BDS-4000 Software Procedure - 1 - B-I Fire Detection System MODEL: BDS-4000 Ver. 1.0 Software Procedure B-I INDUSTRIAL CO., LTD. Web site : www. b-i.co.kr , E-mail : [email protected] ▣ SEOUL HEAD OFFICE ▣ BUSAN FACTORY Ace Hightech City 1-618, 55-20 Munrae-dong3 2508-1, Daejeo-2dong, Kangseo-gu, Yeongdeungpo-gu, Seoul, Korea Busan, Korea Tel: 02) 706-3077 Tel: 051) 441-5670 Fax: 02) 702-3076 Fax: 051) 441-6225

B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

  • Upload
    others

  • View
    104

  • Download
    25

Embed Size (px)

Citation preview

Page 1: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 1 -

B-I Fire Detection System

MODEL: BDS-4000 Ver. 1.0

Software Procedure

B-I INDUSTRIAL CO., LTD. Web site : www. b-i.co.kr , E-mail : [email protected]

▣ SEOUL HEAD OFFICE ▣ BUSAN FACTORY

Ace Hightech City 1-618, 55-20 Munrae-dong3 2508-1, Daejeo-2dong, Kangseo-gu,

Yeongdeungpo-gu, Seoul, Korea Busan, Korea

Tel: 02) 706-3077 Tel: 051) 441-5670

Fax: 02) 702-3076 Fax: 051) 441-6225

Page 2: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 2 -

Index

◈ MAIN PANEL 1. Operation menu 1.1. Start ---------------------------------------------------------- 3

1.2. Fault ---------------------------------------------------------- 4

1.3. Fire pre-alarm ------------------------------------------------- 5

1.4. Fire alarm ----------------------------------------------------- 7

2. Menu construction 2.1. Menu flowchart ----------------------------------------------- 8

2.2. Menu information --------------------------------------------- 9

1. VIEW ALARMS LIST ---------------------------------------------- 10

2. DISABLEMENT -------------------------------------------------- 11

3. SYSTEM CHECK ------------------------------------------------ 14

4. SYSTEM SETTING ----------------------------------------------- 17

5. SYSTEM CONFIGRATION ----------------------------------------- 18

◈ REPEATER PANEL 1. Operation menu 1.1. Start --------------------------------------------------------- 27

1.2. Alarm -------------------------------------------------------- 27

2. Menu construction 2.1. Menu flowchart ---------------------------------------------- 28

2.2. Menu information -------------------------------------------- 28

1. VIEW ALARMS LIST ---------------------------------------------- 29

2. KEY &LED TEST ------------------------------------------------- 30

3. SET TIME ------------------------------------------------------ 30

4. UPGRADE FROM USB -------------------------------------------- 30

Page 3: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 3 -

◈ MAIN PANEL 1. Operation menu

1.1. Start

* Loop display can be indicated up to 12 loops, the maximum loop number of BDS-4000

SYSTEM. And the loops set up as “ABLE” before being reset will be progressing.

* Every device connected with the pertinent loop is checked.

* Progress state is displayed as % through setting standards that maximum 127 detectors per

loop can be loaded

* In case that setting state after system reset is different from the setting state set up before,

device fault will occur.

* NORMAL HOME MENU 상태

INITIALIZE

PLEASE WAIT

BDS-4000 Ver. 0.10

CHECKING LOOPS PLEASE WAIT LOOP DEVICE PROGRESS

1 96 / 127 85 %

2 0 / 127 0 %

3 0 / 127 0 %

4 0 / 127 0 %

5 0 / 127 0 %

6 0 / 127 0 %

7 0 / 127 0 %

8 0 / 127 0 %

9 0 / 127 0 %

10 0 / 127 0 %

11 0 / 127 0 %

12 0 / 127 0 %

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

Page 4: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 4 -

1.2. Fault FAULT TYPE: LOOPS FAULT, DEVICE FAULT, UNEXPECT DEVICE FAULT, MAIN POWER FAULT,

EMERGENCY POWER FAULT, BATTERY FAULT, EARTH FAULT EXTERNAL

SOUNDER FAULT, DOOR HOLDER1,2 FAULT, COMMUNICATION FAULT:

REPEATER, INTERFACE, EXTERNAL RELAY BOARD, LOOP CARD

FAULT PROCESS: In case system fault LED flickers, buzzer beeps and the external output is on,

please push Mute KEY repeatedly which can make buzzer beep or not beep

and touch ACK which can make HOMM MODE(FAULT ALARM MODE)

converted and LIST & RESET windows related to generated fault will be

activated. However, in case of communication fault occurs, COMM ALARM

LED will flicker

* LOOP FAULT EXAMPLE

▼( ACK )

☞ LIST : can make you check generated alarm lists.

☞ RESET : can make you reset generated alarm.

But reset will be processed after the input of ACCESS LEVEL2 SECURITY NUMBER.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FAULT ALARM

ALARM NO: 1 ALARM TYPE: LOOPS FAULT

TIME : 01-01-2010 AM 01:01

LOOP CARD NO: 1 OPEN

ACK

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

FAULT ALARM = 1 LIST RESET

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

Page 5: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 5 -

▼( RESET )

▼ ( ENT ) RESET

1.3. FIRE PRE-ALARM PRE-ALARM PROCESS: In case system fault LED flickers, buzzer beeps and the external output

is on, please push Mute KEY repeatedly which can make buzzer beep or not beep

and touch ACK which can make HOMM MODE(FAULT ALARM MODE) converted

and LIST & RESET windows related to generated pre-alarm will be activated.

