Upload
others
View
14
Download
1
Embed Size (px)
Citation preview
Gas Dehydration
Chapter 11Based on presentation by Prof. Art Kidnay
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Plant Block Schematic
2
Adapted from Figure 7.1, Fundamentals of Natural Gas Processing, 2nd ed.Kidnay, Parrish, & McCartney
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Reasons for Gas Dehydration
Field Operations▪ Prevent hydrate formation
▪ Minimize corrosion
• Need to dry gas to dew point below lowest operating temperature
Plant Operations▪ Need 4 to 7 lb/MMscf (85 to 150 ppmv) in pipeline
• Glycol dehydration most common to produce water contents down to 10 ppmv
▪ Need to have less than 1 ppmv H2O in gas to cryogenc units
• Glycol dehydration cannot get to these low water levels – mole sieves used for this service
3
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Topics
Water Content of Hydrocarbons
Gas Dehydration Processes▪ Absorption processes
▪ Adsorption processes
▪ Non regenerable desiccant processes
▪ Membrane processes
▪ Other processes
▪ Comparison of dehydration processes
Safety and Environmental Considerations
4
Updated: January 4, 2019Copyright © 2017 John Jechura ([email protected])
Water Content of Hydrocarbons
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Equilibrium considerations
Equal fugacities for each component in each phase. Between gas & water phases:
For a gas in contact with pure water:
Formation of the water phase will control the water content in the gas phase
▪ Increasing water in the feed increases the amount of free water, not the concentration of water in the gas.
▪ Can decrease the gas water content by adding compounds that are water soluble
6
= = =
, ,
, ,
where expsat
i
Pvapi L i Li i
i i i i
i V i V P
vPy x K K dP
P RT
=H2OH2O H2O since 1
vapPy x
P
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Water content of natural gasBased on “typical” gas composition
▪ Separate corrections for actual composition & acid gas content
Takes into account non-idealities
Take care if gas is specified as “wet” or “dry” basis – dry basis does not include the amount of water in the MMscf
▪ When less than 5,000 lb/MMscf the wet & dry values are within 0.5%
7
Fig. 20-4, GPSA Engineering Data Book, 13th ed.
Figure 11.1 in Kidnay et. al. text book
=+
=−
H2O H2OH2O H2O H2O
HC H2O
H2O H2O H2O H2OH2O
HC H2O
/Wet Basis: /
/ /Dry Basis:
1
N MX y M
N N
N M y MX
N y
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Water content of natural gas – typical pipeline specs
8
GPSA Engineering Data Book, 13th ed.
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Water content of natural gas
9
GPSA Engineering Data Book, 13th ed.
Figure 11.1 (b) & (c) in Kidnay et. al. text book
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Applicability of dehydration processes
10
1
10
100
1000W
et G
as W
ater
Co
nte
nt,
lb/M
Msc
f
Dry Gas Water Dew-Point, degrees F
806040200-20-40-60-80 100 120 140
Compression and Cooling
Liquid Desiccants
Glycol & Methanol
Molecular
Sieves
Enhanced Glycol
Alumina and
Silica Gel
Updated: January 4, 2019Copyright © 2017 John Jechura ([email protected])
Dehydration by Absorption
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Equilibrium considerationsGlycols tend to be only in the water phase (i.e., non-volatile & very low solubility in the hydrocarbon liquid phase)
For a gas in contact with water/glycol mixture:
Water content in the gas phase is less than that for a pure water phase since x’H2O < 1
Away from glycol, must reduce temperature to create a free water phase.
12
H2OH2O H2O
vapPy x
P
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Typical Glycols
EG DEG TEG
Name Ethylene Glycol
DiethyleneGlycol
TriethyleneGlycol
Formula C2H6O2 C4H10O3 C6H14O4
Molecular Weight 62.1 106.1 150.2
Boiling Point (°F) 386.8 473.5 550.4
Vapor pressure @ 77°F (mmHg) 0.12 < 0.01 < 0.01
Density @ 77°F (lb/gal) 9.26 9.29 9.34
Viscosity @ 77°F (cP) 16.9 25.3 39.4
Decomposition temperature (°F) 329 328 404
13
Fig. 20-50, GPSA Engineering Data Book, 13th ed.
