Upload
hans-de-keulenaer
View
221
Download
0
Embed Size (px)
Citation preview
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
1/16
Guide for electrical design engineers
Zbigniew HanzelkaAGH-University of Science & Technology
Powe
rQuality
Power Quality
Mitigation of voltage unbalance
U12
U23
U31
U2
U3
U1
I23=IC
I31=IL
I12
I1=I12-I31
I2=I23-I12
I3=I31-I23
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
2/16
2
http://www.leonardo-energy.org
Power Quality
1. Introduction
When the limit values o unbalance actor, specifed in standards are exceeded, the use o symmetrizatin systems
is required. A symmetrizator should not cause signifcant active power losses during operation; it implies that the
symmetrization process shall be carried out by means o reactive elements (LC) or using active methods (power
electronic systems).
2. Symmetrization of the load currents
The urther analysis, using the method o symmetrical components, concerns the system node in the confguration
as in Figure 1. An asymmetrical load (A), symmetrical load (S) and compensator (K) are connected to substation bus-
bars o phase voltage U, supplied rom three-phase symmetrical system.
AI 3AI 1
KI 3KI 1
3E
1E
3U
2U
1U
COMPENSATOR
(K)
SYMETRIC
LOAD
(S)
ASYMETRIC
LOAD (A)
1I
3I
2E
Fig. 1. Diagram of the analysed node
Since the system o electromotive orces (E) and the supply line are symmetrical, it is assumed that the voltage
unbalance at the load terminals is caused by the asymmetry o the load currents. It means that, i the asymmetry
o the load currents is eliminated, the voltages at the point o the load connection orm the symmetrical three-phase
system. This is the case o the supply system protection, and the loads connected to it, against the asymmetry caused
by asymmetrical currents o the load (A) and resulting asymmetrical voltage drops across the equivalent impedances
o supply system (on assumption identical in all phases: Z Z Z 1 2 3= = ).
An obvious conclusion rom Figure 1 is that the voltage unbalance at PCC, caused by the load asymmetry, can be mitigated
by reduction o the phase equivalent impedances (short-circuit impedances) i.e. by increasing the short-circuit capacity at
the point o load connection, what in practice means connecting the load to the point o the system o higher voltage.
3. The natural symmetrization The frst and the most basic operation o the symmetrization process is the arrangement o the actual load
connections between the system phases, in such a way that the current unbalance actor (and hence the voltage
unbalance actor) was the smallest possible value. In case o connecting a single load to the network, the level
o unbalance (measured by the current unbalance actor or zero- or negative-sequence component) does not depend
on phase-to-phase or phase-to-neutral voltage, where the load is connected. Similarly, when connecting two single-
element loads, the level o unbalance does not depend on which voltages the loads are connected. However, when
these loads will have a dierent character then, in terms o the natural symmetrization (i.e. the symmetrization,
which does not require any additional elements), it is important to take into account the character o the loads and
phase angles o the voltages they are connected to.
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
3/16
3
http://www.leonardo-energy.org
Mitigation of voltage unbalance
EXAMPLE 1
For the system of three loads on nominal voltage 380 V and powers, respectively: P1
= 7.22 kW, Q1
= 7.22 kVAR (ind.);
P2
= 7.22 kW, Q2
= 7.22 kVAR (cap.); P3
= 7.22 kW, Q3
= 0 delta-connected, supplied from three-phase 3x380/220V
network, determine the arrangement of their connections to the network phases, ensuring minimum value of the
current unbalance factor.________________________
From the load active and reactive power the elements of its equivalent admittance can be determined, i.e.: the
susceptance (B =Q
U2) and conductance (G =
P
U2) (Fig. 2).
GB
Load
(P, Q) U NUN
Y
Fig. 2. The load (P - active power, Q - reactive power) and its equivalent admittance
Hence:
Y G jBP
Uj
Q
U
kW
Vj
kVAR
VA A A1 1 1
1
2
1
2 2 2
7 22
380
7 22
3800= + = = =
.
( )
.
