    EST2

    Submittal Guide

    EST2 Life Safety SystemNetworkable control with voice audio for medium sized applications

    E S T B R A N D L I F E S A F E T Y & C O M M U N I C A T I O N S F R O M E D W A R D SSe e w h a t ' s p o s s i b l e n o

    w . ..

  • Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    Project: ___________________________

    Contact: ___________________________

    Date: ___________________________

    Thank you for giving us the opportunity to provide this submittal for an EST2

    Life Safety System. EST2 combines intelligent detection with technologically

    advanced networking and audio capabilities. Together these innovations offer

    unsurpassed stability, reliability, and flexibility.

    This guide provides a summary of these innovations and includes a

    comprehensive presentation of related system components and devices.

    Products we are submitting for your consideration are indicated by a

    checkmark in the margins of the pages that follow.

    More detailed information can be found in individual data sheets dedicated

    to each product. All these sheets, along with guide specifications and other

    useful product information, are available electronically on our LifeLines

    CD-ROM. This exhaustive collection of life safety related literature is fully

    searchable and includes a utility for printing multiple data sheets.

    Thank you for giving us the opportunity to provide this submittal. Please do

    not hesitate to contact us should you require further information.

    _____________________________

  • Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    vii

    Submittal Guide

    EST2 Life Safety SystemNetworkable control with voice audio for medium sized applications

  • EST2 Submittal GuideNetworkable control with voice audio for medium sized applications

    Copyright 2010 UTC Fire and Security All rights reserved.

    8985 Town Center Parkway, Bradenton, FL 34202

    85005-0105, Issue 7.1

    Wiring diagrams provided herein are for information and reference only and are not to be used for installation pur-poses. Consult the appropriate installation documents for wiring and configuration details.

    This guidebook is for information only and is not intended as a substitute for verbatim legislated requirements. For authoritative specifications regarding the application of life safety, security, and access control systems, consult

    current editions of applicable codes and standards. For authoritative interpretation of those codes and standards, consult your local authority having jurisdiction.

    While every effort has been made to ensure the accuracy and completeness of this guidebook, the authors and publishers assume no responsibility for errors, inaccuracies, omissions, or any inconsistencies herein.

    EST, QuickStart, Genesis Series, and Signature Series are trademarks of UTC Fire and Security.

    Also from Edwards:

    85001-0541: Handbook of Visual Notification Appliances for Fire Alarm ApplicationsA practical guide to regulatory compliance

    85001-0542: Glossary of Fire Alarm and Security TerminologyA desk reference for life safety and security professionals

    85001-0582: Remote Booster Power Supply Application GuideA summary of typical wiring and configuration for everyday and advanced applications

    85010-0139: Installers Wire GuideA concise pocket reference to wire and cable requirements for Edwards products and systems

    85005-0132: iO Series Submittal GuideIntelligent fire alarm solutions for small buildings

    85005-0115 QuickStart Submittal GuideIntelligent/conventional life safety for small to mid-sized applications

    85010-0099: EST3 Submittal GuideIntelligent control for large and medium sized applications

  • Intelligent Analog Initiating Devices 17Smoke Detectors ........................................................... 18Detector Bases ............................................................. 19Duct Detectors ............................................................... 20Input/Output Modules ................................................... 20Input/Output Motherboards ............................................ 24Releasing Module ........................................................... 25Pull Stations .................................................................. 26Intelligent Audio Amplifiers .............................................. 27Intelligent Power Supplies ............................................... 27Accessories ................................................................... 28

    Notification Appliances 31Wall Horns, Strobes and Chimes .................................... 33Wall Speakers and Speaker/strobes ............................... 34Signal Master ................................................................. 35Ceiling Horns, Speakers and Strobes ............................. 35Harsh Environment Signals ............................................. 36Audible Signals ............................................................... 37Audio System ................................................................. 38Firefighers Telephones ................................................... 39Bell Strobe Plates ........................................................... 40Mounting Accessories ................................................... 40

    Hazardous Location Devices 41Hazardous Classifications ............................................... 41Weather/Explosion Proof Heat Detectors ........................ 42Hazardous Location Fire Alarm Station ........................... 42Hazardous Location Strobes, Bells and Horns ................ 43

    Door Holders & Relays 44Door Holders .................................................................. 44Relays ............................................................................ 44SPDT Relays .................................................................. 45

    Index 46

    EST2 Analog 1System configuration ........................................................ 2Main control and display ................................................... 5Audio components ........................................................... 6Power supplies ................................................................. 8Display and remote annunciation .................................... 10Communciations ............................................................ 14Accessories .................................................................... 15Wallboxes and cabinets .................................................. 16

    ix

    A lot can be said about EST2, but when it comes

    to performance, price, installation ease and flex-

    ibility, this remarkable life safety system speaks for

    itself.

