvariableundertheDefinetab.CreateanewvariableTVP&associateitwiththepressureoftheLIQUIDstream(i.e.,thecalculatedbubblepointpressureat100°F).Next,specifythevalueontheSpectab.

Page 22: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐22‐ January9,2018

Finally,weneedtospecifythereboiler’stemperatureasthevariabletovary.ThisisnotstraightforwardtodefinesinceitisitselfadesignspecforthePetroFracblock.FortheBlockSTABspecifyVALUEastheVariable;thiskeywordsignifiesthatwearemodifyingsomethingthathasbeendefinedasaDesignSpec.SpecifythatitisthefirstofSTAB’sdesignspecs(andithappenstobetheonlyone,too)byspecifying1forthevalueofID1.Nowthetrickypart,definingupper&lowerlimitsfortheiterations.Ifwewereoperatingthecolumnat103psiathenthereboilerwouldbeat100°F–thiswouldmakeareasonablelowerlimit.Atelevatedpressuresthenthereboilertemperaturewouldbehigher.Wealreadyknowthat200°Fistoohigh,butthiswouldmakeareasonableupperlimit.Nottootricky.Thetrickyparthastodowiththeunits–eventhoughweareworkingwithtemperatureunitsof°FwemustspecifytheLower&UppervaluesinAspenPlus’sintrinsicunits,Kelvin.Thevaluesof100°F&200°Fareapproximately311K&366K,

Page 23: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐23‐ January9,2018

respectively;thesearethevaluesspecifiedfortheselimits.Finally,specifyreasonablefractionalvaluesfortheperturbation&maximumstepsizes,0.1&0.5,respectively.Nowwecanrerunthesimulation.Thesummaryintheflowsheetshowsthatoperatingthereboilerat166°Fwillgivealiquidthathasa103psiaTVPat100°F.

Whatdoesthestabilizedliquidlooklike?Double‐clickonSTABLIQ&selectResultsintheleft‐handcolumn.(Remembertoexpandanylistofvaluesthatyouwanttoexamine.)Notethatthereisessentiallynomethane&verylittleethane–allofthismaterialhasbeenstrippedoutintotheoverheadvaporstream.

Page 24: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐24‐ January9,2018

Let’slookathowmuchgashasbeenstrippedout.Double‐clickonSTABGAS.LookundertheResultsarea(expandingthelistsasnecessary&addingtheheatingvalues).Noticethatthisgashasveryhighconcentrationsofmethane&ethane(about90mol%).Butcouldthisbedirectlyproducedaspipelinegas?SelectProperties.NotethattheHHVistoohigh,1466Btu/scf(ascalculatedfromthegrossheatingvalue,massflowrate,&molarflowrate).Morethanlikelyitwon’tmakethedewpointspeceither.There’snotalotofitcomparedtotheCOLDVAPbutitwon’tmakethepropertiesofthetotalproducedgasanybetter.RecycleofRecoveredGasOnemightaskwhywedidn’tincludeacondenseronthestabilizercolumn.Acondenserwouldallowustowashthepropane&heavier(C3+)backdownthecolumn&outwiththeStabilizedLiquid.WecaneffectivelygetthiseffectbyreconfiguringtheprocesstorecycletherecoveredgasfromthestabilizingcolumnupstreamofCHILLER.However,sincetherecoveredgasisproducedatalowerpressure,itmustbecompressedtoahigherpressureconsistentwiththeoriginalfeedgas.

Let’saddtwounits:

Page 25: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐25‐ January9,2018

ACompr,RECCOMP AMixer,RECMIX.

ConnectwithmaterialstreamsRECGAS&TOTALandaddtheworkstreamW‐RECCMP.NotethattheiconforRECCOMPhasbeenflippedonthePFDshownabove.Thisdonebyright‐clickingonRECCOMP,selectingRotateIcon,&thenFlipHorizontal.Double‐clickonRECCOMP.SettheTypetoIsentropic.SelectDischargePressure&setitsvalueto400psia.SettheIsentropicefficiencyto0.75(areasonabledefaultadiabaticvalue).