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Glycol molecular structure
Ethylene glycol HO-CH2-CH2-OH
Diethylene Glycol HO-CH2-CH2-O-CH2-CH2-OH
Triethylene Glycol HO-CH2-CH2-O-CH2-CH2-O-CH2-CH2-OH
14
Chemical structures drawn using http://molview.org/
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Equilibrium water content above TEG solutions
15
Based on Fig 20-59 GPSA Data Book 13th ed. & Figure 11.3 in Kidnay et. al. text bookBased on 1,000 psia contactor pressure
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example – Equilibrium water content above TEG solutions
Operate a TEG contactor @ 100oF & 1,000 psiawith 99.9 wt% TEG introduced at the top
Dried gas is protected to a dew point of -40oF
16
Fig. 20-59, GPSA Engineering Data Book, 13th ed.Figure 11.3 in text book
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Equilibrium water content for TEG solutions
17
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Typical Glycol Dehydration UnitSystem
▪ 2 – 5 gal TEG per lb water removed
Absorber / Contactor
▪ 60 – 100oF inlet
▪ Can operate up to 2,000 psia
▪ Typically 4 – 10 bubble cap trays
• 25 – 30% efficiency
▪ 5 – 10 psi pressure drop
Flash tank
▪ 10 – 20 minute residence time
▪ 150oF, 50 – 75 psig
Regenerator
▪ Packed equivalent to 3 – 4 trays
▪ 375 – 400oF
18
Fig. 20-58, GPSA Engineering Data Book, 13th ed.Basis for Figure 11.2 in text book
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Typical Glycol Dehydration UnitSystem
▪ 2 – 5 gal TEG per lb water removed
Absorber / Contactor
▪ 60 – 100oF inlet
▪ Can operate up to 2,000 psia
▪ Typically 4 – 10 bubble cap trays
• 25 – 30% efficiency
▪ 5 – 10 psi pressure drop
Flash tank
▪ 10 – 20 minute residence time
▪ 150oF, 50 – 75 psig
Regenerator
▪ Packed equivalent to 3 – 4 trays
▪ 375 – 400oF
19
H2O H2O H2Ovapy P x P
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-11
30 MMscfd of a 0.65 gravity natural gas enters a TEG contactor at 600 psia and 100oF. The outlet water content specification is 7 lb H2O/MMscf and the TEG circulation rate is 28 lb TEG/ lb H2O absorbed (3 gal TEG/lb H2O). How much water is to be absorbed? What is the rich TEG concentration? What is the lean TEG concentration?
▪ Water content at inlet conditions?
70 lb/MMscf
▪ How much water is removed?
20
lb H2O lb TEG1890 28
day lb H2O
lb TEG52920
day
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-11
30 MMscfd of a 0.65 gravity natural gas enters a TEG contactor at 600 psia and 100oF. The outlet water content specification is 7 lb H2O/MMscf and the TEG circulation rate is 28 lb TEG/ lb H2O absorbed (3 gal TEG/lb H2O). How much water is to be absorbed? What is the rich TEG concentration? What is the lean TEG concentration?
▪ How much TEG is circulated?
21
lb H2O lb TEG1890 28
day lb H2O
lb TEG52920
day
lb H2O gal TEG1890 3
day lb H2O
hr min24 60
day hr
gal TEG3.9
min
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-11 (#2)
30 MMscfd of a 0.65 gravity natural gas enters a TEG contactor at 600 psia and 100oF. The outlet water content specification is 7 lb H2O/MMscf and the TEG circulation rate is 28 lb TEG/ lb H2O absorbed (3 gal TEG/lb H2O). How much water is to be absorbed? What is the rich TEG concentration? What is the lean TEG concentration?
▪ Dew point temperature at thecontactor pressure (600 psia)?
~ 24oF
22
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-11 (#3)
30 MMscfd of a 0.65 gravity natural gas enters a TEG contactor at 600 psia and 100oF. The outlet water content specification is 7 lb H2O/MMscf and the TEG circulation rate is 28 lb TEG/ lb H2O absorbed (3 gal TEG/lb H2O). How much water is to be absorbed? What is the rich TEG concentration? What is the lean TEG concentration?
▪ What is the minimum TEG concentration for a 24oF dew point & the contactor temperature (100oF)? ~98.5 wt%
• Lean TEG has 806 lb/day water
▪ Rich TEG content (after absorbing the water from the wet gas)
23
( )
+ +
lb TEG52920
day
lb H2O lb TEG1890 806 52920
day day
95.2 wt% TEG
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Solubility of hydrocarbons in glycol solutions
Methods to control BTEX emissions from Regenerator
▪ Condense overhead & recover
▪ Burn vent gas through flare or thermal oxidizer
▪ Recycle back to process
24
GPSA Engineering Data Book, 13th ed.
