116
TELEPHONE INTERFERENCE CAUSED BY HARMONICS AND UNBALANCE IN POWER LINES by MARIAM PAUL submitted in partial fulfilment of the requirements for the degree of MASTER IN ENGINEERING in ELECTRICAL AND ELECTRONIC ENGINEERING in the FACULTY OF ENGINEERING of the RAND AFRIKAANS UNIVERSITY SUPERVISOR: PROF. J.A. FERREIRA MARCH 1998

Telephone interference caused by harmonics and unbalance

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Telephone interference caused by harmonics and unbalance

TELEPHONE INTERFERENCE CAUSED BY HARMONICS AND UNBALANCE IN POWER LINES

by

MARIAM PAUL

submitted in partial fulfilment of the requirements for the degree of

MASTER IN ENGINEERING

in

ELECTRICAL AND ELECTRONIC ENGINEERING

in the

FACULTY OF ENGINEERING

of the

RAND AFRIKAANS UNIVERSITY

SUPERVISOR: PROF. J.A. FERREIRA

MARCH 1998

Page 2: Telephone interference caused by harmonics and unbalance

Abstract

Open-wire telecommunications were developed in the 19th and early 20th centuries

without any consideration of the deleterious effects of power lines; compatibility

problems were later caused by the proximity of power lines and telephone lines. The

coexistence of such systems requires careful planning in terms of energy coupled to the

telephone lines; this induction can cause interference, as well as dangerous

overvoltages in telephone circuits, and requires detailed studies of the effects of

coupling between high voltage lines and telephone systems to be done. In terms of

inductive co-ordination in South Africa, the minimum separation distances between

high voltage power lines and communication systems are calculated only for power

frequency and lower order harmonics (up to the 13th). The aim of the study was to

explore the agreement between theory and measurement for frequencies from 50 Hz to

the high order harmonic range of 4 kHz; this makes it possible to extend existing

methods for predicting compatible separations to cases where high order harmonics

(up to the 73rd) are present (balanced and unbalanced) on a 132 kV power line feeding

a large aluminium smelter plant.

Page 3: Telephone interference caused by harmonics and unbalance

Opsomming

Die ontwikkeling van oop-draad telekommunikasie netwerke gedurende die 19de en 20ste

eeu het plaasgevind sonder die nodige inagneming van potensiele kraglyn interaksies en

gevolglike steurings situasies het ontstaan onder sekere omstandigheede. Daar is besef dat

deeglike beplanning noodsaaklik is om aanpasbaarheid te verseker. Geinduseerde energie

kan steurings asook gevaarlike hoogspanningseffekte in telekommunikasie stelsels

veroorsaak wat gevorderde studie van elektromagnetiese koppeling tussen krag- en

telekommunikasie netwerk vereis. Om induksieverskynsels in Suid-Afrika te beheer, word

die minimum skeidingsafstande tussen hoogspannings- en kommunikasielyne bereken op

grond van drywingsfrekwensie en lae orde harmonieke (tot by die 13 de). Die doel van

hierdie studie was om die verwantskap tussen die teorie en praktyk te verken met

spesifieke verwysing na die 50 Hz tot 4 kHz harmoniekfrekwensie-band. Meer spesifiek,

die uitbreiding van voorspellingsmetodes vir minimum skeidingsafstande vir gevalle waar

hoe orde stroomharmonieke (tot die 73de), soos dit voorkom in 132kV kraglynvoer van

`n groot aluminium-verwerkingsaanleg.

Page 4: Telephone interference caused by harmonics and unbalance

LIST OF SYMBOLS AND ABBREVIATIONS

cp Magnetic flux

?t,e Sensitivity Coefficient for Electrostatic Coupling

Sensitivity coefficient for electromagnetic induction

permeability of free space

p earth resistivity

conductivity of soil

co angular velocity

B Magnetic flux density

self capacitance

mutual (coupling) capacitance

Cn C-message weighting factor for the n:th harmonic

Di; distance between induced conductor and image of the inducing

conductor on the surface of the earth

di; actual distance between inducing and induced conductor

E - power line service voltage

EAs transverse electric field on the surface of the earth

EP common mode longitudinal emf

ep psophometric emf acting in a loop

f frequency

H magnetic intensity

If harmonic r.m.s component of the line current at frequency f

In line current of nth harmonic

IP psophometrically - weighted current or Equivalent disturbing current

'peg psophometric equivalent 800 Hz disturbing current

IO earth current

Is current in the shield wire

IR,Iw,IB - phase currents

IRO zero sequence current (red phase)

IR+ positive sequence current (red phase)

negative sequence current(red phase)

Page 5: Telephone interference caused by harmonics and unbalance

IRW

Iwg loop currents

IBR

k screening factor

kf coupling function

kg„, ground wire shield factor

ksn cable shield factor

kT Telephone Harmonic Form Factor

inductance

M mutual inductance between inducing line and induced line

M12 mutual inductance between the inducing line and induced line

n14 coupling function

4 mean value of the coupling function n14

Pf psophometric weighting factor at frequency f

Pi; self potential coefficient

mutual potential coefficient

Q charge per unit length

R DC resistance

TIE Telephone Influence Factor

Uf harmonic r.m.s component of the line voltage at frequency f.

Up Psophometrically weighted voltage

Upeq Equivalent Disturbing Voltage

Vcn common mode voltage

zu Self impedance of a conductor

Page 6: Telephone interference caused by harmonics and unbalance

TABLE OF CONTENTS

Page

Chapter 1 INTRODUCTION 1

Chapter 2 ELECTROMAGNETIC COUPLING 6

2.1 Electromagnetic Coupling 7

2.1.1 General Theory 7 2.1.1.1 Loop Currents 9

2.1.2 General Description About Transmission Line and Telephone Line 10 2.1.2.1 Telecommunication Network 11

2.1.2.1.1 Composition of Transmission Supports 12

2.1.3 Description of Scale Model 12 2.1.3.1 Transmission Line 12 2.1.3.2 Telephone line 13

2.1.4 Modelling of the System 14 2.1.4.1 Solution for a Multi-conductor System 17 2.1.4.2 Equations for Loop Inductance 18

2.1.5 Psophometer and Psophometrically Weighted- Current 18 2.1.5.1 Psophometer 18 2.1.5.2 Psophometrically Weighted Current 19

2.2 Factors Influence the Induced Voltage in a Telephone Line 20 2.2.1 Line Current 20

2.2.2 Separation Distance Between Power and Telephone line 21

2.2.3 Frequency 22

2.2.4 Configuration of Power Line 23

2.2.5 Length of Exposure 23 2.2.5.1 Oblique Exposure and Crossing 24

2.2.6 Earth Resistivity 25

Page 7: Telephone interference caused by harmonics and unbalance

Page

2.2.7 Telephone Pair Spacing 25

Chapter 3 ELECTROSTATIC AND CONDUCTIVE COUPLING 26

3.1 Electrostatic Coupling 27

3.1.1 General Theory 27

3.1.2 Modelling of the System 29 3.1.2.1 Psophometrically Weighted Voltage 32 3.1.2.2 Sensitivity Coefficient for Electrostatic

Coupling 32 3.1.2.3 Telephone Harmonic Form Factor 33

3.1.3 Factors Influencing the Induced Voltage 33 3.1.3.1 Geometric Configuration of Installations 33 3.1.3.2 The Line Voltage and Operating Condition

of the Power Line 33

3.2 Conductive Coupling 34

3.2.1 General Theory 34

3.2.2 Ground Potential Rise Evaluation 35 3.2.2.1 Electrode GPR 35 3.2.2.2 Area of GPR 36

Chapter 4 EXPERIMENTAL MEASUREMENTS 39

4.1 Introduction 40

4.2 Electromagnetic Coupling 41

4.2.1 Balanced Three-phase Condition 41 4.2.1.1 Common Mode Voltage vs. Frequency 42 4.2.1.2 Differential Mode Voltage vs. Frequency 45

4.2.2 Unbalanced Three-phase Condition 45 4.2.2.1 Common Mode Voltage vs. Frequency 46 4.2.2.2 Differential Mode Voltage vs. Frequency 47

4.3 Electrostatic Coupling 48

4.3.1 Balanced Three-phase Condition 48

Page 8: Telephone interference caused by harmonics and unbalance

4.3

4.3.1.1 Differential Mode Voltage

Compatible Separations

Page

48

49

Chapter 5 DISCUSSION AND CONCLUSION 51

5.1 Discussion 52

5.2 Conclusion 54

REFERENCES 56

Appendix A Psophometric Weights 58

Appendix B Curves for Minimum Separation of Power Line

and Communication Line 62

Appendix C Soil Conductivity 68

Appendix D Tower Geometry 73

Appendix E Circuit Diagrams and Results 76

Appendix F Calculation Methods 86

Page 9: Telephone interference caused by harmonics and unbalance

Chapter 1

INT. ODUCTION

The techniques of telecommunication were free to develop without any

consideration of other transmission lines, because they are about five decades

older than those of power transmission. Problems were caused by the

introduction of coexistence of power lines and telephone lines. The coexistence

of power lines and telephone lines requires careful planning in terms of energy

induced into the telephone lines. This induction can cause interference as well

as danger on the telephone circuit, which compelled a detailed study of the

effect of the electromagnetic field produced by high voltage lines. The Comite

Consultatif International Telephonique (C.C.I.F) started research on

interference and protective measures, and published its findings and

recommendation in the form of Directives, in 1925, 1930, 1937/38 and 1952.

In 1957 C.C.I.F and the corresponding Comite Telegraphique (C.C.I.T)

amalgamated in the C.C.I.T.T and new Directives were subsequently produced

in 1963. A complete new set of Directives, comprise of nine volumes, were

published in 1989, incorporating the latest circuit theory and written especially

with computer implementation in mind.

1

Page 10: Telephone interference caused by harmonics and unbalance

Electromagnetic Compatibility (EMC) is a fast developing field. Studies in

Telephone noise interference caused by power line currents and voltages are

done under EMC in power systems environment. Few examples are

Mr.M.Kuussaani's studies about interference voltages in subscriber cables in

rural areas of Finland [12], Mr.Arne V. Johansson and Mr.Ake Ekstrom (both

from Sweden) studies in Telephone interference criteria for HVDC

transmission lines [7], WEE working group on power system harmonics [13]

etc. In all these studies people tried to find the methods to reduce the induced

voltage in the telephone line by improving the telephone circuit balance or by

reducing harmonic components of the voltage and currents in power line.

In South Africa the research work in the co-ordination of power and

communication systems was undertaken by the Power and Communication

Systems Co-ordinating Committee, appointed by the SAIEE, over the period

1938-1957. This committee comprised representatives from the Electricity

Supply Commission, the South African Railways and Harbours, the General

Post Office, the Victoria Falls and Transvaal Power Company, performed

extensive field tests and technical investigations for particular local conditions

[1]. Their conclusions were reflected in the "Code of Practice for Overhead

Power Lines" produced by SAIEE in 1966. In terms of legislation interference

limits are stipulated in the Postmaster General's Requirements, as gazetted [3].

Eskom is bound to this legislation and new power routes have to be approved

by Telkom before construction can start. Under normal circumstances, route

approval of a power line will be preceded by the calculation of the anticipated

induction levels in any nearby cabled or open wire telephone circuits, and these

levels are then compared to the limits stipulated. If the limits are exceeded,

certain remedial action must be taken, such as re-routing of the power line or

telephone line, improved screening on either or both systems, upgraded surge

protection or line isolation, or introduction of additional transpositions in the

case of open wire circuits. The final decision regarding remedial action depends

on the actual limit exceeded and a number of other factors, including cost, as

agreed upon by the respective authorities.

2

Page 11: Telephone interference caused by harmonics and unbalance

START

V

Stipulate protective measures

Identify power and telecommunication facilities involved

Determine electric and geometric parameters required to estimate the effects

Calculate induced voltages and currents

END

General procedure for controlling effects caused by power lines on

telecommunication lines are illustrated in the flowchart below.

Figure 1 Flowchart to be followed when dealing with danger and disturbance

problems in practice.

For the calculation of the induction level, there are three distinct coupling

mechanisms to be considered, namely electrostatic, electromagnetic and

conductive coupling. For each of these there are two types of applicable limits.

The first one considers induced dangerous extraneous voltages and currents to

flow in the telecommunication installations due to abnormal conditions on the

power line (e.g. cable breaks, accidental short circuit, earth fault etc.). The

second one considers the level of interference which could result in degradation

of speech quality, or signal to noise ratio of the telephone circuit, and is

3

Page 12: Telephone interference caused by harmonics and unbalance

normally associated with normal (balanced) conditions on the power line.

Limits regarding danger are normally associated with longitudinal or common

mode voltages, and limits regarding interference with transverse or differential

mode voltage. Longitudinal e.m.f is the electromotive force arising from

induction by current in a power line into the circuit formed by the conductors

of the telecommunication line and earth. Metallic circuit component or

differential mode is the difference in longitudinal component at the two

conductors of the communication line due to system unbalance and the

separation distance between them. The Postmaster General's Requirements of

1978 stipulate the following limits for induction from power or railway lines:

Interference:

2mV maximum psophometrically weighted transverse emf on any wire

pair, which is equivalent to 1 mV potential difference measured with a

psophometer.

Danger:

60 V rms maximum longitudinal induced voltage during normal

operating conditions of the power line.

150 V rms maximum longitudinal voltage in "special cases" during

normal operating conditions.

650 V rms maximum longitudinal voltage during fault conditions on the

power supply system.

The 150 V limit applies to conditions of particular difficulty and is subject to

special precautions being taken such as

the marking of any part of the installation that could be raised to this

potential, and

the issue of special instructions to personnel likely to have access to

this exposed section.

It is generally found that the effect of electrostatic coupling is minimal and

interference levels are acceptable, if minimum stipulated separations between

the circuits can be maintained. The calculation of electromagnetic induction

during line faults as well as interference during normal operating condition are

very important. For the calculation of electromagnetic induction during fault

4

Page 13: Telephone interference caused by harmonics and unbalance

conditions Telkom currently uses a graphical procedure based loosely on the

1963 Directives as well as work produced by Pollaczek in 1926. This

procedure is outlined in their in-house Technical Instruction TI3009 [4]. There

are some limits for this method, especially the case for short exposures, for

which the "infinite line" approximations used in the TI3009 are invalid.

Another problem is that the damage to exchange equipment due to lightning.

For these reasons Eskom tried to establish a mutually (Eskom and Telkom)

accepted computer programme that could incorporate the latest theory and

numerical techniques available, as a general tool for interference problems [11].

Interference due to harmonic currents and voltages on the power line to the

open wire telephone line is a major issue for Eskom in the rural areas.

Harmonics up to 71st and 73rd are present on power lines which are injected

from smelter plant. The aim of this project is to find out the effect of higher

order harmonic voltages and currents on the induced voltage on the

telecommunication line and thus establish recommended guidelines and

techniques for ensuring power system/ telephone system compatibility. The

results will in particular show whether the present separation criteria

(Postmaster General's Directive on separation between power and telephone

lines) needs revision or not.

5

Page 14: Telephone interference caused by harmonics and unbalance

Chapter 2

ELECT °MAGNETIC COUPLING

The voltage induced on a communication circuit can be the result of currents

flowing in a power circuit. This induced voltage can cause interference with

service, damage to apparatus and hazard to persons using the former. The

magnitude of induced voltage increases at higher harmonics. In this chapter the

general theory, modelling of the system and factors influencing the induced

voltage in the case of electromagnetic coupling are discussed.

6

Page 15: Telephone interference caused by harmonics and unbalance

2.1 ELECTR I MAGNETIC COUPLING

2.1.1 GENERAL THEORY

Consider an infinitely long conductor(power line) carrying current of I A.