Runthesimulation.NotethatthereisarecyclestreambutAspenPlussetsitupautomaticallywithoutanythingspecialbeingdone.IfonewastochecktheControlPanelyou’dseethatittook5iterationstoconvergethisrecycle.

Page 26: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐26‐ January9,2018

Howhasaddingtherecyclegasaffectedthefinalresults?ThereisnotagreatdealofRecycledGasbeingmixedwiththefreshfeed(1,063lb/hrvs.218,257lb/hr)sothecompositionofCOLDVAPdoesnotchangebymuch.Wecanrerun&checkPTENV‐1toseethatthecricondenthermisstillabout14.4°F,makingspec.Butwewouldexpecttheproducedgastoalsohaveasimilarhigherheatingvalue&itwillbeabovethespec.Let’slookatthenewResultsforCOLDVAP&calculatethegrossheatingvaluesonanscfmolarunitbasis:

6

hrBtu lb 2423046.6 212180daylb hr

HHVscfMMscf 1099.1861

MMscfday

Btu1183.2

scf

Page 27: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐27‐ January9,2018

ThisHHVishigherthanthespecvalue.WecantrytodecreasetheHHVbyreducingthetemperatureofCHILLER.Let’slowerthistemperaturetothelowestlimitreasonableforasimplepropanechillingloop,‐30°F.Reducingthistemperaturedoesshiftmoreoftheheavyendsoutoftheproducedgas&theHHVislower.However,theHHVofCHILLEDisstilltoohigh,1152Btu/scf(ascalculatedusingthevaluesbelow&theequationabove).Unfortunately,thisisprettymuchthebestwecandowhenusingachilledsingle‐stageflashseparationunit.CalculatorBlockforHHVinMolarUnitsNoticethatwehavehadtodosidecalculationsfortheheatingvalueinunitsofBtu/scfsincethevalueisreportedinmassunits.Wecanaddacalculatorblocktodothiscalculationforus.SincethisvalueisonlyforreportingpurposeswewillwriteitsvaluetotheControlPanel.Intheleft‐handtreestructureexpandtheFlowsheetingOptionscategory&selectCalculator.PresstheNewbutton.GiveitthenameGASHHV.Nowwe’llpullinthevalueforBtu/lbgrossheatingvalueasGROSS,lb/hrmassflowrateasMASS,&MMscf/daymolarflowrateasMOLES.Creatingtheflowratevariablesisstraightforward–theReferenceTypeisStream‐Var,selectedtheMIXEDsubstream,&

Page 28: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐28‐ January9,2018

chooseMASS‐FLOWANDMOLE‐FLOWasappropriate.Thegrossheatingvalueisalittlemorecomplicated.HeretheReferenceTypeisStream‐PropyouhavetoselectadefinedPropSet.We’vedefinedHEATVALSasboththegrossandnetheatingvalues.AspenPluswillusethefirstvalueforitscalculations(butwillgivewarningsthatitisdoingso).Ifyouwanttoeliminatethewarningthencreateanewpropertysetwithjustthegrossheatingvalue,QVALGRS.Let’senterthestatementforthecalculationasacoupleFortranstatements.ThevariableHHVwillbecalculatedwiththefirststatement&writtentotheContolPanelwiththesecond.(Don’tmaketheWRITEstatementmorecomplicatedthanthisunlessyouhaveaFortrancompileronyourcomputer;thisissimpleenoughthatAspenPluswillinterpretthecodewithitsowncapabilities.)Finally,wewillspecifywhentocalculatethevaluebyspecifyingeachoftheinternalvariableasInputvariables.So,thiscalculatorblockwillberecalculatedeverytimeoneormoreofthesevariableshaschanged.NowwhenyourunthesimulationyoucanchecktheControlPanel&findtheHHVintheproperunits.