( )( .005 0 05j S. )
Y G jBP
Uj
Q
U
kW
Vj
kVAR
VA A A2 2 2
2
2
2
2 2 2
7 22
380
7 22
3800= + = + = + =
.
( )
.
( )( .005 0 05+j S. )
Y G jB PU
jQU
kWV
j kVARV
SA A A3 3 33
2
3
2 2 27 22
380
0
3800 1= + = + = + =.
( ) ( ).
Variant 1 Loads connected as in Fig. 3:
Y YA A12 1=
Y YA A23 2=
Y YA A31 3=
Fig. 3. Variant 1 of load connection
The current unbalance factor: kI
I
a Y Y aY
Y Y YI
A A A
A A A
%
( )
( )% % . %= =
+ +
+ +=
2
1
212 23 31
12 23 31
100 100 68 3
a j j= = +exp( )120 12
32
0
a j j2 0120 12
32
= = exp( )
1
2
3
AY12
AY23
AY31
AI1
AI2
AI3
AI 31
AI23
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
4/16
4
http://www.leonardo-energy.org
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
-400
-300
-200
-100
0
100
200
300
400 Three-wire network voltages
Time [s]
Voltages[V
]
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
-40
-30
-20
-10
0
10
20
30
40
Three-wire network currents
Time [s]
Currents[A]
Fig. 4. Voltage waveforms: Example 1 Variant 1 Fig. 5. Current waveforms: Example 1 Variant 1
See Figures 4 and 5.
Variant II - Y YA A12 1=
Y YA A23 3=
Y YA A31 2=
The current unbalance actor: kI
I
a Y Y aY
Y Y YI
A A A
A A A
%
( )
( )% % . %= =
+ +
+ +=
2
1
2
12 23 31
12 23 31
100 100 18 3
This is the minimal value o the current unbalance actor, which can be obtained connecting the impedances
to phase-to-phase voltages in various confgurations. This confguration has been taken or urther considerations (Fig. 6).
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
-40
-30
-20
-10
0
10
20
30
40
Three-wire network currents
Time [s]
Currents[A]
Fig. 6. Waveforms of currents: Example 1 Variant 2
In cases, where the negative component cannot be su ciently reduced solely by means o the more uniorm
distribution o the loads between phases, compensators are used. The purpose o the compensation systems is usually
the elimination or mitigation o the negative- and zero-sequence component o currents at the point o connection
o asymmetric load. Such process is called symmetrization.
4. Compensator/symmetrizator
In the three wire MV systems, usually operated as the isolated neutral point or compensated systems, asymmetrical
loads are connected on phase-to-phase voltages. In such case, there is no zero-sequence component o currents,
thereore the symmetrization resolves into elimination or mitigation o the negative-sequence component. The
LV systems are typically our-wire networks, with grounded neutral point, thus the negative-sequence and zero-
sequence components are present. The symmetrizator (K) is connected in parallel to the asymmetric load (A) (Fig. 1).
The symmetrizator causes the currents I1K
, I2K
, I3K
, which adding to the load currents I1A
, I2A
, I3A
, result in the balanced
system o the source currents I1, I
2, I
3, according to the equation:
I I IA K1 1 1= + I I I a I A K2 2 22
1= + = I I I aI A K3 3 3 1= + = (7)
Power Quality
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
5/16
5
http://www.leonardo-energy.org
As the currents drawn rom the network orm a balanced system, thereore the negative-sequence and zero-sequence
components are equal zero:
I I aI a I ( ) ( )2 1 22
3
1
3
0= + + = I I I I ( ) ( )0 1 2 31
3
0= + + = (8)
The load to be balanced can be represented in general as a circuit o six elements in the star/delta connection (Fig. 4),
where individual elements are connected to phase-to-neutral, as well as to phase-to-phase voltages. The impedances
Z Z Z Z Z Z A A A A A A12 23 31 1 2 3, , , (or admittances Y Y Y Y Y Y A A A A A A12 23 31 1 2 3, , , ), which in the diagram represent the actual
load, can be unctions o time.