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Field Glycol Dehydrator
25
reboiler
contactor
gas burner
heat exchanger,surge tank
Flash separator3-phase, gas,glycol,condensate
Inlet separatorglycol pump
stripper
From Sivalls, “Glycol Dehydration Design,” LRGCC, 2001
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Common Operational Problems
Contactor foaming▪ Contaminates: hydrocarbons, salts, particulates, inhibitors, O2
Poor dehydration (from source other than foaming)▪ Gas rate too low - 80% flow reduction = 20 % tray eff
▪ Glycol rate low - 75% flow reduction = 33% tray eff
▪ Glycol inlet temperature too high
Flash drum / Foaming in Still▪ Presence of heavy hydrocarbons
26
Updated: January 4, 2019Copyright © 2017 John Jechura ([email protected])
Dehydration by Adsorption
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Absorption vs Adsorption
28
Absorption Adsorption
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Adsorption fundamentals
Two types of adsorption▪ Chemisorption
• Chemical interaction between adsorbate and adsorbent
• May not be completely reversible
▪ Physical adsorption
• Only physical interaction between adsorbate and adsorbent
• Completely reversible
-ΔHChem >> -ΔHPhys
30
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Physical Adsorption Fundamentals
Factors affecting selectivity ▪ Size – adsorbent pore diameter major factor
▪ Volatility – less volatile displaces more volatile (e.g., C3 displaces C2)
▪ Polarity
• For desiccants, more polar displaces less polar (e.g., CO2 displaces C2, MeOH displaces CO2, water displaces MeOH)
31
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Adsorption Isotherms
32
From UOP
1.0 E-8 1.0 E-7 1.0 E-6 1.0 E-5 1.0 E-4 1.0 E-3 1.0 E-2 1.0 E-1 1.0 E0 1.0 E+1 1.0 E+2 1.0 E+3 1.0 E+4
5
0
10
15
20
25
600 °F
500 °F
400 °F
150 °F
100 °F
77 °F
32 °F
Partial Pressure of Water, psia
Lb W
ate
r A
dso
rbed /
100 lb A
ctiv
ate
d A
dso
rbent
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Solid Desiccant Dehydrator – Twin Tower System
33
Fig. 20-76, GPSA Engineering Data Book, 13th ed.
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Typical Vessel Loading
6 in of 1/2 in
diameter
ceramic balls
3 in of 1/4 in
diameter
ceramic balls
3 in of 1/2 in
diameter
ceramic balls
floating screen
fixed screen
32,200 lb
MS 4A
4x8 mesh
(1/8 inch)
bed diameter,
7.5 ft
bed height,
16.2 ft
Possible configuration for drying 100 MMscfd to a dew pointof -150ºF, adsorption time ~12 hours
Sample packing of catalyst/dessicant on top of supports
Model prepared by Enterprise Products
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Concentration Profile
35
Equilibrium Zone (Saturated)
Mass Transfer Zone (Partially saturated)
Active Zone (Unsaturated)
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Concentration Profile
36
Time
Vap
or
Co
nce
ntr
atio
n
yIn
0yOut
Dry Break-Through Saturated
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Regenerating Bed Temperature History
37
Heat On
Inlet Temperature
Desorption
Bed Heating Bed Cooling
Outlet Temperature
0 1 2 3 4 5 7 86
Time, Hours
Tem
per
atu
re, º
F
100
200
300
400
600
500
0
Tem
pe
ratu
re, º
C
50
100
150
200
250
300
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Common Adsorbents for Drying
In order of increasing cost:
Silica gel (SiO2)▪ Min exit water content 10 to 20 ppmv (~-60oF)
▪ Inert and used for inlet concentrations of > 1 mol%
Activated Alumina (Al2O3)▪ Min exit water content 5 to 10 ppmv (~-100oF)
▪ High mechanical strength but more reactive
Molecular Sieve (4A and 3A)▪ Min exit water content below 0.1 ppmv (~-150oF)
▪ Highest surface area
▪ Composite of sieve and clay binder
38
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Design stepsDetermine size of vessels for adsorption
▪ Determine the bed diameter based on superficial gas velocity / allowable pressure drop
• Too small – pressure drop will be too high & can damage the sieve
• Too large – need too high a regeneration gas rate to prevent channeling
• Typically use (-P/L) < 0.33 psi/ft with a total pressure drop of 5 – 8 psi max
▪ Choose an adsorption period & calculate the mass of desiccant
