Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

Embed Size (px)

Citation preview

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    1/16

    Guide for electrical design engineers

    Zbigniew HanzelkaAGH-University of Science & Technology

    Powe

    rQuality

    Power Quality

    Mitigation of voltage unbalance

    U12

    U23

    U31

    U2

    U3

    U1

    I23=IC

    I31=IL

    I12

    I1=I12-I31

    I2=I23-I12

    I3=I31-I23

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    2/16

    2

    http://www.leonardo-energy.org

    Power Quality

    1. Introduction

    When the limit values o unbalance actor, specifed in standards are exceeded, the use o symmetrizatin systems

    is required. A symmetrizator should not cause signifcant active power losses during operation; it implies that the

    symmetrization process shall be carried out by means o reactive elements (LC) or using active methods (power

    electronic systems).

    2. Symmetrization of the load currents

    The urther analysis, using the method o symmetrical components, concerns the system node in the confguration

    as in Figure 1. An asymmetrical load (A), symmetrical load (S) and compensator (K) are connected to substation bus-

    bars o phase voltage U, supplied rom three-phase symmetrical system.

    AI 3AI 1

    KI 3KI 1

    3E

    1E

    3U

    2U

    1U

    COMPENSATOR

    (K)

    SYMETRIC

    LOAD

    (S)

    ASYMETRIC

    LOAD (A)

    1I

    3I

    2E

    Fig. 1. Diagram of the analysed node

    Since the system o electromotive orces (E) and the supply line are symmetrical, it is assumed that the voltage

    unbalance at the load terminals is caused by the asymmetry o the load currents. It means that, i the asymmetry

    o the load currents is eliminated, the voltages at the point o the load connection orm the symmetrical three-phase

    system. This is the case o the supply system protection, and the loads connected to it, against the asymmetry caused

    by asymmetrical currents o the load (A) and resulting asymmetrical voltage drops across the equivalent impedances

    o supply system (on assumption identical in all phases: Z Z Z 1 2 3= = ).

    An obvious conclusion rom Figure 1 is that the voltage unbalance at PCC, caused by the load asymmetry, can be mitigated

    by reduction o the phase equivalent impedances (short-circuit impedances) i.e. by increasing the short-circuit capacity at

    the point o load connection, what in practice means connecting the load to the point o the system o higher voltage.

    3. The natural symmetrization The frst and the most basic operation o the symmetrization process is the arrangement o the actual load

    connections between the system phases, in such a way that the current unbalance actor (and hence the voltage

    unbalance actor) was the smallest possible value. In case o connecting a single load to the network, the level

    o unbalance (measured by the current unbalance actor or zero- or negative-sequence component) does not depend

    on phase-to-phase or phase-to-neutral voltage, where the load is connected. Similarly, when connecting two single-

    element loads, the level o unbalance does not depend on which voltages the loads are connected. However, when

    these loads will have a dierent character then, in terms o the natural symmetrization (i.e. the symmetrization,

    which does not require any additional elements), it is important to take into account the character o the loads and

    phase angles o the voltages they are connected to.

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    3/16

    3

    http://www.leonardo-energy.org

    Mitigation of voltage unbalance

    EXAMPLE 1

    For the system of three loads on nominal voltage 380 V and powers, respectively: P1

    = 7.22 kW, Q1

    = 7.22 kVAR (ind.);

    P2

    = 7.22 kW, Q2

    = 7.22 kVAR (cap.); P3

    = 7.22 kW, Q3

    = 0 delta-connected, supplied from three-phase 3x380/220V

    network, determine the arrangement of their connections to the network phases, ensuring minimum value of the

    current unbalance factor.________________________

    From the load active and reactive power the elements of its equivalent admittance can be determined, i.e.: the

    susceptance (B =Q

    U2) and conductance (G =

    P

    U2) (Fig. 2).

    GB

    Load

    (P, Q) U NUN

    Y

    Fig. 2. The load (P - active power, Q - reactive power) and its equivalent admittance

    Hence:

    Y G jBP

    Uj

    Q

    U

    kW

    Vj

    kVAR

    VA A A1 1 1

    1

    2

    1

    2 2 2

    7 22

    380

    7 22

    3800= + = = =

    .

    ( )

    .