There will be a time varying magnetic field around the power line due to the

time varying current flowing through it. According to Biot-Savart law field

intensity H at a point P, produced by a differential current element IdL is

I dL sin dH a (2.1)

2

r

dH 47r r2

1 I dL sin 0 (2.2)

where 9 is the angle between the current carrying conductor and a line

connecting the conductor to the point (p), "r" is the distance between the

conductor and the point (p) and y 7r is the constant of proportionality in 4

m.k.s units.

H = I sit

e dL (A/m) (2.3) 4 7r y .

Magnetic flux density B is defined as

B = poH (Wb/m2)

(2.4)

and magnetic flux (I) passing through any desired area is

0 = JB .dS

(wb)

(2.5)

If there is another conductor (communication line) cutting this magnetic flux,

according to Faraday's law, time varying magnetic field produced by the power

line will produce an electromotive force (emf) on the communication line.

dcb emf = – — (V) (2.6) dt

The minus sign is an indication that the emf is in a direction as to produce a

current whose flux, if added to the original flux, would reduce the magnitude of

the emf (Lenz's law).

7

Page 16: Telephone interference caused by harmonics and unbalance

Consider a single phase power circuit, fig 2.1(a). G is the single phase power

source, P 1 and P2 are the go and return conductors. I is the current flowing

through the power circuit. C 1 and C2 are the communication conductors

located in proximity and TE is the telephone terminal equipment. In fig 2.1(b) it

is shown that C 1 and C2 lie in different equi-potential lines so that unequal

voltages are induced in these conductors.

F G I P2

(b) Figure 2.1 Schematic diagram illustrating magnetic induction from a power

circuit on a communication circuit.

Elementary section

Equi-potential fields

8

Page 17: Telephone interference caused by harmonics and unbalance

2.1.1.1 Loop Currents

Consider a three phase system carrying currents of IR, Iw and IB. If the system

is balanced then:

IR +4 = 0 (A) (2.7.1)

For an unbalanced system:

IR +4 ±IB = IO (A) (2.7.2)

Where Ico is the return current.

Three phase currents that induce voltages in communication circuits can be

classified as (1) positive- and negative-sequence components and (2) the zero-

sequence component. The first type is normally confined to the line conductors

(balanced load) and for the second type the line conductors constitute one side

of the circuit and neutral or ground wires, or earth the return (unbalanced

load). Obviously the coefficients of induction from power-system currents are

different for these two cases.

Considering a 3- phase power line with phase conductors marked Red, White

and Blue, it is possible from knowledge of the respective current vectors (IR

Iw , IB) to determine the loop currents (IRw, IwB, IBR) as well as the earth

current 10 using the concept of sequence components. This reduces any

unbalanced 3 -phase system into balanced positive, negative and zero sequence

components. The sequence components of the red phase current, for example,

are given by the vector [2] :

-IRO 1 1 1 41 T = 3

1 A R+ 1 a a2 (A) (2.8)

a _ R- a2 a

with a = -0.5 + j 43/2 = ei2n5

we further have the relations:

= IR+

IB+ = a IR+

Iw. = a IR- = TR_ (A) (2.9)

IWO = IRO

IBO = IRO

9

Page 18: Telephone interference caused by harmonics and unbalance

rBWB

w

I

I R _

b b-1 r alb ab-14R+1

IR_ (A)

ab a2b-1 (2.10)

Introducing operator b = 43/2 + j/2 = ejni6 , the loop currents are easily shown

to be:

The total earth current equals the sum of the zero sequence currents,

IRO + Iwo + IBO = 31R0 (A) (2.11)

This return current will also produce some induced voltage in the telephone

conductors other than phase currents. In accordance to Lenz's law the flux

they create will be opposite to the flux due to phase currents. Therefore the

return current has a compensating effect on induced voltage and which enables

the neutral or ground wire to serve as electromagnetic screen.

2.1.2 GENERAL DESCRIPTION ABOUT TRANSMISSION LINE AND TELEPHONE LINE

For the transmission of power in South Africa the commonly available nominal

voltages are 400kV, 275kV, 132kV, 88kV, 66kV, 44kV, 22kV, and 11 kV. For

a three phase over head power line mainly there are three types of

configurations available, horizontal, vertical and triangular. Number of

conductors per phase will be one or two. There will be one or two shield or

earth wires at the top of transmission line support. They are usually connected

galvanically. These wires have triple function:

to give protection against lighting ;

to interconnect the support earths;

to reduce fault currents circulating in the earth and thus reduce the induced

voltages and rise in potential of supports and station.

10

Page 19: Telephone interference caused by harmonics and unbalance

Auto transformer

22kV 400 V

Trans-mission subscriber equipment

Local exchange

Distribution cable Transmission cable

nn Surge p otec ion devices

Figure 2.2 Transformation of 275 kV Transmission Line to 400V

Distribution line

2.1.2.1 Telecommunication Network

A general picture showing the telecommunication line is given in the figure

(2.3) below:

Figure 2.3 Telephone Line Network Between a Subscriber and an

Exchange

In two way telecommunication each end of the links comprise a transmitter and

a receiver, and bi-directional propagation is effected via the physical medium.

The temporary links between different telecommunications users are

established by means of switches. Each terminal installation is attached to a

local switching centre by one or more subscriber lines.

11

Page 20: Telephone interference caused by harmonics and unbalance

2.1.2.1.1 Composition of Transmission Supports

The different transmission supports are

open wire lines

Open wire lines are made of bare metal wires. They are arranged in groups and

fixed to supports by means of insulators. Open wire lines are about 6-10m

above the ground and their conductors vary in diameter between 3 and 5 mm.

The distance between associated conductors forming a circuit is between 20

and 40 cm.

symmetrical pairs cable lines

In this type telephone cables are capable of containing a large number of

conductors within an extremely small section. Each cable conductor consists of

an insulated metal wire. Different cabling methods are used for arranging these

conductors in pairs or quads.

coaxial pair cable lines

wave guides

radio relays

optical fibres

2.1.3 DESCRIPTION OF SCALE MODEL

2.1.3.1 Transmission Line

275kV horizontal configuration is used for the scale model of a transmission

line of practical purposes. The tower geometry for 433 A is given in Appendix

D. The scaling is done purely on the basis of area allocated for the

experimental purpose, i.e. the length of the line is chosen arbitrary as 100 m

and height of the power conductors from ground level is 3.5 m.

Transmission line configuration (Refer fig D.2 in Appendix D)

Height of phase conductors from ground level 19.3 m

Separation distance between the phase conductors 7.4 m

Number of earth or shield conductors 2

12

Page 21: Telephone interference caused by harmonics and unbalance

Height of shield conductors from ground level 26.6 m

Separation distance between the shield conductors 6.55 m

Scale model

1.Height of phase conductors from ground level 3.5 m

Scale constant 5.5

Separation distance between the phase conductors 1.35 m

Number of earth or shield conductors 2

Height of shield conductors from ground level 4.4 m

Separation distance between the shield conductors 1.2 m

Total length of the line 100 m

2.1.3.2 Telephone Line

Two wire open line is used for scale model. Scale constant is same as the one

used for transmission line.

Original config: Scale model

Height of conductors from ground level

6.5 m 1.2 m

Separation distance between conductors 15-20 cm 5 cm

Total length of telephone line 80 m

Photograph of Test Line at Rand Afrikaans University

13

Page 22: Telephone interference caused by harmonics and unbalance

2.1.4 MODELLING OF THE SYSTEM

A lot of research works were performed in the 1920's to establish formulae

suitable for the prediction of electromagnetic coupling between two circuits.

Numan's formula for the mutual magnetic energy of two circuits to linear

circuit, [2] gave completely wrong results when an earth return current path

was considered. In 1923, G.A. Campbell gave a solution for the mutual

impedance of earth-return circuits of finite length. Because of the imperfect

knowledge of the conductivity of deeper parts of soil, it was impossible to see

clearly which approximation are permitted in the calculation of the mutual

impedance between lines with earth return. Careful measurements on specially

erected lines, in regions of different conductivity of soil, proved that the later

theory, developed independently and nearly simultaneously by Pollaczek,

Carson, Haberland and Buchholz in 1926-1927, corresponds much better to

experiment than that formerly developed, [2]. This theory is still used in the

1989 Directives.

Carson's general formula is CO

M = j f[Vu 2 + j – u] e-bau ecasf cos(a au) du 0

Pollaczek general formula is 0

Mp = ./P0 {j eu(ja+b)+c tJ 2FT—ja 2 [11 2 j 2 u + a +u] du + 27r a2

-CO

(2.12)

f

e ttCfa-b)+c u2-311-ja2 [ lug •a2 j u]du} (2.13) o

Haberland's formula for a point in the air ( c>0 ) is

- ua(b+c) Mx, ln—D + j[Vu2 +i – ] e cos(a a u) du (2.14)

- 2,r d r 0

Where a - horizontal distance between inducing conductor and

induced conductor, m

b - height of the inducing conductor above surface of earth, m.

14

Page 23: Telephone interference caused by harmonics and unbalance

c - height of induced conductor above surface of earth, m. (in the

buried conductor c<O)

D - distance between induced conductor and image of the

inducing conductor on the surface of the earth, m.

d - actual distance between inducing and induced conductor, m.

a - conductivity of soil, mho/m.

f - frequency; w = 27r f

110 - 4 it x 10 -7 permeability of free space, H/m.

a, - a co

Figure 2.4 Mutual Inductance Between Conductors 1 and 4

Equation for the transverse electric field on the surface of the earth are of the

form,

E AS

co

= a ) . 119- .1[ 21177-Fj eb a uec a PT cos(a a u) du (V/m)

0

(2.15)

where I is the inducing current. This simple equation is valid if both lines are

overhead. In the case of stratified soil, the conductivity of the different layers

can effectively be represented by homogeneous soil with an intermediate value

of a.

The mutual inductance M14 can be obtained from the relation:

M14 =

27r EAs

f I (Wm) (2.16)

The solution to the integral relation for EAs as provided by Pollaczek yields the

following results for M14 a function of separation parameter aa. [2]

15

Page 24: Telephone interference caused by harmonics and unbalance

- if aa < 0.5 :

M14 = 42 7r 15 + —

2 (1+ j) a (b + c)] (H/m) [21n

g a d + 1 – j —

2 3

(2.17)

Where d -actual distance between the conductors, = Va 2 + (b– c)2

g -1.7811.. is the complex of Euler's constant.

- if aa >= 0.5 :

,u 0 kei aa – jker' aa j 4414 7ras (aa)2 -I (H/m) (2.18)

where ker' and kei' are real and imaginary part of the first derivative of the

modified Bessel function (second kind, order zero)

- if as > 10 :

M14 = Po

7r (aa) 2 (Him) (2.19)

From these equations, it is observed that the mutual inductance is complex,

with phase angle always larger than 90 °, and tending towards 180 ° for larger

separations. The real component of M14 is larger near the conductor, initially

decreases slowly (as the logarithm) with increasing distance, then decreases to

negligible values in an oscillatory manner with increasing distance. The

quadrature component of M14 is small near the inducing conductor, eventually

dominates with increasing distance, then decreases as 1/ a 2 .

Mutual impedance Z14 between the conductors 1 and 4 is:

Z 14 = - jcoMia(ohm/m) (2.20)

Voltage induced on conductor 4 due to the current flowing through the

conductorl (I A) is:

V14 ZI4 I lt

(V)

(2.21)

Where It is the length of exposure between 1 and 4.

16

Page 25: Telephone interference caused by harmonics and unbalance

2.1.4.1 Solution for a Multi-conductor System (Three-phase system)

B

b

OT2

Figure 2.5 Mutual Inductance Between Three-phase Conductors and

Telephone Conductors

In the above figure R,W and B represents three phase conductors and T1 and

T2 represents two telephone conductors. Mutual inductance(MRT1) between the

red phase conductor and the first conductor of the telephone line is:

4~ r [2 ln + 1 – j—

+ 2-5 — (1+ j)a(b+c)]

47r gad2

Rn 2 3

(H/m) (2.22)

Where diti= q[aRr1 2 + (b-c)2]

Similarly we can find Mwri and MBT1 .

Mutual impedance between the red phase conductor and the first conductor of

the telephone line, ZRT1 is:

ZRT1 -j(01\ARr1 (H/m)

(2.23)

Similarly find Zwri and Z$T1 •

Loop inductance ZRwri is:

ZRWT1 = ZRT1 ZWT1 (Him) (2.24)

Similarly we can find ZWBT1 and ZBRT1

IR, Iw and IB be the current flowing through red, white and blue phase

conductors respectively. Now we can calculate the loop currents IRW , IwB and

IBR (see section 2.1.1.1)

The induced voltage on the first conductor of the telephone line due three loop

currents and earth current (unbalanced load) is:

MRT1

17

Page 26: Telephone interference caused by harmonics and unbalance

VT1 [ZR1PT1 ZWBTI

[

IRO

[ZRWTI ZW73T1 ZBRT11 Iwo 4 I BO _

(V) (2.25)

For a balanced load the second part of the above equation will be zero.

Similarly we can calculate the induced voltage on the second conductor of the

telephone line (VT2). The differential mode voltage Vd is:

Vd = VT1 - VT2 (V) (2.26)

2.1.4.2 Equations for Loop Inductance - for small separations.

For small separations, loop induction becomes significant. Loop induction

occurs when the current returns via a second conductor, as is the case for

balanced conditions on a power line. The mutual inductance for a double wire

circuit and a circuit with earth return can be found by calculating the partial

derivative of M14 and forming the total differential, resulting in [2]:

Po M12/4 [

2ada +[

2 (b — c) +

ria (1+ j) ]db ] gym)

4n- d2 d2 3

(2.27)

for a loop with horizontal projection da and vertical projection db.

2.1.5 PSOPHOMETER AND PSOPHOMETRICALLY WEIGHTED CURRENT

2.1.5.1 Psophometer

The psophometer is an instrument which has been introduced for measuring the

value of the parasitic voltages produced in telephone circuits by nearby power

lines, from the point of view of the interference which the noises due to these

voltages can cause to the normal use of the circuits[10]. It was developed with

a view to making measurements at the ends of long-distance circuits. It has a

very high input impedance, and can be used in the same circumstances as a

18

Page 27: Telephone interference caused by harmonics and unbalance

voltmeter; it consists essentially of an a.c. measuring instrument, associated

with a weighting network.

2.1.5.2 Psophometrically Weighted Current

In noise interference case, it may be necessary to measure the spectrum of

harmonics in the disturbing current.

The psophometrically - weighted current I„ is

1

p ilE 13; 1-; (A) (2.28) 800 if f

where Pf is the psophometric weighting factor at frequency f

If is the harmonic r.m.s component of the line current at frequency f.

Note:- Psophometric weighting coefficients for different frequencies are given

in Table A-1 in Appendix (A).

The psophometric equivalent 800 Hz disturbing current is:

/peq Pf 2

If 2 ELY (A) (2.29)

P800 800

To find the value of psophometrically induced voltage, the value of current

used in the above section(2.1.4.1) must be psophometrically weighted current.

Another assumption is that for a linear system, the effect of different harmonic

currents present in the line current (fundamental + different harmonics) will be

the same if we treat them separately and then find their combined effect. The

formula use in this case is:

VT = AAVTfiin)2 + (VT1)2 + (VT2 )2 (VT02 (V/m) (2.30)

Where VITun, VT1, VT2 VT„ are the induced voltages at fundamental, first

second and nth harmonics respectively.

Vrfun = Zfun x 1 x ipueun (V/m) (2.31)

2 1 i

( 50) (A) (2.32)PS Pecliun = 800 502 800)

19

Page 28: Telephone interference caused by harmonics and unbalance

VT' Z i X1Xl peg] IM)

(2.33)

Vd = VT x A. m (Wm)

(2.34)

where is the sensitivity coefficient of electromagnetic coupling.