• Sets the bed height – contributions from saturation zone & mass transfer zone heights
• 8 to 12 hour periods with 2 or 3 beds are common
o Too long – more desiccant & larger vessels needed than necessary
o Too short a time – shorter desiccant life
Regeneration
▪ Calculate heat required to desorb water while also heating the desiccant & vessel
▪ Total amount of regeneration gas flow calculated based on heating phase about 50-60% of total regeneration time
▪ Regeneration gas flowrate should give a pressure drop gradient of at least 0.01 psi/ft
39
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Design equations (#1)
Determine gas velocity for bed diameter
▪ Modified Ergun equation for pressure drop
• Viscosity [cP] & density [lb/ft³] determined at inlet conditions
• Solve quadratic equation for maximum superficial velocity (Vmax [ft/min]) for 0.33 psi/ftpressure drop
• Pressure drop gradient in units of psi/ft
▪ Minimum diameter
▪ Adjust diameter upwards to nearest ½ foot increment
• Recalculate superficial linear velocity & pressure drop using adjusted diameter
40
= + 2P
B V C VL
=
min
max
4 mD
V
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Design equations (#2)
Determine bed length (method 1)
▪ Amount of desiccant in saturation zone
Assumes 13 lb water per 100 lb dessicant
▪ Amount of desiccant in the mass transfer zone (MTZ) (GPSA EDB method)
where CZ is 1.70 ft for 1/8 inch sieve & 0.85 for 1/16 inch sieve
… or Trent method for MTZ
41
= =
water satsat sat 2
bulk
4
0.13 SS T
m SS L
C C D
=
0.3
MTZ
ft/minft
35Z
VL C
( )= +0.636 0.0826 ln %satSSC
( )= − 1.20 0.0026 FTC = +MTZ ft 2.5 0.025 ft/minL V
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Design equations (#3)
Determine bed length (method 2)
▪ Calculate “effective desiccant capacity” which includes the MTZ effect, temperature, and relative humidity corrections. An effective capacity of 8–10% is typically assumed.
Finalize bed length
▪ Total bed height (Lsat+LMTZ or Lbed) but should not be less than the bed diameter or 6 ft, whichever is greater
▪ Total bed pressure drop should be 5 – 8 psi max
• If too large increase the bed diameter
Determine vessel height & weight
▪ Total bed height plus other allowances – at least 3 ft (for inlet distributor on top and bed support & hold down balls underneath)
42
= =
water bedbed bed 2
bulk
4
eff
m SS L
C D
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Design equations (#4)
Regeneration calculations
▪ Used to determine the required regeneration gas flow & the fuel gas requirements
• If regeneration gas recycled back to inlet of mole sieves then you must add this rate to that of the feed gas for the bed calculations
▪ Heat loads
• Heat to desorb water – increase water to its desorption temperature, break adherence to surface, & vaporize
o Use 1,800 Btu/lb water adsorbed for conservative design
• Heat to increase sieve to regeneration temperature
• Heat to increase vessel to regeneration temperature
• Heat losses – typically estimated as 10%
43
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Design equations (#5)
Regeneration Calculations (cont.)
▪ Calculation of vessel weight for heating calculations
where the 0.75D term accounts for the weight of the vessel heads
• Design pressure in psig. Usually 10% greater than operating pressure (minimum 50 psig)
▪ Usually have to heat the regeneration gas 50oF hotter than the desired regeneration temperature (e.g., 500oF gas needed to regenerate at 450oF)
▪ Total regeneration load 2.5 times the minimum load
• Assumes only 40% of the heat is transferred from gas to mole sieve system.
• The remainder exits as hot gas. Need to size downstream coolers appropriately.
▪ Regen gas flowrate. Check that pressure drop gradient at least 0.01 psi/ft
44
( )( )= + = + +−
design
steel vessel
design
12in 0.0625 and lb 155 0.125 0.75
37600 1.2
D Pt m t L D D
P
( )= =
−
Total Regen rg
Regen Gas rg 2hot bed rg
4
P
Q mm V
C T T D
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14
100 MMscfd natural gas (molecular weight of 18) is water saturated at 600 psiaand 100oF & must be dried to –150oF dew point. Determine the water content of the gas (inlet & outlet) & amount of water that must be removed.