* FIRE PRE-ALARM EXAMPLE

* Analogue value transmitted by devices is indicated real time ( Refer to page 48)

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

ACCESS LEVEL 2

1 2 3

4 5 6

7 8 9

ESC 0 ENT

0 0 0 0

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FIRE PRE-ALARM

ALARM NO: 1/1

ALARM TYPE: FIRE PRE-ALARM 48

TIME : 01-01-2010 AM 01:01

LOOP NO.: 1 ZONE NO.: 1

DEVICE NO.& TYPE: 1 SMOKE DETECTOR

DISCRIPTION:

ACT

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

Page 6: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 6 -

▼( ACK )

☞ LIST : can make you check PRE-ALARM LIST.

☞ RESET : can make you reset generated PRE-ALARM.

But reset will be processed after the input of ACCESS LEVEL2 SECURITY NUMBER.

▼( RESET )

▼ ( ENT ) RESET

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

FIRE ALARM = 1 LIST RESET

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

ACCESS LEVEL 2

1 2 3

4 5 6

7 8 9

ESC 0 ENT

0 0 0 0

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

Page 7: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 7 -

1.4. FIRE ALARM FIRE ALARM PROCESS: In case system fault LED flickers, buzzer beeps and the external output

is on, please push Mute KEY repeatedly which can make buzzer beep

or not beep and touch ACK which can make HOMM MODE(FAULT

ALARM MODE) converted and LIST & RESET windows related to

generated fire alarm will be activated.

* FIRE ALARM EXAMPLE

* Analogue value transmitted by devices is indicated real time ( Refer to page 64)

▼( ACK )

☞ SILENCE : will make you silence external output to sounder. RESOUND will be converted.

☞ LIST : will make you check a generated fire alarm list.

☞ RESET : will make you reset fire alarm.

But reset will be processed after the input of ACCESS LEVEL2 SECURITY NUMBER.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FIRE ALARM

ALARM NO: 1/1

ALARM TYPE: FIRE ALARM 64

TIME : 01-01-2010 AM 01:01

LOOP NO.: 1 ZONE NO.: 1

DEVICE NO.& TYPE: 1 SMOKE DETECTOR

DISCRIPTION:

ACT

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

FIRE ALARM = 1 SILENCE LIST RESET

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

Page 8: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 8 -

▼( RESET )

▼ ( ENT ) RESET

2. Menu construction 2.1. Menu flowchart

1. VIEW ALARMS LIST

1.1 FIRE ALARMS LIST

1.2 DELETE ALL FIRE ALARMS LIST

1.3 FAULT ALARMS LIST

1.4 DELETE ALL FAULT ALARMS LIST

2. DISABLEMENT

2.1 SET DISABLEMENT

2.1.1 DEVICE

2.1.2 LOOPS

2.1.3 ZONES

2.1.4 EXTERNAL OUTPUTS

2.1.5 SET DISABLEMENT TIME

2.2 DELETE DISABLEMENT

2.3 SET WORKSHOP TIME UNIT

3. SYSTEM CHECK

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

ACCESS LEVEL 2

1 2 3

4 5 6

7 8 9

ESC 0 ENT

0 0 0 0

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

Page 9: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 9 -

3.1 KEY & LED TEST

3.2 SIMULATE FIRE

3.3 TEST MODE

4. SYSTEM SETTING

4.1 SET TIME

4.2 SET ALARM DELAY TIME

4.3 SET SECURITY NUMBER

4.3.1 ACCESS LEVEL2

4.3.2 ACCESS LEVEL3

4.3.3 ACCESS LEVEL4

5. SYSTEM CONFIGURATION

5.1 LOOPS CONFIGURATION

5.1.1 ADDRESSABLE LOOPS

5.1.1.1 SET LOOPS

5.1.1.2 AUTO LOAD

5.1.1.3 ADD DEVICE

5.1.1.4 VIEW DEVICE

5.1.2 CONVENTIONAL LOOPS

5.2 ZONES CONFIGURATION

5.3 EXTERNAL OUTPUTS CONFIGURATION

5.3.1 SET RELAY BOARDS

5.3.2 EDIT RELAY BOARDS

5.3.3 EXTERNAL OUTPUTS

5.4 UNITS CONFIGURATION

5.4.1 REPEATER

5.4.2 INTERFACE

5.5 SYSTEM INTERFACE

5.5.1 UPGRADE FROM USB

5.5.2 TCP-IP LAN

5.5.3 SET INTERFACE

2.2 MENU INFORMATION MENU activated in Home mode should be touched or input key MENU should be pushed In order to

enter menu mode. Menu mode performs some functions such as setup, check and list check of

BDS-4000 SYSTEM. If you touch EXIT activated on the display, the mode will return to higher pre-

mode. And in case of pushing input KEY Home, the mode will return to home mode immediately.

Page 10: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 10 -

MAIN MENU

CURRENT MENU ROUTE AND EXIT TIME INDICATION

☞ In the bottom of the screen, the whole route and exit time of current menu are displayed.

☞ In case of exceeding menu exit time, Home menu will return. (SET TIME: 60 seconds)

1. VIEW ALARM LIST

Alarm list of BDS-4000 SYSTEM can be checked and deleted in this mode.