Sensitivity coefficient of electromagnetic coupling(t) is defined as the ratio

between the psophometric emf acting in a loop ep and the common mode

longitudinal emf Ep caused by magnetic induction.

ep =

Ep (2.35)

Measurement can be done using exiting induction, or for a more systematic

approach, artificial induction can be used. These techniques are

comprehensively detailed in the Directives [10]. Measured values for 2m

typically range from 0.001 to 0.05 for open wire circuits, while for cables

values are normally much lower.

2.2. FACTORS INFLUENCE THE INDUCED VOLTAGE IN A TELEPHONE LINE

From equations 2.22, 2.23 and 2.25 it is clear that the factors influencing the

induced voltage in a telephone line are: line current, separation distance

between the power and telephone line, frequency of the inducing current,

configuration of the power line, earth resistivity (soil conductivity) and

telephone pair spacing.

2.2.1 LINE CURRENT

From equation 2.21 it is clear that voltage induced on a conductor is directly

proportional to the magnitude of current flowing through the inducing line. To

verify this mathematically induced voltage is calculated for two different

inducing currents(10 A and 5 A) in the case of test line configuration (section

2.1.3). The separation distance between the two lines is 1.57 m (from the red

phase conductor to the telephone conductor), the exposure length is 80 m and

soil resistivity is 260 ohm-m. In the graph given below (from 50 Hz- 5 kHz) it

is shown that when magnitude of current doubles the magnitude of induced

20

Page 29: Telephone interference caused by harmonics and unbalance

voltage will also double if there is no change in the other parameters of the

lines.

Indu

ced

diff

:mo

de v

olta

ge

(my)

45

40 —

35 —

30 —

25 —

20 —

15 —

10—

5 —

" 0

Diff:mode induced voltage 1=10 A (my) Diff:mode induced voltage 1=5 A (my)

0 1000 2000 3000 4000

Frequency (Hz)

Figure 2.6 Effect of Line Current on Induced Voltage

2.2.2 SEPARATION DISTANCE BETWEEN POWER AND TELEPHONE LINES

The separation distance between power and telephone routes is the

fundamental factor which determines the value of induced voltage. Even if the

currents are balanced, because of the difference in separation distance between

each phase conductor and the telephone conductor the magnitude of the

induced voltage is different due to each phase current. This causes a differential

voltage in the telephone loop. To minimise the magnitude of this differential

voltage, transposition of power line or telephone line can be done. In the graph

below induced differential mode voltage in the telephone line is calculated for

the test line configuration (section 2.1.3) for two different separation distances

(1,57m and 3,14m) for frequencies 50 Hz- 5 kHz. The magnitude of inducing

current is 10 A, exposure length is 80 m and soil resistivity is 260 ohm-m.

From the curves it is clear that induced voltage decreases the separation

distance between the power and telephone line increases.

21

Page 30: Telephone interference caused by harmonics and unbalance

Indu

ced

diff

:mod

e vo

ltage

(mV

)

45

40 —

35 —

30 —

25 —

20 —

15-

10-

5-

0

for 1.57m separation for 3.14 m separation

0 1000 2000 3000 4000

Frequency (Hz)

Figure 2.7 Effect of separation distance on induced voltage

In Postmaster General's Requirements curves to determine minimum

separation distance between power lines and communication routes for

different exposure lengths are given [ Appendix B].

2.2.3 FREQUENCY

The magnitude of induced voltage varies approximately directly with

frequency. Note that the mutual inductance is also a function of frequency.

Thus, the higher the frequency (higher order harmonics), the higher the value

of the induced voltage. Induction at harmonic frequencies, particularly at 180

Hz and 3000 Hz occurs most frequently during normal operation and may

result in significant audible disturbance which affects transmission and

reception of telephone conversations. In the graph below induced differential

mode voltage (calculated) is shown for frequencies 50 Hz to 4 kHz for the test

line configuration (section 2.1.3) for inducing current of 10 A, exposure length

of 80 m and soil resistivity of 260 ohm-m.

22

Page 31: Telephone interference caused by harmonics and unbalance

Indu

ced

diff

:mod

e vo

ltage

(m

V)

45

40 —

35 —

30 —

25 —

20 —

15-

10-

5-

0 0 1000 2000 3000 4000

Frequency (Hz)

Figure 2.8 Effect of Frequency on Induced Voltage

2.2.4 CONFIGURATION OF THE POWER LINE

The configuration of the power route conductors, i.e. whether they are

arranged in vertical, horizontal or triangular formation, is of importance in that

it determines the relative phase of the induced voltage in the phone line from

each of the phase conductors and consequently, the net longitudinal voltage in

each wire of the telephone line.

2.2.5 LENGTH OF EXPOSURE

The induced longitudinal voltage is a function of the length of exposure

(directly proportional). In normal case, length of exposure indicates the length

over which the separation between telephone and power lines remains sensibly

constant (parallelism). The graph below shows the effect of exposure length

(80 m and 40m) on induced voltage. The test configuration (section 2.1.3) is

used for calculation with inducing current of 10 A, separation distance of 1.57

m and soil resistivity of 260 ohm-m.

23

Page 32: Telephone interference caused by harmonics and unbalance

5— Indu

ced

dif

f:m

ode

vo

ltag

e (m

V)

45

40 —

35 —

30 —

25 —

20 —

15 —

10 — •

Diff:mode induced voltage, 80 m exposure(mV)

Diff:mode induced voltage (mV), 40 m exposure

0 1000 2000 3000 4000

Frequency (Hz)

Figure 2.9 Effect of length of exposure on induced voltage

2.2.5.1 Oblique Exposure and Crossing

An exposure section between the limits of which there is an almost linear

increase or decrease of the distance between the lines is called an oblique

exposure. The passage of a telecommunication line from one side of the electric

line to the other is termed a crossing.

dl

V Inducing line

Figure 2.10 Geometric layout of oblique exposure and crossing

1= exposure length

A crossing is considered as a parallel section having a separation distance,

d= 6m (2.36)

24

Page 33: Telephone interference caused by harmonics and unbalance

where d =Ic11.712 and length "I" equal to the projection of the segment

contained in the zone of 10 meters around the power line. Outside the 10 m

boundary the exposure is treated as a normal oblique exposure.

2.2.6 EARTH RESISTIVITY (p)

The mutual inductance increases with increased values of earth resistivity since

the earth currents will flow at greater depths ( 659 frri), thus increasing the

magnetic effect of the current. Soil conductivity (a = f ) can vary from 0.1

to 0.0001 mho/m, depending on the type and age of the formation. Wenner 4-

electrode method for finding earth resistivity is explained in Appendix C. If the

local composition of the soil is known, a fair estimate for a may be obtained

from table C-1 in Appendix C. In the absence of measured values or adequate

knowledge of the soil composition, fig.C-1 in Appendix C can be used.

2.2.7 TELEPHONE PAIR SPACING

The spacing of the wires of the telephone pair will affect the relative distance of

the two wires from the power route. This difference in distance will produce a

different longitudinal voltage in each conductor and will, therefore, influence

the value of the transverse voltage.

25

Page 34: Telephone interference caused by harmonics and unbalance

Chapter 3

ELECT °STATIC AND CONDUCTIVE COUPLING

The voltage induced on a communication circuit can be the result of its position

in the electric field or electrostatic field produced by the line voltages of the

power line. Electrostatic or capacitive coupling expresses the relation between

the potential of the inducing electric line and the induced charging current, per

unit length occurring on the telecommunication circuit. Conductive coupling is

the phenomena where part of the earth potential (due to power line earth

currents) will transfer to the telecommunication circuit through its earth

electrodes. In this chapter general theory of electrostatic and conductive

coupling, modelling of system for these and factors influencing them are

discussed.

26

Page 35: Telephone interference caused by harmonics and unbalance

3.1 ELECTROSTATIC COUPLING

3.1.1 GENERAL THEORY

An important source of extraneous voltage on communication circuits under

normal operating conditions, may be electric induction from a neighbouring

power circuit. By this is meant the voltage impressed on a communication

circuit because of its position in the electric field, or electrostatic field produced

by the circuit voltages of the power system.

Consider a section of line with power conductor P energised from a single-

phase grounded source (G) and with communication conductor Cl and C2

figure(3.1.a). There are capacitances between conductors and between

conductors and ground. In fig (3.1.b) we can see that even if the

communication conductors are separated for a short distance they lie in

different electric potential lines produced by the power line, and different

potentials are induced on them.

(a)

27

Page 36: Telephone interference caused by harmonics and unbalance

180-

160-

140--

120-

100-

80 _

60 -

40 -

20

M 20- .................................................

....... ........

..• ..... - . . .... '•.

60 - •. .

„.• *-- ... .. . . • ''

... ...

......... ••"..

......... ..•

80 -

100 -

120 -

140 -

160 _

180 -

N

(b)

Figure 3.1 Schematic Diagram Illustrating Electric Induction From a Single

phase Ground-return Power Circuit on a Communication

Circuit Conductor.

Elementary section.

Equi-potential fields.

The effect of electrostatic coupling is important only if induction from an open

power line to open wire telephone line or suspended cables without a metal

sheath are considered.

When calculating the effect of a poly-phase line the phase-to-earth voltages are

replaced by their symmetrical components. The expressions for the induction

effects due to zero-phase sequence voltage U o of an balanced system and to the

balanced voltage U 1 , i.e. positive-phase sequence, differ greatly and will be

studied separately. In the case of a three-phase line the service voltage U is the

28

Page 37: Telephone interference caused by harmonics and unbalance

line-to-line voltage. For a balanced three-phase system the modulus of the

positive sequence component Ui is equal to U/'13 and Uo is zero. If one of the

phase conductors of a three-phase system with insulated neutral is accidentally

earthed then the modulus of the zero sequence voltage Uo is equal to U/43.

3.1.2 MODELLING OF THE SYSTEM

For the calculation of capacitive coupling, we are confined to systems of lines

which are long in relation to all dimensions perpendicular to length and we

suppose also that the lines are parallel with the surface of earth and with each

other, so that a two-dimensional problem results. The effect of earth is taken

into account by means of Kelvin's method of electrostatic images. This method

would be absolutely correct if the soil were a perfect conductor; even if this

condition is not fulfilled the correction may be neglected up to 1 MHz. [2]

1

D1

Figure 3.2 Electrostatic Coupling Between Two Conductors 1 and 4

Consider two thin infinite conductors 1 and 4, of radius r 11 and r44 , with charge

per unit length Q 1 and Q4 parallel to each other and placed horizontally above

the earth, the line potentials can be written as

= Pn + P4 Q4 (V)

(3.1)

U4 = P41 Q1 + P44 Q4 (V)

(3.2)

29

Page 38: Telephone interference caused by harmonics and unbalance

, 2b = ln r:1 1 = ko

P = k 1n R4 14 0 d 14

(m/F)

= ko In a2 1-(1).+c) 2 a2 + 0-0 2

Where

Coupling function

14 = In D14

P41 = P14

, 44 D , 2c P44 = K in = K in— (m/F) 0 r44 0 r44

k0 1

= 18x109 (mIF) 27rso

Similarly for a system of 'n' parallel conductors we have a system of 'n'

equations:

= ko[a 11 1 -F Q2 P2i +....------ -F Q.P.i ] (V)

(3.9)

The factor Pi; is termed as mutual potential coefficient and if i = j it is termed as

self potential coefficient. Multiple conductor bundles are often used no power

lines. In this case the conductor radius rii is replaced by the effective

electrostatic radius.

= VrN A N-1 (m)

(3.10)

Where r = radius of each conductor

N = number of conductors, arranged on circle of radius A

To solve this system of equations the classical (analytical) approach involves

solving for the self and mutual capacitances of the system of conductors.

Mutual (coupling) capacitance

C14 = C41 P14

111 1'44 (F/m) (3.11)

(3.5)

(3.6)

(3.7)

(3.8)

30

Page 39: Telephone interference caused by harmonics and unbalance

Self capacitance

CI I

C44

1

1

P44

(F/m)

(F/m)

(3.12)

(3.13)

Let 1/4 be the electrostatic potential at conductor 4 due to conductor 1:

1 174 = P14 (V)

P1 1

(3.14)

Under normal conditions the telephone lines are closely spaced, and potentials

therefore almost equal. The open circuit voltage of one line is not affected by

others. It is therefore normally only necessary to consider a single induced line,

for calculation of the potentials and for the open circuit voltage of the complete

exposure.

To calculate the discharge current to earth where a person come into contact

with one or two of the telephone line(s), we can treat those line(s) as earth

wire(s) [U4 = 0] and compute the charge present on the line(s). The current is

then obtained by differentiation of this charge for frequency f.

From equation (3.1) (neglecting the second term)

Q i = 1 Ul (coulomb) (3.15)

P11

substituting (3.15) in (3.2)

Q4 = 1

UA„ 4' U, P44 pi 1 P44

• (coulomb) (3.16)

The current flowing through the telephone conductor:

i4 = jcp 1

—U4 /CO 41U1 (Aim) 44 P1 1 P44

when U4 = 0

(3.17)

ja = j w Poi rT

u 1 P„ P44 P44

(A/m) (3.18)

31

Page 40: Telephone interference caused by harmonics and unbalance

3.1.2.1 Psophometrically Weighted Voltage (Up)

The psophometricaly weighted voltage can be defined similarly as the current

(refer section 2.1.2.1).

Up = 1 ilEP; U; (V) (3.19) P800

where Pf - psophometric weighting factor

Ur - harmonic r.m.s component of the line voltage at frequency f.

Equivalent Disturbing Voltage (U peq)

Upeq 81 VEQ f

Pf

)2

(V) (3.20) P800

where k, — — 8f

0 and it represents the increased influence of higher frequency

— 0

term due to the capacitive coupling effect.

3.1.2.2 Sensitivity Coefficient for Electrostatic Coupling (.1, e)

'l e is defined, for a specific telephone pair, as twice the ratio of the differential

voltage uf (line-to line) to the common-mode voltage U r (line-to-ground)

appearing on the wires when the line is subject to electrostatic induction. For a

mixture of frequencies, this coefficient is described as twice the ratio of the

psophometric voltage up to the psophometric voltage Up of the lines with

respect to earth.

= 2uP U p

(3.21)

The sensitivity coefficient applied to a telephone line is normally taken as the

average of all the pairs on the line, and adequate description of its measurement

is provided in the Directives. Its value depends largely on geometric

considerations and the unbalance of the pair. This unbalance has three

components, namely, the unbalance of the coupling parameters with respect to

the power line, the unbalance with respect to earth and the unbalance with

32

Page 41: Telephone interference caused by harmonics and unbalance

respect to nearby wires. The usual means of improving balance and hence the

sensitivity coefficient is regular transpositions of the telephone line, which also

has the benefit of reducing cross-talk. For twisted pairs, the unbalance is

practically zero.

3.1.2.3 Telephone Harmonic Form Factor kr

Also simply termed the Telephone Form Factor, kris defined as the ratio

between Up and the power line service voltage E. For calculation purpose, the

measured value of kr has to be increased by 50 % to allow for the most

unfavourable :working conditions. In the absence of measurements, the

Directive suggest the following values [10]:

E < 80 kV E >= 80 kV

Loads with static converters

All other loads

10

4

5

2

Table 3.1 Suggested Working Values for the Telephone Form Factor

3.1.3 FACTORS INFLUENCING THE INDUCED VOLTAGE

3.1.3.1 Geometric Configuration of Installations.

The induced voltage due to electrostatic coupling depends on the capacitance

between conductors as well as capacitance between conductors and earth. The

value of these capacitance's depend on the height of conductors above ground

level, separation distance between them etc. The longitudinal voltage varies

inversely with the separating distance.