Do preliminary design of a molecular-sieve dehydration system consisting of two towers with down-flow adsorption in one tower and up-flow regeneration in the other. Use 4A molecular sieve of 1/8″beads (i.e., 4x8mesh). The regeneration gas is part of the plant’s residue gas (at 600 psia and 100oF) & has a molecular weight of 17. The bed must be heated to 500oF for regeneration. Base this on a 24-hour cycle consisting of 12 hours adsorbing and 12 hours regenerating (heating, cooling, standby, and valve switching; the heating time is 60% of the regeneration time).
45
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#2)
100 MMscfd natural gas (molecular weight of 18) is water saturated at 600 psiaand 100oF & must be dried to –150oF dew point. Determine the water content of the gas (inlet & outlet) & amount of water that must be removed.
▪ Water content at inlet conditions?
70 lb/MMscf
▪ Water content at outlet conditions?
Essentially 0 lb/MMscf
▪ How much water is to be removed?
46
( ) 70 0 lb/MMscf 100 MMscfd
7,000 lb/day
−
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#3)
… Do preliminary design of a molecular-sieve dehydration system consisting of two towers with down-flow adsorption in one tower and up-flow regeneration in the other. Use 4A molecular sieve of 1/8″ beads (i.e., 4x8 mesh)…
▪ Determine bed diameter. Velocity criteria not given so determine from allowable pressure drop (0.33 psi/ft max)
• Ideal gas flowrate at inlet conditions (600 psia and 100oF)
• Real gas flow much different? Estimate: Z=0.93
47
( )
( )
+ = =
+
3 36 6
IG
100 460 °Rft 14.7 psia ft100 10 2.6 10
day 600 psia 60 460 °R dayV
( )
= = =
3 3 36 6
IG
ft ft ft0.93 2.6 10 2.5 10 1700
day day minactV Z V
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#3)
… Do preliminary design of a molecular-sieve dehydration system consisting of two towers with down-flow adsorption in one tower and up-flow regeneration in the other. Use 4A molecular sieve of 1/8″ beads (i.e., 4x8 mesh)…
▪ Determine bed diameter. Velocity criteria not given so determine from allowable pressure drop (0.33 psi/ft max)
• Real gas density at inlet conditions (600 psia and 100oF)
• Gas viscosity at inlet conditions (600 psia and 100oF). Estimate 0.015 cP.
• Velocity vs. pressure gradient. For given beads & gas properties:
48
( )( )
( )( )( ) = = =
3
600 18 lb1.93
0.93 10.7316 560°R ft
PM
ZRT
( )( ) ( )( )−
= +
= + =
2
5 2 ft0.33 0.056 0.015 8.89 10 1.93 41.4
min
PB u C u
L
u u u
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#4)
… Do preliminary design of a molecular-sieve dehydration system consisting of two towers with down-flow adsorption in one tower and up-flow regeneration in the other. Use 4A molecular sieve of 1/8″ beads (i.e., 4x8mesh)…
▪ Determine bed diameter. Velocity criteria not given so determine from allowable pressure drop (0.33 psi/ft max)
• Minimum diameter is ratio of volumetric flowrate to maximum velocity. Scale up to next 6”.
49
= = = =
2
min
ft4 1700
min7.2 ft D=7.5 ft
ft441.4
min
actVDA D
u
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#5)
… Do preliminary design of a molecular-sieve dehydration system consisting of two towers with down-flow adsorption in one tower and up-flow regeneration in the other. Use 4A molecular sieve of 1/8″ beads (i.e., 4x8mesh)…
▪ Determine bed diameter. Velocity criteria not given so determine from allowable pressure drop (0.33 psi/ft max)
• Determine actual gas velocity & pressure drop in absorbing bed
50
( )( )
= = = =
3
22
4 1700 ft /min438.5 ft/min
7.5 ft
V Vu
A D
( )( )( ) ( )( )( )−
= +
= + =
2
25 psi0.056 0.015 38.5 8.89 10 1.93 38.5 0.29
ft
PB u C u
L
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#6)
… Base this on a 24-hour cycle consisting of 12 hours adsorbing and 12 hours regenerating (heating, cooling, standby, and valve switching; the heating time is 60% of the regeneration time).
