28
2.3.1.3 Fire Alarm System (FAS): Fire can have disastrous consequences and affect operations of a Data Center. The early detection of fire and employing means for automatic suppression of the fire is important for effective functioning of a Data Center. The FAS system should completely meet the NFPA (National Fire Protection Association) standards. 2.3.1.3.1 System Description: The Fire alarm system shall be an automatic 1 to n (e.g. 24) zone single loop addressable fire detection and alarm system, utilizing conventional detection and alarm sounders. Detection shall be by means of automatic heat and smoke detectors located throughout the Data Center (ceiling, false floor and other appropriate areas including Switch gear area where fire can take place) with break glass units on escape routes and exits. 2.3.1.3.2 Control and indicating component: The control panel shall be a microprocessor based single loop addressable unit, designed and manufactured to the requirements of EN54 Part 2 for the control and indicating component and EN54 Part 4 for the internal power supply. All controls of the system shall be via the control panel only. All site-specific data shall be field programmable and stored in an integral EEPROM. The use of EPROM‘s requiring factory ‗burning‘ and re-programming is not acceptable. All internal components of the control panel shall be fully monitored. The control panel shall be capable of supporting a multi device, multi zone 2-wire detection loop. Removal of 1 or

Fire Alarm spec

Embed Size (px)

Citation preview

Page 1: Fire Alarm spec

2.3.1.3 Fire Alarm System (FAS):

Fire can have disastrous consequences and affect operations of a Data Center. The early detection of fire and employing means for automatic suppression of the fire is important for effective functioning of a Data Center. The FAS system should completely meet the NFPA (National Fire Protection Association) standards.

2.3.1.3.1 System Description:

The Fire alarm system shall be an automatic 1 to n (e.g. 24) zone single loop addressable fire detection and alarm system, utilizing conventional detection and alarm sounders. Detection shall be by means of automatic heat and smoke detectors located throughout the Data Center (ceiling, false floor and other appropriate areas including Switch gear area where fire can take place) with break glass units on escape routes and exits.

2.3.1.3.2 Control and indicating component:

The control panel shall be a microprocessor based single loop addressable unit, designed and manufactured to the requirements of EN54 Part 2 for the control and indicating component and EN54 Part 4 for the internal power supply. All controls of the system shall be via the control panel only.

All site-specific data shall be field programmable and stored in an integral EEPROM. The use of EPROM‘s requiring factory ‗burning‘ and re-programming is not acceptable.

All internal components of the control panel shall be fully monitored.

The control panel shall be capable of supporting a multi device, multi zone 2-wire detection loop. Removal of 1 or more detection devices on the loop shall not render the remaining devices on the loop inoperable.

The system status shall be made available via panel mounted LEDs and a backlit 8 line x 40-character alphanumeric liquid crystal display.

All user primary controls shall be password protected over 4 access levels in accordance with EN54 Part 2. Essential controls, such as Start / Stop sounders and Cancel fault buzzer, etc. will be clearly marked.

Page 2: Fire Alarm spec

Cancel fault and display test functions shall be configurable to be accessed from level 1 or level 2.

All system controls and programming will be accessed via an alphanumeric keypad.

The control panel will incorporate form fill menu driven fields for data entry and retrieval.

The control panel shall log a minimum of 700 events comprising of 100 event fire log and 200 event fault, disablement and historic logs, giving time, date, device reference and status of indication.

Fire, fault and disablement events shall be logged as they occur. Visual and audible conformation shall be given on an array of LEDs, the Liquid Crystal Display and the internal supervisory buzzer.

The control panel shall have an integral automatic power supply and maintenance free sealed battery, providing a standby capacity of a minimum 72 hours and further 30 minutes under full alarm load conditions. The system shall be capable of full recharge within 24 hours following full system discharge. The performance of the power supply and batteries shall be monitored and the fault should be detected when alarmed. The system shall protect the batteries from deep discharge. All terminations within the control panel with the exception of the 230V mains connection will be via removable terminal screw fixing points.

The control panel will have a programmable maintenance reminder to inform the user that maintenance of the system is required. This function shall provide the user with the option of a monthly, quarterly, annually or bi-annually reminder prompts. The maintenance reminder will be indicated on the control panel. This message shall be resettable by the user and will not require the intervention of specialist support. The control panel will provide programmable free text field as part of the maintenance reminder facility.

The system will include a detection verification feature. The user shall have the option to act with a time response to the fire condition. This time shall be programmable up to 10 minutes to allow for investigation of the fire condition before activating alarm outputs. The operation of a manual call point shall override any verify command.