    ( )( .005 0 05j S. )

    Y G jBP

    Uj

    Q

    U

    kW

    Vj

    kVAR

    VA A A2 2 2

    2

    2

    2

    2 2 2

    7 22

    380

    7 22

    3800= + = + = + =

    .

    ( )

    .

    ( )( .005 0 05+j S. )

    Y G jB PU

    jQU

    kWV

    j kVARV

    SA A A3 3 33

    2

    3

    2 2 27 22

    380

    0

    3800 1= + = + = + =.

    ( ) ( ).

    Variant 1 Loads connected as in Fig. 3:

    Y YA A12 1=

    Y YA A23 2=

    Y YA A31 3=

    Fig. 3. Variant 1 of load connection

    The current unbalance factor: kI

    I

    a Y Y aY

    Y Y YI

    A A A

    A A A

    %

    ( )

    ( )% % . %= =

    + +

    + +=

    2

    1

    212 23 31

    12 23 31

    100 100 68 3

    a j j= = +exp( )120 12

    32

    0

    a j j2 0120 12

    32

    = = exp( )

    1

    2

    3

    AY12

    AY23

    AY31

    AI1

    AI2

    AI3

    AI 31

    AI23

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    4/16

    4

    http://www.leonardo-energy.org

    0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

    -400

    -300

    -200

    -100

    0

    100

    200

    300

    400 Three-wire network voltages

    Time [s]

    Voltages[V

    ]

    0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

    -40

    -30

    -20

    -10

    0

    10

    20

    30

    40

    Three-wire network currents

    Time [s]

    Currents[A]

    Fig. 4. Voltage waveforms: Example 1 Variant 1 Fig. 5. Current waveforms: Example 1 Variant 1

    See Figures 4 and 5.

    Variant II - Y YA A12 1=

    Y YA A23 3=

    Y YA A31 2=

    The current unbalance actor: kI

    I

    a Y Y aY

    Y Y YI

    A A A

    A A A

    %

    ( )

    ( )% % . %= =

    + +

    + +=

    2

    1

    2

    12 23 31

    12 23 31

    100 100 18 3

    This is the minimal value o the current unbalance actor, which can be obtained connecting the impedances

    to phase-to-phase voltages in various confgurations. This confguration has been taken or urther considerations (Fig. 6).

    0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

    -40

    -30

    -20

    -10

    0

    10

    20

    30

    40

    Three-wire network currents

    Time [s]

    Currents[A]

    Fig. 6. Waveforms of currents: Example 1 Variant 2

    In cases, where the negative component cannot be su ciently reduced solely by means o the more uniorm

    distribution o the loads between phases, compensators are used. The purpose o the compensation systems is usually

    the elimination or mitigation o the negative- and zero-sequence component o currents at the point o connection

    o asymmetric load. Such process is called symmetrization.

    4. Compensator/symmetrizator

    In the three wire MV systems, usually operated as the isolated neutral point or compensated systems, asymmetrical

    loads are connected on phase-to-phase voltages. In such case, there is no zero-sequence component o currents,

    thereore the symmetrization resolves into elimination or mitigation o the negative-sequence component. The

    LV systems are typically our-wire networks, with grounded neutral point, thus the negative-sequence and zero-

    sequence components are present. The symmetrizator (K) is connected in parallel to the asymmetric load (A) (Fig. 1).

    The symmetrizator causes the currents I1K

    , I2K

    , I3K

    , which adding to the load currents I1A

    , I2A

    , I3A

    , result in the balanced

    system o the source currents I1, I

    2, I

    3, according to the equation:

    I I IA K1 1 1= + I I I a I A K2 2 22

    1= + = I I I aI A K3 3 3 1= + = (7)

    Power Quality

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    5/16

    5

    http://www.leonardo-energy.org

    As the currents drawn rom the network orm a balanced system, thereore the negative-sequence and zero-sequence

    components are equal zero:

    I I aI a I ( ) ( )2 1 22

    3

    1

    3

    0= + + = I I I I ( ) ( )0 1 2 31

    3

    0= + + = (8)

    The load to be balanced can be represented in general as a circuit o six elements in the star/delta connection (Fig. 4),

    where individual elements are connected to phase-to-neutral, as well as to phase-to-phase voltages. The impedances

    Z Z Z Z Z Z A A A A A A12 23 31 1 2 3, , , (or admittances Y Y Y Y Y Y A A A A A A12 23 31 1 2 3, , , ), which in the diagram represent the actual

    load, can be unctions o time.