    Until EST2, only large and costly installa-

    tions could deliver the features and the power built

    into each one of these incredibly flexible systems.

    Now, with dual channel audio and network capac-

    ity for up to 960 intelligent detectors and almost an

    equal number of modules, EST2 has the muscle to

    handle 90 per cent of all life safety applications

    and the flexibility to make it a perfect match for any

    mid-range retrofit.

    And when it comes to connected devices,

    nothing beats EST2. In fact, the Signature Series

    line of intelligent analog detectors was singled out

    by Underwriters Laboratories as the first such de-

    vices on the market that do not require a calibration

    sensitivity test in order to comply with NFPA72.

    Quality and reliability are built into every

    EST2 component, from the simplest control switch

    to the systems main processor. And thats not just

    a corporate mandate: its a proven fact supported

    by ESTs commitment to ISO 9000 international

    quality standards. EST2 is certified under ISO, not

    only for manufacturing, but for design, training,

    customer service, and technical support as well.

    This ensures that your EST2 system will provide ex-

    tremely reliable service the day its brought on-line

    and well into the future.

    Cost-effective technology with audio and network

    Notifi

    catio

    n Appliances

    Haza

    rdous L

    ocatio

    n Devices

    Door H

    olders

    & Relays

    Initia

    ting

    Devices

    EST2

    Analo

    g Contro

    l

    EST2Life Safety System

  • Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    1

    EST2Analog Control

    EST2 is a modular system with expansion capacity broad enough to meet the demands of over 90 per cent of new and retrofit building applications. Available with integrated dual-channel audio and peer-to-peer networking, EST2 keeps pace with the changing requirements of virtually any mid-range application.

    EST2 provides the benefit of starting small and expanding as system requirements change. Standalone capacity provides 192 intelligent detectors or 600 con-ventional detectors, 188 intelligent I/O modules or any mix of 192 relay, isolator or sounder bases.

    Networking extends EST2s capacity to 960 intelligent detectors, 3000 con-ventional detectors, 940 intelligent I/O modules and any mix of 960 relay, isolator or sounder bases. When networked, EST2 will drive up to 30 remote annunciators per panel each with a capacity of 96 input/output functions. EST2 will also support custom graphic annunciators and LCD displays with or without local control.

    Peer-to-peer communications and remote panel intelligence provides the enhanced survivability and performance the world has come to expect from EST brand products.

    Audio capability offers an efficient emergency paging, evacu-ation signalling and firefighters telephone system in perfectly integrated one or two channel packages. When distributed amplification is required, a remote mounting audio closet cabinet supports mounting of up to two 50 watt distributed amplifiers in remote locations.

    Full support for the advanced Signature Series family of detectors and modules means EST2 enjoys a wide range of installation and operation benefits. Signature Series detectors and modules use electronic addressing there are no dip switches or dials to set. This makes installation and programming incredibly fast and efficient.

    And whats more, Signature Series plug-in multi-function and dual circuit modules reduce wiring and installation costs, while

    its true multisensor technology eliminates detector application guesswork and makes nuisance alarms a thing of the past.

    Identification of dirty or defective detectors is automatic with EST2. Maintenance scheduling is easy and effective, ensuring that life safety protection is always maintained. EST2 even allows the adjustment of detector sensitivity at different times of the day.

    EST2 can use existing wiring, thanks to a unique communications protocol. This protocol eliminates the need for special

    communications-grade wiring, making EST2 fully compatible with existing conventional device wiring in most retrofit appli-cations. Re-wiring a building is no longer a costly element of a life safety system upgrade.