2.3.1.3.3 Manual Controls:

• Start sounders

Page 3: Fire Alarm spec

• Silence sounders • Reset system • Cancel fault buzzer • Display test • Delay sounder operation • Verify fire condition • Enter or modify device text label • Setup maintenance reminder • Assign or modify zones • Disable zones, device, sounders, FRE contact and auxiliary contacts • Enable zones, device, sounders, FRE contact and auxiliary contacts • Action weekly test • Disable loop

2.3.1.3.4 Cable entries:

The control panel will include the necessary top entry and rear entry cable entry points via 20mm knockouts.

2.3.1.3.5 Manual call points (MCP):

MCP‘s shall be addressable and of the steady pressure break glass type manufactured to the requirements of BS 5839: Part 2. A test key shall be provided to allow the routine testing of the unit to meet the requirements of BS 5839 Part 1 1988, without the need for special tools or the need to unfasten the cover plate.

The device shall be automatically addressed by the CIE (Control and indicating Equipment) on power up of the loop without the need of the insertion of a pre-

programmed EPROM or setting of DIL (Dual-In Line) switches. The device shall incorporate a short circuit isolation device and a red LED indicator.

The MCP (Manual Call Point) shall be suitable for surface or flush mounting. When flush mounted the device shall be capable of fixing to an industry standard single gang box.

2.3.1.3.6 Smoke detectors:

Smoke detectors shall be of the optical or ionization type. Devices shall be compatible with the CIE conforming to the requirements of EN54 Part 7 and be LPCB approved.

Page 4: Fire Alarm spec

The detectors shall have twin LEDs to indicate the device has operated and shall fit a common addressable base.

2.3.1.3.7 Heat detectors:

Heat detectors shall be of the fixed temperature (58° C) or rate of temperature rise type with a fixed temperature operating point.

Devices shall be compatible with the CIE conforming to the requirements of EN54 Part 5 and be LPCB approved.

The detectors shall have a single LED to indicate the device has operated and shall fit a common addressable base.

2.3.1.3.8 Addressable detector bases:

All bases shall be compatible with the type of detector heads fitted and the control system component used. Each base shall comprise all necessary electronics including a short circuit isolator.

The device shall be automatically addressed by the CIE on power up of the loop without the need of the insertion of a pre-programmed EPROM or setting of DIL switches.

Detector bases shall fit onto an industry standard conduit box.

2.3.1.3.9 Audible Alarms: Electronic sounders shall be colored red with adjustable sound outputs and at least 3 sound signals. The sounders should be suitable for operation with a 24V DC supply providing a sound output of at least 100dBA at 1 meter and 75 dBA/ min, for a bed head or sounder base type device. The sounder frequency shall be in the range of 500Hz to 1000Hz.

2.3.1.3.10 Commissioning:

The fire detection and alarm system will be programmable and configurable via an alpha numeric keypad on the control panel.

The labeling of Device and Zone labels should be part of the system.

Necessary Software to the control panel.

2.3.1.4 Fire Alarm Safety Control System:

2.3.1.4.1 Manual Addressed Module:

Page 5: Fire Alarm spec

The Manually Addressed Module shall allow the connection and addressing of conventional detectors and call points and offer a Micro Input, Micro Output and conventional Sounder driver/address Module. The Module shall provide the facility to upgrade all the components of a conventional system to a full addressable system, ideal for retrofit installations using its small physical size and convenient 8 way DIL switch for address setting and configuration. The Module shall be fully compatible with all standard address modules, addressable sounders, addressable manual call points and detectors facilitating extensions to the existing systems. To assist easy identification the Manually Addressed Module shall be supplied in different colored plastic housings for: Manual call point interface / Micro Input Module. Micro Output Module / LOOP SOUNDER / BEACON Controller Smoke / Heat Detector interface.

2.3.1.4.2 Addressable Input / Output Module:

The Addressable Input/Output Module shall be a fully monitored device which permits the interfacing of third party equipment with the Fire Alarm Control panel using normally open dry contact connections while also providing a changeover output relay to control ancillary equipment. The connection to the input is monitored for fault (open or short circuit) and Alarm conditions. The output relay shall be powered from the detection loop (default) or optionally by an external 24V DC supply. Relay operation shall be confirmed by an on board yellow LED. The interface shall be used to monitor the contacts of an external system which must be interfaced to the Fire Alarm System, for example a Flow Switch in a sprinkler system to indicate if the sprinklers have been activated or extinguishant level monitoring in Gas Extinguishing systems etc. The output relay shall be programmed to close fire doors, activate smoke removal systems etc. The factory default setting for the relay shall be such that it shall receive it‘s operating power from the Loop. Opening a link on the underside of the PCB shall allow the use of external power which is optically isolated from the detection loop. This option is recommended in the event that many I/O units are connected to the same Loop. The Addressable I/O module shall be available as an electronic module with four fixing holes or as a boxed unit for field installation.