Page 29: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐29‐ January9,2018

PreventionofFreezinginDPCSeparatorTheinletfeedgasisnearlywatersaturatedattheentrytotheprocess.WhenthewaterdropsoutofthegasphasewhenitiscooledthereisapotentialforfreezingintheCHILLER&COLDSEP.Atypicaltechniquetopreventiceorhydrateformationistoinjectethyleneglycol(EG)upstreamoftheCHILLER.AnaqueoussolutionofEGhastheabilitytosuppresstheformationofice.Init’spurestateEGhasafreezingpointof8°F,butaqueoussolutionshavefreezingpointsthatarelower.Noticefromthechartontheright1onemaygetfreezingprotectionto‐30°ForlowerbymaintainingaEGconcentrationinwaterof85wt%to50wt%.Whataretheappropriateconcentrationstoconsiderforourprocess?

Wewouldliketomakesurethatthereisfreezingprotectionfortheentireconcentrationrangebefore&afterthewaterisabsorbed.

Wewantprotectionnotonlyattheprocesstemperaturebutalsothecoldesttemperatureatthetubewall.Thismeanswehavetoprotectbelowthe‐30°Fprocesstemperaturebuttothecoolanttemperatureof‐40°Forlower.

BasedontheseconsiderationswewillwantaconcentratedEGsolutionof83wt%(protectionto‐40°F,thecoldesttubetemperatureexpectedinCHILLER).Thisshouldbeinjectedatasufficientratesothatitwillbedilutedtonolowerthan80wt%(protectionto‐50°F)2.TobeabletoaddanEGsolutionwemustaddethyleneglycoltothecomponentlist.ReturntothePropertiessection.SelectComponentstoviewthecomponentlist.PressFind,enter“glycol”intheContainsbox,&pressFindNow.ThecomponentETHYLENE‐GLYCOLshouldbeinthemiddleofthelist;select&pressAddselectedcompounds.PresstheAddbutton.Double‐clicktheComponentIDtochangeETHYL‐01toEG.ReordertoputEGbetweenH2O&N2.

1EngineeringandOperatingGuideforDOWTHERMSR‐1andDOWTHERM4000InhibitedEthyleneGlycol‐basedHeatTransferFluids,DowChemicaltechnicalpublication,http://msdssearch.dow.com/PublishedLiteratureDOWCOM/dh_010e/0901b8038010e413.pdf?filepath=/heattrans/pdfs/noreg/180‐01190.pdf&fromPage=GetDoc2Notethateventhoughwecouldtrytooperateintheregionoflowerglycolconcentrations(60wt%dilutedto55wt%)thenormalpracticeistooperateinthehigherconcentrationrange;ifexcesswatercomesinwiththegasthenthehigherconcentrationsactuallygetbetterfreezeprotection,notworse.

Page 30: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐30‐ January9,2018

ReturntotheSimulationsection.Let’saddastreamfortheethyleneglycol,EG,intotheRECMIX.Double‐clickonthestreamEG.Specifythecompostionas83wt%EG&17wt%H2O.UndertheStatevariablessetthepressureto400psia&itstemperatureto60°F(typicalforundergroundstorage;we’llfindoutamorereasonabletemperaturelater).Fornowsetthemassflowrateto5,333lb/hr(thisshouldmaketheColdWaterstreamabout80wt%glycol).

Page 31: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐31‐ January9,2018

Runthesimulation.DoubleclickonCOLDSEP&selectStreamResultssowecanlookattheeffectofaddingtheglycol.Lookingatthemassfractionsthesplitoftheglycolbetweentheoil,gas,&waterphaseslookveryreasonable.Butlookatthetemperatures–thetemperatureofthestreamsoutofCOLDSEPareabout1°differentthanthatcomingin(eventhoughtheyshouldbethesame).ThetemperatureissuecanberesolvedbygoingbacktotheCHILLERspecifications&changetheValidphasestoVapor‐Liquid_DirtyWater.Nowrerunthesimulation.Thetemperaturediscrepancyhasdisappeared.PropaneRefrigerationLoopThenextdetailwecanisarefrigerationlooptobeabletocoolthefeed&recyclegasestoCHILLER.Wewillnotactuallyadda“loop”butratherasequentialsetofoperationsthatare“brokenopen”afterthecondenser.Addthefollowingequipmenttotheflowsheet:

AHeater,CHILL‐C ACompr,REFCOMP AHeater,REFCOND AValve,VLV‐REF.