VIEW ALARMS LIST MENU

1.1. FIRE ALARM LIST Fire alarm list can be checked.

☞ ALARM TYPE: FIRE ALARM, FIRE PRE-ALARM

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FIRE ALARMS LIST

ALARM NO: 1/50

ALARM TYPE: FIRE ALARM

TIME : 01-01-2010 AM 01:01

LOOP NO.: 1 ZONE NO.: 1

DEVICE NO.& TYPE: 1 SMOKE DETECTOR

ROCATION: NAVI DECK

EXIT PREV NEXT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

MAIN MENU

1. VIEW ALARMS LIST

2. DISABLEMENT

3. SYSTEM CHECK

4. SYSTEM SETTING

5. SYSTEM CONFIGURATION

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

VIEW ALARMS LIST

1. FIRE ALARMS LIST

2. DELETE ALL FIRE ALARMS LIST

3. FAULT ALARMS LIST

4. DELETE ALL FAULT ALARMS LIST

EXIT

Page 11: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 11 -

1.2. DELETE ALL FIRE ALARM LIST (ACCESS LEVEL3) Every fire alarm list can be deleted, and therefore initialized.

1.3. FAULT ALARMS LIST SYSTEM FAULT ALARM LIST can be checked.

1.4. DELETE ALL FAULT ALARMS LIST (ACCESS LEVEL3) Every FAULT ALARM LIST can be deleted, and therefore initialized.

2. DISABLEMENT (ACCESS LEVEL3) DISABLEMENT MENU

2.1. SET DISABLEMENT This mode is used to set up disablement function of loop, zone & device.

SET DISABLEMENT MENU

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FAULT ALARMS LIST

ALARM NO: 1/50 ALARM TYPE: LOOP FAULT

TIME : 01-01-2010 AM 01:01

EXIT PREV NEXT

ALARM REPORT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

DISABLEMENT

1. SET DISABLEMENT

2. DELETE DISABLEMENT

3. SET WORKSHOP TIME UNIT

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET DISABLEMENT

1. DEVICES

2. LOOPS

3. ZONES

4. EXTERNAL OUTPUTS

5. SET DISABLEMENT TIME

EXIT

Page 12: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 12 -

2.1.1. DEVICES

☞ If you choose the loop where the device you want to select is loaded after current enabled

loop is activated,, you can enter SET DEVICE DISABLEMENT MODE

▼( 01 )

☞ UP DOWN : Devices loaded in the pertinent loop can be selected.

☞ STATE DISABLE : “ENABLE” or “DISABLE” can selected.

☞ SAVE : Revised facts can be saved.

2.1.2. LOOPS

☞ SAVE : 선택된 LOOPS의 DISABLEMENT설정 저장

☞ If you touch SAVE after selecting current activated loops, revised facts will be saved

and the mode will return to pre-mode.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET LOOPS DISABLEMENT SELELCT LOOP

01 02 03 04 05 06

07 08 09 10 11 12

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET DEVICES DISABLEMENT SELELCT LOOP

01 02 03 04 05 06

07 08 09 10 11 12

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET DEVICES DISABLEMENT

LOOP: 1

ZONE NO.: 1

DEVICE NO: 1 UP DOWN

DEVICE TYPE: SMOKE DETECTOR

STATE: DISABLE

EXIT SAVE

Page 13: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 13 -

2.1.3. ZONES

☞ If you touch SAVE after touching zone to be selected and choosing either ENABLE or

DISABLE, revised facts will be saved.

UP DOWN : Up to maximum 100 ZONES can be set up through moving to other pages.

2.1.4. EXTERNAL OUTPUTS

☞ The disablement function of each RELAY OUTPUT CHANNEL of INTERFACE PCB can

be set up or canceled.

☞ If you touch SAVE after selecting either ENABLE or DISABLE for output to be set up,

revised facts will be saved.

2.1.5. SET DISABLEMENT TIME

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET ZONES DISABLEMENT

SELELCT ZONE PAGE

ZONE 1: Enable ZONE 6: Enable UP

ZONE 2: Enable ZONE 7: Enable DOWN

ZONE 3: Enable ZONE 8: Enable

ZONE 4: Enable ZONE 9: Enable

ZONE 5: Enable ZONE 10: Enable

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET DISABLEMENT TIME

START TIME: 01-01-2010 00 : 01

END TIME: 01-01-2010 00 : 10

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET OUTPUTS DISABLEMENT

SELELCT RELAY

1 2 3 4

5 6 7 8

EXIT SAVE

Page 14: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 14 -

☞ If you touch SAVE after setting up start time & end time, revised time will be saved

and the mode will return to pre-mode. If a set disablement time is not set up,

disablement function will be proceeding until manual cancellation.

2.2. DELETE DISABLEMENT You can remove the pertinent list when selected disablement list is indicated

☞ REMOVE : Each item set up for disablement can be canceled

2.3. SET WORKSHOP TIME UNIT This mode is used to set up devices which can be connected with function of workshop

time.

SET WORKSHOP TIME UNIT

▼( 01 )

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

DELETE DISABLEMENT

LOOPS 1 REMOVE

ZONES 1 REMOVE

DEVICES 1 REMOVE

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET WORKSHOP TIME UNIT SELELCT LOOP

01 02 03 04 05 06

07 08 09 10 11 12

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET WORKSHOP TIME UNIT

LOOP: 1

ZONE NO.: 1

DEVICE NO: 1 UP DOWN

DEVICE TYPE: SMOKE DETECTOR

STATE: LOAD

EXIT SAVE

Page 15: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 15 -

☞ UP DOWN : Devices to be set up can be selected.

☞ STATE: LOAD : You can choose whether WORKSHOP TIMMER will be set up

☞ SAVE : Revised facts is saved.

3. SYSTEM CHECK This mode is used to check whether BDS-4000 SYSTEM is normally operated.

SYSTEM CHECK MENU

3.1. KEY & LED TEST When this mode is entered, the whole LEDs are lighted up. If you push the key for test, internal

buzzer will beep and the mark of key will be displayed on the LCD.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

KEY & LED TEST

PRESS KEY TO TEST

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SYSTEM CHECK

1. KEY & LED TEST

2. SIMULATE FIRE

3. TEST MODE

EXIT

Page 16: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 16 -

3.2. SIMULATE FIRE (ACCESS LEVEL3) This mode is used to perform a test for fire simulation. Through designating a detector to be

tested, simulated fire can take place intentionally and the operation of every output connected

with the designated detector will be processing like the state of real fire

☞ If you choose the loop where the device you select is loaded when current enabled loop is

activated, you can enter SET SIMULATE FIRE MODE.