2.3.1.4.3 Manual Call Point:

Page 6: Fire Alarm spec

Manual Call Point shall be used as manual alarm at the fire site when the person confirms that there is a fire. Each Manual Call Point shall have push button enclosed in to it. 2.3.1.4.4 Analog Addressable Module:

The detector shall use the light-scattering principal to measure smoke density and shall send data to the FACP indicating analog level of smoke density. Detectors shall be Analog and Addressable, and shall connect to the Fire Alarm Control Panel using Signaling Line Circuits. The Detector shall have following features: • Dual LEDs for 360°visibility • Advanced detection and discrimination algorithms • Easy installation and maintenance • Sleek low-profile housing design • Durable sensor head, no need for replacement • Sensor base option: standard and Schottky Diode The Detector shall be EN-54 approved. The Addressable INPUT Module shall be a fully monitored device which permits the interfacing of third party equipment with the Fire Alarm Control panel using normally open dry contact connections. The connection to the Addressable INPUT Module shall be monitored for fault (open or short circuit) and Alarm conditions. The interface shall be used to monitor the contacts of an external system which must be interfaced to the Fire Alarm System, for example a Flow Switch in a sprinkler system to indicate if the sprinklers have been activated or extinguishant level monitoring in Gas Extinguishing systems etc. The module shall be powered by the detection loop and is available as an electronic module with four fixing holes or as a boxed unit for field installation.

2.3.1.4.5 Analog Addressable Control Panel The Fire Alarm Panel shall be Analogue Addressable Fire Alarm control system with networking capabilities that facilitate the configuration of complex wide area Fire detection systems. Its Modular construction and distributed intelligence shall allow systems of up to 96 Loops to be constructed. With a high level of built in redundancy and emergency backup features, the offered Fire Alarm System shall be fully equipped to control the most complex installations. The Panel shall be available as a standalone system of up to 12 Loops in a single cabinet and can be expanded up to 96 Loops via a networked array of sub-panels. The sub Panels shall be supplied in a blank box version or combined with a repeater to allow remote display and control of the system. Networking shall be carried out by a monitored redundant RS422/485, Fibre optic loop or TCP/IP network. It shall be possible to enhance the networking capabilities by a wide range of programming options which provide the

Page 7: Fire Alarm spec

capability to customize the system according to the needs of the customer. Flexible cause and effect programming of I/O devices and warning devices shall ensure that Fire or Fault warnings trigger the appropriate response. An interactive Graphic representation of the system shall be displayed on the user‘s computer via the Graphics software. This shall be available as optional feature of the system. All the devices on the system shall be displayed on a building plan showing their status in real time. In the event of Fire or fault it shall be possible for customer to control the system and access all the necessary information with a few mouse-clicks. To reduce the time spent at the commissioning stage, the panel shall perform Automatic Device detection at start up. In Installation mode, the system shall detect and recognize addressed and connected devices with the system being fully operational in less than two minutes. The default programming shall ensure that the system is ready to detect Fire / fault alerts from the moment that power is applied. Additional programming, to customize the system shall be implemented via the onboard keypad, IR programmer, PS 2 Keyboard or with a laptop PC running the Loader software. The Fire Alarm Control Panel should be listed under EN54. It shall be possible to integrate addressable fire alarm system with BMS. It shall be possible to have 3 Different Communication Mediums (RS485/Fiber Optics/TCP I/P) in one System. Offered system shall have Class – connectivity. The panel shall have following features: The addressable fire alarm system shall be expandable from 1-96 Loops with distributed intelligence for added security.

The addressable fire alarm system shall be able to connect 125 device addresses per loop. And up to 96 Loop sounders with 32 individually programmable addresses per Loop.

The addressable fire alarm system shall have 2 Fire output changeover relays.

The addressable fire alarm system shall have open collector outputs for Fire, Fault and pre-alarm remote indication.

The addressable fire alarm system shall also have 2 fully monitored sounder outputs on main panel and each sub panel.

Repeaters shall be available with optional integrated Sub-Panels.

Black box option shall be available for Sub Panels. The addressable fire alarm system shall have detector loops which shall be fully monitored for integrity.

Page 8: Fire Alarm spec

The addressable fire alarm system shall have 384 programmable zones.

The addressable fire alarm system shall have 512 fully programmable sounder and I/O groups.

The addressable fire alarm system shall have event Log of 2000 entries with FIFO principle.

The addressable fire alarm system shall have Backlit LCD display 4 * 40

The addressable fire alarm system shall have multiple programming options, onboard keypad, Remote IR(Optional), PS2 Keyboard

The addressable fire alarm system shall come with Windows™ based Loader Software for Programming with Laptop PC.

The addressable fire alarm system shall provide Windows™ based PC Graphics package for alarm management and reporting as an optional feature.

The addressable fire alarm system shall provide a Multiple Language support (menu selectable)

The addressable fire alarm system shall provide BMS output RS 232 as an optional feature.