    )( 1212 AAYZ

    )( 21 AAYZ

    )( 2323 AA YZ )( 22 AA YZ

    )( 3131 AA YZ )( 33 AA YZ

    1 3 02

    Fig. 4. General diagram of the three-phase unbalanced load

    To establish the rules o compensation and symmetrization, the values o specifed impedances should be assumed

    constant, and generally dierent rom each other. This does not exclude considerations on their variability in time.These impedances can be regarded as a representation o the time-varying load, but only in the specifc, selected

    instants o time the sampling instants. The set o such constant values o impedances represents the load at discrete

    instants o time.

    The compensation o asymmetric load will be understood as the compensation o reactive part o the positive-

    sequence symmetrical component (reactive power compensation or the undamental requency) and o the zero-

    sequence component (or three-phase, our-wire systems) and negative-sequence component or the undamental

    requency. Among various possible methods, the inductive-capacitive systems are o particular importance. Their

    practical applications are certain solutions o static ollow-up compensators.

    5. The compensator/symmetrizator parameters

    The symmetrization and compensation o the undamental harmonic reactive current is a process, which in practice

    consists in connecting in parallel to the asymmetric load the asymmetric reactive elements (reactors, capacitors)

    o such values as to ulfl the conditions (9):

    I IA K( ) ( )2 2 0+ = I IA K

    ( ) ( )0 0 0+ = Im ( ) ( )I I IA K1 1

    0+ = (9)

    where: I I IA A A( ) ( ) ( ), ,0 1 2 , I I IK K K

    ( ) ( ) ( ), ,0 1 2 are symmetrical components o the asymmetric load and compensator (index (K))

    currents, respectively or the zero- (0), positive- (1) and negative-sequence component; Im ( )IA1 denotes the reactive

    part o the positive-sequence o the load current component (imaginary part in complex numbers notation); I0

    is the value o reactive current, which is the measure o the load non-compensating level permitted in the supply

    conditions by electrical power supplier. Thus, according to the presented notation, the processes o the reactive

    current compensation and symmetrization (or the zero-sequence and negative-sequence component) have been

    separated.

    Mitigation of voltage unbalance

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    6/16

    6

    http://www.leonardo-energy.org

    For the load as in Fig. 4, the relations, describing the values o the negative- and zero-sequence symmetrical

    components can be written as ollows (according to (8)):

    I U Y aY a Y a Y Y aY A A A A A A A( )2

    1 22

    32

    12 23 31

    1

    3= + +( ) + +( )

    (10a)

    IU

    Y a Y aY A A A A( )0

    12

    2 33= + +( ) (10b)

    I the expressions (10) are not identically equal zero, and the asymmetry level is inadmissibly high, the load symmetrization

    is needed and can be made by connecting a symmetrization-compensating device with elements B B BK K K1 2 3, , connected

    to the phase-to-neutral voltages and B B BK K K12 23 31, , connected to the phase-to-phase voltages. The problem resolves into

    fnding the compensating susceptances, which in connection with the admittances to be compensated will constitute

    a symmetric load. The relations, where the parameters o symmetrizator/compensator are expressed as a unction

    o the equivalent impedances (admittances) o the load to be compensated/symmetrized, will be presented urther in

    this paper. This is particularly useul when designing a symmetrizator. The symmetrizator parameters can be expressed

    as a unction o other quantities, which describe a compensated load, i.e.: the current symmetrical components, values

    o phase currents or powers, instantaneous values o phase voltages and currents, etc.

    6. Symmetrization of a star-connected load with neutral conductor elimination of the zero-sequence symmetrical component

    In this case the process o compensation comprises o two stages. The frst one concerns the elimination o the

    zero-sequence symmetrical component elimination o the current in neutral conductor. The confguration in Fig. 5

    has been taken or urther considerations; it is distinguished by the minimum value o the current unbalance actor

    (the values o elements as in the EXAMPLE 1).