▼( 01 )

☞ UP DOWN : devices loaded in the pertinent loop can be selected.

☞ STATE DISABLE : either “ENABLE” or “DISABLE” can be selected

☞ EXIT : This is used to return to pre-mode without saving revised facts.

☞ SAVE : This is used to save the setting for SIMULATE FIRE and proceed to setting up

next devices.

☞ In case of returning to home mode, the function of simulation fire for set devices will be

performed.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SIMULATE FIRE SELELCT LOOP

01 02 03 04 05 06

07 08 09 10 11 12

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET SIMULATE FIRE

LOOP: 1

ZONE NO.: 1

DEVICE NO: 1 UP DOWN

DEVICE TYPE: SMOKE DETECTOR

STATE: DISABLE

EXIT SAVE

Page 17: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 17 -

* FIRE ALARM EXAMPLE

▼( ACK )

☞ LIST : This is used to check generated firm alarm lists.

☞ RESET : this is used to reset generated fire alarm and setting value of simulation fire.

3.3. TEST MODE (ACCESS LEVEL3) This mode is used to test the system. (TEST MODE LED ON)

Each alarm is displayed, but relay output is not operated.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FIRE ALARM

ALARM NO: 1/1

ALARM TYPE: FIRE ALARM 64

TIME : 01-01-2010 AM 01:01

LOOP NO.: 1 ZONE NO.: 1

DEVICE NO.& TYPE: 1 SMOKE DETECTOR

DISCRIPTION:

ACT

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

FIRE ALARM = 1 LIST RESET

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

TEST MODE

SELELCT ZONE PAGE

ZONE 1: Disable ZONE 6: Disable UP

ZONE 2: Disable ZONE 7: Disable DOWN

ZONE 3: Disable ZONE 8: Disable

ZONE 4: Disable ZONE 9: Disable

ZONE 5: Disable ZONE 10: Disable

EXIT SAVE

Page 18: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 18 -

☞ If you touch SAVE after touching zone to be set up and choosing either ENABLE or DISABLE,

revised facts will be saved. A test function for enabled zone will be processing.

UP DOWN : Up to maximum 100 ZONES can be set up through moving to other pages.

4. SYSTEM SETTING This mode is used to set up time setting and security number according to each access level.

SYSTEM SETTING

4.1. SET TIME (ACCESS LEVEL2) This mode is used to set up time.

4.2. SET ALARM DELAY TIME (ACCESS LEVEL3)

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SYSTEM SETTING

1. SET TIME

2. SET ALARM DELAY TIME

3. SET SECURITY NUMBER

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET TIME

01 – 01 – 2010 01 : 01 : 01

MM – DD – YYYY hh : mm : ss

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET ALARM DELAY TIME

00 MINUTE

UP DOWN

EXIT SAVE

Page 19: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 19 -

In case of fire, external output will be delayed, but fire state continues to remain and every

fire function including external output will be proceeding during delay time set up in this

mode. A basic value is 0 and increases at intervals of 1 minute. And it is possible to set up

up to maximum 10 minutes.

4.3. SET SECURITY NUMBER This mode is used to resister security number according to security rank,

4.3.1. ACCESS LEVEL2 (ACCESS LEVEL2) Security number corresponding to ACCESS LEVEL2 can be changed.

When goods are delivered, setting number: 2222

4.3.2. ACCESS LEVEL3 (ACCESS LEVEL3) Security number corresponding to ACCESS LEVEL3 can be changed.

When goods are delivered, setting number: 3333

4.3.3. ACCESS LEVEL4 (ACCESS LEVEL4) Security number corresponding to ACCESS LEVEL4 can be changed.

When goods are delivered, setting number: 3333

5. SYSTEM CONFIGRATION This mode is used to set up loop, zone, devices and related unit and system upgrade.

SYSTEM CONFIGRATION

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET SECURITY NUMBER

ACCESS LEVEL2

ACCESS LEVEL3

ACCESS LEVEL4

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SYSTEM CONFIGURATION

1. LOOPS CONFIGURATION

2. ZONES CONFIGURATION

3. EXTERNAL OUTPUTS CONFIGURATION

4. UNITS CONFIGURATION

5. SYSTEM INTERFACE

EXIT

Page 20: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 20 -

5.1. LOOPS CONFIGRATION (ACCESS LEVEL3) LOOPS CONFIGRATION

5.1.1. ADDRESSABLE LOOPS This mode is used to set up addressable loop.

5.1.1.1. SET LOOPS This mode is used to set up whether loops are applied

☞ If you touch SAVE after activating loops set up for “ENABLE”, the mode will return to

pre-mode.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET LOOPS SELELCT LOOP

01 02 03 04 05 06

07 08 09 10 11 12

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

LOOPS CONFIGURATION

1. ADDRESSABLE LOOPS

2. CONVENTIONAL LOOPS

3. EXTERNAL SERIAL LOOP

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

ADDRESSABLE LOOPS

1. SET LOOPS

2. AUTO LOAD

3. ADD DEVICE

4. VIEW DEVICE

EXIT

Page 21: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 21 -

5.1.1.2. AUTO LOAD Devices connected with a selected loop are automatically loaded.

☞ if pertinent LOOP : START is performed when enabled loops are activated in loop

configuration, function for AUTO LOAD will be processing.

5.1.1.3. ADD DEVICE A device is loaded into selected loop by manual.

☞ SELECT DEVICE UP DOWN : select devices not loaded in the pertinent loop.

☞ DEVICE TYPE UP DOWN : select the type of a chosen device.