Page 32: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐32‐ January9,2018

Inaddition,adda“dummy”Heater,NET‐LOOP,tocalculatethelow&highpressuresforthesaturatedvapor&liquidconditions.Thiswillbeusefulfordetermining&feeding‐forwardvariousprocessconditions.TherearetwoissueswithmodelingthisrefrigerationloopinAspenPlusthatwillrequiresomeadvancedsetup.

Wedon’tknowtheflowrateofthepropanerefrigerantsinceitwillincreaseordecreasetobalancetheheatloadinthechiller.

Wedon’tknowthepressureoutofthecompressor,onlythattheeffluentfromthecondenserwillbeatasettemperature.

Let’screatethestreamREFVAPthatrepresentsthepropanerefrigerantattheoutletofthechiller.Setitscompositionas100%C3.SetitsFlashTypetoTemperature&VaporFraction,theTemperatureto‐40°F,&theVaporfractionto1(torepresentasaturatedvapor).Wedon’tknowtheflowratefortherefrigerant.Fornow,setitsTotalflowrateto100lb/hr.Let’sreallystarttheloopcalculationsforthesaturatedliquidoutoftherefrigerant’scondenser,streamHPLIQ.We’llspecifytheconditionsoutofthe“dummy”HeaterNET‐LOOPassaturatedvaporat120°F.

Page 33: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐33‐ January9,2018

NowwewanttospecifythepressuredropacrossVLV‐REF.Wedon’treallyknowwhatthispressureisthough–well,wekindado,sincewe’vecalculatedthepressurewhenwedefinedstreamREFVAP,butwedon’thavethatinformationavailabletousyet.Sofornow,let’sjustassumethatthepressureis10psia;we’lladjustthistothecorrectvaluelater.Next,let’ssettheconditionsforthecoldsideofthechiller,CHILL‐C.Wewanttherefrigeranttoleaveassaturatedvaporat‐40°F.Butwealsoknowthedutyrequiredbytheprocessside,theheatstreamQ‐CHILLR.Inactualoperationwewouldvarytherefrigerantflowratetobeabletoprovidethisamountofcoolingfromthevaporizationacrosstherefrigerant’ssideofthischiller.Butwecan’tsetthatviaCHILL‐C.Thewaywe’regoingtomodelthisisto:

specifytheoutletconditionsforstreamREFVAP‐2(temperature&phasecondition),

letAspenPluscalculatetheenthalpychangeassociatedwiththegivenflowrate,and

figureoutaresidualamountofheatneeded(representedbyheatstreamQ‐RESID)above&beyondthatcalculatedinQ‐CHILLR.

So,settheoperatingconditionsforCHILL‐CasaFlashTypeofVaporFraction&TemperaturewiththeTemperatureas‐40°F(tomatchREFVAP)&theVaporfractionof1(todenoteasaturatedvapor).Nowlet’scompressthisrefrigerant.WeknowthepressureviathecalculationforstreamHPLIQbutwecan’tdirectlyaccessit.So,we’lltemporarilysetadischargepressure.SpecifytheTypeofCompressortoIsentropic.Setareasonabledefaultefficiencyto0.75.Fornow,settheDischargePressureto150psia.

Page 34: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐34‐ January9,2018

Let’ssettheconditionsfortherefrigerant’scondenser,REFCOND.AswesetthecalculationsforHPLIQwewillbecoolingtherefrigeranttoasaturatedliquidstateat120°F.SowespecifyaFlashTypeofVaporFraction&Temperaturewiththeappropriatevalues.SpecifyingVaporfractionof0denotesasaturatedliquid.Nowwecanrunthesimulation&examinetheresults.Weseethatthereareacouplediscrepancieswiththespecificationsontheoperationofthisrefrigerationloop:

TheoutletpressureofVLV‐REFisslightlylow&doesnotmatchupwiththepressurerequiredtogiveasaturatedvaporinREFVAP‐2.Itshouldbeabout16psia.

TheoutletpressureonREFCOMPisnothighenoughtomatchupwiththerequiredpressuretogiveasaturatedliquidlikethatinHPLIQ.Itshouldbeabout244psia.