    EST2 offers the very best in modular flexibility, high-end fea-tures, and low-cost installation and maintenance. Its easy to see why this life safety system is fast becoming the industrys choice for small- to mid-range applications worldwide.

    EST2 Analog Control

    System configuration p. 2

    Main control and display p. 5

    Audio components p. 6

    Power supplies p. 8

    Ethernet Networking p. 9

    Display and remote annunciation p. 10

    Communciations p. 14

    Accessories p. 15

    Wallboxes and cabinets p. 16

  • EST2

    Ana

    log Con

    trol

    2

    EST2 ships with all the necessary ingredients. Each panel features a built-in Signature data circuit and two notification appliance circuits. An op-tional 2-LCX expansion module dou-bles the panels stand-alone capacity, and more power can be added in 6.4 amp increments to the generous fully-rated standard supplies. Provisions for notification appliance circuit risers also allow for additional multiplex ap-pliance circuits.

    For applications calling for coded signals, the optional CDR-3 module provides a choice of march time gen-erator or Positive Successive Non-Interfering (PSNI) outputs. CDR-3 outputs are selectable as a coded dry contact or supervised coded 1000Hz audio tone.

    EST2 provides individual status queues annunciating Alarm, Super-visory, Trouble and Monitor opera-tions. When a device operates, the appropriate message queues status LED illuminates. At the same time, a programmed point or zone descrip-tion displays on the back-lit LCD, giving specific text information for the active devices.

    Operators can review messages by selecting the queue from the front panel and scrolling through it. The last 512 events can be reviewed at any time via the enhanced history log. The enhanced history log contains the complete event message with LIFO (last in first out) protocol. This ensures that the most current events are always logged.

    Standalone system configuration

    L E G E N D

    Page

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Manual Pull Station 25

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Smoke detector with relay base 18

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Smoke detector with standard base 18

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Combination horn/strobe 31

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Signal module 22

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Control relay module 22

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Input module 21

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Monitor module 23

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    End-of-line resistor

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Junction box

    J

    S

    R

    S

    S

    S

    S S S

    J

    J

    S

    S

    S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    S

    S

    S

    S

    S

    S S

    S S

    F

    EDWARDS SYSTEMS TECHNOLOGY

    J

    J

    J

    J

    FF

    F

    24 VDCRISER

    2 Pr.2 Pr.

    HORN SUPERVISION& CONTROL

    HORN SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    STROBE SUPERVISION& CONTROL

    24 VDC RISERINTEGRITY MONITOR

    EOL RELAYIN J BOX

    2 Pr.

    2 Pr.

    2 Pr. 2 Pr.

    2 Pr.

    2 FLOORND

    3 FLOORRD

    SIGNATUREDATA CIRCUIT

    EST2 Panel

    J

    CC1

    CC1

    CC1

    CC1

    J

    J

    S

    CT

    J

    MMCRITICALPROCESSMONITOR

    FIREDAMPER

    F

    F

    CTCT

    JCR

    WATERFLOWSWITCH

    ELEVATORCAPTURE

    SPRINKLERSUPERVISORYSWITCH

    2 MULTIPLEXED CLASS 'B' NOTIFICATION APPLIANCE CIRCUITS

    NOTIFICATIONAPPLIANCECIRCUITS

    Typical EST2 Panel WiringClass B Signature Data Circuit

    EST2Analog Control

  • Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    3

    EST2 audio suits applications requiring emergency voice paging and evacuation signaling with or without firefighters telephone. Single channel or dual channel applications easily configure using Signature distributed amplifiers or centrally banked amplifiers. Distributed amplifiers are available in 30 watt and 50 watt sizes. All EST2 audio amplifiers configure for 25VRMS or 70VRMS operation through simple jumper selection.

    Signature amplifiers provide Class B or Class A wiring of audio output circuits. Speakers connect directly to the output of the Signature amplifier or the amplifier output can run as an audio riser to Signature modules where speaker zone selection is made. Each Signature amplifier has a built-in 1kHz tone generator and provision for a backup amplifier. Should an amplifier lose its input signal, the output will switch to a backup amplifier. If there is no backup amplifier or the output from the backup is unavailable, the output will receive the internal 1kHz tone as the evacuation signal.