If you touch SAVE, value of the pertinent device will be saved and then other devices can be set

up.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

AUTO LOAD

LOOP 1 : START LOOP 7 : DISABLE

LOOP 2 : START LOOP 8 : DISABLE

LOOP 3 : START LOOP 9 : DISABLE

LOOP 4 : START LOOP10 : DISABLE

LOOP 5 : DISABLE LOOP11 : DISABLE

LOOP 6 : DISABLE LOOP12 : DISABLE

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

ADD DEVICE

LOOP: 1

SELECT DEVICE UP DOWN

DEVICE ID: 1

DEVICE TYPE: UP DOWN

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

ADD DEVICE SELELCT LOOP

01 02 03 04 05 06

07 08 09 10 11 12

EXIT SAVE

Page 22: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 22 -

5.1.1.4. VIEW DEVICE This mode is used to see information regarding an selected device.

☞ If you select the loop when current enabled loops are activated, you will enter DEVICE VIEW

MODE.

▼( LOOP1 : VIEW )

☞ ZONE NO UP DOWN : can select a zone.

☞ DEVICE NO UP DOWN : can select a device.

☞ SET RELAY UP DOWN : can select CHANNEL of EXTERNAL RELAY OUTPUT connected with

the pertinent device and can be set up in case of touching SET.

☞ DESCRIPTION: can set up description of the pertinent device. .

☞ SAVE : If you touch SAVE, value of the pertinent device will be saved and then other devices

can be set up.

5.1.2. CONVENTIONAL LOOPS This mode is used to set up CONVENTIONAL LOOPS

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET CONVENTIONAL LOOPS

LOOP NO: 1 ENABLE

DISCRIPTION:

EXIT PREV NEXT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

VIEW DEVICE

LOOP 1 : VIEW LOOP 7 : DISABLE

LOOP 2 : VIEW LOOP 8 : DISABLE

LOOP 3 : VIEW LOOP 9 : DISABLE

LOOP 4 : VIEW LOOP10 : DISABLE

LOOP 5 : DISABLE LOOP11 : DISABLE

LOOP 6 : DISABLE LOOP12 : DISABLE

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

VIEW DEVICE

LOOP: 1

ZONE NO: 1 UP DOWN

DEVICE ID : 1 UP DOWN

DEVICE TYPE: SMOKE DETECTOR ( 24 )

SET RELAY : 1 UP DOWN SET

DESCRIPTION:

EXIT SAVE

Page 23: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 23 -

☞ ENABLE : can set up whether loop are used.

☞ DESCRIPTION : can set up description of the pertinent loop.

☞ PREV NEXT : can move to loops, which can be selected.. (Maximum 32 LOOPS)

☞ If you touch SAVE, value of the pertinent loop will be saved and then other loops can be

set up.

5.2. ZONES CONFIGURATION (ACCESS LEVEL3) This mode is used to set up and edit whether a zone is used.

☞ If you select a zone, you will enter the mode to set up the selected zone.

☞ UP DOWN : Up to maximum 100 ZONES can be set up through moving to other pages.

▼(ZONE1)

☞ SELECT LOOP UP DOWN : can select loops connected with a device to be setup.

☞ ADD DEVICE UP DOWN ADD : can select and add devices which are supposed to be loaded

in a zone

☞ DELETE DEVICE UP DOWN DEL : can select and delete the devices loaded in a zone.

☞ SET RELAY OUT UP DOWN SET : can select the channel of external relay connected with a

zone.

☞ DISCRIPTION: : can set up the description of a zone.

☞ SAVE :If you touch SAVE, setting value of the pertinent zone will be saved and the

mode will return to pre-mode.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

ZONES EDIT

SELECT ZONE DEVICE SELECT ZONE DEVICE PAGE

ZONE 1 : 12 ZONE 6 : 0 UP

ZONE 2 : 17 ZONE 7 : 0 DOWN

ZONE 3 : 10 ZONE 8 : 0

ZONE 4 : 11 ZONE 9 : 0

ZONE 5 : 0 ZONE10 : 0

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

EDIT ZONE1

LOAD DEVICE NO: 0

SELECT LOOP: UP DOWN

ADD DEVICE: UP DOWN ADD

DELETE DEVICE: UP DOWN DEL

SET RELAY OUT: UP DOWN SET

DISCRIPTION:

EXIT SAVE

Page 24: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 24 -

5.3. EXTERNAL OUTPUT CONFIGRATION (ACCESS LEVEL3) EXTERNAL OUTPUT CONFIGRATION

5.3.1. SET RELAY BOARDS This mode is used to set up whether PROGRAMMABLE RELAY BOARDS are used.

☞ it is possible to be extended up to maximum 16 relay boards and they can be activated through

selecting ENABLE RELAY BOARDS.

☞ If you touch SAVE, the mode will return to pre-mode.

5.3.2. EDIT RELAY OUTPUTS This mode is to decide each Relay Output qualities of Programmable Relay Boards.

▼(RELAY BOARD 01 )

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

EXTERNAL OUTPUT

1. SET RELAY BOARDS

2. EXTERNAL OUTPUTS

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET RELAY BOARDS

SELELCT EXTERNAL RELAY BOARDS

01 02 03 04 05 06 07 08

09 10 11 12 13 14 15 16

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

EDIT RELAY OUTPUTS

SELELCT EXTERNAL RELAY BOARDS

01 02 03 04 05 06 07 08

09 10 11 12 13 14 15 16

EXIT

Page 25: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 25 -

▼(RELAY NO.1 )

☞ LOAD DEVICE : Select the device to set up.

☞ TYPE FIRE PRE ALARM WARNING FAULT : Select the Alarm Type of the device to load.

☞ OPTION ACK MUTE GA MORSE : Specify the quality of output when the relevant alarm occurs.

☞ DELAY TIME UP DOWN : Select the delay time for the Relay Output.