)( 1212 AAYZ
)( 21 AAYZ
)( 2323 AA YZ )( 22 AA YZ
)( 3131 AA YZ )( 33 AA YZ
1 3 02
Fig. 4. General diagram of the three-phase unbalanced load
To establish the rules o compensation and symmetrization, the values o specifed impedances should be assumed
constant, and generally dierent rom each other. This does not exclude considerations on their variability in time.These impedances can be regarded as a representation o the time-varying load, but only in the specifc, selected
instants o time the sampling instants. The set o such constant values o impedances represents the load at discrete
instants o time.
The compensation o asymmetric load will be understood as the compensation o reactive part o the positive-
sequence symmetrical component (reactive power compensation or the undamental requency) and o the zero-
sequence component (or three-phase, our-wire systems) and negative-sequence component or the undamental
requency. Among various possible methods, the inductive-capacitive systems are o particular importance. Their
practical applications are certain solutions o static ollow-up compensators.
5. The compensator/symmetrizator parameters
The symmetrization and compensation o the undamental harmonic reactive current is a process, which in practice
consists in connecting in parallel to the asymmetric load the asymmetric reactive elements (reactors, capacitors)
o such values as to ulfl the conditions (9):
I IA K( ) ( )2 2 0+ = I IA K
( ) ( )0 0 0+ = Im ( ) ( )I I IA K1 1
0+ = (9)
where: I I IA A A( ) ( ) ( ), ,0 1 2 , I I IK K K
( ) ( ) ( ), ,0 1 2 are symmetrical components o the asymmetric load and compensator (index (K))
currents, respectively or the zero- (0), positive- (1) and negative-sequence component; Im ( )IA1 denotes the reactive
part o the positive-sequence o the load current component (imaginary part in complex numbers notation); I0
is the value o reactive current, which is the measure o the load non-compensating level permitted in the supply
conditions by electrical power supplier. Thus, according to the presented notation, the processes o the reactive
current compensation and symmetrization (or the zero-sequence and negative-sequence component) have been
separated.
Mitigation of voltage unbalance
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
6/16
6
http://www.leonardo-energy.org
For the load as in Fig. 4, the relations, describing the values o the negative- and zero-sequence symmetrical
components can be written as ollows (according to (8)):
I U Y aY a Y a Y Y aY A A A A A A A( )2
1 22
32
12 23 31
1
3= + +( ) + +( )
(10a)
IU
Y a Y aY A A A A( )0
12
2 33= + +( ) (10b)
I the expressions (10) are not identically equal zero, and the asymmetry level is inadmissibly high, the load symmetrization
is needed and can be made by connecting a symmetrization-compensating device with elements B B BK K K1 2 3, , connected
to the phase-to-neutral voltages and B B BK K K12 23 31, , connected to the phase-to-phase voltages. The problem resolves into
fnding the compensating susceptances, which in connection with the admittances to be compensated will constitute
a symmetric load. The relations, where the parameters o symmetrizator/compensator are expressed as a unction
o the equivalent impedances (admittances) o the load to be compensated/symmetrized, will be presented urther in
this paper. This is particularly useul when designing a symmetrizator. The symmetrizator parameters can be expressed
as a unction o other quantities, which describe a compensated load, i.e.: the current symmetrical components, values
o phase currents or powers, instantaneous values o phase voltages and currents, etc.
6. Symmetrization of a star-connected load with neutral conductor elimination of the zero-sequence symmetrical component
In this case the process o compensation comprises o two stages. The frst one concerns the elimination o the
zero-sequence symmetrical component elimination o the current in neutral conductor. The confguration in Fig. 5
has been taken or urther considerations; it is distinguished by the minimum value o the current unbalance actor
(the values o elements as in the EXAMPLE 1).