Evacuate / Class Change input

2.3.1.4.6 Power Supply:

The power supply unit shall accept 85-265 V AC Power Supply. The Power supply unit shall supply DC Power to all Modules/ within Fire Alarm Panel as well as to all devices wired on all the FACP Loops. Batteries shall be rechargeable, sealed maintenance-free type. Battery Capacity shall be sized to provide backup power to Fire Alarm Panel.

2.3.1.4.7 Cabling:

2C X 1.5Sq. mm FRLS (Flame retardant Low Smoke) armoured cable, PVC insulated and screened copper wire.

2.3.1.4.8 Addressable Isolator Module:

Page 9: Fire Alarm spec

The Isolator shall be designed to provide protection against short circuit faults on Analogue Addressable systems. The isolator shall protect the loop in the event of a short circuit by disconnecting the section of the loop where the short circuit has occurred. After rectifying the fault, isolating circuitry shall reconnect the affected part of the System. The Isolator shall be delivered in a White round junction box with knockouts that permit easy cable entry. Two Yellow LED indicators shall be provided to indicate on which side of the Device there is a short circuit (Loop In and Loop Out) to facilitate easy localization of the fault. It shall be not necessary to look for two isolators to confirm the location of the affected section. It shall be possible to connect up to 32 devices between two isolator (EN54) or 20 devices for BS5839 compliance. Under Normal conditions the Isolator shall provide a low resistance of 0.3ohm in either direction. When a short circuit condition is detected the isolator shall switch to the open state thereby isolating the Loop ―IN‖ and Loop ―OUT‖ lines. An Isolator shall be polarity sensitive. The isolated section shall be tested every 3 seconds with a voltage pulse and shall be automatically reconnected when the load resistance is greater than 175 ohm. The Addressable INPUT Module shall be a fully monitored device which permits the interfacing of third party equipment with the Fire Alarm Control panel using normally open dry contact connections. The connection to the Addressable INPUT Module shall be monitored for fault (open or short circuit) and Alarm conditions. The interface shall be used to monitor the contacts of an external system which must be interfaced to the Fire Alarm System, for example a Flow Switch in a sprinkler system to indicate if the sprinklers have been activated or extinguishant level monitoring in Gas Extinguishing systems etc. The module shall be powered by the detection loop and is available as an electronic module with four fixing holes or as a boxed unit for field installation.

2.3.1.4.9 Addressable Sounder:

The Sounder shall be a surface mount Addressable sounder with low power consumption available in either Red or White housings. Sounder shall have provision of different tones selection by jumper settings and lowering Sound levels by using potentiometers. Sounders shall be capable of freeing up addresses for more detection devices, i.e., when individual address reporting is not required. Up to 32 individually addressed sounders shall be possible to install in per loop. The address shall be set using switches 1 to 5 of the 6 way DIL switch.

Page 10: Fire Alarm spec

Shadow sounders shall not report back to the control panel so their presence on the loop shall not be monitored. Shadow sounders shall draw current from the loop (3.5mA in alarm) and shall be included in loop load calculations.

2.3.1.4.10 Cables:

All PVC insulated copper, armoured/ unarmoured, multi strand, FRLS, Twisted Pair, Shielded cables shall be 650V grades and shall generally confirm to IS –1554 – 1988 and meet the signal cabling requirement of the system manufacturer. The strands of cable shall not be cut to accommodate & connect the terminals. Terminals shall have sufficient cross sectional area to take in all the strands. Cables shall be laid by skilled and experienced workmen. Great care shall be taken while laying cables to avoid links. At all changes in directions (vertical & horizontal planes) the cables shall be bent smooth with a radius as recommended by the manufacturers.

2.3.1.5 Aspiration Smoke Detection (ASD) System:

Aspiration Smoke Detection System is the vital system for any critical area. Its high sensitivity of detecting smokes at the level of 0.005 obs/m ensures alerts at very early stages of fire. The ASD system shall be designed for server room only. (obs/m Obscuration level – Make less visible or unclear)

2.3.1.5.1 Technical Compliance for Aspiration Smoke Detection

The Aspiration Smoke Detection (ASD) system shall provide an early warning of fire in its incipient stage, analyze the risk and provide alarm and actions appropriate to the risk. The system shall include, but not be limited to, a Display Control Panel, Detector Assembly and the properly designed sampling pipe network. The system component shall be supplied by the manufacturer or by its authorized distributor. Regulatory Requirements: • National Electrical Code (NEC) • Factory Mutual • Local Authority having Jurisdiction

2.3.1.5.2 Codes and standards:

The ASD System shall comply one or more of the following codes and standards NFPA Standards, US

Page 11: Fire Alarm spec

British Standards, BS 5839 part :1

2.3.1.5.3 Approvals

All the equipments shall be tested, approved, and/or listed by : LPCB (Loss Prevention Certification Board), UK FM (Factory Mutual), US UL (Underwriters Laboratories Inc.), US ULC (Underwriters Laboratories Canada), Canada

2.3.1.5.4 Design Requirements:

The System shall consist of a high sensitive LASER-based smoke detector, aspirator, and filter. It shall have a display featuring LEDs and Reset/Isolate button. The system shall be configured by a PC software or a hand held programmer. The system shall allow programming of: Multiple Smoke Threshold Alarm Levels.