    For installations requiring firefighters telephone, EST2 offers a master telephone module that allows communication with remote telephone stations. System paging is available through the front panel master microphone or through configured remote telephone stations. Six front panel switches allow emergency users to Page to the Evac riser, Page to the Alert riser, or quickly place Evac or Alert tones on all risers. After a paging operation, the system Audio Controller automatically returns to its pre-page state.

    Audio system configuration

    Zoned Amplifier Wiring

    2

    Typical Speaker Circuit25Vrms or 70VrmsAudio Outputs

    UL/ULC Listed47K EOL

    UL/ULC Listed47K EOL

    Typical AudioReturn (Class A Only)

    UL/ULC Listed47K EOL

    - +

    Style Y (Class B)

    TypicalTelephone

    Circuit:1

    1

    11

    2

    2

    2

    2

    2

    SIGA-CC1

    Typical Speaker Circuit25Vrms or 70VrmsAudio Outputs

    Typical Two Channel AudioPanel interconnect 1vrms or25Vrms. PHONE

    RISER OUTTo Next Deviceor 47K EOLResistor

    UL/ULC Listed47K EOL

    Typical AudioChannel Return(Class A Only)

    (+)

    Signature DATA OUTTo All Signature Devices

    (-)

    DATA OUTTo Next Device

    DATA IN

    (+)

    (+)

    (-)

    (-)

    From Signature Controlleror Previous Signature Device

    1

    2

    Twisted-Shielded Pair WireOne Twisted Pair Wire, Shield optional

    SIGA-AMP

    SIGA-APS

    SIGA-AMP

    120VAC 50/60 Hzor 220VAC 50/60Hz

    120VAC 50/60 Hzor 220VAC 50/60Hz

    Distributed Banked Amplifier Wiring

    Typical Two Channel25Vrms or 70VrmsAudio Outputs SIGA-

    CC1, CC2, or UM

    SIGA-CC1, CC2, or UM

    SIGA-CC1, CC2, or UM

    UL/ULC Listed47K EOL

    Typical AudioChannel Return(Class A Only)

    UL/ULC Listed47K EOL

    - +

    Style Y (Class B)

    TypicalTelephone

    Circuit:1

    1

    11

    2

    2

    2

    2

    SIGA-CC1

    Typical Two Channel25Vrms or 70VrmsAudio Outputs

    Typical Two Channel AudioPanel interconnect 1vrms or25Vrms. PHONE

    RISER OUTTo Next Deviceor 47K EOLResistor

    UL/ULC Listed

    47K EOL

    SIGA-CC1, CC2, or UM

    SIGA-CC1, CC2, or UM

    SIGA-CC1, CC2, or UM

    Typical AudioChannel Return(Class A Only)

    SIGA-CC2

    SIGA-CC2

    SIGA-CC2

    SIGA-CC2

    SIGA-CC2

    SIGA-CC2

    (+)

    Signature DATA OUTTo All Signature Devices

    (-)

    DATA OUTTo Next Device

    DATA IN

    (+)

    (+)

    (-)

    (-)

    From Signature Controlleror Previous Signature Device

    1

    2

    Twisted-Shielded Pair WireOne Twisted Pair Wire, Shield optional

    EST2Analog Control

  • EST2

    Ana

    log Con

    trol

    4

    Networked system configuration

    EST2 network configurations provide application flexibility and installation options that allow site-specific customization and meet local and national requirements. Networked EST2 panels support up to ten signature data circuits (SDCs), each with a capacity of 96 intelligent detectors and 94 intelligent Signature modules.

    Each panel configures using standard EST2 audio and control components that communicate on a peer-to-peer two-wire RS-485 circuit. Network and annunciator communications can be configured for Class B or Class A wiring.

    Unique programming flexibility allows network panels to meet most building applications including independent campus style arrangements or multiple control interfaces typical of high-rise applications.

    Signature Devices

    120 or 220V ac

    RS-485

    RS-485

    NACs

    IBM compatible PC

    RS-232

    ASCII printer

    RJ-11Download

    The EST2 Networksupports up to five2-MCMNs and five

    2-CPUs.

    For Class A wiringinstall 2-DLM innetwork wiring path.