TheflowrateismuchtoolowsincethevaporizationoftherefrigerantinCHILL‐C“absorbs”aninsignificantamountoftheheatfromQ‐CHILLR.AlmostallQ‐CHILLR’sheatpassesthroughtoQ‐RESID.

Let’sfirsttakecareofthetemperature&pressurediscrepancies.Wecouldrunthesimulation,examinetheresults,andmanuallyupdatetheoutletconditionsforREFCOMP&VLV‐REF.Instead,let’slookathowwecantransferthisinformationprogrammaticallyusingTransferblocks.First,let’stalkaboutadirectmethodthatweultimatelywillnotuse:

WecantransferthepressureofREFVAPtotheoutletofVLV‐REFinafeedforwardmannerusingaTransferblock.ExpandFlowsheetingoptionsintheleft‐handtreestructure&selectTransfer;presstheNewbutton&specifythenameTRN‐P.IntheFromtabspecifythepressurefromREFVAPastheinformationtothetransferred.IntheTotabright‐clickonVariableNumber&selectNew;thenspecifythisasthereferencepressureoutofVLV‐REF.

Page 35: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐35‐ January9,2018

Thisnormallyisaneasy&directmethodtocopyvaluesfromoneunittoanotherinafeed‐forwardmanner.However,wewanttotransfermultiplevariables,eachofwhichwouldrequiretheirownTransferstatement.WecanalsodothiswithasingleCalculatorblock.SelecttheCalculatoritemunderFlowsheetingOptionsintheleft‐handtreestructure.PresstheNewbutton&namethecalculatorblockREFLOOP.Let’sdefinevariables:

TLOW&PLOWforthetemperature&pressureconsistentwiththerefrigerantatthechilleroutlet,streamREFVAP.

THIGH&PHIGHforthetemperature&pressureconsistentwiththerefrigerantatthecondenseroutlet,streamHPLIQ.

PVLVforthepressureoutofvalveVLV‐REF(variableP‐Out)&intothechiller. TCHILLforthetemperatureoutoftheexchangerCHILL‐C(variableTEMP). PCMPforthedischargepressurefromthecompressorREFCOMP(variablePRES). TCNDforthetemperatureoutoftheexchangerREFCOND(variableTEMP).

Page 36: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐36‐ January9,2018

NowwecanuseasetofFortranstatementstoequatethepressures&temperaturesfromREFVAP&HPLIQtotheblocksdownstreamoftheseinitialstreamcalculations.

Finally,let’ssetthestreamvariablesasimportedvariables&theblockvariablesasexportedvariables.(Theorderisnotimportant.)

Oneadvantagetousingacalculatorblocktosetthesevaluesisthatwecanincorporateoffsetstotheblockvariables.Forexample,ifthereisanon‐zeropressuredropinthecondenserREFCONDthenwecouldincludethatinsettingtheREFCOMP’sdischargepressure(assomethinglikePCMP=PHIGH+DELTAP).Nowwhenwere‐runthesimulationwecanseethatthepressuresarematchedup.

WealsoneedtoadjusttheflowrateintherefrigerationlooptobalancetheheatrepresentedinQ‐CHILLR;wecandothisusingaDesignSpectomaketheresidualheatstreamQ‐RESIDtobezero.

Page 37: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐37‐ January9,2018

ExpandFlowsheetingOptionsintheleft‐handtreestructure&createanewDesignSpecDS‐FLOW.DefineaVariableRESIDUALastheheatstreamQ‐RESID.GototheSpectab&setTHETargetvalueforRESIDUALas0withaToleranceof0.1.OntheVarytabspecifytheadjustablevariableasthemassflowrateinREFVAP.TokeepthisgeneralallowaLowerlimitof0;fornowlet’sassumetheUpperlimittobe500,000lb/hr.

Page 38: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐38‐ January9,2018

Nowwhenwere‐runthesimulationweseethattheactualrefrigerantflowrateis276,668lb/hrofpropane&requires79,963hpforthecompressor.

ProductCompressionThefinalstepinthissimplesimulationistoaddcompressionforthefinalproductgas.Addtotheflowsheettheunit:

ACompr,PRODCOMPConnectusingmaterialstreamPRODGAS&workstreamW‐PRDCMP.