    AY

    1

    1

    AY

    2

    2

    AY

    3

    3

    NI

    AI1

    AI2

    AI3

    Fig. 5. Three-phase four-wire network - star-connected load

    EXAMPLE 2

    U V1 220= U a V2 2 220= U a V3 220=

    I U Y j j AA A1 1 2 220 0 05 0 05 11 11= = + = +( . , ) ( )

    I U Y j AA A2 2 1 15 026 4 026= = ( . . )

    I U Y j AA A3 3 3 11 19 052= = ( . )

    The current in neutral conductor: I I I I I j AN A A A= = + + = 3 15 026 26 0260

    1 2 3( ) ( . . )

    where I

    ( )0

    is the current zero-sequence symmetrical component. The negative-sequence symmetrical component:

    I I a I aI j AA A A A( ) ( ) ( . . )2 1

    22 3

    1

    31 342 2 325= + + = +

    Power Quality

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    7/16

    7

    http://www.leonardo-energy.org

    The positive-sequence symmetrical component: I I aI a I AA A A A( ) ( ) .1 1 2

    23

    1

    314 667= + + =

    The current unbalance actor: k

    I

    II

    A

    A%

    ( )

    ( ) % %= =

    2

    1 100 50

    AY

    1

    1

    AY

    2

    2

    AY

    3

    3

    NI

    AI1

    AI

    2

    3I

    KB1 KB 2

    1I

    2I

    AI

    3

    Fig. 6. The elimination of the zero-sequence component (EXAMPLE 2)

    0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

    -40

    -20

    0

    20

    40Supply network c urrents

    0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1-40

    -20

    0

    20

    40current in neutral conductor

    [A]

    [A]

    [s]

    [s]

    0 0. 01 0. 02 0. 03 0. 04 0. 05 0. 06 0. 07 0. 08 0. 09 0. 1-40

    -20

    0

    20

    40Supply network c urrents

    0 0. 01 0. 02 0. 03 0. 04 0. 05 0. 06 0. 07 0. 08 0. 09 0. 1-0.02

    -0.01

    0

    0.01

    0.02current in neutral conductor

    [A]

    [A]

    [s]

    [s]

    Fig. 7. Waveforms of currents: EXAMPLE 2 before Fig. 8. Waveforms of currents: EXAMPLE 2 after

    the elimination of zero-sequence component the elimination of zero-sequence component

    The elimination o the current zero-sequence component is perormed by means o the two-element symmetrizator

    in the example confguration as in Fig. 6.

    Supply network currents:

    I U Y jBA K1 1 2 1= +( ) I U Y jBA K2 2 1 2= +( ) I U Y A3 3 3=

    The condition or the current in neutral conductor to become zero takes orm:

    I I I1 2 3 0+ + =

    Hence:

    Reactive part o neutral current: Im( I I I1 2 3 0+ + =) and

    Active part o neutral current: Re( I I I1 2 3 0+ + =)Substituting the numerical values:

    0.05 - 0.0683 + 0.866B2K

    - 0.05 = 0 and 0.05 + B1K

    0.0183 0.5B2K

    + 0.0866 = 0

    Mitigation of voltage unbalance

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    8/16

    8

    http://www.leonardo-energy.org

    Hence: B SK1 0 0789= . B SK2 0 0789= .

    Y Y jB j SA K1 2 1 0 05 0 0289= + = ( . . )

    Y Y jB j SK2 1 2 0 05 0 0289= + = +( . . )

    Y Y jB SK3 3 3 0 1= + = .I U Y j j A1 1 1 220 0 005 0 0289 11 6 358= = = ( . . ) ( . )

    I U Y j A2 2 2 0 006 12 705= = ( . . )

    I U Y j A3 3 3 11 19 052= = + ( . )

    I I I1 2 3 0+ +

    The current zero-sequence component has been eliminated (Fig. 8).

    7. Symmetrization a three-wire load

    7.1. Symmetrization of a delta-connected load

    B BG G

    B B BG G

    B G

    K AA A

    AA A

    K A

    12 1223 31

    0 12 031 23

    23 12

    3 3 3

    3

    = + + + = + +

    = + BB G B B B G G

    BG G

    B

    A A A A A

    KA A

    A

    23 31 0 23 0 31 23

    3112 23

    31

    3 3

    3 3

    + + = + +

    = + + + BB B BG G

    AA A

    0 31 031 23

    3= + +

    In practice, the susceptances o a static compensator perorm both processes simultaneously, that meanssymmetrization and reactive current compensation and then the resulting values o the susceptance are defned

    by (11), where B0

    represents the permissible level o non-compensation. As it results rom (11), the three susceptances

    that are necessary or reactive current compensation and symmetrization can be expressed through real and

    imaginary components o the load admittance. The frst elements o the right side o the relation (11) represent

    the components o the compensation susceptances, necessary or the compensation o the imaginary part o the

    adequate load admittance. The second element represents the components o the compensator that are necessary

    or the symmetrization o the real parts o the load admittance. These relations clearly indicate that the process

    o compensation can also be treated as an activity concerning each o the interphase load admittances separately.