AY
1
1
AY
2
2
AY
3
3
NI
AI1
AI2
AI3
Fig. 5. Three-phase four-wire network - star-connected load
EXAMPLE 2
U V1 220= U a V2 2 220= U a V3 220=
I U Y j j AA A1 1 2 220 0 05 0 05 11 11= = + = +( . , ) ( )
I U Y j AA A2 2 1 15 026 4 026= = ( . . )
I U Y j AA A3 3 3 11 19 052= = ( . )
The current in neutral conductor: I I I I I j AN A A A= = + + = 3 15 026 26 0260
1 2 3( ) ( . . )
where I
( )0
is the current zero-sequence symmetrical component. The negative-sequence symmetrical component:
I I a I aI j AA A A A( ) ( ) ( . . )2 1
22 3
1
31 342 2 325= + + = +
Power Quality
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
7/16
7
http://www.leonardo-energy.org
The positive-sequence symmetrical component: I I aI a I AA A A A( ) ( ) .1 1 2
23
1
314 667= + + =
The current unbalance actor: k
I
II
A
A%
( )
( ) % %= =
2
1 100 50
AY
1
1
AY
2
2
AY
3
3
NI
AI1
AI
2
3I
KB1 KB 2
1I
2I
AI
3
Fig. 6. The elimination of the zero-sequence component (EXAMPLE 2)
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
-40
-20
0
20
40Supply network c urrents
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1-40
-20
0
20
40current in neutral conductor
[A]
[A]
[s]
[s]
0 0. 01 0. 02 0. 03 0. 04 0. 05 0. 06 0. 07 0. 08 0. 09 0. 1-40
-20
0
20
40Supply network c urrents
0 0. 01 0. 02 0. 03 0. 04 0. 05 0. 06 0. 07 0. 08 0. 09 0. 1-0.02
-0.01
0
0.01
0.02current in neutral conductor
[A]
[A]
[s]
[s]
Fig. 7. Waveforms of currents: EXAMPLE 2 before Fig. 8. Waveforms of currents: EXAMPLE 2 after
the elimination of zero-sequence component the elimination of zero-sequence component
The elimination o the current zero-sequence component is perormed by means o the two-element symmetrizator
in the example confguration as in Fig. 6.
Supply network currents:
I U Y jBA K1 1 2 1= +( ) I U Y jBA K2 2 1 2= +( ) I U Y A3 3 3=
The condition or the current in neutral conductor to become zero takes orm:
I I I1 2 3 0+ + =
Hence:
Reactive part o neutral current: Im( I I I1 2 3 0+ + =) and
Active part o neutral current: Re( I I I1 2 3 0+ + =)Substituting the numerical values:
0.05 - 0.0683 + 0.866B2K
- 0.05 = 0 and 0.05 + B1K
0.0183 0.5B2K
+ 0.0866 = 0
Mitigation of voltage unbalance
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
8/16
8
http://www.leonardo-energy.org
Hence: B SK1 0 0789= . B SK2 0 0789= .
Y Y jB j SA K1 2 1 0 05 0 0289= + = ( . . )
Y Y jB j SK2 1 2 0 05 0 0289= + = +( . . )
Y Y jB SK3 3 3 0 1= + = .I U Y j j A1 1 1 220 0 005 0 0289 11 6 358= = = ( . . ) ( . )
I U Y j A2 2 2 0 006 12 705= = ( . . )
I U Y j A3 3 3 11 19 052= = + ( . )
I I I1 2 3 0+ +
The current zero-sequence component has been eliminated (Fig. 8).
7. Symmetrization a three-wire load
7.1. Symmetrization of a delta-connected load
B BG G
B B BG G
B G
K AA A
AA A
K A
12 1223 31
0 12 031 23
23 12
3 3 3
3
= + + + = + +
= + BB G B B B G G
BG G
B
A A A A A
KA A
A
23 31 0 23 0 31 23
3112 23
31
3 3
3 3
+ + = + +
= + + + BB B BG G
AA A
0 31 031 23
3= + +
In practice, the susceptances o a static compensator perorm both processes simultaneously, that meanssymmetrization and reactive current compensation and then the resulting values o the susceptance are defned
by (11), where B0
represents the permissible level o non-compensation. As it results rom (11), the three susceptances
that are necessary or reactive current compensation and symmetrization can be expressed through real and
imaginary components o the load admittance. The frst elements o the right side o the relation (11) represent
the components o the compensation susceptances, necessary or the compensation o the imaginary part o the
adequate load admittance. The second element represents the components o the compensator that are necessary
or the symmetrization o the real parts o the load admittance. These relations clearly indicate that the process
o compensation can also be treated as an activity concerning each o the interphase load admittances separately.