3.1.3.2 The Line Voltage and Operating Conditions of the Power Line.

Like power system currents, power system voltages which produce induction

effects in communication circuits can be classified as (1) positive- and negative-

sequence components (balanced load) (2) zero-sequence component

33

Page 42: Telephone interference caused by harmonics and unbalance

(unbalanced load). Balanced conditions will produce significantly less effects

than unbalanced condition. The induced voltage depends on the magnitude of

the line voltage.

3.2 CONDUCTIVE COUPLING

3.2.1 GENERAL THEORY

Alk 1s7i

iii

NAM

Figure 3.3 Current Distribution in the Event of a Phase-earth Fault

Occurring Inside a Substation.

When a phase to earth fault occurs the fault current will have two paths to

choose, earth or shield. Most of the fault current will flow through earth and

that will cause a potential rise at the earthmat or electrode closer to the point

where fault happens. Currents flowing in the ground in the case of a short-

circuit to earth in an electric system will cause a potential difference between

the electrode and remote earth. This happens in the regions where current

enters or leaves the ground. The potential difference is referred to as electrode

ground potential rise (GPR). The area surrounding a high voltage earth

electrode that is raised in potential is referred to as zone of GPR.

If a telecommunication electrode is located in the zone of GPR a part of

potential transfers to this electrode. This may enter the telecommunication

circuit through over voltage protection which are connected to these

34

Page 43: Telephone interference caused by harmonics and unbalance

electrodes. The phenomenon described above is, the effect of conductive

coupling.

When there is an unbalance in the three-phase power line (normal operating

condition) part of the return current flows through earth. This happens in the

single wire earth return line as well. Thus there will a zone of GPR around the

electrode which allows the return current to enters or leaves the ground.

3.2.2 GROUND POTENTIAL RISE (GPR) EVALUATION

3.2.2.1 Electrode GPR

The magnitude of conductive coupling between the electrode e and the point p

can, in a general manner, be expressed by the transfer resistance which is

defined as

Re(p) =v(p)

(ohm) Ie

(3.22)

where R. (p) is the transfer resistance between the electrode e and the point

I); V(p) is the potential to remote earth of the point p due to current

injected in the ground by electrode e;

1e is the total current injected in the ground by electrode e.

The idea of transfer resistance can be used to obtain the potential at a given

point in the zone of GPR due to an earth electrode and can be expressed as

V(p) = Re (p). (V) (3.23)

The GPR voltage of an earth electrode, e.g. tower footing is:

Ve = Re I. (V) (3.24)

Where Ve is the electrode GPR;

Ie is the current flowing through the electrode; it is

= Ics I

I is the earth-fault current (in three-phase network I = 310, where

10 is the zero-sequence current component);

35

Page 44: Telephone interference caused by harmonics and unbalance

x Netural Zone Zone of Influence

Potential rise

!<1

ks is a factor expressing the reduction in the current; due to tower

footing resistance and earth wires;

Re is the earth resistance of the electrode.

3.2.2.2 Area of GPR

One of the simplest form of electrode is the driven rod. Suppose this rod is a

part of an infinite conductor of uniform resistivity and a unit current enters to

it. This current will flow away radially from the point of entry and at a distance

`r. ' from the point of entry the current density will be 1/4 it ?. This follows

from the fact that at a radius r, the current will be uniformly distributed over a

sphere of radius r and hence of area 4 it r2. From these assumptions we can

prove that the earth electrode resistance of that is,(the resistance of a

hemisphere on the surface of homogeneous soil) [10]:

2 ,rre (n)

(3.25)

Where p is the resistivity of soil;

re is the radius of the hemisphere

2 7i. re

Electrode

Figure 3.4 Resistance and Potential Rise of Equivalent Hemisphere

36

Page 45: Telephone interference caused by harmonics and unbalance

When a current I is injected into the ground, then potential of electrode is:

V = P I (volt) (3.26) 2n-re

and GPR Vx around the electrode is:

V = 2 / (volt) (3.27)

7rX

Where I is the injected current;

x is the distance from the axis of hemisphere (x bigger than r e);

If we combine the formulas (3.24) and (3.25) then the GPR:

Vz = V re (volt) (3.28)

The equivalent hemisphere of a real electrode is defined in such a way that the

resistance of the hemisphere electrode and the real ones should be equal to

each other:

Re = P (CI) 2 7rre

From this, the radius of the equivalent hemisphere is given by:

(3.29)

re = 22rRe (m)

(3.30)

The formulas of resistance R e and equivalent radius r e are given in the table

below for three common electrode shapes [10]

37

Page 46: Telephone interference caused by harmonics and unbalance

Electrode Earth resistance

Re

Radius of equivalent hemisphere

re Type Shape and size

Driven

rod

P 11 11n81 — /

1 d 27z-li_ d j ln-

8/ —1

d

Ring of

wire

p 4D In ,—

7rD C=Z5 r h 7r2D Vd h

21n 4D frrh O

Earth

plate

Area of the plate

A

p

4 A 2 '—

,M =0.35921171 71- .11 7r

Table 3.2 Formulae for the Earth Resistance R e and Radius re of

Equivalent Hemisphere

38

Page 47: Telephone interference caused by harmonics and unbalance

Chapter 4

EXPERIMENTAL MEASUREMENTS

In this chapter the results of experimental work done on the practical (scale

model) set-up is compared with the calculated/ predicted values.

Psophometrically weighted induced voltage is calculated for different harmonic

components of the inducing current. Curve showing the minimum separation

distance vs. exposure length is done for an original 132 kV line.

39

Page 48: Telephone interference caused by harmonics and unbalance

4.1 INTRODUCTION

The aim of the experimental work was to explore the agreement between

theory and measurement of induced voltage for frequencies from 50 Hz to the

high order harmonic range of 4 kHz. This makes it possible to extend the

existing methods for predicting compatible separations to cases where high

order harmonics are present on power lines.

For experimental purposes, a scale model of a three phase power line and an

open wire telephone line was constructed at the Rand Afrikaans University

campus. Scaling was done purely on the basis of area available; the total length

of the power line is 100 m length and the attachment height of the phase

conductors was arbitrarily chosen as 3.5 m. A 275 kV horizontal configuration

light suspension tower was used for the basic scaling of the transmission line.

The open-wire telephone was scaled from standard Telkom designs.

An ELGAR (132 V / 22 A, 50 Hz-5 kHz, power amplifier) was used as the

three phase power source and load (resistors) was connected in the star

formation. For the telephone line both ends were terminated at 600 ohm. A

selective voltmeter (HP 3581 A, 0-50 kHz, 20 V-0.1 ptV) was used to measure

the induced voltage. To measure the magnitude and phase shift of phase

currents by using an oscilloscope three LEM 101 were connected in the circuit.

To get more accurate values for phase currents shunts were connected in series

(at each phase) and voltage was measured across them. Common mode and

differential mode induced voltages were measured on the telephone conductors

for frequencies 50 Hz- 4 kHz. Special attention was given to make sure that the

measured values are the real components of the specified frequency.

The cases discussed are;

Electromagnetic Coupling:

1. Balanced three phase condition (three phase currents are equal in magnitude,

10A)

Common mode induced voltage

Differential mode induced voltage

40

Page 49: Telephone interference caused by harmonics and unbalance

2. Unbalanced three phase condition, ground return (the magnitude of three

phase currents are not equal and the return current flows through true earth)

Common mode induced voltage

Differential mode induced voltage

3. Single Wire Earth Return

Electrostatic Coupling:

1. Balanced three phase condition (three phase voltages are equal in magnitude,

65V)

For all these conditions the induced voltage is calculated using the equations

from C.C.I.T.T. Directives [5] and HRJ Klewe's book [2]. The calculation

procedure is given in Appendix F. Experimental work proved that these

equations are valid even at high order harmonic frequencies (4 kHz). To find

the effect of these high order harmonic frequencies on induced voltage (limit of

1 mV) psophometrically weighted induced voltage is calculated for different

harmonic components of the inducing current. The maximum exposure length

for different separation distances are then calculated. This is done for a 132 kV

transmission line (not for test line).

4.2 ELECTROMAGNETIC COUPLING

For balanced three phase condition the three phase currents were equal in

magnitude, 10A and induced voltage is measured from 50 Hz- 4 kHz. The

magnitude of three phase currents were kept as a constant value by adjusting

the load and the line voltage at each frequency. Common and differential mode

induced voltages were measured and compared with the calculated values.

4.2.1 BALANCED THREE-PHASE CONDITION

IR = Iw = IB = 1 0 A at 120° phase shift

41

Page 50: Telephone interference caused by harmonics and unbalance

- - - - SHUNT LEM 101

Source 132 V/ 22 A

0

Com

mon

mod

e vo

ltage

(V)

2

1.8 —

1.6 —

1.4 —

1.2 —

1-

0.8 —

0.6 —

0.4 —

0.2 —

0

—o—Calculated value (V) o Measured value (V)

Figure 4.1 Circuit Diagram for Balanced Three-phase Condition

Like as showed in the circuit diagram the star point of the load is not connected

to earth or shield wires to make sure that there were no return current.

4.2.1.1 Common Mode Voltage vs. Frequency

0 1000 2000 3000 4000 Frequency (Hz)

Figure 4.2 Common mode Voltage versus Frequency

42

Page 51: Telephone interference caused by harmonics and unbalance

Frequency (kHz)

Common mode voltage

Calculated (V)

Measured (V)

Error (%) Corrected Calculated Voltage (V)

Error after correction (%)

0.06 0.028 0.0256 8.5 0.0264 3.1

0.15 0.072 0.07 2.7 0.068 -3.1

0.25 0.12 0.116 3.3 0.1132 -2.5

0.35 0.168 0.18 -7.1 0.1585 -13.6

0.5 0.242 0.26 -7.4 0.228 -13.9

0.65 0.316 0.293 7.3 0.2981 1.7

1.0 0.483 0.454 6.0 0.4557 0.36

1.5 0.725 0.658 9.2 0.684 3.8

2.0 0.966 0.858 11.2 0.9113 5.9

2.5 1.208 1.04 13.9 1.14 8.7

3.0 1.45 1.226 15.5 1.368 10.4

3.5 1.691 1.421 16 1.595 11

4.0 1.933 1.653 14.5 1.824 9.4

Table 4.1 Result : Balanced Three-phase, Common Mode Voltage

This is the voltage induced on each conductor of the telephone line and which

is measured with respect to earth. Narrow band measurement was performed

to make sure that the values measured were accurate. The reasons for the

deviation between the measured and the calculated values could be the

following:

The equation used to find the mutual impedance between the inducing loop

and the induced loop is a partial derivative equation. This itself can cause an

error in the calculation.

The equation is more accurate if the separation distance between the

inducing loop and the induced loop is much bigger than the separation distance

43

Page 52: Telephone interference caused by harmonics and unbalance

between the conductors of the inducing loop. For the scale model these two

separation distances are almost same. This also influence the calculated value.

3. The input impedance of the selective voltmeter, which was used to measure

the common mode voltage has relatively low input impedance (in the order of

10 kn).

Rt/2

Re

Re

eas

Figure 4.3 Thevenin Equivalent Circuit for Measurement

In the above figure Veal is the calculated common mode voltage and V.I. is the

measured common mode voltage. Rt /2 =300 n which is half of the terminating

resistance of the telephone line. R e=150 n which is the earth electrode

resistance and Rin=10 ica which is the input impedance of the selective

voltmeter. Using \I'm,as at each frequency V eal is found by circuit analysis and

given in Table 4.1 as corrected calculated voltage. At higher frequencies (from

650 Hz) error drops down significantly if this corrected voltage is used. But at

the same time it has a negative impact on the lower frequency range. The

reason for this can be the variation of the input impedance of the selective

voltmeter with frequency.

4. The magnitude of current at each phase at each frequency was taken as 10 A

for calculation. But in the experimental measurement there could be a slight

variation in this value and that makes a small error.

44

Page 53: Telephone interference caused by harmonics and unbalance

4.2.1.2 Differential Mode Voltage vs. Frequency

Diff

ere

ntia

l mo

de v

olta

ge

(mV)

45

40

35

30

25

20

15

10

5

0

—x—Calculated value (mV) o Measured value (mV)

0 1000 2000 3000

4000 Frequency (Hz)

Figure 4.4 Differential mode voltage versus Frequency

The differential mode induced voltage was measured between the two

conductors of the telephone line (the other end of the telephone line was

earthed). Measurement was performed by tuning the frequency (the required

value) to get accurate readings especially at lower frequencies. Result of this

measurement is given in Table E.1 of Appendix E. From the result it is quite

clear that there is a good agreement between the predicted and measured

values (max. error is 9%). The reason for this small deviation can be the

following:

1. The experimental set-up and the ideal set-up for calculation will have

variations in the physical modelling. This will influence the differential mode

voltage. Moreover the errors at the common mode voltage will also have an

influence on the differential mode voltage.

4.2.2 Unbalanced Three-phase Condition (Return current through earth)

IR = 8.21 A Iw = 8.35 A Ig = 7.03 A

45

Page 54: Telephone interference caused by harmonics and unbalance

50 — Com

mon

mod

e vo

ltage

(my)

300

250 —

200 —

150 —

100 —

Calculated (mV) A Measured (mV)

Figure 4.5 Circuit Diagram for Unbalanced Three-phase Condition

(Return current through true earth)

The star point of the load is connected to earth to allow the return current to

flow through true earth.

4.2.2.1 Common Mode Voltage vs. Frequency

0 1 2 3

4

Frequency (kHz)

Figure 4.6 Common mode versus Frequency

The' common mode induced voltage on each conductor of the telephone line

was measured between the conductor and true earth. Voltage induced on the

earth electrodes of the telephone line due to conductive coupling influenced the

46

Page 55: Telephone interference caused by harmonics and unbalance

—x--Calculated value (mV)

❑ Measured value (mV)

1000 2000 3000

4000 Frequency (Hz)

Diff

eren

tial

mod

e vo

ltag

e (m

V)

measured common mode voltage. Detailed study was done on this matter

(measurement of earth electrode potential with respect to remote earth). More

details are given under discussion section. Result of this measurement is given

in Table E.2 of Appendix E.

4.2.2.2 Differential Mode vs. Frequency

Figure 4.7 Differential mode versus Frequency

The differential mode induced voltage was measured between the two

conductors of the telephone line (the other end of the telephone line was

earthed). Readings were taken by tuning the frequency (the required value) to

get accurate values especially at lower frequencies. Result of this measurement

is given in Table E.2 of Appendix E. The reason for the small deviation can be

the following:

1. The experimental set-up and the ideal set-up for calculation will have

variations in the physical modelling. This will influence the differential mode

voltage. Moreover the errors at the common mode voltage will also have an

influence on the differential mode voltage.

47

Page 56: Telephone interference caused by harmonics and unbalance

Unbalanced three phase (return current through shield wires) and Single Wire

Earth Return (SWER) conditions were also performed. Results of these

measurements are given in Table E.3 and Table E.4 in Appendix E.

4.3 ELECTROSTATIC COUPLING

For electrostatic coupling experimental work is done only for balanced three

phase condition (V R = Vw = VB = 65 V). Differential mode induced voltage is

measured and *compared with the calculated value. The reason for not

measuring common mode voltage is due to the unavailability of high impedance

measuring equipment.

4.3.1 BALANCED THREE-PHASE CONDITION

VR Vw -= VB -= 65 V

V

B 100 m

0

Source 132V/ 22A 1.2m

80 m

Wept 600Ohm 600 ohm

Figure 4.8 Circuit Diagram for Balanced Three-phase

(Electrostatic)

4.3.1.1 Differential mode versus Frequency

Result of this measurement is given in Table E.5 of Appendix E.