▪ Since the overall removal rate is 7,000 lb/day we must have enough adsorbent to safely contain 3,500 lb of water (corresponding to the adsorbing time).
▪ No other criteria given for amount of water to be contained by desiccant –determine size using the zone analysis (method 1)
• Size saturation zone to contain all water for the cycle. Use a typical sieve bulk density of 45.0 lb/ft3
51
( ) ( )
( ) ( )
= = =−
= = =
watersat
satsat 22
bulk
350028,600 lb sieve
0.13 0.13 1 1.20 0.0026 100
4 4 2860014.4 ft
7.5 45.0
SS T
mS
C C
SL
D
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#7)
… Base this on a 24-hour cycle consisting of 12 hours adsorbing and 12 hours regenerating (heating, cooling, standby, and valve switching; the heating time is 60% of the regeneration time).
▪ … determine size using the zone analysis
• Add appropriate length for the mass transfer zone (MTZ) to ensure no breakthrough of water. CZ=1.7 for this size sieve
• Total bed height is the sum of these two zones. Total vessel height adds 3 ft for supports, …
52
( )
= = =
0.3 0.3
MTZ
38.61.7 1.74 ft
35 35Z
uL C
= + = + = = + =Bed sat MTZ vessel Bed14.4 1.74 16.1 ft 3 19.1 ftL L L L L
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#7)
… Base this on a 24-hour cycle consisting of 12 hours adsorbing and 12 hours regenerating (heating, cooling, standby, and valve switching; the heating time is 60% of the regeneration time).
▪ … determine size using the zone analysis
• Check that the bed length is at least the bed diameter (here 7.5 ft) or 6 ft, whichever is greater.
o This bed depth does not need to be adjusted
• Check that total pressure drop is 5 – 8 psi. If too small, add bed height; if too large, add diameter
53
( )( )
= =
bed 0.29 16.1 =4.7 psi (close enough)p
p LL
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#8)
… The regeneration gas is part of the plant’s residue gas (at 600 psia & 100oF) & has a molecular weight of 17. The bed must be heated to 500oF for regeneration…
▪ Determine amount of heat needed for regeneration
• Heat to desorb water
• Heat the sieve to regeneration temperature
54
( ) ( )( )= = =3500 1800 6,300,000 Btuw w wQ m H
( ) ( )
( ) ( )( )( )( )
= − = −
= −
=
2
, ,
2
4
7.5 16.1 45.00.24 500 100
4
3,070,000 Btu
bed bulksi si p si regen ads p si regen ads
D LQ m C T T C T T
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#9)
… The regeneration gas is part of the plant’s residue gas (at 600 psia & 100oF) & has a molecular weight of 17. The bed must be heated to 500oF for regeneration…
▪ Determine amount of heat needed for regeneration (cont.)
• Heat the steel to regeneration temperature
55
( )( )( )( )
= −
= −
=
,
50620 0.12 500 100
2,430,000 Btu
steel steel p steel regen adsQ m C T T
( ) ( ) ( )
( )( )
( )( )( )
= +−
−= + =
− −
= + +
= + + =
design
design
steel vessel
12in 0.0625
37600 1.2
12 7.5 1.1 600 14.70.0625 1.636 in
37600 1.2 1.1 600 14.7
lb 155 0.125 0.75
155 1.636 0.125 19.1 0.75 7.5 7.5 50620 lb
D Pt
P
m t L D D
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#10)
… The regeneration gas is part of the plant’s residue gas (at 600 psia & 100oF) & has a molecular weight of 17. The bed must be heated to 500oF for regeneration…
▪ Determine amount of heat needed for regeneration (cont.)
• Total regeneration heat needed
▪ Determine amount & rate of regen gas needed
• Heat that must be transferred to the regeneration gas
56
( )( )
( )( )
= + + + = + + +
= + + +
=
1
6,300,000 3,070,000 2,450,00 1 0.10
13,002,000 Btu
regen w si steel loss w si steel lossQ Q Q Q Q Q Q Q f
( )= =2.5 2.5 13,002,000 =32,505,000 Bturg regenQ Q
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#11)
… The regeneration gas is part of the plant’s residue gas (at 600 psia & 100oF) & has a molecular weight of 17. The bed must be heated to 500oF for regeneration…
▪ Determine amount & rate of regen gas needed (cont.)