E.g. or the load Y12A
compensation o the imaginary part is achieved through parallel connection o a susceptance (-B12
)
ollowed by symmetrization o the remaining part o such a single interphase load by connecting the symmetrizing
susceptances respectively: (G12A/ 3 ) or the voltage U12 and (-G12A/ 3 ) or the voltage U31. The compensation processo such a load with its indication diagrams has been presented in Fig. 9. For a symmetric system o supply voltages
o positive sequence, such a circuit is equivalent to three star-connected resistors, each o them having a conductance
G12
.
compensationand symmetrization
o the admittanceY
23A
compensationo the reactive part othe load admittances
compensationand symmetrization
o the admittanceY
12A
compensationand symmetrization
o the admittanceY
31A
symmetrization o the load
(11)
Power Quality
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
9/16
9
http://www.leonardo-energy.org
The above considerations illustrate the well known Steinmetz rule o symmetrization, according to which any single-
phase active load (or active-reactive one, ater its equivalent susceptance has been compensated), connected e.g.
between phases 1-2 (Fig. 9), can be symmetrized by means o reactive elements LCo such values, that the currents
ulfl the relations (12).
I I I A23 31 1213
= = (12)
The obtained relations (11) transorm any three-phase asymmetric load into the symmetric, resistive or resistive-
inductive load with a defned level o reactive current. For a symmetric system o supply voltages o positive sequences
the generated circuit is equivalent (or B0
= 0) to three, star connected resistors, each having a conductance value
G = G12A
+ G23A
+ G31A
.
The condition or the compensator elements selection can also be expressed as a unction o the phase reactive
powers o an asymmetric load:
Q Q Q Q Q Q QA K A K A K 1 1 2 2 3 3 0+ = + = + = (12)
Q1A
, Q2A
, Q3A
- the load phase reactive powers,
Q1K
, Q2K
, Q3K
- the compensator phase reactive powers,
Q0
- assumed non-compensating level.
For the compensator delta-connected elements, the interphase reactive powers can be determined with respect to
the load phase reactive powers, according to the relations:
Q Q Q Q Q
Q Q Q Q Q
Q Q Q Q
K A A A
K A A A
K A A A
12 1 2 3 0
23 1 2 3 0
31 1 2 3
= + +
=+ +
= + +QQ0
(13)
I3
I12
I23=IC
I2
I1
1
2
3
I31=IL
3
12G
C =
3
112
G
L
I3 = 0
I2
I1
1
2
3
I12G12
(a) (b)
Mitigation of voltage unbalance
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
10/16
10
http://www.leonardo-energy.org
U12
U23
U31
U2
U3
U1
I23=IC
I31=IL
I12
I1=I12-I31
I2=I23-I12
I3=I31-I23
(c)
Fig. 9. (a) A single-phase system before the symmetrization;
(b) single-phase system with the symmetrizator;
(c) phasor diagram, which illustrates the process of symmetrization
EXAMPLE 3
For the loads confguration as in the EXAMPLE 1 Variant II, susceptances o the delta-connected symmetrizator/
compensator are:
B B G G SK A A A12 12 23 311
30 0211= =( ) .
B B G G SK A A A23 23 31 121
30= =( )
B B G G SK A A A31 31 12 231
30 0211= =( ) .
The sign + preceding the susceptance denotes its capacitive character, the sign - the inductive character.
The capacitance o the capacitor connected between phases 1-2 is determined rom the relation:
CB
f
S
HzFK
K12
12
2
0 0211
2 5067 2= =
..
The inductance o the reactor connected between phases 3-1 is determined rom the relation:
LfB Hz S
mHKK
3131
1
2
1
2 50 0 0211150= =
.
