BDS-4000 Software Procedure - 1 -
B-I Fire Detection System
MODEL: BDS-4000 Ver. 1.0
Software Procedure
B-I INDUSTRIAL CO., LTD. Web site : www. b-i.co.kr , E-mail : [email protected]
▣ SEOUL HEAD OFFICE ▣ BUSAN FACTORY
Ace Hightech City 1-618, 55-20 Munrae-dong3 2508-1, Daejeo-2dong, Kangseo-gu,
Yeongdeungpo-gu, Seoul, Korea Busan, Korea
Tel: 02) 706-3077 Tel: 051) 441-5670
Fax: 02) 702-3076 Fax: 051) 441-6225
BDS-4000 Software Procedure - 2 -
Index
◈ MAIN PANEL 1. Operation menu 1.1. Start ---------------------------------------------------------- 3
1.2. Fault ---------------------------------------------------------- 4
1.3. Fire pre-alarm ------------------------------------------------- 5
1.4. Fire alarm ----------------------------------------------------- 7
2. Menu construction 2.1. Menu flowchart ----------------------------------------------- 8
2.2. Menu information --------------------------------------------- 9
1. VIEW ALARMS LIST ---------------------------------------------- 10
2. DISABLEMENT -------------------------------------------------- 11
3. SYSTEM CHECK ------------------------------------------------ 14
4. SYSTEM SETTING ----------------------------------------------- 17
5. SYSTEM CONFIGRATION ----------------------------------------- 18
◈ REPEATER PANEL 1. Operation menu 1.1. Start --------------------------------------------------------- 27
1.2. Alarm -------------------------------------------------------- 27
2. Menu construction 2.1. Menu flowchart ---------------------------------------------- 28
2.2. Menu information -------------------------------------------- 28
1. VIEW ALARMS LIST ---------------------------------------------- 29
2. KEY &LED TEST ------------------------------------------------- 30
3. SET TIME ------------------------------------------------------ 30
4. UPGRADE FROM USB -------------------------------------------- 30
BDS-4000 Software Procedure - 3 -
◈ MAIN PANEL 1. Operation menu
1.1. Start
▼
* Loop display can be indicated up to 12 loops, the maximum loop number of BDS-4000
SYSTEM. And the loops set up as “ABLE” before being reset will be progressing.
* Every device connected with the pertinent loop is checked.
* Progress state is displayed as % through setting standards that maximum 127 detectors per
loop can be loaded
* In case that setting state after system reset is different from the setting state set up before,
device fault will occur.
* NORMAL HOME MENU 상태
INITIALIZE
PLEASE WAIT
BDS-4000 Ver. 0.10
CHECKING LOOPS PLEASE WAIT LOOP DEVICE PROGRESS
1 96 / 127 85 %
2 0 / 127 0 %
3 0 / 127 0 %
4 0 / 127 0 %
5 0 / 127 0 %
6 0 / 127 0 %
7 0 / 127 0 %
8 0 / 127 0 %
9 0 / 127 0 %
10 0 / 127 0 %
11 0 / 127 0 %
12 0 / 127 0 %
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Software Procedure - 4 -
1.2. Fault FAULT TYPE: LOOPS FAULT, DEVICE FAULT, UNEXPECT DEVICE FAULT, MAIN POWER FAULT,
EMERGENCY POWER FAULT, BATTERY FAULT, EARTH FAULT EXTERNAL
SOUNDER FAULT, DOOR HOLDER1,2 FAULT, COMMUNICATION FAULT:
REPEATER, INTERFACE, EXTERNAL RELAY BOARD, LOOP CARD
FAULT PROCESS: In case system fault LED flickers, buzzer beeps and the external output is on,
please push Mute KEY repeatedly which can make buzzer beep or not beep
and touch ACK which can make HOMM MODE(FAULT ALARM MODE)
converted and LIST & RESET windows related to generated fault will be
activated. However, in case of communication fault occurs, COMM ALARM
LED will flicker
* LOOP FAULT EXAMPLE
▼( ACK )
☞ LIST : can make you check generated alarm lists.
☞ RESET : can make you reset generated alarm.
But reset will be processed after the input of ACCESS LEVEL2 SECURITY NUMBER.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FAULT ALARM
ALARM NO: 1 ALARM TYPE: LOOPS FAULT
TIME : 01-01-2010 AM 01:01
LOOP CARD NO: 1 OPEN
ACK
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
FAULT ALARM = 1 LIST RESET
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Software Procedure - 5 -
▼( RESET )
▼ ( ENT ) RESET
1.3. FIRE PRE-ALARM PRE-ALARM PROCESS: In case system fault LED flickers, buzzer beeps and the external output
is on, please push Mute KEY repeatedly which can make buzzer beep or not beep
and touch ACK which can make HOMM MODE(FAULT ALARM MODE) converted
and LIST & RESET windows related to generated pre-alarm will be activated.
* FIRE PRE-ALARM EXAMPLE
* Analogue value transmitted by devices is indicated real time ( Refer to page 48)
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
ACCESS LEVEL 2
1 2 3
4 5 6
7 8 9
ESC 0 ENT
0 0 0 0
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FIRE PRE-ALARM
ALARM NO: 1/1
ALARM TYPE: FIRE PRE-ALARM 48
TIME : 01-01-2010 AM 01:01
LOOP NO.: 1 ZONE NO.: 1
DEVICE NO.& TYPE: 1 SMOKE DETECTOR
DISCRIPTION:
ACT
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Software Procedure - 6 -
▼( ACK )
☞ LIST : can make you check PRE-ALARM LIST.
☞ RESET : can make you reset generated PRE-ALARM.
But reset will be processed after the input of ACCESS LEVEL2 SECURITY NUMBER.