48

Page 57: Telephone interference caused by harmonics and unbalance

—x— Calculated value (micro volt)

❑ Measured value (micro volt)

1000 2000 3000

4000

Frequency (Hz)

Diff

eren

tial m

ode

vol

tag

e (m

icro

vol

t) 160

140

120

100

80

60

40

20

Figure 4.9 Differential mode versus Frequency

The deviation between measured and calculated value can be due to the

resolution of the measuring instrument at these very low values (in the micro

volt range). The physical set-up of the experimental line will also have an

influence on the deviation.

4.4 COMPATIBLE SEPARATIONS

The power line (6.6 kV to 765 kV) separation distance versus exposure to

parallel communication lines are given in NRS 041 of 1995. But these curves

were done by considering only upto 11th harmonics. Very high order, 71st and

73rd, harmonic components are now present on certain 132 kV power lines

supplying a large smelter plant.. So it is necessary to find the compatible

separations between power and telephone lines for this type of situation.

Experimental work on test line revealed that the method described in C.C.I.T.T

Directives and HRJ. Klewe's book could be used for calculating induced

voltage even at high frequencies (4 kHz). To calculate compatible separation

between a 132 kV line and an open wire telephone line the following

informations of both lines are used.

49

Page 58: Telephone interference caused by harmonics and unbalance

132 kV power line

Rating : 800 MVA (three lines)

Line voltage : 132 kV

Phase current : 50 A

Percentage of different harmonic currents (split busbar at hill side)

5th - 13.5% 23rd - 9.6%

7th - 11.4% 25th - 9.8%

11th - 17.3% 29th - 8.9%

13th - 12.0% 31st - 8.3%

17th - 11.1% 71st - 2.9%

19th - 9.9% 73rd - 3.05%

This data is provided by Eskom.

A 275 kV horizontal configuration light suspension tower geometry is used for

calculation purpose.

For open wire telephone line standard Telkom line geometry is used.

100 90 80 70 60 50 40 30 20 10

0

Sep

arat

ion

(m)

0 20 40 60 80

100

Exposure (m)

Figure 4.10 Power Line Separation Distance versus Exposure to

Parallel Communication Lines (132 kV, horizontal

configuration, I= 50 A, p = 1000 n m)

50

Page 59: Telephone interference caused by harmonics and unbalance

Chapter 5

DISCUSSION AND CONCLUSION

In this chapter accuracy in modelling and measurement is discussed.

Measurement problems faced due to conductive coupling effect is mentioned.

Recommendation for the revision for Postmaster General's Requirement for

minimum separation distance is also given under conclusion.

51

Page 60: Telephone interference caused by harmonics and unbalance

5.1 DISCUSSION

The main objective of this project was to explore the agreement between

theory and measurement for frequencies from 50 Hz to the higher order

harmonic range of 4 kHz. This make it possible to extend the existing methods

for predicting compatible separations to cases where high order harmonics (up

to the 73rd) are present. During the experimental work more importance was

given to electromagnetic coupling compared to electrostatic coupling. This is

due to the fact that current harmonics are more common and severe than

voltage harmonics. Another fact is if the telephone lines are properly balanced

the effect of electrostatic coupling can be eliminated.

In the case of electromagnetic coupling the two main cases studied are induced

voltage on the telephone line during balanced and unbalanced operating

conditions of the power line from 50 Hz to 4 kHz. From the results it is clear

that for balanced condition the agreement between the predicted and measured

value (common mode induced voltage) is in the limit of <15%. Deviation is

higher at higher frequencies. The reasons for this are:

The three-phase power source used couldn't give properly balanced output

at higher frequencies. Therefore the assumption of balanced current on three

phases is not accurate at higher frequencies (±2%).

At higher frequencies the reactance of the power line and the load increases

and to get 10 A at these higher frequencies the line voltage has to be increased

in step. This also causes an error in keeping phase current at exactly 10 A.

The magnitude of the induced voltage measured was in the range of 0 to 30

mV. The accuracy of the selective voltmeter used to measure the induced

voltage also got an influence on the reading.

The geometry of the test line will also have an effect on measured value.

When we are looking at small separations like this (less than 3m), the height of

the conductors (power and telephone) will also have an effect. The real test line

geometry (experimental set-up) is not that accurate if we compare the values

with the scale model. Line sag (power and telephone conductors) will also have

an effect on induced voltage.

52

Page 61: Telephone interference caused by harmonics and unbalance

For an unbalanced three-phase condition all the above reasons are valid. But

the most important reason for the variation in induced common mode voltage is

conductive coupling. During unbalanced condition the return current was

allowed to flow through true earth. This causes a ground potential rise at the

earth electrodes of the power line. For the test line (the experimental set-up)

the earth electrodes of the telephone line are also very close to the earth

electrodes of the power line and they are in the zone of area of GPR. The

magnitude of induced voltage measured was higher than predicted values.

Potential on the earth electrode of the telephone line was measured and it is

found that this voltage is adding in quadrature to the induced common mode

voltage due to the power line current. To reduce this effect measurement is

done with respect to a remote earth. The problem faced at that point is the

induced voltage on the voltmeter leads. That means accuracy of the

measurement is under question.

In the case of SWER condition lot of time was spent on finding out the reason

for very high induced common mode voltage compared to the predicted value.

This leads to the fact that the induced voltage sitting at the earth electrodes of

the telephone line due to conductive coupling is adding in quadrature to the

real common mode induced voltage due to the current flowing through the

SWER line.

At 500 Hz: the voltage at the earth electrode of the telephone line due to

conductive coupling (measured profile), V3 = 0.905 V

Common mode induced voltage measured, V2 = 1.004 V

Common mode induced voltage calculated, V1 = 0.058 V

From this we can conclude that,

V(Vi2 + V32 ) = V22 (V)

(5.1)

In the case of capacitive coupling measurement was done only for differential

mode induced voltage. This is due to the unavailability of proper measuring

instrument.

53

Page 62: Telephone interference caused by harmonics and unbalance

Calculation of compatible separation between the power and the

telecommunication line is done for a 132 kV, horizontal configuration with I =

50 A and earth resistivity of 1000 ohm-m. Harmonics up to 73 rd were

considered. Comparison of this criteria with compatible separations specified in

"Code of Practice for Overhead Power Lines for Conditions Prevailing in

South Africa" NRS 041 shows that the exposure length for a specific

separation distance is only 1/280 th. This means for a 100 m separation,

according to NRS 041, the exposure length can be 28 km. But this new criteria

will give only 100 m of exposure length for 100 m of separation. Due to this

very high difference in these two values calculation was done for the same

power line configuration considering only harmonics up to the 11th.

Comparison between this result and NRS 041 showed that for a 100 m

separation instead of 28 km (NRS 041) the new calculated value was 9 km.

The reasons for this can be the following:

The curves for power line separation distance versus exposure to parallel

communication lines were considered the effect of frequencies in the band of

800-1400 Hz other than the power frequency. This makes a big difference.

Instead of considering the effect of each harmonic frequency in that band the

spectrum was considered as a whole and form factor was used. Value of this

form factor was given by Eskom and it is not specified any where.

The conditions used for this curves are also not specified clearly. For

example the magnitude of current in the 132 kV line. This factor has got a big

influence on exposure length.

Moreover all these calculations were done 30 years ago and it is too difficult

to get hold of more details required to verify these curves against the new

criteria.

5.2 CONCLUSION

It is proven that the existing methods for predicting compatible separations

between power and telephone lines are valid even at higher order harmonic

frequencies. The calculation for minimum separation distance versus exposure

length is done for the worst case. Comparing the result with the existing

54

Page 63: Telephone interference caused by harmonics and unbalance

requirement for minimum separation and exposure length it is obvious that it

needs revision to accommodate the effect of higher order harmonic

frequencies.

Detailed study must be done on different types of power line configurations to

make recommendations on the separation criteria. Research work in the field of

modelling of earth is required. It is recommended that new techniques should

be developed to predict electromagnetically induced voltages on the telephone

line when considering conductive coupling effects as well.

55

Page 64: Telephone interference caused by harmonics and unbalance

REFERENCES

"Inductive Interference in South Africa, " The Power and Communication Systems Co-ordinating Committee, SAME, 1959.

Klewe HRJ, "Interference between Power Systems and Telecommunication Lines", E Arnold Ltd, London, 1958.

"Postmaster General's Requirements for Electrical Works," Issue 1, August 1978.

"Low Frequency Induction in Telecommunication Lines due to Faults on Paralleling Power Lines," SAPO Technical Instructions, Protection, Power A 3009, June 1982.

C.C.I.T.T. "Directives concerning the protection of telecommunication lines against harmful effects from electric power and electrified railway lines, volume II," International Telecommunication Union, Geneva, 1989.

Reference Guide, "Eskom Quality of Supply Group", 1995.

Arne V Johansson and Ake Ekstrom, "Telephone Interference Criteria for HVDC Transmission Lines," IEEE Trans. on Power Delivery, Vol. 4, No. 2, pp. 1408-1421, April 1989.

C.C.I.T.T "Directives concerning the protection of telecommunication lines against harmful effects from electric power and electrified railway lines, volume VI," International Telecommunication Union, Geneva, 1989.

William H. Hayt, JR "Engineering Electromagnetics," Fifth Edition, Mc Graw-Hill International 1989.

56

Page 65: Telephone interference caused by harmonics and unbalance

C.C.I.T.T "Directives concerning the protection of telecommunication lines against harmful effects from electric power and electrified railway lines", International Telecommunication Union, Geneva, 1963.

Bart Druif, " The Theory and Calculations of Coupling Parameters Between High Voltage AC Power Systems and Metallic Telephone Circuits," thesis presented for degree of Master of Engineering Science at the University of Stellenbosch, September 1994.

M.Kuussaari, " Statistical Evaluation of Telephone Noise Interference Caused by AC Power Line Harmonic Currents," IEEE Trans. on Power Delivery, Vol.8, No.2, pp. 524-530, April 1993.

IEEE Working Group on Power System Harmonics, " Power Line Harmonic Effects on Communication Line Interference," IEEE Trans. on Power Apparatus and Systems, Vol. PAS- 104, No. 9, pp. 2578-2587 September 1985.

Tagg G.F, "Earth Resistances", George Newnes Ltd, London, 1964.

"Electricity Transmission and Distribution- Code of Practice for Overhead Power Lines for Conditions Prevailing in South Africa" NRS 041: 1995

57

Page 66: Telephone interference caused by harmonics and unbalance

Appendix A

JD SOPHOMETRIC WEIGHTS

58

Page 67: Telephone interference caused by harmonics and unbalance

A.1 PSOPHOMETER

The psophometer is an instrument which has been introduced for measuring the

value of the parasitic voltages produced in telephone circuits by nearby

interferance sources eg. power lines. It was developed with a view to make

measurements at the end of long-distance circuits. It has a very high input

impedance, and thus can be used as a voltmeter without disturbing the circuit.

The psophometer consists essentially of an a.c. measuring instrument,

associated with a weighting network. It has got the ability to determine an

average sensitivity curve for various single frequencies for the combination

made up of a telephone receiver and the ear. When the voltage applied to a

psophometer is a combination of frequencies, the reading obtained on the

indicating instrument gives the square root of the sum of the squares of the

readings which would be obtained if each component were considered

separately.

Table A.1 indicates the psophometric weights attributed to by various

frequencies. Only the values corresponding to the underlined frequencies need

be regarded as specifying the weighting network of the psophometer and only

these need be taken into consideration for verification tests of the apparatus.

The other values, obtained by interpolation, are given to facilitate calculations.

59

Page 68: Telephone interference caused by harmonics and unbalance

Frequenc'y

c/s

Weights

Numerical values

The square of the numerical

values

Values in decibels

Values in nencra

16.66.. 50

0.056 0.71

0.003136 0.5041

85.0 - 63.0

- 9.79 - 7.25

100 8.91 79.3881 -41.0 - 4.72 150 35.5 1 260.25 - 29.0 - 3.34 200 89.1 7 933.81 - 21.0 -2.42 250 178 3! 684 - 15.0 - 1.73 300 295 87 025 - 10.6 - 1.22 350 376 141 376 - 8.5 - 0.98 400 434 234 256 - 6.3 - 0.73

450 582 338 724 - 4.7 - 0.54 500 661 436 921 - 3.6 - 0.41 550 733 • 537 239 - 2.7 - 0.31 600 794 630 436 - 2.0 - 0.23 650 851 724 201 - 1.4 - 0.16 700 902 813 604 - 0.9 - 0.10 750 955 912 025 - 0.4 - 0.046 800 1 000 1 000 000 0.0 0.000

850 1 035 1 071 225 0.3 ÷ 0.034 900 1 072 1 149 184 ± 0.6 + 0.069 950 1 109 1 229 831 ± 09 ± 0.103

1 000 1 1 77 1 253 884 ÷ 1.0 ± 0.115 1 050 1 109 1 229 831 ± 0.9 ± 0.103 1 100 1 072 1 149 184 ± 0.6 ± 0.069 1 150 1 035 1 071 225 ± 0.3 ± 0.034 1 200 1 000 1 000 000 0.0 0.000

1 250 977 954 529 - 0.20 - 0.023 1 300 955 912 025 - 0.40 - 0.046 1 350 923 861 184 - 0.65 - 0.075 1 400 905 819 025 - 0.87 - 0.100 1 450 831 776 161 - 1.10 - 0.126 1 500 861 741 321 - 1.30 - 0.150 1 550 84 7 708 964 -- 1.49 - 0.172 1 600 824 678 976 - 1.68 - 0.193

1 650 807 651 249 - 1.86 - 0.214 1 700 791 625 681 - 2.04 - 0.234 1 750 77) 600 625 - 2.22 - 0.255 1 800 760 577 600 - 2.39 - 0.275 1 850 745 555 025 - 2.56 - 0.295 1 900 732 535 824 - 2.71 - 0.311 1 950 720 518 400 - 2.86 - 0.329 2 000 708 501 264 - 3.00 - 0.345

2 050 693 487 204 - 3.12 - 0.359 2 100 689 474 721 - 3.24 - 0.373 2 150 679 461 041 - 3.36 - 0.386 2 200 670 448 900 - 3.43 - 0.400 2 250 661 436 921 - 3.60 --0.414 2 300 652 425 104 - 3.72 - 0.428 2 350 643 413 449 - 3.84 - 0.442 2 400 634 401 956 - 3.96 - 0.456

Table A.1 Psophometric Weights for Commercial Telephone Circuits

60

Page 69: Telephone interference caused by harmonics and unbalance

Frequency

cis

Weights

Numerical values

The square of the numerical

values in Values decibels

Values in nepers

2 450 625 390 625 - 4.08 - 0.470 2 500 617 380 689 - 4.20 - 0.484 2 550 607 368 449 - 4.33 - 0.499 2 600 598 357 604 - 4.46 -0.513 2 650 590 348 100 - 4.59 - 0.528 2 700 580 336 400 - 4.73 - 0.544 2 750 571 326 041 - 4.87 - 0.560 2 800 562 315 844 - 5.01 - 0.576

2 850 553 305 809 - 5.15 - 0.593 2 900 543 294 849 - 5.30 - 0.610 2 950 534 285 156 - 5.45 - 0.627 3 000 525 275 625 - 5.60 - 0.645 3 100 501 251 001 - 6.00 - 0.691 3 200 473 223 729 - 6.50 - 0.748 3 300 444 197 136 - 7.05 - 0.812 3 400 412 169 744 - 7.70 -0.886

3 500 376 141 376 - 8.5 - 0.979 3 600 '335 112 225 - 9.5 - 1.09 3 700 297 85 26• - 10.7 - 1.23 3 800 251 63 001 - 12.0 - 1.38 3 900 214 45 796 - 13.4 - 1.54

' 4 000 178 31 684 - 15 0 *-- 1.73 4 100 • 144.5 20 880.25 - 16.8 - 1.93 4 200 116.0 13 456 - 18.7 - 2.15

4 300 92.3 ' 8 519.29 - 20 7 - 2.38 4 400 72.4 5 241.76 - 22.8 - 2.62 4 500 56.2 3 158 44 - 25.0 - 2.88 4 600 43.7 1 909.69 - 17 . 2 - 3.13 4 700 33.9 1 149.21 - 29.4 - 3.38 4 800 26.3 691 69 - 31.6 - 3.64 4 900 20.4 416.16 - 33.8 - 3.89 5 000 ' 15.9 252.81 - 36.0 - 4.14

> 5 000 < 15.9 <252.81 < - 36.0 < - 4.14

Table A.1 Psophometric Weights for Commercial Telephone Circuits

(contd.)