The load and compensator are shown in Fig. 10. Ater connecting the compensator/symmetrizator:
I I I j A j A1 12 31043 89 0 001 43 89 0* * * ( . . ) . exp( )= = +
Power Quality
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
11/16
11
http://www.leonardo-energy.org
I I I j A j A2 23 12021 945 37 988 43 87 120* * * ( . . ) . exp( )= =
I I I j A j 3 31 23021 945 37 987 43 87 120* * * ( . . ) . exp( )= = +
The phase currents of supply network constitute the three-phase symmetrical system.
AI12
AY23
KB
23
AY12 K
B12
AY31 K
B31
1
2
3
*
1I
*
2I
*
3I I
*
31I
*
31
*
12I
AI23
AI31
Fig. 10. Delta-connected asymmetric load with the symmetrizator
0 0.01 0.02 0. 03 0.04 0.05 0.06 0.07 0. 08 0. 09 0.1-400
-300
-200
-100
0
100
200
300
400
Three-wire network voltages
Time [s]
Voltages[V]
0 0. 01 0.02 0.03 0.04 0.05 0. 06 0.07 0. 08 0.09 0. 1-80
-60
-40
-20
0
20
40
60
80 Three-wire network currents
Time [s]
Currents[A]
Fig. 11. Voltage and current waveforms (EXAMPLE 3)
Mitigation of voltage unbalance
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
12/16
12
http://www.leonardo-energy.org
7.2. Star-connected asymmetrical load
The symmetrization o a star-connected load is analysed ater star-to-delta transormation. Further procedure o the
symmetrizator parameters selection is analogical as in section 7.1.
8. Static compensatorsReactive power static compensators are widely used in transmission and distribution systems, cooperating with
medium and large power, rapidly variable loads, which are the most disturbing or the electric power system. Static
compensators can perorm various tasks, such as compensation o the undamental component reactive power,
symmetrization and mitigation o voltage fuctuations (ficker). Also some active lters congurations have a capability
o symmetrization.
8.1. Static VAR compensators
The purpose o a compensator (with control and measuring system) is to measure adequate electric quantities
o the load and generate in the compensator such currents, that the resultant load: compensator compensated load,
as seen rom the supply network, was symmetrical, and the undamental harmonic reactive current drawn rom thenetwork did not exceed the value permitted in the supply conditions.
Generally, static compensators are the systems, which comprise reactors and/or capacitors controlled by means
o semiconductor circuits.
They can be treated as the values o susceptances, controlled according to the needs o compensation/symmetrization.
Thyristors in these systems are used as switches or phase-controlled elements. In practice various solutions
o compensators are applied. Among the most oten used compensators is the FC/TCR compensator with xed
capacitor and controlled (variable) reactor current.
8.1.1. Compensator/symmetrizator FC/TCR
So-called FC/TCR circuits are the most commonly used static VAr compensators/stabilizers in industry. They arecomposed o a Fixed Capacitor (FC) connected in parallel to a Thyristor-Controlled-Reactor (TCR). FC is most commonly
a passive lter, ltering the harmonic/harmonics o a load and/or o the TCR. This solution is an example o the indirect
compensation method in which the sum o the basic (1) TCR current harmonic ITCR(1)
and the load reactive current
IO(1)
is constant, and equals the FC current IFC(1)
(Fig. 12a). The TCR current waveorm or three sampled control
angles is shown in Figure 12b (single-phase circuit). The control angle (with respect to the positive voltage zero-
crossing) and the basic current harmonic o TCR can vary in each supply voltage hal-cycle, within the range o values
( , )
2
.