    E.g. or the load Y12A

    compensation o the imaginary part is achieved through parallel connection o a susceptance (-B12

    )

    ollowed by symmetrization o the remaining part o such a single interphase load by connecting the symmetrizing

    susceptances respectively: (G12A/ 3 ) or the voltage U12 and (-G12A/ 3 ) or the voltage U31. The compensation processo such a load with its indication diagrams has been presented in Fig. 9. For a symmetric system o supply voltages

    o positive sequence, such a circuit is equivalent to three star-connected resistors, each o them having a conductance

    G12

    .

    compensationand symmetrization

    o the admittanceY

    23A

    compensationo the reactive part othe load admittances

    compensationand symmetrization

    o the admittanceY

    12A

    compensationand symmetrization

    o the admittanceY

    31A

    symmetrization o the load

    (11)

    Power Quality

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    9/16

    9

    http://www.leonardo-energy.org

    The above considerations illustrate the well known Steinmetz rule o symmetrization, according to which any single-

    phase active load (or active-reactive one, ater its equivalent susceptance has been compensated), connected e.g.

    between phases 1-2 (Fig. 9), can be symmetrized by means o reactive elements LCo such values, that the currents

    ulfl the relations (12).

    I I I A23 31 1213

    = = (12)

    The obtained relations (11) transorm any three-phase asymmetric load into the symmetric, resistive or resistive-

    inductive load with a defned level o reactive current. For a symmetric system o supply voltages o positive sequences

    the generated circuit is equivalent (or B0

    = 0) to three, star connected resistors, each having a conductance value

    G = G12A

    + G23A

    + G31A

    .

    The condition or the compensator elements selection can also be expressed as a unction o the phase reactive

    powers o an asymmetric load:

    Q Q Q Q Q Q QA K A K A K 1 1 2 2 3 3 0+ = + = + = (12)

    Q1A

    , Q2A

    , Q3A

    - the load phase reactive powers,

    Q1K

    , Q2K

    , Q3K

    - the compensator phase reactive powers,

    Q0

    - assumed non-compensating level.

    For the compensator delta-connected elements, the interphase reactive powers can be determined with respect to

    the load phase reactive powers, according to the relations:

    Q Q Q Q Q

    Q Q Q Q Q

    Q Q Q Q

    K A A A

    K A A A

    K A A A

    12 1 2 3 0

    23 1 2 3 0

    31 1 2 3

    = + +

    =+ +

    = + +QQ0

    (13)

    I3

    I12

    I23=IC

    I2

    I1

    1

    2

    3

    I31=IL

    3

    12G

    C =

    3

    112

    G

    L

    I3 = 0

    I2

    I1

    1

    2

    3

    I12G12

    (a) (b)

    Mitigation of voltage unbalance

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    10/16

    10

    http://www.leonardo-energy.org

    U12

    U23

    U31

    U2

    U3

    U1

    I23=IC

    I31=IL

    I12

    I1=I12-I31

    I2=I23-I12

    I3=I31-I23

    (c)

    Fig. 9. (a) A single-phase system before the symmetrization;

    (b) single-phase system with the symmetrizator;

    (c) phasor diagram, which illustrates the process of symmetrization

    EXAMPLE 3

    For the loads confguration as in the EXAMPLE 1 Variant II, susceptances o the delta-connected symmetrizator/

    compensator are:

    B B G G SK A A A12 12 23 311

    30 0211= =( ) .

    B B G G SK A A A23 23 31 121

    30= =( )

    B B G G SK A A A31 31 12 231

    30 0211= =( ) .

    The sign + preceding the susceptance denotes its capacitive character, the sign - the inductive character.

    The capacitance o the capacitor connected between phases 1-2 is determined rom the relation:

    CB

    f

    S

    HzFK

    K12

    12

    2

    0 0211

    2 5067 2= =

    ..