Time Delays.

Faults including airflow, detector, power, filter block and network as well as an indication of the urgency of the fault.

Configurable relay outputs for remote indication of alarm and fault Conditions.

It shall consist of an air sampling pipe network to transport air to the detection system, supported by calculations from a computer-based design modeling tool.

Performance Requirements

Shall provide very early smoke detection and provide multiple output levels corresponding to Fault, Pre-Alarm, and Fire. These levels shall be programmable and shall be able to set sensitivities ranging from 0.005 – 20% obscuration / metre

Shall report any fault on the unit by using configurable fault output relays.

Shall monitor for filter contamination.

2.3.1.5.5 Materials and Equipments

Page 12: Fire Alarm spec

Both Light Scattering and Particle Counting shall be utilized in the device as follows: The Laser detection Chamber shall be of the mass Light Scattering type and capable of detecting a wide range of smoke particle types of varying size. A particle counting method shall be employed for the purposes of preventing large particles from affecting the true smoke reading.

Monitoring contamination of the filter (dust & dirt etc.) to notify automatically when maintenance is required.

The Laser Detection Chamber shall incorporate a separate secondary clean air feed from the filter; providing clean air barriers across critical detector optics to eliminate internal detector contamination. The detector shall not use adaptive algorithms to adjust the sensitivity from the set during commissioning. A learning tool shall be provided to ensure the best selection of appropriate alarm thresholds during the commissioning process.

2.3.1.5.6 Detector Assembly:

The Detector, Filter, Aspirator and Relay Outputs shall be housed in a mounting box and shall be arranged in such a way that air is drawn continuously from the fire risk area by the Aspirator and a sample passed through the Dual Stage Filter and then to the detector. The detector shall be LASER-based and shall have an obscuration sensitivity range of 0.005 – 20% obs/m. The detector shall have three independent field programmable smoke alarm thresholds across its sensitivity range with adjustable time delays for each threshold between 0-60 seconds. The Detector shall also incorporate facilities to transmit the following faults Detector Zone Airflow System Network Filter Power

Urgent and Minor faults. Minor faults shall be considered as servicing or maintenance signals. Urgent fault shall indicate that the unit may

Page 13: Fire Alarm spec

not be able to detect. The detector shall have single pipe inlet which must be reporting both Minor and Urgent flow faults. The filter must be a two-stage disposable filter cartridge. The first stage shall be capable of filtering particles in excess of 20 microns from the air sample. The second stage shall be ultra-fine, removing more than 99% of contaminant particles of 0.3 microns or larger, to provide a clean air barrier around the detector‘s optics to prevent contamination and increase service life. The aspirator shall be a purpose-designed rotary vane air pump. It shall be capable of allowing/ supporting for a single pipe run with a transport time of less than 90 seconds. The Assembly must contain relays for fire alarm and fault conditions. The relays shall be software programmable (latching or non-latching). The relays must be rated at 2 A at 30V DC. Remote relays shall be offered as an option and either configured to replicate those on the detector or programmed differently. The Assembly shall have built-in event and smoke logging. It shall store smoke levels, alarm conditions, operator actions and faults. The date and time of each event shall be recorded. Each detector (Zone) shall be capable of storing up to 12000 events. The detector shall be programmed through a PC software.

2.3.1.5.7 Displays on the Detector Assembly:

The detector shall have a LED display for the multiple alarm threshold levels indicated and faults such as detector fault, airflow fault and indication for Isolate and Reset.

2.3.1.5.8 Sampling Pipe:

The PVC sampling pipe shall be smooth bore with an internal diameter between 15-25mm. Normally, pipe with an outside diameter of 25mm and internal diameter of 21mm should be used. The PVC pipe material should be suitable for the environment in which it is installed, or should be the material as required by the specifying body. All joints in the sampling pipe must be air tight except at entry to the detector. The PVC pipe shall be identified as Aspirating Smoke Detector Pipe along its entire length at regular intervals not exceeding the manufacturer‘s recommendation or that of local codes and standards. All PVC pipes should be supported at not less than 1.0 m centres , or that of the local codes or standards. The far end of each trunk or branch pipe shall be fitted with an end cap and drilled with a hole appropriately sized to achieve the performance as specified and as calculated by the system design. 2.3.1.5.9 Sampling Holes:

Page 14: Fire Alarm spec

Sampling Holes of 2 – 6 mm, or otherwise appropriately sized holes, shall not be separated by more than the maximum distance allowable for conventional detectors as specified in the local codes & standards. Intervals may vary according to calculations. Each sampling point shall be identified in accordance with Codes or Standards.