▼( RESET )
▼ ( ENT ) RESET
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
FIRE ALARM = 1 LIST RESET
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
ACCESS LEVEL 2
1 2 3
4 5 6
7 8 9
ESC 0 ENT
0 0 0 0
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Software Procedure - 7 -
1.4. FIRE ALARM FIRE ALARM PROCESS: In case system fault LED flickers, buzzer beeps and the external output
is on, please push Mute KEY repeatedly which can make buzzer beep
or not beep and touch ACK which can make HOMM MODE(FAULT
ALARM MODE) converted and LIST & RESET windows related to
generated fire alarm will be activated.
* FIRE ALARM EXAMPLE
* Analogue value transmitted by devices is indicated real time ( Refer to page 64)
▼( ACK )
☞ SILENCE : will make you silence external output to sounder. RESOUND will be converted.
☞ LIST : will make you check a generated fire alarm list.
☞ RESET : will make you reset fire alarm.
But reset will be processed after the input of ACCESS LEVEL2 SECURITY NUMBER.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FIRE ALARM
ALARM NO: 1/1
ALARM TYPE: FIRE ALARM 64
TIME : 01-01-2010 AM 01:01
LOOP NO.: 1 ZONE NO.: 1
DEVICE NO.& TYPE: 1 SMOKE DETECTOR
DISCRIPTION:
ACT
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
FIRE ALARM = 1 SILENCE LIST RESET
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Software Procedure - 8 -
▼( RESET )
▼ ( ENT ) RESET
2. Menu construction 2.1. Menu flowchart
1. VIEW ALARMS LIST
1.1 FIRE ALARMS LIST
1.2 DELETE ALL FIRE ALARMS LIST
1.3 FAULT ALARMS LIST
1.4 DELETE ALL FAULT ALARMS LIST
2. DISABLEMENT
2.1 SET DISABLEMENT
2.1.1 DEVICE
2.1.2 LOOPS
2.1.3 ZONES
2.1.4 EXTERNAL OUTPUTS
2.1.5 SET DISABLEMENT TIME
2.2 DELETE DISABLEMENT
2.3 SET WORKSHOP TIME UNIT
3. SYSTEM CHECK
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
ACCESS LEVEL 2
1 2 3
4 5 6
7 8 9
ESC 0 ENT
0 0 0 0
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Software Procedure - 9 -
3.1 KEY & LED TEST
3.2 SIMULATE FIRE
3.3 TEST MODE
4. SYSTEM SETTING
4.1 SET TIME
4.2 SET ALARM DELAY TIME
4.3 SET SECURITY NUMBER
4.3.1 ACCESS LEVEL2
4.3.2 ACCESS LEVEL3
4.3.3 ACCESS LEVEL4
5. SYSTEM CONFIGURATION
5.1 LOOPS CONFIGURATION
5.1.1 ADDRESSABLE LOOPS
5.1.1.1 SET LOOPS
5.1.1.2 AUTO LOAD
5.1.1.3 ADD DEVICE
5.1.1.4 VIEW DEVICE
5.1.2 CONVENTIONAL LOOPS
5.2 ZONES CONFIGURATION
5.3 EXTERNAL OUTPUTS CONFIGURATION
5.3.1 SET RELAY BOARDS
5.3.2 EDIT RELAY BOARDS
5.3.3 EXTERNAL OUTPUTS
5.4 UNITS CONFIGURATION
5.4.1 REPEATER
5.4.2 INTERFACE
5.5 SYSTEM INTERFACE
5.5.1 UPGRADE FROM USB
5.5.2 TCP-IP LAN
5.5.3 SET INTERFACE
2.2 MENU INFORMATION MENU activated in Home mode should be touched or input key MENU should be pushed In order to
enter menu mode. Menu mode performs some functions such as setup, check and list check of
BDS-4000 SYSTEM. If you touch EXIT activated on the display, the mode will return to higher pre-
mode. And in case of pushing input KEY Home, the mode will return to home mode immediately.
BDS-4000 Software Procedure - 10 -
MAIN MENU
CURRENT MENU ROUTE AND EXIT TIME INDICATION
☞ In the bottom of the screen, the whole route and exit time of current menu are displayed.
☞ In case of exceeding menu exit time, Home menu will return. (SET TIME: 60 seconds)
1. VIEW ALARM LIST
Alarm list of BDS-4000 SYSTEM can be checked and deleted in this mode.