With the increase o the angle the undamental harmonic o the reactor current decreases, what is tantamount to
the increase o its equivalent inductive reactance or this harmonic and to the decrease in the undamental harmonic
reactive power, drawn by the reactor. The undamental harmonic o the reactor current is expressed by the ormula:
I UB I I I
TCR K K FC m
( ) ( ) ( )( ) ( ) ( ) sin ( )1 1 13 2 2 = = = [ ] (14)
where: control angle o the switch T thyristors, IFC(1)
capacitor current, ITCR(1)
() reactor current (undamental
harmonic), Im
- the reactor current amplitude or =
2. Thyristor are ully conducting or = /2. B
Kis the controlled
susceptance o the TCR step, its value is controlled by changing the conduction angle o thyristors. The resultant
compensator current ik(t) is the sum o the capacitor and reactor currents:
i t i t i t k FC TCR( ) ( ) ( )= + (15)
Power Quality
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
13/16
13
http://www.leonardo-energy.org
I the current in the reactor branch is equal zero ( = ), then the compensator eeds reactive power to the supply
network and its current has a capacitive character. When thyristors are ully conducting, and the reactor power
is greater than the capacitor power, the compensator draws reactive power and its current has an inductive character.
The compensator current is controlled rom IFCmax
to ITCRmax
in a continuous manner. The disadvantage o this system
is generation o the current harmonics, which results rom the phase control o thyristor switch (Fig. 12c).
In the three-phase conguration (Fig. 13a) the single-phase TCRs (as in Fig. 12) are delta-connected in parallel with
xed capacitors; together they constitute a triangle o equivalent phase-to-phase susceptances or the supply network
(Fig. 13b). Their values vary independently and continuously as a result o changes in the control angles (12
, 23
, 31
). This
way, the circuit implements the Steinmetz procedure in order to compensate and symmetrize the three-phase load.
Fig. 12. (a) Conceptual diagram;
(b) TCR current waveforms;
(c) harmonics amplitudes per unit of basic current component amplitude
I23L( 23)
23I23C
I31L( 31)
31I31C
I12L( 12)
12I12C
1
2
3
B12K
B23K
B31K
I12K
I23K
I31K
(a) (b)
Fig. 13. Diagram of FC/TCR static compensator
Mitigation of voltage unbalance
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
14/16
14
http://www.leonardo-energy.org
8.1.2. TSC/TCR (Thyristor Switched Capacitor/ Thyristor Controlled Reactor)
In this confguration a capacitor bank is divided into the steps, switched by means o thyristor AC switches, according
to the compensation/symmetrization needs. Synchronization o the instant o switching with respect to the supply
voltage waveorm guarantees elimination o overvoltages and inrush currents, normally associated with capacitor
switching. Also reduced are the values o current high harmonics, as related to the FC/TCR structure o the samenominal power.
8.1.3. STATCOM
The newest solutions o compensating systems are the STATCOM devices, based on AC/DC converters. The STATCOM
compensator can be considered as a controlled voltage source (VSI inverter in IGBT or GTO technology) connected
to the power supply system through the reactors (Fig. 14), or as an inertialess, three-phase synchronous machine,
whose phase voltages their amplitude, phase and requency are independently controlled. The reactive power/
current ow is controlled by means o the voltage amplitude control. Due to the independent control in each phase o
the system, the compensator enables voltage symmetrization by elimination o the negative-sequence component.
The relationship between the values and phase angles o the supply network voltages (Ubus
) and the compensator
output voltages (UVSC) (beore and ater the reactor Xr Fig. 14) determines the value and character (inductive orcapacitive) o the compensator current (power). At the zero phase shit between voltages U
busand U
VSC, only reactive
current ows. When Ubus
< UVSC
the current is capacitive, or Ubus
> UVSC
the current is inductive (Fig. 15). This way the
compensator can be a source or a load o reactive power. The STATCOM compensators are characterized with the
ollowing basic eatures:
they can simultaneously perorm combine unctions o reactive power compensation, load symmetrization
and fltering o harmonics,
do not require use o passive components; their overall dimensions are several times smaller than those
o SVC compensators o analogical power,
compared to the TSC/TCR and FC/TCR system they have better dynamic properties,
due to the development in power electronics their prices show a declining tendency.