2.3.1.6 Gas Based Fire Suppression (GBFS) System:

The proposed design shall be based on NFPA standards, taking the minimum design concentration of 6.25% (0.485 gm/m3) as applicable to class ‗A‘ & ‗C‘ risks.

2.3.1.6.1 Technical Compliance for Gas Based Fire Suppression System:

The Clean Agent Fire Suppression system cylinder, CCOE, Nagpur approved seamless cylinders, discharge hose, fire detectors and panels and all other accessories required to provide a complete operational system meeting applicable requirements of NFPA 2001 Clean Agent Fire Extinguishing Systems, NFPA 70 National Electric Code, NFPA 72 National Fire Alarm Code or ISO standards must be considered to ensure proper performance as a system with UL/FM approvals and installed in compliance with all applicable requirements of the local codes and standards. The Clean Agent system considered for Total flooding application shall be in compliance with the provisions of Kyoto Protocol.

Care should be taken that none of the Greenhouse Gases identified in the Kyoto Protocol is used for fire suppression application.

The minimum criterion for the selection of the Clean Agent will be on the following parameters

Zero Ozone Depleting Potential. Global Warming Potential not exceeding one. Atmospheric Lifetime not exceeding one week.

The clean agent fire suppression system with FK-5-1-12 and Inert Gas based systems are accepted as a replacement of HCFC and HFC as per Kyoto Protocol.

The Clean Agent considered for the suppression system must be suitable for man occupied areas with NOAEL Level (No observable adverse effect level) of 10% as compared to the design concentration

Page 15: Fire Alarm spec

to ensure high safety margin for the human who might be present in the hazard area.

The minimum design standards shall be as per NFPA 2001, 2004 edition or latest revisions.

Care shall be given to ensure proper early warning detection system with minimum sensitivity of 0.03% per foot obscuration as per NFPA 318 & NFPA 72 to ensure that one gets a very early warning to investigate the incipient fire much before the other detectors activate the fire suppression system automatically.

All system components furnished and installed shall be warranted against defects in design, materials and workmanship for the full warranty period which is standard with the manufacturer, but in no case less than five (5) years from the date of system acceptance.

Additionally, Portable Extinguishers (CO2 or Halon based Extinguishers are not acceptable) shall be placed at strategic stations throughout the Data Centre.

OR Fire suppression system shall deploy FM-200 (ETG-5) based gas suppression systems with cross-zoned detector systems for all locations. These detectors should be arranged in a manner that they activate the suppression system zone wise to cater to only the affected area.

Illuminated Signs indicating the location of the extinguisher shall be placed high enough to be seen over tall cabinets & racks across the room. Linear heat detection cable should be placed along all wire pathways in the ceiling. This should not directly trigger the suppression system—rather; it should prompt the control system to sound an alarm. The OEM (/ Bidder) shall give a Certificate stating that their FM-200 system is approved by UL / FM / VdS / LPC/CNPP for use with Seamless Steel Cylinders (Component as well as System Approval).

The OEM (/ Bidder) shall also provide a Letter that the OEM has FM-200 Flow Calculation software suitable for Seamless Steel cylinder bided for as per the Bill of materials and that such Software shall be type approved by FM / UL / VdS / LPC.

The Storage Container offered shall be of Seamless type, meant for exclusive use in FM- 200 systems, with VdS/FM/UL/LPC/CNPP component approval. Welded cylinders are not permitted.

Page 16: Fire Alarm spec

The Seamless storage cylinder shall be approved by Chief Controller of Explosives, Nagpur and shall have NOC from CCoE, Nagpur for import of the same. Documentary evidence to be provided for earlier imports done by the bidder.

The FM-200 valve should be Differential Pressure Design and shall not require an Explosive / Detonation type Consumable Device to operate it. The FM-200 Valve operating actuators shall be of Electric (Solenoid) type, and it should be capable of resetting manually. The Valve should be capable of being functionally tested for periodic servicing requirements and without any need to replace consumable parts.

The individual FM-200 Bank shall also be fitted with a manual mechanism operating facility that should provide actuation in case of electric failure.

The system flow calculation is to be carried out on certified software, suitable for the Seamless Steel Cylinder being offered for this project. Such system flow calculations shall be also approved by VdS / LPC/ UL / FM.

The system shall utilize 25 Bar / High pressure (362 psi) technology that allows for a higher capacity to overcome frictional losses and allow for higher distances of the agent flow; and also allow for better agent penetration in enclosed electronic equipments such as Server Racks/ Electrical Panels etc.