Double‐clickonPRODCOMPtosetupitsparameters.SpecifytheTypeofCompressortoIsentropic.Setareasonabledefaultefficiencyto0.75.FornowsettheDischargePressureto1000psia.Runthesimulation.

Page 39: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐39‐ January9,2018

Notethatoutlettemperatureislessthan120°F,soafinalcoolerisnotneededtobeabletointroducethisgasintothepipeline.

AdditionaldetailtotheFlowsheetTheremanydetailsthatcanbeaddedtothisflowsheet.InparticularwewilladddetailforregeneratingtheEG.EthyleneGlycolRegenerationTheinitialflowsheetassumesthat83wt%ethyleneglycol(EG)canbemadeavailabletotheprocess.ThisEGisnotafreshfeed,butratheritisrecirculatedafterthewaterpickedupinCOLDSEPisstrippedout.WewillbeaddingthefollowingmajoroperationstoregeneratetheEGare:

astrippingcolumnwithareboiler&partialcondenser.UsetheRADFRACFRACT1unit.

across‐exchangertorecoverheatfromthestrippedEG.UseanMHeatXunit.

apumptobringtheleanEGuptotheinjectionpressure.UsethePUMPunit.

Connectstreamsasshowninthefigureabove.UsetheexistingstreamCOLDWATRtoconnecttoEGHX.Fornow,let’snotcloseofftheEGrecyclebutrathercreateanewstreamforthepumpoutlet,EG‐RETRN.

Page 40: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐40‐ January9,2018

Let’sdefinetheEGstripper,EGSTRIP.Doubleclickonthismodule;onthefirsttabset: KeeptheEquilibriumCalculationtype. Setthenumberofstagesto4.Thiswillcreateonestageforthereboiler,oneforthe

condenser,&2stageswithinthecolumnitself. Setthecondensertype

toPartial‐Vapor. SettheValidPhasesto

Vapor‐Liquid. EstimatetheReflux

Ratioas0.15(bymole)andtheBottomsRateas5333lb/hr(theratespecifiedfortheEGrecyclestream).Thesewillonlybeusedasestimates&willultimatelybereplacedbyotherdesignspecsonthecolumn.

ClickontheStreamstab.SettheRICHEGfeedstreamtostage3(thebottomstagerepresentingatray)&specifyAbove‐Stage.

EGstrippersoperatenearatmosphericconditiontokeepthereboilertemperaturesaslowaspossible.We’llfirstassumeazeropressuredropacrossthecolumn.SettheStage1/CondenserPressureto1atm&allpressuredropstozero.

Page 41: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐41‐ January9,2018

Eventhoughwe’vegivenanapproximatespecificationonthebottomofthisstripper(i.e.,thebottomsrate)whatwereallywanttospecifyglycolconcentration(83wt%).Let’sexpandtheSpecificationsitemintheleft‐handtreestructure,selectDesignSpecifications,&addaNewspec.SettheMasspurityas0.83.BasethispurityasfractionEGoutofanH2O&EGmixture(Componentstab).Finally,thisspecwillbeappliedtotheLEANEGstream.

Page 42: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐42‐ January9,2018

Toachievethisspecwemustadjustthereboileroperation.UnderSpecificationsclickVary&createaNewitem.SelectBottomsrateastheType.Putinfairlytightboundsonthisflowrate–uselower&upperboundsof5000to5500lb/hr.

Let’sdefinethecrossexchangerthatwillpreheatthecoldwater/EGfeedandrecoverheatfromtheleanglycolashotstripperbottoms.Bythewayyou’veattachedthestreamsyoushouldhaveCOLDWATRastheCOLDsideinletstream&LEANEGastheHOT.Let’signorepressuredropsfornow,sokeepthePressurevaluesas0.We’dliketostartthecalculationswithoutcreatingaheat‐basedrecycleloop,so,let’sspecifytheoutlettemperaturefortheCOLDsideas200°F.(ThisshouldallowthedutyrequiredtobepassedontotheHOTsideinafeed‐forwardmanner.)