    The inductance o the reactor connected between phases 3-1 is determined rom the relation:

    LfB Hz S

    mHKK

    3131

    1

    2

    1

    2 50 0 0211150= =

    .

    The load and compensator are shown in Fig. 10. Ater connecting the compensator/symmetrizator:

    I I I j A j A1 12 31043 89 0 001 43 89 0* * * ( . . ) . exp( )= = +

    Power Quality

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    11/16

    11

    http://www.leonardo-energy.org

    I I I j A j A2 23 12021 945 37 988 43 87 120* * * ( . . ) . exp( )= =

    I I I j A j 3 31 23021 945 37 987 43 87 120* * * ( . . ) . exp( )= = +

    The phase currents of supply network constitute the three-phase symmetrical system.

    AI12

    AY23

    KB

    23

    AY12 K

    B12

    AY31 K

    B31

    1

    2

    3

    *

    1I

    *

    2I

    *

    3I I

    *

    31I

    *

    31

    *

    12I

    AI23

    AI31

    Fig. 10. Delta-connected asymmetric load with the symmetrizator

    0 0.01 0.02 0. 03 0.04 0.05 0.06 0.07 0. 08 0. 09 0.1-400

    -300

    -200

    -100

    0

    100

    200

    300

    400

    Three-wire network voltages

    Time [s]

    Voltages[V]

    0 0. 01 0.02 0.03 0.04 0.05 0. 06 0.07 0. 08 0.09 0. 1-80

    -60

    -40

    -20

    0

    20

    40

    60

    80 Three-wire network currents

    Time [s]

    Currents[A]

    Fig. 11. Voltage and current waveforms (EXAMPLE 3)

    Mitigation of voltage unbalance

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    12/16

    12

    http://www.leonardo-energy.org

    7.2. Star-connected asymmetrical load

    The symmetrization o a star-connected load is analysed ater star-to-delta transormation. Further procedure o the

    symmetrizator parameters selection is analogical as in section 7.1.

    8. Static compensatorsReactive power static compensators are widely used in transmission and distribution systems, cooperating with

    medium and large power, rapidly variable loads, which are the most disturbing or the electric power system. Static

    compensators can perorm various tasks, such as compensation o the undamental component reactive power,

    symmetrization and mitigation o voltage fuctuations (ficker). Also some active lters congurations have a capability

    o symmetrization.

    8.1. Static VAR compensators

    The purpose o a compensator (with control and measuring system) is to measure adequate electric quantities

    o the load and generate in the compensator such currents, that the resultant load: compensator compensated load,

    as seen rom the supply network, was symmetrical, and the undamental harmonic reactive current drawn rom thenetwork did not exceed the value permitted in the supply conditions.

    Generally, static compensators are the systems, which comprise reactors and/or capacitors controlled by means

    o semiconductor circuits.

    They can be treated as the values o susceptances, controlled according to the needs o compensation/symmetrization.

    Thyristors in these systems are used as switches or phase-controlled elements. In practice various solutions

    o compensators are applied. Among the most oten used compensators is the FC/TCR compensator with xed

    capacitor and controlled (variable) reactor current.

    8.1.1. Compensator/symmetrizator FC/TCR

    So-called FC/TCR circuits are the most commonly used static VAr compensators/stabilizers in industry. They arecomposed o a Fixed Capacitor (FC) connected in parallel to a Thyristor-Controlled-Reactor (TCR). FC is most commonly

    a passive lter, ltering the harmonic/harmonics o a load and/or o the TCR. This solution is an example o the indirect

    compensation method in which the sum o the basic (1) TCR current harmonic ITCR(1)

    and the load reactive current

    IO(1)

    is constant, and equals the FC current IFC(1)

    (Fig. 12a). The TCR current waveorm or three sampled control

    angles is shown in Figure 12b (single-phase circuit). The control angle (with respect to the positive voltage zero-

    crossing) and the basic current harmonic o TCR can vary in each supply voltage hal-cycle, within the range o values

    ( , )

    2

    .