• Determine amount regen gas needed
• Determine rate of regen gas needed
57
( ) ( ) ( )= = =
+ −−,
32,505,000111,100 lb
0.65 500 50 100
rg
rg
p rg rg cold
Qm
C T T
( )= = =
111,10015,430 lb/hr 257 lb/min
0.6 12
rg
rg
mm
t
, 0.65 Btu/lb F (based on Fig. 23-48 in GPSA EDB averaged between 100 & 550 F)o op rgC
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Example based on GPSA Data Book example 20-14 (#12)
… The regeneration gas is part of the plant’s residue gas (at 600 psia & 100oF) & has a molecular weight of 17. The bed must be heated to 500oF for regeneration…
▪ Verify there is sufficient pressure drop during regeneration to prevent channeling (i.e., pressure drop is above 0.01 psi/ft)
• For the hot regen gas (@ 550oF):
Flow rate is sufficient
58
( )( )
( )( )( ) = = =
+ 3
600 17 lb0.94
1 10.7316 550 460 ftrg
PM
ZRT
= 0.023 cP (from Fig. 23-23 in GPSA EDB)
( )( )( ) ( )( )( )−= + = + =
22 5 psi0.056 0.023 6.2 8.89 10 0.94 6.2 0.011
ft
PB u C u
L
( )= = = =
22
4 4 2576.2 ft/min
0.947.5
rg rg
rg
rg
V mu
A D
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Common Mole Sieve Operational Problems
Loss of bed capacity▪ Aging, rapid initial loss then
gradual loss over years
▪ Coking by partial oxidation of heavy hydrocarbons
▪ Coking by conversion of H2S to elemental sulfur
▪ Poor regeneration
Increased pressure drop▪ Attrition
▪ Caking at top of bed
Fines▪ Attrition
▪ Failed bed support
COS formation▪ Chemical equilibrium
H2S + CO2 COS + H2O
59
Updated: January 4, 2019Copyright © 2017 John Jechura ([email protected])
Other Dehydration Processes
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Other processes
Consumable salts (CaCl2)
Refrigeration with MEOH addition, more complex
Membranes, ideal for remote sites when low pressure permeate gas can be used effectively
If drying high pressure gas:▪ Vortex tube – one application known
• Simple but poor turndown ratio and efficiency
▪ Twister Supersonic Separator one known offshore application
• Simple, poor turndown ratio but better efficiency
61
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Twister Operating Principle
Acceleration to Mach >1 cools gas (typically 60 – 80oC) ΔP = 30%
Cooling causes condensation (water and heavier hydrocarbons)
Swirl centrifuges liquid droplets to the tube wall
Drainage section removes liquid film from the wall + ~20% gas
Diffuser section recompresses the gas
62
http://twisterbv.com/PDF/resources/Twister_-_How_Does_It_Work.pdf
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Comparison of Dehydration Processes
For < 1 ppmv H2O need mole sieve.
For higher concentrations:▪ Glycol (usually TEG) widely used
• Minimal manpower requirements
• High turndown
▪ Regenerative desiccants (silica gel, alumina) more costly
▪ Membranes, and Twister(?) where pressure drop acceptable
▪ Nonregenerative desiccants (CaCl2) for remote, low water content gas
63
Updated: January 4, 2019Copyright © 2017 John Jechura ([email protected])
Summary
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Summary
Water content can be estimated from Fig. 20-4▪ Units of lb/MMscf
▪ Wet & dry bases essentially the same below 5,000 lb/MMscf
Three primary separation technologies▪ Bulk removal by cooling & separation
▪ TEG dehydration to pipeline specs (4 – 7 lb/MMscf)
▪ Mole sieves required upstream of cryogenic applications
65
Updated: January 4, 2019Copyright © 2017 John Jechura ([email protected])
Supplemental Slides
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Glycol Dehydration Unit
67
contactor
stripping still
reboiler
http://www.kirkprocess.com/products/highspeed-gas-dehydration/
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Glycol Dehydration Unit
68
contactor
stripping still
reboiler
http://www.en-fabinc.com/en/glycol_dehydration_system.shtml
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Mole Sieve Dehydration Unit
69
http://www.enerprocess.com/processing-&-treating-units/gas-conditioning-&-treating/mol-sieve-dehydration-units
Updated: January 4, 2019Copyright © 2019 John Jechura ([email protected])
Zeolite structures
Zeolite A Zeolite X
70