WemustfinishspecifyingthepumpfortheEGreturnbeforewecanrunthesimulation.SpecifytheDischargepressureas400psia(tomatchuptheotherinletpressures)&thepumpefficiencyas0.75.

Page 43: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐43‐ January9,2018

Let’srunthesimulation&lookattheoverallresultsfortheEGstrippingsection.OnethingwecanseeisthatthevaporoffofEGSTRIPisalittlehigherthanexpected,215°F.Wewouldexpectittobecloserto212°Fifitwasnearlypurewater.

Let’slookatthecompositionsofthetop&bottomstreamsfromEGSTRIP.Double‐clickonEGSTRIP&selecttheStreamResultsoptionintheleft‐handtreestructure.ExpandtheMassFractionsitem.NotethatthebottomstreamLEANEGisasexpected,83wt%EGwithminimalamountsofhydrocarboncomponents.ButtheoverheadWATERVAPhasabout2wt%EGinit;thisrepresentsalossthat(1)needstobemadeupintheprocess&(2)needstobeaccountedforwhendischargingtotheenvironment.

FurthertuningoftheEGStripperoperationcouldbeperformedtoreducetheamountofEGlosttoWATERVAP.Let’salsolookatthereturntemperatureoftheleanEG,EG‐RETRN.Noticethatthepumpoutletis‐1°F.Thisisnotablefortworeasons:

Thisislowerthantheinitialspecthattheethyleneglycolwouldbeenteringat60°F.EGHXactuallyallowsustogettoocoldbyrecoveringtoomuchrefrigerationintheCOLDWATRstream.

Infact,thistemperaturemayactuallybetoolow.Typicalreturntemperaturesshouldbe40to55°F.ThishighertemperaturecouldbedirectlyspecifiedinEGHX;BUTassoonasyouchangethespecfromoneontheoutletofthehotsidetooneonthecoldsideyousetupa

Page 44: Simple Dew Point Control - AspenPlus v10inside.mines.edu/~jjechura/GasProcessing/Simple... · The gas is nearly saturated with water at the inlet conditions, 48 lb water per MMscf

Rev2.1 ‐44‐ January9,2018

recycleloop.ButyoucanmanuallyreducethetemperatureofTHERICHEGstreamuntilthetemperatureofEG‐RETRNrisesabove40°F.Reducingthespecfrom200°Fto160°Fwilldothis.

OptimizingProcessThebasicprocesshasnowbeensetup.Notethattherearethreemajorpowerusers:

ProductGasCompressor–4,024hp RecycleGasCompressor–112hp RefrigerationCompressor–7,963hp

Inadditiontherearetwomajorheatusers:

Stabilizer’sreboiler–3.3MMBtu/hr EGstripper’sreboiler–0.5MMBtu/hr.

Aquestionforoptimization–cananyofthesestreamsbereducedtoreducetheoperatingexpensefortheprocess?Somethoughts:

MostofthesevaluesaredependentontheoperatingconditionsofCOLDSEP.Thissetstheamountofgasthatneedstoberecompressed,theamountoflightendstotheSTABthatneedtobestrippedoff,compressed,&recycledback,andtheamountofwaterabsorbed&regeneratedinEGSTRIP.

Thebigoperatingcostandonethatcanbeaddressedwithfurtherdesignisthepowerneededfortherefrigerationloop.Therearetwowaysthatthiscouldbedone:

o WecouldtrytorecovertherefrigerationfromthecoldstreamsfromCOLDSEP.Bydoingsotherewouldbelessrefrigerationdutyneeded,reducingthepowerrequirementforREFCOMP.Also,bywarmingCOLDLIQbeforegoingtoSTABtheamountofreboilerdutywillalsobereduced.However,notethatbyincreasingthetemperatureofthegasbeforePRODCOMPtherequiredpowerinthiscompressorwillincrease,possiblynegatingthemajorityofthepowersavings.

o Wecouldincreasethenumberofrefrigerationstagesofcompressionwithassociaterecycleoftheintermediategasesfromtheintermediatestageeconomizers.Itistypicalthatatwo‐stagesystemcansaveabout20%ofthepowerrequiredbytherefrigerationsystem.