    With the increase o the angle the undamental harmonic o the reactor current decreases, what is tantamount to

    the increase o its equivalent inductive reactance or this harmonic and to the decrease in the undamental harmonic

    reactive power, drawn by the reactor. The undamental harmonic o the reactor current is expressed by the ormula:

    I UB I I I

    TCR K K FC m

    ( ) ( ) ( )( ) ( ) ( ) sin ( )1 1 13 2 2 = = = [ ] (14)

    where: control angle o the switch T thyristors, IFC(1)

    capacitor current, ITCR(1)

    () reactor current (undamental

    harmonic), Im

    - the reactor current amplitude or =

    2. Thyristor are ully conducting or = /2. B

    Kis the controlled

    susceptance o the TCR step, its value is controlled by changing the conduction angle o thyristors. The resultant

    compensator current ik(t) is the sum o the capacitor and reactor currents:

    i t i t i t k FC TCR( ) ( ) ( )= + (15)

    Power Quality

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    13/16

    13

    http://www.leonardo-energy.org

    I the current in the reactor branch is equal zero ( = ), then the compensator eeds reactive power to the supply

    network and its current has a capacitive character. When thyristors are ully conducting, and the reactor power

    is greater than the capacitor power, the compensator draws reactive power and its current has an inductive character.

    The compensator current is controlled rom IFCmax

    to ITCRmax

    in a continuous manner. The disadvantage o this system

    is generation o the current harmonics, which results rom the phase control o thyristor switch (Fig. 12c).

    In the three-phase conguration (Fig. 13a) the single-phase TCRs (as in Fig. 12) are delta-connected in parallel with

    xed capacitors; together they constitute a triangle o equivalent phase-to-phase susceptances or the supply network

    (Fig. 13b). Their values vary independently and continuously as a result o changes in the control angles (12

    , 23

    , 31

    ). This

    way, the circuit implements the Steinmetz procedure in order to compensate and symmetrize the three-phase load.

    Fig. 12. (a) Conceptual diagram;

    (b) TCR current waveforms;

    (c) harmonics amplitudes per unit of basic current component amplitude

    I23L( 23)

    23I23C

    I31L( 31)

    31I31C

    I12L( 12)

    12I12C

    1

    2

    3

    B12K

    B23K

    B31K

    I12K

    I23K

    I31K

    (a) (b)

    Fig. 13. Diagram of FC/TCR static compensator

    Mitigation of voltage unbalance

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    14/16

    14

    http://www.leonardo-energy.org

    8.1.2. TSC/TCR (Thyristor Switched Capacitor/ Thyristor Controlled Reactor)

    In this confguration a capacitor bank is divided into the steps, switched by means o thyristor AC switches, according

    to the compensation/symmetrization needs. Synchronization o the instant o switching with respect to the supply

    voltage waveorm guarantees elimination o overvoltages and inrush currents, normally associated with capacitor

    switching. Also reduced are the values o current high harmonics, as related to the FC/TCR structure o the samenominal power.

    8.1.3. STATCOM

    The newest solutions o compensating systems are the STATCOM devices, based on AC/DC converters. The STATCOM

    compensator can be considered as a controlled voltage source (VSI inverter in IGBT or GTO technology) connected

    to the power supply system through the reactors (Fig. 14), or as an inertialess, three-phase synchronous machine,

    whose phase voltages their amplitude, phase and requency are independently controlled. The reactive power/

    current ow is controlled by means o the voltage amplitude control. Due to the independent control in each phase o

    the system, the compensator enables voltage symmetrization by elimination o the negative-sequence component.

    The relationship between the values and phase angles o the supply network voltages (Ubus

    ) and the compensator

    output voltages (UVSC) (beore and ater the reactor Xr Fig. 14) determines the value and character (inductive orcapacitive) o the compensator current (power). At the zero phase shit between voltages U

    busand U

    VSC, only reactive

    current ows. When Ubus

    < UVSC

    the current is capacitive, or Ubus

    > UVSC

    the current is inductive (Fig. 15). This way the

    compensator can be a source or a load o reactive power. The STATCOM compensators are characterized with the

    ollowing basic eatures:

    they can simultaneously perorm combine unctions o reactive power compensation, load symmetrization

    and fltering o harmonics,

    do not require use o passive components; their overall dimensions are several times smaller than those

    o SVC compensators o analogical power,

    compared to the TSC/TCR and FC/TCR system they have better dynamic properties,

    due to the development in power electronics their prices show a declining tendency.