VIEW ALARMS LIST MENU
1.1. FIRE ALARM LIST Fire alarm list can be checked.
☞ ALARM TYPE: FIRE ALARM, FIRE PRE-ALARM
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FIRE ALARMS LIST
ALARM NO: 1/50
ALARM TYPE: FIRE ALARM
TIME : 01-01-2010 AM 01:01
LOOP NO.: 1 ZONE NO.: 1
DEVICE NO.& TYPE: 1 SMOKE DETECTOR
ROCATION: NAVI DECK
EXIT PREV NEXT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
MAIN MENU
1. VIEW ALARMS LIST
2. DISABLEMENT
3. SYSTEM CHECK
4. SYSTEM SETTING
5. SYSTEM CONFIGURATION
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
VIEW ALARMS LIST
1. FIRE ALARMS LIST
2. DELETE ALL FIRE ALARMS LIST
3. FAULT ALARMS LIST
4. DELETE ALL FAULT ALARMS LIST
EXIT
BDS-4000 Software Procedure - 11 -
1.2. DELETE ALL FIRE ALARM LIST (ACCESS LEVEL3) Every fire alarm list can be deleted, and therefore initialized.
1.3. FAULT ALARMS LIST SYSTEM FAULT ALARM LIST can be checked.
1.4. DELETE ALL FAULT ALARMS LIST (ACCESS LEVEL3) Every FAULT ALARM LIST can be deleted, and therefore initialized.
2. DISABLEMENT (ACCESS LEVEL3) DISABLEMENT MENU
2.1. SET DISABLEMENT This mode is used to set up disablement function of loop, zone & device.
SET DISABLEMENT MENU
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FAULT ALARMS LIST
ALARM NO: 1/50 ALARM TYPE: LOOP FAULT
TIME : 01-01-2010 AM 01:01
EXIT PREV NEXT
ALARM REPORT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
DISABLEMENT
1. SET DISABLEMENT
2. DELETE DISABLEMENT
3. SET WORKSHOP TIME UNIT
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET DISABLEMENT
1. DEVICES
2. LOOPS
3. ZONES
4. EXTERNAL OUTPUTS
5. SET DISABLEMENT TIME
EXIT
BDS-4000 Software Procedure - 12 -
2.1.1. DEVICES
☞ If you choose the loop where the device you want to select is loaded after current enabled
loop is activated,, you can enter SET DEVICE DISABLEMENT MODE
▼( 01 )
☞ UP DOWN : Devices loaded in the pertinent loop can be selected.
☞ STATE DISABLE : “ENABLE” or “DISABLE” can selected.
☞ SAVE : Revised facts can be saved.
2.1.2. LOOPS
☞ SAVE : 선택된 LOOPS의 DISABLEMENT설정 저장
☞ If you touch SAVE after selecting current activated loops, revised facts will be saved
and the mode will return to pre-mode.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET LOOPS DISABLEMENT SELELCT LOOP
01 02 03 04 05 06
07 08 09 10 11 12
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET DEVICES DISABLEMENT SELELCT LOOP
01 02 03 04 05 06
07 08 09 10 11 12
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET DEVICES DISABLEMENT
LOOP: 1
ZONE NO.: 1
DEVICE NO: 1 UP DOWN
DEVICE TYPE: SMOKE DETECTOR
STATE: DISABLE
EXIT SAVE
BDS-4000 Software Procedure - 13 -
2.1.3. ZONES
☞ If you touch SAVE after touching zone to be selected and choosing either ENABLE or
DISABLE, revised facts will be saved.
UP DOWN : Up to maximum 100 ZONES can be set up through moving to other pages.
2.1.4. EXTERNAL OUTPUTS
☞ The disablement function of each RELAY OUTPUT CHANNEL of INTERFACE PCB can
be set up or canceled.
☞ If you touch SAVE after selecting either ENABLE or DISABLE for output to be set up,
revised facts will be saved.
2.1.5. SET DISABLEMENT TIME
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET ZONES DISABLEMENT
SELELCT ZONE PAGE
ZONE 1: Enable ZONE 6: Enable UP
ZONE 2: Enable ZONE 7: Enable DOWN
ZONE 3: Enable ZONE 8: Enable
ZONE 4: Enable ZONE 9: Enable
ZONE 5: Enable ZONE 10: Enable
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET DISABLEMENT TIME
START TIME: 01-01-2010 00 : 01
END TIME: 01-01-2010 00 : 10
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET OUTPUTS DISABLEMENT
SELELCT RELAY
1 2 3 4
5 6 7 8
EXIT SAVE
BDS-4000 Software Procedure - 14 -
☞ If you touch SAVE after setting up start time & end time, revised time will be saved
and the mode will return to pre-mode. If a set disablement time is not set up,
disablement function will be proceeding until manual cancellation.
2.2. DELETE DISABLEMENT You can remove the pertinent list when selected disablement list is indicated
☞ REMOVE : Each item set up for disablement can be canceled
2.3. SET WORKSHOP TIME UNIT This mode is used to set up devices which can be connected with function of workshop
time.
SET WORKSHOP TIME UNIT
▼( 01 )
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
DELETE DISABLEMENT
LOOPS 1 REMOVE
ZONES 1 REMOVE
DEVICES 1 REMOVE
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET WORKSHOP TIME UNIT SELELCT LOOP
01 02 03 04 05 06
07 08 09 10 11 12
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET WORKSHOP TIME UNIT
LOOP: 1
ZONE NO.: 1
DEVICE NO: 1 UP DOWN
DEVICE TYPE: SMOKE DETECTOR
STATE: LOAD
EXIT SAVE
BDS-4000 Software Procedure - 15 -
☞ UP DOWN : Devices to be set up can be selected.
☞ STATE: LOAD : You can choose whether WORKSHOP TIMMER will be set up
☞ SAVE : Revised facts is saved.
3. SYSTEM CHECK This mode is used to check whether BDS-4000 SYSTEM is normally operated.
SYSTEM CHECK MENU
3.1. KEY & LED TEST When this mode is entered, the whole LEDs are lighted up. If you push the key for test, internal
buzzer will beep and the mark of key will be displayed on the LCD.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
KEY & LED TEST
PRESS KEY TO TEST
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SYSTEM CHECK
1. KEY & LED TEST
2. SIMULATE FIRE
3. TEST MODE
EXIT
BDS-4000 Software Procedure - 16 -
3.2. SIMULATE FIRE (ACCESS LEVEL3) This mode is used to perform a test for fire simulation. Through designating a detector to be
tested, simulated fire can take place intentionally and the operation of every output connected
with the designated detector will be processing like the state of real fire
☞ If you choose the loop where the device you select is loaded when current enabled loop is
activated, you can enter SET SIMULATE FIRE MODE.
▼( 01 )
☞ UP DOWN : devices loaded in the pertinent loop can be selected.