LOAD VSC
ubus
uvsc
Xr
i
ubus
ubus
ubus
ubus
uxux
uvsc u vsc
< uvsc
> uvsc
i i
Fig. 14. Schematic diagram o a compensator (VSC) Fig. 15. Phasor diagrams or diferent
connected to the supply network relations between Ubus
and UVSC
8.2. Static series compensators
The series compensator can be provided with an additional - aside rom the load voltage control - unction o
symmetrization. The concept o such a compensator and block diagram o the example design is shown in Fig. 16.
The series voltages applied to individual phases o the system - UXSR , (X = 1, 2, 3) can be expressed as the sum o twothree-phase systems, which execute two independent processes:
- Symmetrization. This unction is perormed by means o the three-phase system o series voltages, determined
on the basis o the measurement o negative-sequence component o load voltages. In result o adding
appropriate components o series voltages ( UXS or x = 1, 2, 3) to the source voltages, the symmetric systemo voltages is obtained at the point B (Fig. 16).
Power Quality
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
15/16
15
http://www.leonardo-energy.org
- Stabilization of the voltage positive-sequence component value. For this purpose, to the source voltages
has to be added the symmetric system of series voltages ( UXR for x = 1, 2, 3), which guarantees an increaseor reduction of the load voltages, according to the stabilization needs Fig. 16.
U1
U1S U1R
U01
U1SR
U2 U2S U2R
U02
U2SR
U3 U3S U3R
U03
U3SR
COMPENSATOR
SUPPLYNETWORK
VOLTAGESLOAD
Balanced voltages system withcontrolled values
Unbalanced system of thesupply network voltages
Fig. 16. Procedure of symmetrization and control of the load voltages by means of the series compensator
The example of a practical system, shown in schematic diagram in Fig. 17, of comprises three single-phase dc/ac
PWM converters connected in series with the supply line through three single-phase transformers. The load voltages
are measured and used for determination of the symmetrical components and hence to the determination of the
converters switching patterns, which ensure obtaining the series voltages. It is also possible to employ a three-phase
inverter with asymmetrical switching functions in individual branches of the converter. The symmetrization and
control / regulation of the load voltage are then performed by means of controlling the amplitude and phase angle
of reference voltages.
Mitigation of voltage unbalance
8/14/2019 Guide for electrical design engineers - Chapter 5 : Mitigation of voltage unbalance
16/16
http://www.leonardo-energy.org
U(2)
U(1)
U1SR
U
U3SR
rectifer
Filters o thevoltagesymmetrical
components
Control
system
(U(1)
)reerence
(U(2)
)reerence
Fig. 17. The schematic diagram of series system of stabilization symmetrization of the load voltage
References
1. ANSI C84.1: 1995, American national standard or electric power systems and equipment voltage ratings.
2. Engineering Recommendation P29: Planning limits or voltage unbalance in the United Kingdom.
The Electricity Council (U.K.), 1989.
3. Gyugyi L., Otto R.A., Putman T.H.: Principles and applications o static, thyristor-controlled shunt compensators.
IEEE Transactions Vol. PAS 97, no 5, Sep./Oct. 1978.
4. IEC 61000-2-1, 1990: Electromagnetic compatibility-Part 2: Environment-Section 1: Description o the
environment - Electromagnetic environment or low-requency conducted disturbances and signalling in
public power supply systems.
5. IEC 61000-2-5, 1995: Electromagnetic compatibility-Part 2: Environment-Section 5: Classifcation
o electromagnetic environments.
6. IEC 1000-2-12, 1995:Electromagnetic compatibility-Part 2: Environment-Section 12: Compatibility levels or
low-requency conducted disturbances and signalling in public medium-voltage power systems.
7. IEC 61000-4-27, 2000: Electromagnetic compatibility Part 4-27: Testing and measurement techniques
Unbalance, immunity test.
8. IEEE P1159.1: Guide or recorder and data acquisition requirements or characterisation o power quality events.
9. Miller J. E.: Reactive power controlled in electric systems. John Willey & Sons 1982.
10. UIE Guide to quality o electrical supply or industrial installations. Part 4: Voltage unbalance. 1998.
Power Quality
This publication is subject to copyright and a disclaimer. Please refer to the Leonardo ENERGY website.