    LOAD VSC

    ubus

    uvsc

    Xr

    i

    ubus

    ubus

    ubus

    ubus

    uxux

    uvsc u vsc

    < uvsc

    > uvsc

    i i

    Fig. 14. Schematic diagram o a compensator (VSC) Fig. 15. Phasor diagrams or diferent

    connected to the supply network relations between Ubus

    and UVSC

    8.2. Static series compensators

    The series compensator can be provided with an additional - aside rom the load voltage control - unction o

    symmetrization. The concept o such a compensator and block diagram o the example design is shown in Fig. 16.

    The series voltages applied to individual phases o the system - UXSR , (X = 1, 2, 3) can be expressed as the sum o twothree-phase systems, which execute two independent processes:

    - Symmetrization. This unction is perormed by means o the three-phase system o series voltages, determined

    on the basis o the measurement o negative-sequence component o load voltages. In result o adding

    appropriate components o series voltages ( UXS or x = 1, 2, 3) to the source voltages, the symmetric systemo voltages is obtained at the point B (Fig. 16).

    Power Quality

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    15/16

    15

    http://www.leonardo-energy.org

    - Stabilization of the voltage positive-sequence component value. For this purpose, to the source voltages

    has to be added the symmetric system of series voltages ( UXR for x = 1, 2, 3), which guarantees an increaseor reduction of the load voltages, according to the stabilization needs Fig. 16.

    U1

    U1S U1R

    U01

    U1SR

    U2 U2S U2R

    U02

    U2SR

    U3 U3S U3R

    U03

    U3SR

    COMPENSATOR

    SUPPLYNETWORK

    VOLTAGESLOAD

    Balanced voltages system withcontrolled values

    Unbalanced system of thesupply network voltages

    Fig. 16. Procedure of symmetrization and control of the load voltages by means of the series compensator

    The example of a practical system, shown in schematic diagram in Fig. 17, of comprises three single-phase dc/ac

    PWM converters connected in series with the supply line through three single-phase transformers. The load voltages

    are measured and used for determination of the symmetrical components and hence to the determination of the

    converters switching patterns, which ensure obtaining the series voltages. It is also possible to employ a three-phase

    inverter with asymmetrical switching functions in individual branches of the converter. The symmetrization and

    control / regulation of the load voltage are then performed by means of controlling the amplitude and phase angle

    of reference voltages.

    Mitigation of voltage unbalance

  • 8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance

    16/16

    http://www.leonardo-energy.org

    U(2)

    U(1)

    U1SR

    U

    U3SR

    rectifer

    Filters o thevoltagesymmetrical

    components

    Control

    system

    (U(1)

    )reerence

    (U(2)

    )reerence

    Fig. 17. The schematic diagram of series system of stabilization symmetrization of the load voltage

    References

    1. ANSI C84.1: 1995, American national standard or electric power systems and equipment voltage ratings.

    2. Engineering Recommendation P29: Planning limits or voltage unbalance in the United Kingdom.

    The Electricity Council (U.K.), 1989.

    3. Gyugyi L., Otto R.A., Putman T.H.: Principles and applications o static, thyristor-controlled shunt compensators.

    IEEE Transactions Vol. PAS 97, no 5, Sep./Oct. 1978.

    4. IEC 61000-2-1, 1990: Electromagnetic compatibility-Part 2: Environment-Section 1: Description o the

    environment - Electromagnetic environment or low-requency conducted disturbances and signalling in

    public power supply systems.

    5. IEC 61000-2-5, 1995: Electromagnetic compatibility-Part 2: Environment-Section 5: Classifcation

    o electromagnetic environments.

    6. IEC 1000-2-12, 1995:Electromagnetic compatibility-Part 2: Environment-Section 12: Compatibility levels or

    low-requency conducted disturbances and signalling in public medium-voltage power systems.

    7. IEC 61000-4-27, 2000: Electromagnetic compatibility Part 4-27: Testing and measurement techniques

    Unbalance, immunity test.

    8. IEEE P1159.1: Guide or recorder and data acquisition requirements or characterisation o power quality events.

    9. Miller J. E.: Reactive power controlled in electric systems. John Willey & Sons 1982.

    10. UIE Guide to quality o electrical supply or industrial installations. Part 4: Voltage unbalance. 1998.

    Power Quality

    This publication is subject to copyright and a disclaimer. Please refer to the Leonardo ENERGY website.