☞ DISCRIPTION: : Set up the Reply Output Description.

☞ Touching SAVE saves the setting value of relevant Replay Output and return to the pre-

mode.

5.3.3 EXTERNAL OUTPUTS This mode is used to set up standard output of BDS-4000 SYSTEM.

☞ If you touch SAVE after being set up, setting value will be saved and then the mode will

return to pre-mode.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

EXTERNAL OUTPUTS

SOUNDER1 OUTPUT ENABLE

DOOR1 HOLDER OUTPUT ENABLE

DOOR2 HOLDER OUTPUT ENABLE

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

EDIT RELAY OUTPUTS

SELELCT EXTERNAL RELAY

NO 1 :

NO 2 :

NO 3 :

NO 4 :

EXIT UP DOWN

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

EDIT RELAY OUTPUTS

RELAY BOARD #1 (1)

LOAD DEVICE : 0

TYPE : FIRE PRE ALARM WARNING FAULT

OPTION : ACK MUTE GA MORSE

DELAY TIME : 00 min UP DOWN

DISCRIPTION:

EXIT SAVE

Page 26: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 26 -

5.4. UNITS CONFIGRATION (ACCESS LEVEL3) UNITS CONFIGRATION

5.4.1. REPEATER This mode is used to set up the repeater of BDS-4000 SYSTEM

☞ If you touch SAVE after you select connected repeater number, the pertinent repeater will be

connected.

☞ it is possible to be extended up to maximum 4 repeaters

5.4.2. INTERFACE This mode is used to set up the interface connected with BDS-4000 SYSTEM.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

UNITS CONFIGUATION

1. REPEATER

2. INTERFACE

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

REPEATER UNITS

SELELCT REPEATER UNIT

01 02 03 04

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

INTERFACE UNITS

SELELCT INTERFACE UNIT

01 02 03 04

EXIT SAVE

Page 27: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 27 -

☞ If you touch SAVE after you select connected interface number, the pertinent interface will be

connected.

☞ it is possible to be extended up to maximum 4 interface.

5.5. SYSTEM INTERFACE (ACCESS LEVEL3) SYSTEM INTERFACE

5.5.1. UPGRADE FROM USB This mode is used to upgrade system software through using USB memory device.

☞ if you touch START UPGRADE, system software will be upgraded into version-up program.

5.5.2. TCP-IP LAN

It is feasible for BDS-4000 to communicate with remote PC through built-in TCP-IP

LAN port. This mode is used to set up whether this function is applied.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

UPGRADE FROM USB

START UPGRADE

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

TCP-IP LAN

ENABLE

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SYSTEM INTERFACE

1. UPGRADE FROM USB

2. TCP-IP LAN

3. SET INTERFACE

EXIT

Page 28: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 28 -

☞ If you touch SAVE after you select whether TCP-IP LAN PORT is applied, the TCP-IP LAN

PORT will be connected.

5.5.3. SET INTERFACE

SET INTERFACE

☞ If you touch SAVE after selecting and using one of 4 modes and then the pertinent mode is

activated, selected modes will be set up.

◈ REPEATER PANEL 1. Operation menu

1.1. Start

* NORMAL HOME MENU STATE

INITIALIZE

PLEASE WAIT

BDS-4000 REPEATER Ver. 0.10

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET INTERFACE

1. VDR

2. AMS

3. BI PC SOFTWARE

4. PRINTER

EXIT SAVE

Page 29: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 29 -

1.2. Alarm This mode is used to display alarm state occurring in a main panel.

* FIRE ALARM EXAMPLE

▼(ACK)

* NORMAL HOME MENU STATE

BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)

FIRE ALARM

ALARM NO: 1/1

ALARM TYPE: FIRE ALARM 64

TIME : 01-01-2010 AM 01:01

LOOP NO.: 1 ZONE NO.: 1

DEVICE NO.& TYPE: 1 SMOKE DETECTOR

DISCRIPTION:

ACT

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)

BI FIRE DETECTION SYSTEM

MENU

BI INDUSTRIAL Co., Ltd www.b-i.co.kr

Page 30: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 30 -

2. Menu construction 2.1. Menu flowchart

1. VIEW ALARMS LIST

1.1 FIRE ALARMS LIST

1.2 DELETE ALL FIRE ALARMS LIST

1.3 FAULT ALARMS LIST

1.4 DELETE ALL FAULT ALARMS LIST

2. KEY & LED TEST

3. SET TIME

4. UPGRADE FROM USB

2.2 MENU INFORMATION

MENU activated in Home mode should be touched or input key MENU should be pushed in order to

enter menu mode. If you should select and touch a window activated in the pertinent mode in order to

enter or set up lower mode, designated operation will be processing.

If you touch EXIT activated on the display, the mode will return to higher pre-mode. And in case of

pushing input KEY Home, the mode will return to home mode immediately.

MAIN MENU

1. VIEW ALARMS LIST

This mode is used to check or delete the alarm list of BDS-4000 SYSTEM.