The designer shall consider and address possible Fire hazards within the protected volume at the design stage. The delivery of the FM-200 system shall provide for the highest degree of protection and minimum extinguishing time. The design shall be strictly as per NFPA standard NFPA 2001.

The suppression system shall provide for high-speed release of FM-200 based on the concept of total Flooding protection for enclosed areas. A Uniform extinguishing concentration shall be 7% (v/v) of FM-200 for 21 degree Celsius or higher as recommended by the manufacturer. The system discharge time shall be 10 seconds or less, in accordance with NFPA standard 2001.

Sub floor and the ceiling void to be included in the protected volume.

The FM-200 systems to be supplied by the bidder must satisfy the various and all requirements of the Authority having Jurisdiction over

Page 17: Fire Alarm spec

the location of the protected area and must be in accordance with the OEM‘s product design criteria.

The detection and control system that shall be used to trigger the FM-200 suppression shall employ cross zoning of photoelectric and ionization smoke detectors. A single detector in one zone activated, shall cause in alarm signal to be generated. Another detector in the second zone activated, shall generate a predischarge signal and start the pre-discharge condition.

The discharge nozzles shall be located in the protected volume in compliance to the limitation with regard to the spacing, floor and ceiling covering etc. The nozzle locations shall be such that the uniform design concentration will be established in all parts of the protected volumes. The final number of the discharge nozzles shall be according to the OEM‘s certified software, which shall also be approved by third party inspection and certified such as UL / FM / VdS / LPC.

The Cylinder shall be equipped with differential pressure valves and no replacement parts shall be necessary to recharge the FM-200 containers.

FM-200 shall be discharged through the operation of an Electric (solenoid) operated device or pneumatically operated device, which releases the agent through a differential pressure valve.

The bidder shall provide all documentation such as Cylinder Manufacturing Certificates, Test and Inspection Certificates and Fill Density Certificates.

The FM-200 discharge shall be activated by an output directly from the `FM-200‘ Gas Release control panel, which will activate the solenoid valve. FM-200 agent is stored in the container as a liquid. To aid release and more effective distribution, the container shall be super pressurized to 600 psi (g) at 21°C with dry Nitrogen.

The releasing device shall be easily removable from the cylinder without emptying the cylinder. While removing from cylinder, the releasing device shall be capable of being operated, with no replacement of parts required after this operation.

Upon discharge of the system, no parts shall require replacement other than gasket, lubricants, and the FM-200 agent. Systems requiring replacement of disks, squibs, or any other parts that add to the recharge cost will not be acceptable.

Page 18: Fire Alarm spec

The manual release device fitted on the FM-200 Cylinder(s) shall be of a manual lever type and a faceplate with clear instruction of how to mechanically activate the system. In all cases, FM-200 cylinders shall be fitted with a manual mechanical operating facility that requires two-action actuation to prevent accidental actuation.

FM-200 storage cylinder valve shall be provided with a safety rupture disc. An increase in internal pressure due to high temperature shall rupture the safety disc and allow the content to vent before the rupture pressure of the container is reached.

The contents shall not be vented through the discharge piping and nozzles.

FM-200 containers shall be equipped with a pressure gauge to display internal pressure.

Brass Discharge nozzles shall be used to disperse the `FM-200‘. The nozzles shall be brass with female threads and available in sizes as advised by the OEM system manufacturer. Each size shall come in two styles: 180° and 360° dispersion patterns.

All the Major components of the FM-200 system such as the Cylinder, Valves and releasing devices, nozzles and all accessories shall be supplied by one single manufacturer under the same brand name.

Manual Gas Discharge stations and Manual Abort Stations, in conformance to the requirements put forth in NFPA 2001 shall be provided.

Release of FM-200 agent shall be accomplished by an electrical output from the FM- 200 Gas Release Panel to the solenoid valve and shall be in accordance with the requirements set forth in the current edition of the National Fire Protection Association Standard 2001.

2.3.1.6.2 Specification for FM 200 gas based fire suppression system

2.3.1.6.2.1 Introduction:

FM 200 is one of the clean agents to replace Halon - 1301 in total flooding applications. FM 200 is the product from Great Lakes Chemical Corporation (GLCC). It is a member of the hydro fluorocarbon (HFC) family of chemicals and is referred to as HFC-227 ea. The most notable property of FM 200 is an Ozone depleting potential (ODP) of zero.

Page 19: Fire Alarm spec

2.3.1.6.2.2 SPECIFICATION:

The fire suppression system shall include and not be limited to gas release control panel, CCE approved seamless cylinders, discharge valve (with solenoid or pneuma -tic actuator) as the case may be, discharge pipe, non-return valve and all other accessories required to provide a complete operation system meeting applicable requirements of NFPA 2001 or ISO standards and installed in compliance with all applicable requirements of the local codes and standards. The system design should be based on the specifications contained herein, NFPA 2001 & in accordance with the requirements specified in the design manual of the agent. The bidder shall confirm compliance to the above along with their bid.