61

Page 70: Telephone interference caused by harmonics and unbalance

Appendix

CURVES FOR MINIMUM SEFA N OF

OWER LINE AND COMMUNICATIoN LINE

62

Page 71: Telephone interference caused by harmonics and unbalance

In South Africa the research work in the co-ordination of power and communication

systems was undertaken by the Power and Communication Systems Co-ordinating

Committee, appointed by the SAIEE, in the period 1938-1957. Their conclusions were

reflected in the "Code of Practice for Overhead Power Lines" produced by SAIEE in

1966. In terms of legislation, interference limits are stipulated in Electricity

Transmission and Distribution- Code of Practice for Overhead Power Lines for

Conditions Prevailing in South Africa (NRS 042:1995) [15]. Eskom is bound to this

legislation for the new power routes have to be approved by Telkom before

construction can start.

Under normal circumstances, route approval of a power line will be preceded by the

calculation by Telkom for the anticipated induction levels (fault and steady state) in

any nearby cabled or open wire telephone circuits, and these levels are then compared

to the CCITT limits stipulated. The horizontal separation between the power line and

the telephone line should be in accordance with figures B.1, B.2, B.3 and B.4. This

separation distance shall grant the level of immunity required in the "Postmaster

General Requirements", for communication systems without reference to the power-

frequency carrier operator. These limits require that induced power-frequency voltages

shall not exceed:

50 V r.m.s. in steady state;

430 V r.m.s. on power lines where an earth fault is cleared in more than 0.5 s;

1000 V r.m.s. on power lines where an earth fault is cleared in 0.35 s to 0.5 s; or

1200 V r.m.s. on power lines where an earth fault is cleared in less than 0.35 s.

The curves are based on the recommendations of the CCITT, viz. that the noise

induced in a communication circuit should not exceed 2 mV e.m.f when measured

with a psophometer fitted with the CCITT telephone weighting network. The 2 mV

e.m.f is equivalent to 1 mV potential difference, as measured on the psophometer. For

power line voltages up to and including 33 kV, a TIF (Telephone Influence Factor) of

10 % has been used. For lines of higher voltage, a TIF of 5 % has been adopted, since

it is likely that interfering factors (such as phase balance, wave form etc.) are more

closely controlled on such routes.

63

Page 72: Telephone interference caused by harmonics and unbalance

65"

E C

.O

CJ

a) cn 16

10 15 20 25 30 35 40 45

34

32

30

28

26

24

22

14

12

A A K

211 pP91111111/-

Exposure (km)

20

18

10

8

6

4

2

Figure B.1 Power Line Separation Distance versus Exposure to Parallel Communication Lines (up to 33 kV) [15]

64

Page 73: Telephone interference caused by harmonics and unbalance

4b1Aidli 130

120

110

100

90

80

70

60

10

Exposure (km)

10 15 20 25 30 35 40 45

50

40

30

20

Figure B.2 Power Line Separation Distance versus Exposure to Parallel Communication Lines (from 44 kV to 132 kV) [15]

65

Page 74: Telephone interference caused by harmonics and unbalance

1 400

1 300

1 200

1 100

1 000

900

'&7 800 fa..

C) E C

700 -2

C3

D.

600 u)

500

400

300

200

100

III I

Exposure (km)

5 10 15 20 25 30 35 40 45

Figure B.3 Power Line Separation Distance versus Exposure to Parallel Communication Lines (from 275 kV to 400 kV) [15]

66

Page 75: Telephone interference caused by harmonics and unbalance

'1c3 ‘41

—se

para

tion

(met

res}

—{

i

Exposure (km) I

0

5

10

15

20

25

30

35

40

45

50

Figure B.4 Power Line Separation Distance versus Exposure to Parallel Communication Lines (for 765 kV) [15]

3 600

3 400

3 200

3 000

2 900

2 500

2 400

2 200

2 000

1 800

1 600

1 400

1 200

1 000

800

600

400

200

0

• 67

Page 76: Telephone interference caused by harmonics and unbalance

Appendix C

SOIL C#Nti UCTIVITY

68

Page 77: Telephone interference caused by harmonics and unbalance

C.1 SOIL. CONDUCTIVITY

Soil conductivities can vary from 0.1 to 0.0001 1/S/ m, depending on the type

and age of the formation. For the calculation of electromagnetic induction

effects, measurement methods are required that penetrate into the deep layers

of the soil, such as Wenner (4-electrode) method [14]. If the local composition

of the soil is known, a fair estimate for a may be obtained from Table C.1. In

the absence of measured values or adequate knowledge of the soil composition,

Figure C.2 can be used.

C.1.1 Wenner 4-electrode Method

For a homogerieous soil, conductivity can be measured by conducting Wenner

4 - electrode method. The arrangement of four electrodes in a straight line at

equal intervals is shown in Figure C.1. C1 & C2 are current electrodes and P1 &

P2 are potential electrodes.

a a a

C1 P1 P2 C2

Figure C.1 Wenner 4 - electrode configuration

In homogeneous soil the soil resistivity is given by the formula;

p=27caR (e (C.1)

Where a - actual spacing between two adjacent electrodes

R - resistance calculated from the potential readings and the value

of current injected into the soil

Result of soil resistivitiy measurement done at the RAU campus by Wenner 4-

electrode method is given in Table C.1. The soil resistivity at that site is 260

ohm-m. For more details, practical set-up and theoretical background, refer

[14].

69

Page 78: Telephone interference caused by harmonics and unbalance

Separation distance- adjacent electodes, a (m)

Meggar reading, R (0) Soil resistivity p = 2iraR (ohm- m)

1 49.8 312.9

2 9.64 121.14

4 5.36 134.71

6 5.16 194.53

8 4.85 243.79

10 4.03 253.21

12 3.49 263.14

14 3.16 277.96

16 2.72 273.44

18 2.22 251.08

Table C.1 Result of soil Resistivity Measurement

70

Page 79: Telephone interference caused by harmonics and unbalance

Condition relating to the climate _ Rainfall readings

Saline subterranean

water Nature

of earth

normal or high - i.e. more than 500 millimeters

per year

low and desert conditions - i.e. lower than 250 millimetres per

year

Probable value

Possible variation

Possible variation

Possible variation

1 2 3 4 5

Alluvial and light clay soil

0.2 0.5 to 0.1 according to the level of water in area concerned

0.2 to 0.001 according to the level of water in area concerned

1 to 0.2

Clay (without alluvium)

0.1 0.2 to 0.05 0.1 to 0.01

Marl (e.g. Keuper marl)

0.05 0.1 to 0.03 0.02 to 0.003 0.3 to 0.1

Porous calcium (e.g. chalk)

0.02 0.03 to 0.01

Porous sandstone (e.g. Keuper sandstone and clayey slate)

0.01 0.03 to 0.003

5 0.001

0.1 to 0.03

Quartz, hard crystalline limestone (e.g. marble, carboniferous chalk

0.003 0.01 to 0.001

Clayey slate and slaty shale

0.001 0.003 to 0.0003

0.03 to 0.01 Granite 0.001

0.001 to 0 Slate, fossils, schists, gneiss, igneous rocks .

0.0005

Table C.2 Earth Conductivities (mhos per meter) for Different Soil Compositions [10]

71

Page 80: Telephone interference caused by harmonics and unbalance

ilk 44ar.s.ttisr.

I II 61.1.A if It 4.4) A.11' LAIIIIC

)(1108tV11

0

mr fun 1...“

°•

o p t i on

r1d.V1111 A ;.;••

A

C

1)

A ILE A

• Cut‘'(

PP4 IC 4511.

1.1 1.0!it SI. rims II/ATA

I WA Lt:: I • AA 1,Its-;••• ■•I . • :.--- • •

,....-PI•orkT nit- air) LA I • l' 4 4 lulvil

AREA A : a < 0.0003 mho/m

AREA B : 0.003 < a < 0.0003 mho/m

AREA C : 0.01 < a < 0.003 mho/m

AREA D : a > 0.01 mho/m

Figure C.2 Soil Conductivities Applicable in south Africa [1]

72

Page 81: Telephone interference caused by harmonics and unbalance

Ap endix D

T WE GEOMETRY

73

Page 82: Telephone interference caused by harmonics and unbalance

,•

n

-

C

ci

/ \ •

G • L

TYP E A 7. SS q.

Figure D.1 'Type - 433A' Tower Geometry

74

Page 83: Telephone interference caused by harmonics and unbalance

1.35 m 1.57 m

14

2.4 m

es2

T2

The "433 A" Light Suspension Tower Type is mainly used for 275 kV power lines.

Conductors are arranged in flat horizontal configuration. This "433 A" tower is used

for the Athene- Smelter 132 kV lines as well. The phase conductors of these 132 kV

lines are of 'ZEBRA' ACSR (Aluminium Conductor Steel Reinforced) type.

GL

Figure D.2 Transmission and Telephone Line Configuration (experimental

set up)

S1 and S2 are shield wires

R, W and B are phase conductors

T1 and T2 are telephone conductors

75

Page 84: Telephone interference caused by harmonics and unbalance

Appendix E

CIRCUIT IAGRAMS AND RESULTS

76

Page 85: Telephone interference caused by harmonics and unbalance

- - - - SHUNT LEM 101

Source 132 V/ 22 A

E.1 CIRCUIT DIAGRAMS

E.1.1 Electromagnetic Coupling

E.1.1.1Balanced three-phase

IR =Iw =IB = 10 A

Figure E.1 Circuit Diagram - Balanced Three-phase

E.1.1.2 Unbalanced three-phase (return current through true earth)

IR = 8.21 A Iw =8.35 A IB = 7.03 A

Source 132V/ 22A 80 m

V 600ohm 600 ohm

Vcm

Figure E.2 Circuit Diagram - Unbalanced Three-phase (return current

through true earth)

E.1.1.3Unbalanced Three-phase (return current through shield wire)

:= 8.21 A Iw =8.35 A L = 7.03 A

77

Page 86: Telephone interference caused by harmonics and unbalance

shield wire

1k

- - - SHUNT LEM 101

Source 1.2m 132 V/ 22 A

80 m

1.74 600ohm

Figure E.3 Unbalanced Three-phase (return current through shield

wire)

E.1.1.4 Single Wire Earth Return System

I = 0.22 A

h 600 ohm

Figure E.4 Circuit Diagram - Single Wire Earth Return

E.1.2 Electrostatic Coupling

E.1.2.1Balanced Three-phase

VR Vw VB = 65 V

78

Page 87: Telephone interference caused by harmonics and unbalance

100 m

0

Source 132V/ 22A

80 m

WI) 600ohm 600 ohm

Figure E.5 Circuit Diagram - Balanced Three-phase (electrostatic)

E.2 RESULTS

E.2.1 Electromagnetic Coupling

E.2.1.1Balanced Three-phase

IR = Iw =IB = 10 A

1.2m

79

Page 88: Telephone interference caused by harmonics and unbalance

Frequency (kHz)

Common mode voltage Differential mode voltage

Induced voltage: Calculated (V)

Induced voltage: Measured (V)

Induced voltage: Calculated (mV)

Induced voltage: Measured (mV)

0.06 0.028 0.0256 0.624 0.72

0.15 0.072 0.07 1.2 0.8

0.25 0.12 0.116 2.6 2.24

0.35 0.168 0.18 3.64 3.2

0.5 0.242 0.26 5.2 3.54

0.65 0.316 0.293 6.76 - 5.4

1.0 0.483 0.454 10.4 8.6

1.5 0.725 0.658 15.6 13.2

2.0 0.966 0.858 20.8 18.4

2.5 1.208 1.04 26.1 24.2

3.0 1.45 1.226 31.3 30

3.5 1.691 1.421 36.5 34

4.0 1.933 1.653 41.7 37.9

Table E.1 Result : Balanced Three-phase

E.2.1.2 Unbalanced Three -phase (return current through true earth)

IR = 8.21 A Iw =8.35 A TB = 7.03 A

80

Page 89: Telephone interference caused by harmonics and unbalance

Frequency (kHz)

Common mode voltage Differential mode voltage

Induced voltage: Calculated (mV)

Induced voltage: Measured (mV1

Induced voltage: Calculated (mV1

Induced voltage: Measured (mV)

0.06 7 7.25 0.103 0.3

0.15 16 27.5 0.259 0.4

0.25 25 32.9 0.431 0.62

0.35 33 37.5 0.603 0.7

0.5 45 42.3 0.862 0.76

0.65 56 61 1.12 0.84

1.0 79 81.8 1.72 1.4

1.5 111 121.9 2.59 2.9

2.0 140 161.25 3.45 3.8

2.5 168 207.12 4.31 5.6

3.0 194 218.2 5.2 5.85

3.5 220 307.41 6.03 6.8

4.0 244 360.5 6.9 8

Table E.2 Result : Unbalanced Three-phase (return current through true

earth)

81

Page 90: Telephone interference caused by harmonics and unbalance

E.2.1.3Unbalanced Three-phase (return current through shield wire)

IR = 8.21 A Iw =8.35 A. LEI -= 7.03 A

Frequency (kHz)

Common mode voltage Differential mode voltage

Induced voltage: Calculated (mV)

Induced voltage: Measured (mV)

Induced voltage: Calculated (mV)

Induced voltage: Measured (mV)

0.05

1.5

3.0

5

137

, 274

8

143

275.6

0.0175

0.525

1

0.03

0.2

0.5

Table E.3 Result : Unbalanced Three-phase (return current through shield

wire)

E.2.1.4Single Wire Earth Return

Frequency (kHz)

Common mode induced voltage (V)

I = 0.22 A I = 0.44 A

Calculated value (V1)

Measured value (V2)

Calculated value (V1)

Measured value (V2)

0.5

1.0

0.058

0.11

1.004

1.033

0.166

0.217

2.04

2.074

Table E.4 Result : Single Wire Earth Return

At 500 Hz:

Voltage sitting at the earth electrode of the telephone line (conductive

coupling) V3 = 0.905V 4(1712 ± v32) = V2

82

Page 91: Telephone interference caused by harmonics and unbalance

E.2.2 Electrostatic Coupling

E.2. 2.1 Balanced Three-phase

VR = Vw VB 65 V

Differential mode voltage (micro volt)

Frequency (kHz) Calculated value Measured value

0.05 1.824 2.0

0.07 2.553 2.4

0.15 5.4 5.5

0.25 9.12 10

0.5 18 14

1.0 36.5 40

1.5 55 60

3.0 109 100

4.0 146 132

Table E.5 Result : Electrostatic Coupling (balanced three-phase)

83

Page 92: Telephone interference caused by harmonics and unbalance

Eart

h po

tent

ial (

V)

25 5 10 15 20

14

12 —

10 —

8 —

6 —

4 —

2 —

0 0

—a-- Earth pot: measured(V)

• Earth pot: calculated(V)

E.1.3 Earth Potential Distribution

Earth electrode distance (m)

Figure E.6 Earth Potential Distribution (Measured with respect to remote

earth; I= 0.43 A)

E.2.4 Compatible Separations

Experimental work done on the scale model agreed well with the modelling.