BDS-4000 REPEATER 01-01-2010 AM 07:32:01 (FRI)

MAIN MENU

1. VIEW ALARMS LIST

2. KEY & LED TEST

3. SET TIME

4. UPGRADE FROM USB

EXIT

Page 31: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 31 -

VIEW ALARMS LIST MENU

1.1. FIRE ALARMS LIST A fire alarm list can be checked.

☞ ALARM TYPE: FIRE ALARM, FIRE PRE-ALARM

1.2. DELETE ALL FIRE ALARMS LIST This mode is used to be initialized through deleting every fire alarm list.

1.3. FAULT ALARMS LIST A system fault alarm list can checked.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FIRE ALARMS LIST

ALARM NO: 1/50

ALARM TYPE: FIRE ALARM

TIME : 01-01-2010 AM 01:01

LOOP NO.: 1 ZONE NO.: 1

DEVICE NO.& TYPE: 1 SMOKE DETECTOR

ROCATION: NAVI DECK

EXIT PREV NEXT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

FAULT ALARMS LIST

ALARM NO: 1/50 ALARM TYPE: LOOP FAULT

TIME : 01-01-2010 AM 01:01

EXIT PREV NEXT

ALARM REPORT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

VIEW ALARMS LIST

1. FIRE ALARMS LIST

2. DELETE ALL FIRE ALARMS LIST

3. FAULT ALARMS LIST

4. DELETE ALL FAULT ALARMS LIST

EXIT

Page 32: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BDS-4000 Software Procedure - 32 -

1.4. DELETE ALL FAULT ALARMS LIST This mode is used to be initialized through deleting every fault alarm list.

2. KEY & LED TEST When this mode is entered, the whole LEDs are lighted up. If you push the key for a test, internal

buzzer will beep and the mark of a pertinent key will be displayed on the LCD.

3. SET TIME This mode is used to set up time.

4. UPGRADE FROM USB This mode is used to upgrade system software through using USB memory device.

☞ if you touch START UPGRADE, system software will be upgraded into version-up program.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

KEY & LED TEST

PRESS KEY TO TEST

EXIT

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

SET TIME

01 – 01 – 2010 01 : 01 : 01

MM – DD – YYYY hh : mm : ss

EXIT SAVE

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

UPGRADE FROM USB

START UPGRADE

EXIT

Page 33: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

BI Fire Detection System(BDS-4000) Trouble shooting 1. Menu flowchart

1. VIEW ALARMS LIST

1.1 FIRE ALARMS LIST

1.2 DELETE ALL FIRE ALARMS LIST

1.3 FAULT ALARMS LIST

1.4 DELETE ALL FAULT ALARMS LIST

2. DISABLEMENT

2.1 SET DISABLEMENT

2.1.1 LOOPS

2.1.2 ZONES

2.1.3 DEVICE

2.1.4 EXTERNAL OUTPUTS

2.1.5 SET DISABLEMENT TIME

2.1.6 ALARM DELAY TIME

2.2 SET WORKSHOP TIME UNIT

2.3 DISABLEMENT LIST & EDIT

3. SYSTEM CHECK

3.1 KEY & LED TEST

3.2 SIMULATE FIRE

3.3 TEST MODE

4. SYSTEM SETTING

4.1 SET TIME

4.2 SET ALARM DELAY TIME

4.3 SET SECURITY NUMBER

4.3.1 ACCESS LEVEL2

4.3.2 ACCESS LEVEL3

4.3.3 ACCESS LEVEL4

4.4 SET SENSITIVITY

5. SYSTEM CONFIGURATION

5.1 LOOPS CONFIGURATION

5.1.1 ADDRESSABLE LOOPS

5.1.1.1 SET LOOPS

5.1.1.2 AUTO LOAD

5.1.1.3 ADD DEVICE

5.1.1.4 VIEW DEVICE

5.1.2 CONVENTIONAL LOOPS

5.1.3 EXTERNAL SERIAL LOOP

5.2 ZONES CONFIGURATION

5.3 EXTERNAL OUTPUTS CONFIGURATION

5.3.1 SET RELAY BOARDS

5.3.2 EDIT RELAY OUTPUTS

5.3.3 EXTERNAL OUTPUTS

5.3.4 EDIT FIRE FIGHTING OUTPUTS

5.4 UNITS CONFIGURATION

5.4.1 REPEATER

5.4.2 INTERFACE

5.5 SYSTEM INTERFACE

5.5.1 UPGRADE FROM USB

5.5.2 SET INTERFACE

2. Password ACCESS LEVEL2 : 2222 ENTER

ACCESS LEVEL3 : 3333 ENTER

ACCESS LEVEL4 : 4444 ENTER

3. Main Panel ~ Detector communication check a. Menu touch => Menu flowchart “5.1.14 VIEW DEVICE” Menu Touch

b. Select Loop Touch

C. Analogue data : Main panel ~ Detector communication data. (Reference chart)

Analogue data

Detector Fault Contamination Normal

Pre-

Alarm Fire

Smoke 0 1~5 6~47 48~63 64~127

Heat 0 1~5 6~47 48~63 64~127

Callpoint 0 - 20 - 64~127

Flame 0 - 20 - 64~127

Timer 0 - 20 - 64

(operating)

d. All detector Analogue data check.

* Smoke or Heat detector

☞ Smoke detector analogue data : 35 more than => Detector clean (Make advise)

☞ 10. Smoke / Heat detector clean reference.

☞ Contamination fault alarm(1~5) => changed Smoke or Heat detector.

☞ Device fault alarm(0) => 9. Smoke or heat detector fault alarm reference.

BDS-4000 Ver 1.0 01-01-2010 AM 07:32:01 (FRI)

VIEW DEVICE

LOOP: 1

ZONE NO: 1

DEVICE ID : 1 UP DOWN

DEVICE TYPE: OPTICAL SMOKE DETECTOR ( 24 )

SET RELAY : 1

DESCRIPTION:

EXIT SAVE

Analogue data

Page 34: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

4. Loop / Zone / Device Disablement setting a. Loop disablement : Select loop all detector => no operating.

☞ Menu touch => Menu flowchart : “2.1.1 LOOPS” Menu Touch

☞ Select Loop touch => SAVE => Disablement LED : ON =>

Main panel display : Disablement list : 1

☞ Remove : “2.3 Disablement list & edit” touch => “Remove “ touch

b. Zone disablement : Select zone all detector => no operating.