2.3.1.6.2.3 Design and Engineering:

FM 200 systems shall be designed taking the minimum design concentration of 6.25% (0.485 gm/m3) as applicable to class ‗A‘ & ‗C‘ risks. The system design must consider the limitations caused by the void height. It should also consider temperature in the void. The qualifying bidder should clearly indicate the qty. of the gas in Kgs. to be used for the system. All voids within each hazard shall be discharged simultaneously. Each hazard shall have an independent system, unless otherwise specifically stated, when a centralized system with directional valves can be used. FM 200 systems shall have a working pressure of 25 bar. A fill density between 0.56 Kg / lt. to 0.85 Kg/lt. should be considered for the agent to be discharged within the specified time of 10 seconds maximum. The system engineering company should carry out the piping Isometric design and validate the same with a hydraulic flow calculation generated by using the agent's design software. The appropriate fill density shall be arrived based on the same. The design & calculation shall be checked & certified by Manufacturer. The calculation is the only guarantee that the system will work, provided the system is installed exactly as per the design. The contractor has to take into consideration the routing available while designing the pipe network. A certification (from the manufacturer of the agent or their direct distributor) on the authenticity with gas chromatography and quality of the agent filled in the system procured should be submitted by the system engineering company.

2.3.1.6.2.4 Refilling and Maintenance:

In case of any leakage or accidental discharge of the agent, it should be possible to refill the cylinders in India itself. The contractor should

Page 20: Fire Alarm spec

indicate the source of refilling and time that will be taken for refilling and replacement. 2.3.1.6.2.5 Discharge Time:

As gas has to be fully discharged within 10 seconds for effective quenching of fire as per the relevant standards, the contractor has to ensure that the design meets this requirement. Once the discharge takes place there should be warning signs restricting personal from entering the protected area until the gas has been cleared from the area.

2.3.1.6.2.6 Materials and Equipments:

All materials and equipments shall be from approved manufacturers and shall be suitable for the performance of their respective functions. The cylinders should be complete with all accessories. The contractor shall indicate the dimensions of the cylinders required for each area while quoting.

2.3.1.6.2.7 Cylinder:

The cylinder shall be high pressure, seamless steel gas cylinder, flat type, concave bottom as per IS 7285 complete with neck ring welded and cylinders without CCE approval shall not be accepted. The maximum fill density of FM 200 in a cylinder shall not be less than 0.56 kg/lt. and not exceed 0.85 Kg/lt. of internal volume. Appropriate fill density shall be chosen based on the cylinder location and piping retrofit. The hydraulic calculations should prove that the fill density is appropriate and total discharge will take place within 10 seconds. The cylinders shall be super-pressurized with dry nitrogen to 25 bar at 20°C. The cylinder shall be capable of withstanding any temperature between -30° C and 70°C. Cylinder shall be mounted according to manufacturer recommendations. The cylinder shall withstand Hydrostatic test pressure up to 250 bar and maximum working pressure at 15°C shall be 150 bar. The discharge valve shall be approved or listed for use with FM 200. All the gaskets, O-ring, sealant and other valve component shall be constructed of materials compatible with the clean agent. The system should be engineered using hardware approved for use with FM 200 systems. This would include main discharge valve, solenoid, check valve / non-return valve and pneumatic actuators.

2.3.1.6.2.8 Pipes & Fittings:

Page 21: Fire Alarm spec

All Pipes shall be of ASTM - A-106, Gr: B, schedule - 40 seamless mild steel pipes and fittings shall be as per ASTM-A-105 standard.

2.3.1.6.2.9 Discharge Nozzle:

Nozzle shall control the flow of FM 200 to ensure high velocity, proper mixing in the surrounding air and uniform distribution of the agent throughout the enclosure. The number of nozzles and their positions must be chosen so that the design concentration is maintained everywhere in the enclosure. Nozzle shall be located where they can be adequately supported on walls, ceiling or structural members. Software generated calculation supporting the nozzle design shall be submitted by the successful bidder before signing of contract.

2.3.1.6.2.10 Documentation:

The system engineering company should prepare & submit along with the bid documents, the piping Isometric drawing and support the same with a hydraulic flow calculation generated by using the agent's design software. The calculations shall validate the fill density assumed by the bidder. The bidder shall submit copies of the datasheets of the hardware used in the system. The bidder shall also submit copy of CCE approval letter for the cylinder proposed to be used. These documents shall be attached to the bid. The bidder shall also submit calculations to evidence the qty of agent considered for the system. The qualifying bidder must submit, along with the supply invoice, a certificate of authenticity, for the agent from the system engineering company duly checked and verified by distributor.