Scaling was done for a 132 kV horizontal configuration. Final calculation for

minimum separation for different exposure lengths are done for a 132 kV line.

Information about different harmonic current contents were provided by

Eskom and calculation is done for the worst case. After calculating the

common mode voltage differential mode voltage is calculated for a balance

factor of 200. This information is provided by Telkom.

For the 132kV line ; I= 50 A

84

Page 93: Telephone interference caused by harmonics and unbalance

Frequency (Hz) Common mode voltage (my)

Differential mode voltage (mV)

50 0.939 0.00195

250 4.69 0.0099

350 6.57 0.014

550 10.3 0.022

650 12.21 0.026

850 16 0.034

950 17.83 0.038

1150 21.6 0.046

1250 23.5 0.05

1450 27.2 0.058

1550 29.11 0.062

3550 66.7 0.141

3650 69.5 0.145

Table E.6 Calculated induced voltage for 132 kV horizontal configuration

(separation distance 100m and soil resistivity is 1000 n

Exposure length (m) Separation distance (m)

26 10

28 25

43 50

69 75

90 100

Table E.7 Exposure Length for Different Separation Distances (132 kV,

Horizontal configuration, p = moon m)

85

Page 94: Telephone interference caused by harmonics and unbalance

Appendix F

CALCULATION METHODS

86

Page 95: Telephone interference caused by harmonics and unbalance

All the calculations were done by using Mathcad PLUS 6.0, Professional

Edition.

F.1 Calculation of electromagnetic coupling (balanced three phase, no return current)

a - conductivity of the soil f - frequency pto - permeability of free space

a :=0.0038• (ohm .m)

f rad sec

It 0 :=4.71.10_ 7 henry

a :=411.0.a.2.711 a =1.225-10 •M 1

g - Euler's constant'

aRT is the horizontal distance between the red phase conductor and the first conductor of the telephone line b is the height of the red phase conductor from thr ground level c is the height of the telephone conductor from the ground level g:=1.7811 a RT := b := 3.6.m c := 1.3.m

d 1 :=jaRT2+ (13- c ) 2 d 1 =2.785•m

RT =1.923.10

Mu _ Mutual impedance between the red phase and the first conductor of the telephone line

AO 2 .42 MRT:=—. 2.1n + 1 - i 2 (1+i )•a•(b+c)

4•7t (g•a•d

henry

a wT := 2.92.m d 2 := Jawr2+(b-c)2 d 2 =3.717.m

M WT 2.11 .a.d 2

AO 2 ) +1 i • + (1+1 ) • a.(b+c)

4-a g 2 3

.

henry

m

a BT := 4.27.m d 3 := ja BT2 + (1)- c d 3 =4.85.m

M BT 11 0 2 ) 2.12. .

2171 ga.

+ 1 .

+ •(1 +1 ).a.(b + c d 3

2 3

MBT =1.148944.10 6 - 1.565138.10-7 i .henry

MRT =1.259909.10 6 - 1.565138.10-7 i

M WT =1.202156.10 6 - 1.565138.10-7 i

87

Page 96: Telephone interference caused by harmonics and unbalance

ZRT - mutual inductance between the red phase and the first conductor of the telephone line

ZRT '2' 1111‘11 RT

Z BT I ' 2*ThfI MBT IR - red phase current

ZRT =4.917026.10 5 +3.958121.10i ohm m ohm

m

ZBT =4.917026.10 5 +3.609515-10-4 1 ohm

m

Z WT := i •2•71•f•M WT Z WT = 4.917026-10 5 +3.776684-10 4 i

IR := (10 + .0)-ampI w := (- 5 + 8.664 )•amp IB := (- 5 - 8.664 )•amp

a :=- 0.5 i . 5 2

I RO is the zero sequence of the red phase current

iRi is the positive sequence of the red phase current

IR2 is the negative sequence of the red phase current

I RO

IR1

IR2

:= 1 3

i

1

1

1

1

a

a2

1

a2

a

I R

1 w

I B

IRO

R1

IR2

[0

= 1.467-10

10

I .amp

2 2

I Rw is the loop current between the red phase and the white phase

I RW

IWB

I BR

b b-1

:= -. a2 .13 a.b 1 -

4-3 a•b a2.13-1

(1 R1

R2

I RW

I wB

I BR

(5 - 2.886667i

= 5.773333i •amp

-5 - 2.886667i

I t - tota length of the telephone line

t := 40.m

ZRW is the loop impedance between the red phase and the white phase

5. o ZRW:=ZRT-ZWT Z 1.814368.10 Rw =

•hm

m

Z wB :=Z wr -ZBT ZwB =1.671698.105 .

•ohm

m

Z BR :=Z BT Z RT Z BR =-3.486•10 •o 5. lun

VTI is the voltage induced on the first conductor of the telephone conductor

m

88

Page 97: Telephone interference caused by harmonics and unbalance

I RW

V T1 := (Z Rw Z wB Z BR). I wg • 1 t

I BR

V T1 =-5.791.10-7 +0.011i •voliV T1 I = 0.012 .volt

a RT2 := 1.62.m b :=3.6•m c := 1.3.m

d RT2 := Ja RT22 + c 2

0 2 + .7t +2 M RT2 • 2.1n (1+i )•a•(b+c)

"" n ga.dRT2 2 3

M RT2 = 1.258.10 6 — 1.565.10-7i .henry

m

a WT2 := 2- 97•m d WT2 := Va WT22 ÷ (b c ) 2 d• WT2 = 3 .756•m

ft 0 [ ( 2 M WT2 '=• ‘.

„, -111 + - i

4.7c g- d WT2

7c i.. 2.42 i(1 2 3

).a. (13 + c )1

M WT2 = 1.200047-10 6 - 1.565138.10-7 i .henry

m

d RT2 =2.813•m

a BT2 := 4. 32'm d BT2 := BT22 + c)2

) M BT2

:=110 .4'1"

2 + 1 i +

2 5.(1 + i

4.7c g.a.dBT2 2 3

= 4.894.m d BT2

)•ct•(b+c)1

M BT2 1.147135.10 6 - 1.565138.10-7 1 •henry

Z i• — RT2 Z RT2 = 4.917026.10 5 +3.951725.10 4 i

Z WT2 i WT2 Z WT2 =4.917026.10-5 +3.770058.10 4 i

Z BT2 := i .2.71-f*M BT

Z BT2 = 4.917026.10 5 +3.609515.10 4 i

Z R2w2 = 1.816669.10 5 i -° hm

m

Z W2B2 WT2 - Z BT2

Z B2R2 :=Z BT2 Z RT2

ZW2B2 =1.605438.10-5 i -cam

ZB2R2 =- thm 5 i -

Z := Z - Z z RT2 WT2

ohm

m •

ohm

m •

ohm •

89

Page 98: Telephone interference caused by harmonics and unbalance

VT2 IS the voltage induced on the second conductor of the telephone line

I RW

V T2 := (z R2W2 Z W2B2 Z B2R2 )* I WB ' 1 t .

I BR

V T2 = -5.561.10 +0.01i 'volt IV T21 =0.012.volt

VTd is the differential voltage induced on the telephone line

VTd :=V T1 - VT2

V Td = -2.295.10 4 +1.233.10 4 i -voll V Tdi =2.605555.10 4 'volt

90

Page 99: Telephone interference caused by harmonics and unbalance

G := 0.0038•(ohinl rad f '= 50-- g o :=4•m104 henry

m sec

F.2 Calculation of induced voltage due to magnetic coupling (unbalanced three phase condition,return current through true earth)

a :=,ig 0.a-2.711

a= 1.225.10 g := 1.7811

aRT is the horizontal distance between the red phase conductor and the first conductor of the telephone line b is the height of the red phase conductor from thr ground level c is the height of the telephone conductor from the ground level

a RT := 1.57.m b 3.6•m c := 1.3-m

d 1 :=,ja RT2 + (13- c )2d 1 =2.785•m

•aRT =1.923.10-3

MRT is the mutual inductance between the red phase connductor and the telephone conductor

wi 0 „

11

( 2 ) . 242. . RT := 4.1

g.a. +1 • + (1+1 )-a-(b+c)

d

2 3

MRT =1.259909.10 6 - 1.565138.10-7 i .henry

m

a WT := 2.92•m d 2 := ja wT2 + (b - c ) 2 d 2 =3.717-m

m wi• := P-O • 2•In 1_( 2 ) 1 i • a ÷ 242 (1+i )•ct• (3 ÷ e )

4•1 g.ad 2 2 3

M WT =1.202156.10 6 - 1.565138.10-7 i

a BT :=4.27.m

P- M BT 2111

0 ( 2 ) +1 .

+ (1 4-1 )••(b+c) gad 3

2 3

MBT =1.148944.10 6 - 1.565138.10-7i .henry

m

ZR-r is the mutual impedance between the red phase conductor and the telephone conductor

.henry

m

d 3 := Ja BT2 + 03- c d 3 =4.85.m

Z RT ' 2.7141M RT ZRT =4.917026.10 5 +3.9581 .21°10i ohm

91

Page 100: Telephone interference caused by harmonics and unbalance

Z WT := .2.711M WT

Z BT

Z WT = 4.917026.10 5 +3.776684-10 4 i

ZBT =4.917026.10 5 +3.609515-10 4 i

ohm m

ohm

• I R Is the red phase current

I R := (8.21 + i •0)•amp I w := (- 4.175 ÷ 7.234 )•amp IB :=(- 3.515 - 6.0884 )•amp

2 IRO Is the zero sequence of the red phase current

I RI is the positive sequence of the red phase current

I R2 is the negative sequence of the red phase current

IRO

IR1

1 R2

1 1 1

:= 1 1 a a2 • —3

1 a2 a

I R

1 w

B

IRO

IR1

1R2

[0.173 + 0.381i

= 0.174 - 0.381i

7.863 + 1.923.10 i

amp

b := 43

II Rol =0.418 •amp

2 2 IRw is the loop current between the red phase and the white phase

I RW

I wB

'BR

1 b b-1

a2•b a•b- 1

a2•b-1

(I RI

R2

I Rw

I wB

'BR

(4.128333 - 2.41i

= -0.22 + 4.439331 ) •amp

-3.908333 - 2.029333i

l is the total length of the telephone line

1 t :=20•m

ZRW is the loop impedance between the red phase and the white phase

Z RW ZWT

ZwB:=Z wT-ZBT

Z BR :=Z BT Z RT

Z Rw = 1.814368.10 5 i •°hm m

Z wB =1.671698.10 5 ohm

Z=- B 3.486.10 5 i •thni

m

/ WO :7-- I RO / BO :7- I RO

VT1 is the voltage induced on the first conductor of the telephone conductor

I RW I RO

IWB 1 t - RT ZWT Z BT )• I WO

I BR 'BO

I t V T1 := Rw Z wE3 Z BR ).

92

Page 101: Telephone interference caused by harmonics and unbalance

b c )1

V Ti =6.101.10 - 9.063.10 4 i •volt I V Ti I =6.168.1V •volt

aRT2 is the horizontal distance between the white phase conductor and the second conductor of the telephone line

a RT2 := 1.62.m b :=3.6•m c := 1.3.m

c )2 d RT2 = 2.813.m

+ 1 i + 2.42 ct )..

g'cc'dRT2 2 3 4 ,

.1

,"

M RT2 =1.258.10 6 - 1.565.10-7 i henry

m

a WT2 := 2 • 97•m d wn := ja WT22+ (b - c )2 d WT2 = 3 •756 •m

7 2 ,12- 4.a (g' a. - WT) 2 3 M WT2 := ---11 o ' 2411 A2 I+1 i • + (1+i )•cqb+c)

henry

m

a BT2 :=4.27•m

d BT2 BT22 ÷ )2 d BT2 =4 .85 •m

[1 0 2 ) 2-.1 M BT2 —A • 4.1"

÷ I i • -I- (1+i )•cv(b+c) 4.n BT2

2 3

d RT2

M RT2 110 •

'P•11

RT22 +

M wr2 = 1.200047.10 6 - 1.565138.10-7 i

M BT2 = 1.148944.10 6 - 1.565138.10-7 i • henry

Z RT2 :=i • 2 •71.1 MRT2 Z RT2 = 4.917026.10-'5 +3.951725.10 4 i

• ohm

m

Z WT2 := . 2. 7t . CM WT2

Z BT2 :=i • 2 •71•fMBT

Z RW2 Z RT2 Z WT2

Z WB2 Z WT2 - Z BT2

Z BR2 Z BT2 Z RT2

Z wT2 = 4.917026.10 5 +3.770058.10-4 i

Z BT2 V =4.917026-1 +3.609515.10 4 1

ZRW2 = 1.816669.10-5 i .°11m m

Z wB2 = 1.605438-10 5 i. •ohm m

Z BR2 = -3.422-10 5 i

• ohm

m

• ohm

m

VT2 is the voltage induced on the second conductor of the telephone line

93

Page 102: Telephone interference caused by harmonics and unbalance

V T2 :z (Z RW2 Z WD2 Z BR2 )•

I RW

WB

I BR

[ IRO

' 1 t - (Z RT2 Z WT2 Z BT2 )* I WO

'BO -

.1 t

V T2 =6.177.10 3 - 9.47.10 4 i •vo4V T21 =6.249.10-3 •volt IV TII =6.168.10 3 •volt

V-rd is the differential voltage induced on the telephone line

V Td := V T1 V T2

V Td =-7.598.10 5 +4.067-10 5 i •volt IV Tdi = 8.618173.10 5 •volt

94

Page 103: Telephone interference caused by harmonics and unbalance

F.3 Calculation of induced voltage due to magnetic coupling (Single Wire Earth Return, SWER)

:=0.004•( 1 ) f :. 500 om.m sec li

IL 0 :=4.71.10 7 henry

a :=4110.0.2.711 a=3.974.10 •m 1

aRT is the horizontal distance between the red phase conductor and the first conductor of the telephone line b is the height of the red phase conductor from the ground level c is the height of the telephone conductor from the ground level

g := 1.7811 a RTi := 1.57.m b := 3.6.m c := 1.3.m

d 1 :=,ja RT12 (1) c )2; d 1 =2.785•m

a. a RT1 =6.239.10

MRT1 Mutual

M RT1 4•n

M RT1 = 1.025791.10 6

impedance between the red phase

243, nn

2 1 i

÷ ÷ +1

.henry

and the first

• )

conductor of the telephone line

(g•c•:1 1 2 3

- 1.552438.10-7i

ZRT1 mutual inductance between the red phase and the first conductor of the telephone line

Z RT1 :=i .2. n• f:M RT1 ZRT1 -4.877.10 +3.223.10-3 ohm i •

I R - red phase current It - total length of the telephone line VTR - voltage induced on the first conductor of the telephone line

IR := 0.22•amp 1 t :=80.m

V T1 := IRlf Z RT1 VT1 = 8.584.10 ÷0.057i •volt IV T1 I =0.057364•volt

aRT2 is the horizontal distance between the red phase conductor and the second conductor of the telephone line

a RT2 := 1.62.m b := 3.6.m c := 1.3.m

d RT2 := ja RT22 + (b - c )

2 d - RT2 =2.813.m

M RT2 :::-11° • (2-111 ( ,21 A [ ) + 1- i .-11 i.-2 "-±(1+i ).a.(b÷c) 2 3 '''n g a. " RT2