☞ STATE DISABLE : either “ENABLE” or “DISABLE” can be selected
☞ EXIT : This is used to return to pre-mode without saving revised facts.
☞ SAVE : This is used to save the setting for SIMULATE FIRE and proceed to setting up
next devices.
☞ In case of returning to home mode, the function of simulation fire for set devices will be
performed.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SIMULATE FIRE SELELCT LOOP
01 02 03 04 05 06
07 08 09 10 11 12
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET SIMULATE FIRE
LOOP: 1
ZONE NO.: 1
DEVICE NO: 1 UP DOWN
DEVICE TYPE: SMOKE DETECTOR
STATE: DISABLE
EXIT SAVE
BDS-4000 Software Procedure - 17 -
* FIRE ALARM EXAMPLE
▼( ACK )
☞ LIST : This is used to check generated firm alarm lists.
☞ RESET : this is used to reset generated fire alarm and setting value of simulation fire.
3.3. TEST MODE (ACCESS LEVEL3) This mode is used to test the system. (TEST MODE LED ON)
Each alarm is displayed, but relay output is not operated.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FIRE ALARM
ALARM NO: 1/1
ALARM TYPE: FIRE ALARM 64
TIME : 01-01-2010 AM 01:01
LOOP NO.: 1 ZONE NO.: 1
DEVICE NO.& TYPE: 1 SMOKE DETECTOR
DISCRIPTION:
ACT
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
FIRE ALARM = 1 LIST RESET
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
TEST MODE
SELELCT ZONE PAGE
ZONE 1: Disable ZONE 6: Disable UP
ZONE 2: Disable ZONE 7: Disable DOWN
ZONE 3: Disable ZONE 8: Disable
ZONE 4: Disable ZONE 9: Disable
ZONE 5: Disable ZONE 10: Disable
EXIT SAVE
BDS-4000 Software Procedure - 18 -
☞ If you touch SAVE after touching zone to be set up and choosing either ENABLE or DISABLE,
revised facts will be saved. A test function for enabled zone will be processing.
UP DOWN : Up to maximum 100 ZONES can be set up through moving to other pages.
4. SYSTEM SETTING This mode is used to set up time setting and security number according to each access level.
SYSTEM SETTING
4.1. SET TIME (ACCESS LEVEL2) This mode is used to set up time.
4.2. SET ALARM DELAY TIME (ACCESS LEVEL3)
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SYSTEM SETTING
1. SET TIME
2. SET ALARM DELAY TIME
3. SET SECURITY NUMBER
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET TIME
01 – 01 – 2010 01 : 01 : 01
MM – DD – YYYY hh : mm : ss
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET ALARM DELAY TIME
00 MINUTE
UP DOWN
EXIT SAVE
BDS-4000 Software Procedure - 19 -
In case of fire, external output will be delayed, but fire state continues to remain and every
fire function including external output will be proceeding during delay time set up in this
mode. A basic value is 0 and increases at intervals of 1 minute. And it is possible to set up
up to maximum 10 minutes.
4.3. SET SECURITY NUMBER This mode is used to resister security number according to security rank,
4.3.1. ACCESS LEVEL2 (ACCESS LEVEL2) Security number corresponding to ACCESS LEVEL2 can be changed.
When goods are delivered, setting number: 2222
4.3.2. ACCESS LEVEL3 (ACCESS LEVEL3) Security number corresponding to ACCESS LEVEL3 can be changed.
When goods are delivered, setting number: 3333
4.3.3. ACCESS LEVEL4 (ACCESS LEVEL4) Security number corresponding to ACCESS LEVEL4 can be changed.
When goods are delivered, setting number: 3333
5. SYSTEM CONFIGRATION This mode is used to set up loop, zone, devices and related unit and system upgrade.
SYSTEM CONFIGRATION
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET SECURITY NUMBER
ACCESS LEVEL2
ACCESS LEVEL3
ACCESS LEVEL4
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SYSTEM CONFIGURATION
1. LOOPS CONFIGURATION
2. ZONES CONFIGURATION
3. EXTERNAL OUTPUTS CONFIGURATION
4. UNITS CONFIGURATION
5. SYSTEM INTERFACE
EXIT
BDS-4000 Software Procedure - 20 -
5.1. LOOPS CONFIGRATION (ACCESS LEVEL3) LOOPS CONFIGRATION
5.1.1. ADDRESSABLE LOOPS This mode is used to set up addressable loop.
5.1.1.1. SET LOOPS This mode is used to set up whether loops are applied
☞ If you touch SAVE after activating loops set up for “ENABLE”, the mode will return to
pre-mode.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET LOOPS SELELCT LOOP
01 02 03 04 05 06
07 08 09 10 11 12
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
LOOPS CONFIGURATION
1. ADDRESSABLE LOOPS
2. CONVENTIONAL LOOPS
3. EXTERNAL SERIAL LOOP
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
ADDRESSABLE LOOPS
1. SET LOOPS
2. AUTO LOAD
3. ADD DEVICE
4. VIEW DEVICE
EXIT
BDS-4000 Software Procedure - 21 -
5.1.1.2. AUTO LOAD Devices connected with a selected loop are automatically loaded.
☞ if pertinent LOOP : START is performed when enabled loops are activated in loop
configuration, function for AUTO LOAD will be processing.
5.1.1.3. ADD DEVICE A device is loaded into selected loop by manual.
▼
☞ SELECT DEVICE UP DOWN : select devices not loaded in the pertinent loop.
☞ DEVICE TYPE UP DOWN : select the type of a chosen device.