☞ Menu touch => Menu flowchart : “2.1.2 ZONES” Menu Touch

☞ Select Zone touch => “zone ○○ : Enable” touch => SAVE =>

Disablement LED : ON => Main panel display : Disablement list : 1

☞ Remove : “2.3 Disablement list & edit” touch => “Remove “ touch

c. Device disablement : Select device => Detector no operating.

☞ Menu touch => Menu flowchart : “2.1.3 DEVICES” Menu Touch

☞ Select Loop touch => DEVICE ID : UP / DOWN touch => select address no display =>

“STATE : ENABLE” one touch => SAVE => Disablement LED : ON =>

Main panel display : Disablement list : 1

☞ Remove : “2.3 Disablement list & edit” touch => “Remove “ touch

5. Loop Short alarm Check a. Loop Analogue data check

☞ “3. Main~Detector communication check” reference.

b. Loop Short area : Line isolator LED ON.(address list reference)

c. Interface panel : power off

d. Isolator ~ Isolator : Loop line check.

☞ Loop line : Normal

☞ Interface panel : power on

☞ “3. Main~Detector communication check” reference.

e. Loop line : Normal, Main panel display : short alarm

☞ Interface panel : loop cable open => Loop connector : DC 20~27V check.

☞ No voltage : Maker contact.(Loop card or Loop base board : correct)

6. Loop Open alarm Check a. Loop Analogue data check

☞ “3. Main~Detector communication check” reference.

b. Device fault reporting. (address list reference)

c. Interface panel : power off.

d. Isolator ~ Isolator : Loop line check.

☞ Loop line : Normal

☞ Interface panel : power on

☞ “3. Main~Detector communication check” reference.

e. Loop line : Normal, Main panel display : open alarm

☞ Interface panel : loop cable open => Loop connector : DC 20~27V check.

☞ No voltage : Maker contact.

7. Main or Em’cy power fault alarm Check

(Interface panel inside photo)

① : Main power(AC_L, AC_N), Em’cy power(AC_L, AC_N)

☞ Main / Em’cy AC 220V check

☞ ③, ④ : Main / Em’cy power fuse(5A) check

② : Auto change AC power : 220V check

☞ ⑤ : Auto change AC power fuse(5A) check

* ① : Main / Em’cy power : AC 220V => OK => ② : No power => Maker contact.

8. Battery fault alarm Check a. All power : off

☞ Internal cable check.=>Red cable:One by One check.

=>Blue cable : One by one check.

b. Battery Voltage Check photo : DC 22~26.5V(Normal)

① ②

Page 35: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

c. Interface PCB Short Check

☞ All power : off

☞ +BAT, -BAT Internal cable : open ☞ Battery input connector : +BAT, -BAT short check

☞ Fuse : open

☞ Battery input connector :-BAT, fuse short check

9. Smoke or Heat Detector fault alarm a. Interface panel : power off

b. Smoke / Heat detector head : left rotation => Loop line : Rubber cutting => re-connection

(polarity caution => L2:+, L1:-)

c. Loop Analogue data check

☞ “3. Main~Detector communication check” reference.

☞ Analogue data : 0 => Detector Voltage check : DC 20~27V => Voltage Ok

=>Smoke / Heat Detector : change

10. Smoke / Heat Detector clean a. Smoke or Heat detector head ~ detector base devide : detector head Left .

[ Smoke detector front] [ Smoke detector bottom]

b. bolt : “+” drive use => Devide detector head cover.

RUBBER CUTTING

Page 36: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

c. Cap left rotation. => Devide cap and sensor

d. Cap + sensor : clean.

e. a~d : inverse

11. Flame detector check a. Sensivity control

① Control Resistor

☞ Left Rotation : Sensivity Low, Right Rotation : Sensivity Fast

② Dip switch => 0 : Sensivity Fast => 3 : Sensivity Low

b. Fault alarm

☞ +, - cable check => DC 20~27V => Voltage Ok => PCB : change(Address setting caution)

12. Call point check a. Fault alarm

☞ +, - cable check => DC 20~27V => Voltage Ok => PCB : change(Address setting caution)

13. Workshop Timer check a. Main panel workshop timer setting check.

☞ Menu touch => Menu flowchart “2.2 SET WORKSHOP TIME UNIT” Menu touch =>

Select loop touch => Device ID : UP touch(Workshop location detector move) =>

“STATE : UNLOAD” touch => “STATE : LOAD” change => Save touch.

(Caution : workshop timer => “STATE : UNLOAD” setting)

b. Workshop Time unit check

① : “MODE 1” check

② : “Min” check

c. Device fault check.

☞ Workshop time unit open => Loop “+”, “-“ cable check DC 20~27V => Voltage Ok

=> PCB : change(Address setting caution)

cap Sensor

cap

Page 37: B-I Fire Detection System User Manual (Eng.).pdf1.1. fire alarm list fire alarm list can be checked. ☞ alarm type: fire alarm, fire pre-alarm bds-4000 ver 1.0 01-01-2010 am 07:32:01

14. Earth fault check a. Loop Analogue data check

☞ “3. Main~Detector communication check” reference.

☞ Analogue data & Detector type : Different => Make contact

(Analogue data photo : Make send)

☞ Analogue data & Detector type : Normal => Interface panel open => Interface PCB

Bolt open(blue line reference) => PCB ~ support : Gap => PCB ~ support : Insulation.

=> Bolt : No insert.

☞ Main panel : Earth fault alarm Reset. => Normal display => Make contact.

15. Main / Repeat panel CPU change method

16. Interface panel inside photo

(Interface panel inside photo)

(Main panel inside photo)

a. Lock : left / right push => CPU remove.(①~② reference)

b. CPU insert : “a” inverse

CPU

① ①

DC24V SWITCH LOOP CARD BATTERY

FUSE(5A)

Loop1 Loop2 Loop3 Loop4

Loop base

board