95

Page 104: Telephone interference caused by harmonics and unbalance

M RT2 1.024.10 6 — 1.552.10-7i •henry

Z RT2 :=i 2 nfMRT2

V T2 :=IRl t Z RT2

V Td :=V T1 — V T2

=4.877.10 4 +3.216.10-3i elm Z RT2 m

•volt IV T21 =0.057253 • volt

1.126.10 4 ••volt 1 V Td1

V T2 =8.584.10 +0.057i

V Td = 1.126.10 4 i welt

96

Page 105: Telephone interference caused by harmonics and unbalance

F.4 Calculation of capacitive coupling for three phase balance condition

Inducing line (power line) Induced line (tele: line)

aRT1 is the horizontal distance between the red phase conductor and the first conductor of the telephone line b is the height of the red phase conductor from thr ground level c is the height of the telephone conductor from the ground level

a RT1 := 1.57'm b := 3.5.m c := 1.3.m

d RT1 RT12+ (b - c)2 d RT1 =2 .703•m

D RT1 4RT12-1- (b c)2 D RT1 =5.05•m

0 := 8.854.10-12. farad 1 1( 1( 0 :- 10 m 0 =1.798.10 farad 2-m2 0

r1 is radius of the power line conductor

r2 is radius of the telephone line conductor

r 1 := 0.892.10-3 .m r 2 := 0.691.10-3•m

pRR :=k 21) P RR =1.612.1011 . m

(r ) farad

PT1T1 2c PT1T1 =1.48.10 11 • m

r 2 farad

97

Page 106: Telephone interference caused by harmonics and unbalance

D RT1

d RT I PRTI =1.124.10 10 • m P RTI •• = k0.1n

farad P TIR :=P RT1

C RT I – 4.711.10– • 13 farad

m

C6.757.10 12 . farad

T1T1 =

m

U w := (- 32.5+ 56.29•i ).volt

b := 3.5•m

d wri =3.656•m

D wn =5.618•m

P ww = 1.612.10 11

1.48.1011 P TITI

m • farad

m

farad

UR

P WT I =7.724-109 • m farad

P RT I C RTI P TIT1

1

C T1T1 •–• t, T1T1

U R := (65 + •0)•volt

a WTI := 2.92.m

wr1 2 ÷ (b._ 02 d WTI

2 D WTI WTI +" (b÷

r p ww 0.111 (2.1

2•c P TIT1 :=1( 0.111 (— r 2

WTI P :=k0 In

dwr

UB := (-32.5 -- 56.29•i )•volt

P TIW -1° WT1

98

Page 107: Telephone interference caused by harmonics and unbalance

CWrlP WT1

P WWP TIT1

C T1T1 T1T1

a BTI :=4 .27•m

CWT1 =3.238.1013 farad m

C 4 ./ ci. 1012 farad

TITI 1 -11 m

b :=3.5•m 1.3.m

dBT1 : ' ,.sia BT1 2 + ( 1) - c)2 dBT1 =4.803•m

D BTI := Ja BT12 ÷ (b + 02 D BTI =6.424•m

P BB =1.612-1011•

m r 1 P BB :="k 0411 (-2.13

farad

P TITI := k 0 .1",.. 2.c

(— P TIT1 = 1.48.10 11 • m r 2 farad

D BT1) P BT1 ::'0.111 A

''BT1 . far PBTI -5.227.109

m farad P T1B :=PBT1

P BT I C CBTI CBT1 - 2.191.1013 farad

I BB' T1T1 m

1 C T1T1 •-• C 6.757.1012 farad T1TI = m

TI T1

C RTI U RT1 '= U R c T1T1 C RTI

U RT1 =4.235909.volt

IURT11 =4.236 .volt

C WT1 U w U WT1 T1T1 1-C WT1

U WT1 = -1.485952 +2.573669i °volt IU WT 1 =2.972 -volt

C BT1 UBT1' r, UB

`-' T1T1 C BT1

UBT1 = -1.020674 - 1.767808i •volt IU

=2.041 •volt

99

Page 108: Telephone interference caused by harmonics and unbalance

P WT2 :=k0.1nr WT2 )

PwT2 =7.611'109 • m farad d wr2

P T2W WT2

UT1 := URT1+ U WT1+ U BT1

U Ti = 1.729 +0.806i •volt

IUT11 =1.908 •volt

aRT2 is the horizontal distance between the white phase conductor and the second conductor of the

telephone line

c := 1.3.m aRT2 := 1.62.m

2 dRT2 RT22 + (b -

D RT2 Ala RT22÷ (b + c)2

P WW :=k0.1n(2.1

r 1

b := 3.5•m

dRT2 2 .732•m

D RT2 =5.066.m

P ww =1.612.1011 • m farad

, 2•c) P T2T2 r 2

„(D RT2) P RT2 :=1` V" A

uRT2

P RT2 C RT2

T2T2

P T2T2 =1.48.10 11 • m farad

P RT2 =1.11.101° • m farad

C = 4.653.10-13 •farad

RT2 m

P T2R := P RT2

1 C T2T2

T2T2 CT2T2 6.757

. 10 12 .faradm

a WT2 2 . 97'm

b := 3.5.m

d WT2 = 3.696•m

D WT2 =5.645•m

Pww=1.612•1011 ° m farad

c := 1.3.m

d WT2 :-7'ja WT22 + (b 2

D WT2 := Ja WT22+ (b + c)2

, 2 • 11 P ww :=K 0.m(—

r 1

„ 2•c) P T2T2

r 2

P T2T2 = 1.48'1011 • m farad

100

Page 109: Telephone interference caused by harmonics and unbalance

m P WT2

C WT2 ' „ WW-s. T2T2

= 3.19.10-13 .farad

C WT2

P BB =1.612.1011 • M

farad

P T2T2 1.48• 10 11 • in farad

m

P BT2 =5.154-10 ° 9 In

farad

C BT2 2.16.1013 farad

P T2B :=P BT2

1 12 • farad C T2T2 • C T2T2 = 6.757.10

T2T2 m

a BT2 :=4.32•m b :=3.5.m

d BT2 BT22 + (b -c)2 d BT2 = 4.848•m

D BT2 BT221- (b C)2 D BT2 =6.458.1n

c := 1.3•m

p k 111(21 BB 0'

r 1

2•c) P T2T2 := '0'"±(----

r 2

(D BT2) P BT2. ••=k 0 .111 d BT2

P BT2 C BT2 • 1,

BB'- T2T2

1 = 6.757.1012 •farad C T2T2 C T2T2 P T2T2

C RT2 U RT2 • 0 U R

T2T2 C RT2

U RT2 = 4.187206 wok

C w-r2 U'- WT2 '

C T2T2 C WT2 U w

U WT2 =-1.4653 +2.537899i •volt

C BT2 U '- BT2 • U B

T2T2 C BT2

U BT2 =-1.006913 - 1.743974i •volt

U RT2I = 4.187 •volt

I U wa.2 1 = 2.931 •volt

= 2.014 *volt U BT21

101

Page 110: Telephone interference caused by harmonics and unbalance

U "-*U RT2 U WT2 + U BT2

U T2 =1.715 +0.794i 'volt

I U T21 =1.89.volt

U Td :=U T1 - U T2 U Td = 0.014 +0.012i •volt I U TdI = 0.019 •volt

R tel := 1.84. ohm L tel :=1.713.80.10 6 .henry C tel := 6.496.80.10- 12. farad

f := 150.Hz co := 2•71.f 1 t := 80•m

X Ltel := 'cu'L tel X Ctel . 1 *6).•-• tel

Z T := 600•ohm

Z :=R tel X Ltell- X.Ctel÷ T

. U Td 1 z

U Tdl :=Z T

U Tdl = -3.505.106 +4.201.10 6 i -voltIU Tdi = 5.471 - 10- -volt

102

Page 111: Telephone interference caused by harmonics and unbalance

F.5 Calculation of electromagnetic coupling (balanced three phase, no return current) for a 132kV line at the smelter plant

a - conductivity of the soil f - frequency 116- permeability of free space

a :=0.001.( ohml .m) ra f := 50. d--

see p. :=4•a.10-7 henry

a :=410.0.2.n.f a = 6.283.10 4

g - Euler's constant

aRT is the horizontal distance between the red phase conductor and the first conductor of the telephone line b is the height of the red phase conductor from thr ground level c is the height of thetelephone conductor from the ground level

g := 1.7811 aRT :=42.6.m b := 19.3.m c :=6.5•m

d 1 := Ja RT2 + (13- c d 1 =44.481•m

a.a RT =0.027

MRT _ Mutual impedance between the red phase and the first conductor of the telephone line

11 0 2 ) . n+ 2 .

MRT ill.

In +1 + •(1+1 ).a.(b+c) g•a•d 2 3

. henry

m

a wr := 50.m d 2 :=

wT2 + - d 2 =51.612.m

M wT :=2.1n 11 0 2 ) 7( 2 • .

.a.d2 +1 .

+ •(1+1 ).a.(b÷c)

g 2 3

M =8.104518.10-7 - 1.555513.10-7i .henryWT

a BT 57.4 • m

11 0 ,„( 2 ) 2.4-2 M BT := L.L"

+ 1 1 • + (1+i )•a•(b+c) g•a•d3 2 3

MBT =7.843423.10-1 - 1.555513.10-7i ,henry

ZRT - mutual inductance between the red phase and the first conductor of the telephone line

M RT =8.401897.10-7 - 1.555513.10-7 i =8.545.10-7 •kg•m•coul-2 I M RTI

m

d 3 :=,.ja BT2 ÷ (b- c d 3 =58.81•m

103

Page 112: Telephone interference caused by harmonics and unbalance

ZRT :=i •2•11•MRT ZRT =4.886788.10 5 +2.639534.104i .ohm

ohm

m

ZBT :7- '2.71.11\11BT Z BT =4.886788.10 5 +2.464084.104i .olun

Z WT :=i • 2.n.f.M WT Z WT =4.886788.10 5 +2.546109.10 4 i

IR - red phase current

I R :=(50-1-i .0).ampIw:=(-25-h 43.301.i

a :=- 0.5 + 2

I RO is the zero sequence of the red phase current IRi is the positive sequence of the red phase current IR2 is the negative sequence of the red phase current

)•amPB :=(- 25- 43.301•i )•amp

I RO

RI

R2

1 1 . 1

3 [1

1

a

a2

1

a2

a

IR

I w

I B

I RO

IRI

I R2

[0

= 1.56-10

50

-amp

2 2 I Rw is the loop current between the red phase and the white phase

b 1)-1

a2•b •b-1

a2•b-1

I RI

(I R2

I RW 25 - 14.433667i

I wB = (28.867333i

I BR -25 - 14.433667i

amp

It - tota length of the telephone line

l t :=1•m

ZRW is the loop impedance between the red phase and the white phase

Z RW :=Z RT Z WT Z Rw =9.342442.10 6 • ohm

ZWB :=Z WT ZBT Z wB =8.202547.10 6 i • ohni m

Z-5. ohm —1.754.10 • BR :=Z BT - Z RT Z BR 1

Vri is the voltage induced on the first conductor of the telephone conductor I RW

m

I W13 V T1 (Z RW ZWB Z BR)• V TI =- 3.552 4-10 +6.722.10- TI[ve1?.603•10 4

•VOlt

'BR

.I t

104

Page 113: Telephone interference caused by harmonics and unbalance

a RT2 42.75•m

b := 19.3 . m c := 6.5 • m

d RT2 := ja RT22+ (1) - c )2 d RT2 = 44.625 .m

M RT2 := 2 • [ (2.1n 2 +1-1 7

) +24-

2- (1+1 )a. (b+c) A"1 g C'u RT2

2 3

M RT2 = 8.395- 10-7 - 1.556.10-7i •henry m

a wT2 := 50.15 • m d wT2 wr22 c d wT2 = 51.758 • m

4-2 M WT2 := --(212.1n

2 ( + 1 - i 7 — +

2 (1 +i ). •(b+c)I 4.7 g•c•d WT2 2 3

M wT2 = 8.098895. 10-7 - 1.555513 . 10-7 1 henry

m

a BT2 := 57.55'm d BT2 := Ja BT22÷ (b )2 d BT2 = 58.956'm

It 0 { , 2 ) 242- M BT2 *= 4.1" 1- 1

. ( 1+ i) a•(b+c )

g••BT2 2 3

= 7.83845 . 10-7 - 1.555513.10-71 •henry

M BT2 m

Z RT2 :=5 .2.11.f"M RT2 Z RT2 = 4.886788 . 10 5 +2.637508. 10 4 i ohm m

Z WT2 wT2 Z wT2 = 4.886788 . 10 5 +2.544343 . 10 4 i

Z BT2 :=5 .2.711M BT Z BT2 = 4.886788. 10 5 +2.464084. 10 4 i

Z R2W2 := Z RT2 Z WT2 Z R2W2 = 9.31649 . 10 6 i -Ohm

Z W2B2 Z WT2 - Z BT2 Z = 8.025878 . 10 6 i • thni W2B2 m

Z B2R2 := Z BT2 Z RT2 Z B2R2= -1.734 . 10-5 i

VT2 is the voltage induced on the second conductor of the telephone line

ohm m

ohm • m

V T2 := R2W2 Z W2B2 Z B2R2 ).

I Rw

I wB

'BR

.1 t

105

Page 114: Telephone interference caused by harmonics and unbalance

V T2 — 4 3.475.10 +6.665.10 4 • •volt IVT21

=7.516384.10 4 •volt

IVT1I =7.602536.10 4 .volt

VTd is the differential voltage induced on the telephone line

Balance factor is 200

I V T 1 1 V Td 200 V Td =3.801°103

106

e.

Page 115: Telephone interference caused by harmonics and unbalance

F.6 Calculation of psophometrically weighted induced differential mode voltage (fundamental + harmonics) for 132kV line at the smelter plant

Psophometric weighting factor for 50 Hz (k) = 0.0007079 for 250 Hz (f5)= 0.178

f fun := 7.079.10-4 f 23 := 0.966

f5 :=0.178 f 25 := 0.977

f 7 := 0.376 f 29 := 0.881

f 11 :=0.733 f 31 := 0.842

f 13 :=0.851 f 71 :=0.355

f 17 := 0.966 1 73 := 0.313

f 1 9 :=0.902

Percentage of different harmonic currents (split busbar at hill side) Percentage of 5th harmonic: i5 = 13.5%

1 5 :=0.135

i7 :=0.114

i 11 :=0.173

i 13 :=0.12

i 1 7 :=0.111

i 19 := 0.099

i 23 := 0.096

i 25 :=0.098

i 29 := 0.089

i 31 :=0.083

i 71 :=0.029

i 73 := 0.0305

Calculateddifferential mode voltage (mV/m) For a separation of 100m and earth resistivity of 1000 ohm m

V fun := 0.00195 V 17 := 0.034

V 5 := 0.009923 V 1 9 :=0.038

V 7 := 0.014 V 23 := 0.046

V 11 :=0.022 V 25 :=0.05

V 13 := 0.026 V 29 := 0.058

V 31 := 0.062

V 71 :=0.141

V 73 :=0.145

107

Page 116: Telephone interference caused by harmonics and unbalance

Psophometrically weighted induced differential mode voltage Vpd

P800' 1 Psophometrically weighted signal at fundamental frequency Ufun

U fun := (NT fun.f fun) U 23 :=V 234' 234 23

U 5 :=V 5 • 5 • 5 U 25 := V 254. 254 25

U 7 := V 7 •f•i 7 U 29 := 291 294 29

U 11 :=V 11 4 11 .i 11 U 31 := 3 14' 3 0 31

U 13 :=V 13•f 13 •i 13 U 71 :=V 71170 71

U 1 7 := V 1 7117.1 17 U 73 := V 73.f 73.i73

U 19 := 194' 1 0 1 9

V pd I Al TT ,2 TT 2 +U 2 +U 2 +U fun -r 5 + V + LI 11 -I- V 132 1-U 172 + u 192 ÷u 232 ±u 252 +u 292" 312" 712 +1

P 800

V pd = 0.011165

Psophometrically weighted induced voltage is 0.011 mV/m

Limit for interference is 1mV (psophometrically weighted)

Calculation of exposure length (lexp)

l exp v 1 exp = 89.568 pd

For a separation of 100m the exposure length will be 90m

108