If you touch SAVE, value of the pertinent device will be saved and then other devices can be set
up.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
AUTO LOAD
LOOP 1 : START LOOP 7 : DISABLE
LOOP 2 : START LOOP 8 : DISABLE
LOOP 3 : START LOOP 9 : DISABLE
LOOP 4 : START LOOP10 : DISABLE
LOOP 5 : DISABLE LOOP11 : DISABLE
LOOP 6 : DISABLE LOOP12 : DISABLE
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
ADD DEVICE
LOOP: 1
SELECT DEVICE UP DOWN
DEVICE ID: 1
DEVICE TYPE: UP DOWN
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
ADD DEVICE SELELCT LOOP
01 02 03 04 05 06
07 08 09 10 11 12
EXIT SAVE
BDS-4000 Software Procedure - 22 -
5.1.1.4. VIEW DEVICE This mode is used to see information regarding an selected device.
☞ If you select the loop when current enabled loops are activated, you will enter DEVICE VIEW
MODE.
▼( LOOP1 : VIEW )
☞ ZONE NO UP DOWN : can select a zone.
☞ DEVICE NO UP DOWN : can select a device.
☞ SET RELAY UP DOWN : can select CHANNEL of EXTERNAL RELAY OUTPUT connected with
the pertinent device and can be set up in case of touching SET.
☞ DESCRIPTION: can set up description of the pertinent device. .
☞ SAVE : If you touch SAVE, value of the pertinent device will be saved and then other devices
can be set up.
5.1.2. CONVENTIONAL LOOPS This mode is used to set up CONVENTIONAL LOOPS
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET CONVENTIONAL LOOPS
LOOP NO: 1 ENABLE
DISCRIPTION:
EXIT PREV NEXT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
VIEW DEVICE
LOOP 1 : VIEW LOOP 7 : DISABLE
LOOP 2 : VIEW LOOP 8 : DISABLE
LOOP 3 : VIEW LOOP 9 : DISABLE
LOOP 4 : VIEW LOOP10 : DISABLE
LOOP 5 : DISABLE LOOP11 : DISABLE
LOOP 6 : DISABLE LOOP12 : DISABLE
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
VIEW DEVICE
LOOP: 1
ZONE NO: 1 UP DOWN
DEVICE ID : 1 UP DOWN
DEVICE TYPE: SMOKE DETECTOR ( 24 )
SET RELAY : 1 UP DOWN SET
DESCRIPTION:
EXIT SAVE
BDS-4000 Software Procedure - 23 -
☞ ENABLE : can set up whether loop are used.
☞ DESCRIPTION : can set up description of the pertinent loop.
☞ PREV NEXT : can move to loops, which can be selected.. (Maximum 32 LOOPS)
☞ If you touch SAVE, value of the pertinent loop will be saved and then other loops can be
set up.
5.2. ZONES CONFIGURATION (ACCESS LEVEL3) This mode is used to set up and edit whether a zone is used.
☞ If you select a zone, you will enter the mode to set up the selected zone.
☞ UP DOWN : Up to maximum 100 ZONES can be set up through moving to other pages.
▼(ZONE1)
☞ SELECT LOOP UP DOWN : can select loops connected with a device to be setup.
☞ ADD DEVICE UP DOWN ADD : can select and add devices which are supposed to be loaded
in a zone
☞ DELETE DEVICE UP DOWN DEL : can select and delete the devices loaded in a zone.
☞ SET RELAY OUT UP DOWN SET : can select the channel of external relay connected with a
zone.
☞ DISCRIPTION: : can set up the description of a zone.
☞ SAVE :If you touch SAVE, setting value of the pertinent zone will be saved and the
mode will return to pre-mode.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
ZONES EDIT
SELECT ZONE DEVICE SELECT ZONE DEVICE PAGE
ZONE 1 : 12 ZONE 6 : 0 UP
ZONE 2 : 17 ZONE 7 : 0 DOWN
ZONE 3 : 10 ZONE 8 : 0
ZONE 4 : 11 ZONE 9 : 0
ZONE 5 : 0 ZONE10 : 0
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
EDIT ZONE1
LOAD DEVICE NO: 0
SELECT LOOP: UP DOWN
ADD DEVICE: UP DOWN ADD
DELETE DEVICE: UP DOWN DEL
SET RELAY OUT: UP DOWN SET
DISCRIPTION:
EXIT SAVE
BDS-4000 Software Procedure - 24 -
5.3. EXTERNAL OUTPUT CONFIGRATION (ACCESS LEVEL3) EXTERNAL OUTPUT CONFIGRATION
5.3.1. SET RELAY BOARDS This mode is used to set up whether PROGRAMMABLE RELAY BOARDS are used.
☞ it is possible to be extended up to maximum 16 relay boards and they can be activated through
selecting ENABLE RELAY BOARDS.
☞ If you touch SAVE, the mode will return to pre-mode.
5.3.2. EDIT RELAY OUTPUTS This mode is to decide each Relay Output qualities of Programmable Relay Boards.
▼(RELAY BOARD 01 )
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
EXTERNAL OUTPUT
1. SET RELAY BOARDS
2. EXTERNAL OUTPUTS
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET RELAY BOARDS
SELELCT EXTERNAL RELAY BOARDS
01 02 03 04 05 06 07 08
09 10 11 12 13 14 15 16
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
EDIT RELAY OUTPUTS
SELELCT EXTERNAL RELAY BOARDS
01 02 03 04 05 06 07 08
09 10 11 12 13 14 15 16
EXIT
BDS-4000 Software Procedure - 25 -
▼(RELAY NO.1 )
☞ LOAD DEVICE : Select the device to set up.
☞ TYPE FIRE PRE ALARM WARNING FAULT : Select the Alarm Type of the device to load.
☞ OPTION ACK MUTE GA MORSE : Specify the quality of output when the relevant alarm occurs.
☞ DELAY TIME UP DOWN : Select the delay time for the Relay Output.
☞ DISCRIPTION: : Set up the Reply Output Description.
☞ Touching SAVE saves the setting value of relevant Replay Output and return to the pre-
mode.
5.3.3 EXTERNAL OUTPUTS This mode is used to set up standard output of BDS-4000 SYSTEM.
☞ If you touch SAVE after being set up, setting value will be saved and then the mode will
return to pre-mode.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
EXTERNAL OUTPUTS
SOUNDER1 OUTPUT ENABLE
DOOR1 HOLDER OUTPUT ENABLE
DOOR2 HOLDER OUTPUT ENABLE
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
EDIT RELAY OUTPUTS
SELELCT EXTERNAL RELAY
NO 1 :
NO 2 :
NO 3 :
NO 4 :
EXIT UP DOWN
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
EDIT RELAY OUTPUTS
RELAY BOARD #1 (1)
LOAD DEVICE : 0
TYPE : FIRE PRE ALARM WARNING FAULT
OPTION : ACK MUTE GA MORSE
DELAY TIME : 00 min UP DOWN
DISCRIPTION:
EXIT SAVE
BDS-4000 Software Procedure - 26 -
5.4. UNITS CONFIGRATION (ACCESS LEVEL3) UNITS CONFIGRATION
5.4.1. REPEATER This mode is used to set up the repeater of BDS-4000 SYSTEM
☞ If you touch SAVE after you select connected repeater number, the pertinent repeater will be
connected.
☞ it is possible to be extended up to maximum 4 repeaters
5.4.2. INTERFACE This mode is used to set up the interface connected with BDS-4000 SYSTEM.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
UNITS CONFIGUATION
1. REPEATER
2. INTERFACE
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
REPEATER UNITS
SELELCT REPEATER UNIT
01 02 03 04
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
INTERFACE UNITS
SELELCT INTERFACE UNIT
01 02 03 04
EXIT SAVE
BDS-4000 Software Procedure - 27 -
☞ If you touch SAVE after you select connected interface number, the pertinent interface will be
connected.
☞ it is possible to be extended up to maximum 4 interface.
5.5. SYSTEM INTERFACE (ACCESS LEVEL3) SYSTEM INTERFACE
5.5.1. UPGRADE FROM USB This mode is used to upgrade system software through using USB memory device.
☞ if you touch START UPGRADE, system software will be upgraded into version-up program.
5.5.2. TCP-IP LAN
It is feasible for BDS-4000 to communicate with remote PC through built-in TCP-IP
LAN port. This mode is used to set up whether this function is applied.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
UPGRADE FROM USB
START UPGRADE
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
TCP-IP LAN
ENABLE
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SYSTEM INTERFACE
1. UPGRADE FROM USB
2. TCP-IP LAN
3. SET INTERFACE
EXIT
BDS-4000 Software Procedure - 28 -
☞ If you touch SAVE after you select whether TCP-IP LAN PORT is applied, the TCP-IP LAN
PORT will be connected.
5.5.3. SET INTERFACE
SET INTERFACE
☞ If you touch SAVE after selecting and using one of 4 modes and then the pertinent mode is
activated, selected modes will be set up.
◈ REPEATER PANEL 1. Operation menu
1.1. Start
▼
* NORMAL HOME MENU STATE
INITIALIZE
PLEASE WAIT
BDS-4000 REPEATER Ver. 0.10
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET INTERFACE
1. VDR
2. AMS
3. BI PC SOFTWARE
4. PRINTER
EXIT SAVE
BDS-4000 Software Procedure - 29 -
1.2. Alarm This mode is used to display alarm state occurring in a main panel.
* FIRE ALARM EXAMPLE
▼(ACK)
* NORMAL HOME MENU STATE
BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)
FIRE ALARM
ALARM NO: 1/1
ALARM TYPE: FIRE ALARM 64
TIME : 01-01-2010 AM 01:01
LOOP NO.: 1 ZONE NO.: 1
DEVICE NO.& TYPE: 1 SMOKE DETECTOR
DISCRIPTION:
ACT
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)
BI FIRE DETECTION SYSTEM
MENU
BI INDUSTRIAL Co., Ltd www.b-i.co.kr
BDS-4000 Software Procedure - 30 -
2. Menu construction 2.1. Menu flowchart
1. VIEW ALARMS LIST
1.1 FIRE ALARMS LIST
1.2 DELETE ALL FIRE ALARMS LIST
1.3 FAULT ALARMS LIST
1.4 DELETE ALL FAULT ALARMS LIST
2. KEY & LED TEST
3. SET TIME
4. UPGRADE FROM USB
2.2 MENU INFORMATION
MENU activated in Home mode should be touched or input key MENU should be pushed in order to
enter menu mode. If you should select and touch a window activated in the pertinent mode in order to
enter or set up lower mode, designated operation will be processing.
If you touch EXIT activated on the display, the mode will return to higher pre-mode. And in case of
pushing input KEY Home, the mode will return to home mode immediately.
MAIN MENU
1. VIEW ALARMS LIST
This mode is used to check or delete the alarm list of BDS-4000 SYSTEM.
BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)
MAIN MENU
1. VIEW ALARMS LIST
2. KEY & LED TEST
3. SET TIME
4. UPGRADE FROM USB
EXIT
BDS-4000 Software Procedure - 31 -
VIEW ALARMS LIST MENU
1.1. FIRE ALARMS LIST A fire alarm list can be checked.
☞ ALARM TYPE: FIRE ALARM, FIRE PRE-ALARM
1.2. DELETE ALL FIRE ALARMS LIST This mode is used to be initialized through deleting every fire alarm list.
1.3. FAULT ALARMS LIST A system fault alarm list can checked.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FIRE ALARMS LIST
ALARM NO: 1/50
ALARM TYPE: FIRE ALARM
TIME : 01-01-2010 AM 01:01
LOOP NO.: 1 ZONE NO.: 1
DEVICE NO.& TYPE: 1 SMOKE DETECTOR
ROCATION: NAVI DECK
EXIT PREV NEXT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
FAULT ALARMS LIST
ALARM NO: 1/50 ALARM TYPE: LOOP FAULT
TIME : 01-01-2010 AM 01:01
EXIT PREV NEXT
ALARM REPORT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
VIEW ALARMS LIST
1. FIRE ALARMS LIST
2. DELETE ALL FIRE ALARMS LIST
3. FAULT ALARMS LIST
4. DELETE ALL FAULT ALARMS LIST
EXIT
BDS-4000 Software Procedure - 32 -
1.4. DELETE ALL FAULT ALARMS LIST This mode is used to be initialized through deleting every fault alarm list.
2. KEY & LED TEST When this mode is entered, the whole LEDs are lighted up. If you push the key for a test, internal
buzzer will beep and the mark of a pertinent key will be displayed on the LCD.
3. SET TIME This mode is used to set up time.
4. UPGRADE FROM USB This mode is used to upgrade system software through using USB memory device.
☞ if you touch START UPGRADE, system software will be upgraded into version-up program.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
KEY & LED TEST
PRESS KEY TO TEST
EXIT
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
SET TIME
01 – 01 – 2010 01 : 01 : 01
MM – DD – YYYY hh : mm : ss
EXIT SAVE
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
UPGRADE FROM USB
START UPGRADE
EXIT
BI Fire Detection System(BDS-4000) Trouble shooting 1. Menu flowchart
1. VIEW ALARMS LIST
1.1 FIRE ALARMS LIST
1.2 DELETE ALL FIRE ALARMS LIST
1.3 FAULT ALARMS LIST
1.4 DELETE ALL FAULT ALARMS LIST
2. DISABLEMENT
2.1 SET DISABLEMENT
2.1.1 LOOPS
2.1.2 ZONES
2.1.3 DEVICE
2.1.4 EXTERNAL OUTPUTS
2.1.5 SET DISABLEMENT TIME
2.1.6 ALARM DELAY TIME
2.2 SET WORKSHOP TIME UNIT
2.3 DISABLEMENT LIST & EDIT
3. SYSTEM CHECK
3.1 KEY & LED TEST
3.2 SIMULATE FIRE
3.3 TEST MODE
4. SYSTEM SETTING
4.1 SET TIME
4.2 SET ALARM DELAY TIME
4.3 SET SECURITY NUMBER
4.3.1 ACCESS LEVEL2
4.3.2 ACCESS LEVEL3
4.3.3 ACCESS LEVEL4
4.4 SET SENSITIVITY
5. SYSTEM CONFIGURATION
5.1 LOOPS CONFIGURATION
5.1.1 ADDRESSABLE LOOPS
5.1.1.1 SET LOOPS
5.1.1.2 AUTO LOAD
5.1.1.3 ADD DEVICE
5.1.1.4 VIEW DEVICE
5.1.2 CONVENTIONAL LOOPS
5.1.3 EXTERNAL SERIAL LOOP
5.2 ZONES CONFIGURATION
5.3 EXTERNAL OUTPUTS CONFIGURATION
5.3.1 SET RELAY BOARDS
5.3.2 EDIT RELAY OUTPUTS
5.3.3 EXTERNAL OUTPUTS
5.3.4 EDIT FIRE FIGHTING OUTPUTS
5.4 UNITS CONFIGURATION
5.4.1 REPEATER
5.4.2 INTERFACE
5.5 SYSTEM INTERFACE
5.5.1 UPGRADE FROM USB
5.5.2 SET INTERFACE
2. Password ACCESS LEVEL2 : 2222 ENTER
ACCESS LEVEL3 : 3333 ENTER
ACCESS LEVEL4 : 4444 ENTER
3. Main Panel ~ Detector communication check a. Menu touch => Menu flowchart “5.1.14 VIEW DEVICE” Menu Touch
b. Select Loop Touch
C. Analogue data : Main panel ~ Detector communication data. (Reference chart)
Analogue data
Detector Fault Contamination Normal
Pre-
Alarm Fire
Smoke 0 1~5 6~47 48~63 64~127
Heat 0 1~5 6~47 48~63 64~127
Callpoint 0 - 20 - 64~127
Flame 0 - 20 - 64~127
Timer 0 - 20 - 64
(operating)
d. All detector Analogue data check.
* Smoke or Heat detector
☞ Smoke detector analogue data : 35 more than => Detector clean (Make advise)
☞ 10. Smoke / Heat detector clean reference.
☞ Contamination fault alarm(1~5) => changed Smoke or Heat detector.
☞ Device fault alarm(0) => 9. Smoke or heat detector fault alarm reference.
BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)
VIEW DEVICE
LOOP: 1
ZONE NO: 1
DEVICE ID : 1 UP DOWN
DEVICE TYPE: OPTICAL SMOKE DETECTOR ( 24 )
SET RELAY : 1
DESCRIPTION:
EXIT SAVE
Analogue data
4. Loop / Zone / Device Disablement setting a. Loop disablement : Select loop all detector => no operating.
☞ Menu touch => Menu flowchart : “2.1.1 LOOPS” Menu Touch
☞ Select Loop touch => SAVE => Disablement LED : ON =>
Main panel display : Disablement list : 1
☞ Remove : “2.3 Disablement list & edit” touch => “Remove “ touch
b. Zone disablement : Select zone all detector => no operating.
☞ Menu touch => Menu flowchart : “2.1.2 ZONES” Menu Touch
☞ Select Zone touch => “zone ○○ : Enable” touch => SAVE =>
Disablement LED : ON => Main panel display : Disablement list : 1
☞ Remove : “2.3 Disablement list & edit” touch => “Remove “ touch
c. Device disablement : Select device => Detector no operating.
☞ Menu touch => Menu flowchart : “2.1.3 DEVICES” Menu Touch
☞ Select Loop touch => DEVICE ID : UP / DOWN touch => select address no display =>
“STATE : ENABLE” one touch => SAVE => Disablement LED : ON =>
Main panel display : Disablement list : 1
☞ Remove : “2.3 Disablement list & edit” touch => “Remove “ touch
5. Loop Short alarm Check a. Loop Analogue data check
☞ “3. Main~Detector communication check” reference.
b. Loop Short area : Line isolator LED ON.(address list reference)
c. Interface panel : power off
d. Isolator ~ Isolator : Loop line check.
☞ Loop line : Normal
☞ Interface panel : power on
☞ “3. Main~Detector communication check” reference.
e. Loop line : Normal, Main panel display : short alarm
☞ Interface panel : loop cable open => Loop connector : DC 20~27V check.
☞ No voltage : Maker contact.(Loop card or Loop base board : correct)
6. Loop Open alarm Check a. Loop Analogue data check
☞ “3. Main~Detector communication check” reference.
b. Device fault reporting. (address list reference)
c. Interface panel : power off.
d. Isolator ~ Isolator : Loop line check.
☞ Loop line : Normal
☞ Interface panel : power on
☞ “3. Main~Detector communication check” reference.
e. Loop line : Normal, Main panel display : open alarm
☞ Interface panel : loop cable open => Loop connector : DC 20~27V check.
☞ No voltage : Maker contact.
7. Main or Em’cy power fault alarm Check
(Interface panel inside photo)
① : Main power(AC_L, AC_N), Em’cy power(AC_L, AC_N)
☞ Main / Em’cy AC 220V check
☞ ③, ④ : Main / Em’cy power fuse(5A) check
② : Auto change AC power : 220V check
☞ ⑤ : Auto change AC power fuse(5A) check
* ① : Main / Em’cy power : AC 220V => OK => ② : No power => Maker contact.
8. Battery fault alarm Check a. All power : off
☞ Internal cable check.=>Red cable:One by One check.
=>Blue cable : One by one check.
b. Battery Voltage Check photo : DC 22~26.5V(Normal)
① ②
③
④
⑤
c. Interface PCB Short Check
☞ All power : off
☞ +BAT, -BAT Internal cable : open ☞ Battery input connector : +BAT, -BAT short check
☞ Fuse : open
☞ Battery input connector :-BAT, fuse short check
9. Smoke or Heat Detector fault alarm a. Interface panel : power off
b. Smoke / Heat detector head : left rotation => Loop line : Rubber cutting => re-connection
(polarity caution => L2:+, L1:-)
c. Loop Analogue data check
☞ “3. Main~Detector communication check” reference.
☞ Analogue data : 0 => Detector Voltage check : DC 20~27V => Voltage Ok
=>Smoke / Heat Detector : change
10. Smoke / Heat Detector clean a. Smoke or Heat detector head ~ detector base devide : detector head Left .
[ Smoke detector front] [ Smoke detector bottom]
b. bolt : “+” drive use => Devide detector head cover.
RUBBER CUTTING
②
③
①
c. Cap left rotation. => Devide cap and sensor
d. Cap + sensor : clean.
e. a~d : inverse
11. Flame detector check a. Sensivity control
① Control Resistor
☞ Left Rotation : Sensivity Low, Right Rotation : Sensivity Fast
② Dip switch => 0 : Sensivity Fast => 3 : Sensivity Low
b. Fault alarm
☞ +, - cable check => DC 20~27V => Voltage Ok => PCB : change(Address setting caution)
12. Call point check a. Fault alarm
☞ +, - cable check => DC 20~27V => Voltage Ok => PCB : change(Address setting caution)
13. Workshop Timer check a. Main panel workshop timer setting check.
☞ Menu touch => Menu flowchart “2.2 SET WORKSHOP TIME UNIT” Menu touch =>
Select loop touch => Device ID : UP touch(Workshop location detector move) =>
“STATE : UNLOAD” touch => “STATE : LOAD” change => Save touch.
(Caution : workshop timer => “STATE : UNLOAD” setting)
b. Workshop Time unit check
① : “MODE 1” check
② : “Min” check
c. Device fault check.
☞ Workshop time unit open => Loop “+”, “-“ cable check DC 20~27V => Voltage Ok
=> PCB : change(Address setting caution)
cap Sensor
cap
①
②
①
②
②
14. Earth fault check a. Loop Analogue data check
☞ “3. Main~Detector communication check” reference.
☞ Analogue data & Detector type : Different => Make contact
(Analogue data photo : Make send)
☞ Analogue data & Detector type : Normal => Interface panel open => Interface PCB
Bolt open(blue line reference) => PCB ~ support : Gap => PCB ~ support : Insulation.
=> Bolt : No insert.
☞ Main panel : Earth fault alarm Reset. => Normal display => Make contact.
15. Main / Repeat panel CPU change method
16. Interface panel inside photo
(Interface panel inside photo)
(Main panel inside photo)
a. Lock : left / right push => CPU remove.(①~② reference)
b. CPU insert : “a” inverse
CPU
① ①
②
DC24V SWITCH LOOP CARD BATTERY
FUSE(5A)
Loop1 Loop2 Loop3 Loop4
Loop base
board