    Node 01: 2-MCMN

    Node 02: 2-CPU

    Node 03: 2-MCMN

    Node 04: 2-CPU

    Node 05: 2-MCMN

    Node 06: 2-CPU

    Node 07: 2-MCMN

    Node 08: 2-CPU

    Node 09: 2-MCMN

    Node 10: 2-CPU

    EST2Analog Control

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    5

    Thanks to the modular flexibility of EST2, specifiying the panels main control com-ponents is extremely simple. If a standalone (i.e.: non-networked) configuration is required, the 2-MCD provides all the basics, including two notification appliance circuits, a Signature data circuit, an RS-232 printer port, and an RS-485 commu-nication port for remote annunciation. The 2-MCD also includes the panels main LCD display, which provides four 20-character lines of alpha-numeric messaging, as well as general condition LEDs, and a wide range of command and display controls. Wallboxes accommodate up to six panel mounted annunciator modules.

    Where networked configuration is required, the network controller (2-MCMN) and the LCD display (2-LCD) are specified separately. Together these provide the same basic features as the 2-MCD described above, but may be networked together to provide up to five control panel nodes.

    Networked and non-networked controllers accommodate the optional 2-LCX expansion module. This provides an additional Signature data circuit and two notification circuits. Both standalone and networked control components also support one or two channel audio configurations. Audio components are found on page 6.

    2-MCD* Main Control and Display (for standalone configurations) Data Sheet: 85005-0097

    2-MCMN* Network Main Control Module Data Sheet: 85005-0099

    2-LCD* Network LCD Display Module Data Sheet: 85005-0099

    2-DLM Network Data Line Monitor (Class A) Data Sheet: 85005-0099

    2-LCX Expander Signature Data Circuit with two Notification Appliance Circuits Data Sheet: 85005-0097

    CDR3 Coder Module Data Sheet: 270009

    IOP3A RS-232 Optical Isolator Card Data Sheet: 270039

    2-CCI City of Chicago Interface

    DLSM Data Line Short Monitor

    * Add -CC for City of Chicago approved equipment

    2-MCD or 2-MCMN

    2-LCD

    2-LCX (optional)

    All EST2 panels feature an 80-character LCD display with an array of command switches, as well as a main

    controller that includes two built-in notification

    appliance circuits, a Signature data circuit,

    and ports for printers and annunciators.

    Main control and display

    EST2Analog Control

  • EST2

    Ana

    log Con

    trol

    SUBMIT

    6

    EST2Analog ControlAudio components

    EST2 audio panels provide efficient emergency pag-ing, evacuation signaling and firefighters telephone systems in a range of perfectly integrated modular packages. Audio cabinets integrate both fire alarm control equipment and audio control equipment in one compact design. Wallboxes are available in sizes that accommodate a paging microphone, or a fire-fighters handset, or both handset and microphone.

    The audio sub-system features a powerful auto backup routine, built-in tone generator with 15 se-lectable tones, and dual channel Class A or B audio output.

    System paging is available through the front panel master microphone or through configured remote telephone stations. For installations requiring firefight-ers telephone, EST2 offers a master telephone module that allows communication with remote telephone stations.

    Six front panel switches allow the emergency user to Page to the Evac riser, Page to the Alert riser or quickly place Evac or Alert tones on selected risers. After a paging operation, the audio controller auto-matically returns to its pre-page state.

    When distributed amplification is needed, a single remote mounting audio closet cabinet supports mounting of up to two 50 watt distributed amplifiers in remote locations.

    Both single channel or dual channel applications easily configure using Signature distributed amplifiers or Edwards centrally banked amplifiers. Distributed amplifiers are available in 30 watt and 50 watt sizes.

    2-WB7 wallbox with master microphone

    and firefighters telephone

    2-TEL firefighters telephone

    2-MIC paging

    microphone

    2-AAC audio controller

    2-AAC Audio Controller Data Sheet: 85005-0093

    2-MIC Master Paging Microphone Data Sheet: 85005-0093

    2-TEL Firefighters Master Telephone Data Sheet: 85005-0093

    SIGA-MDM Intelligent Digital Message Module Data Sheet: 85001-0363

    SIGA-UIO2R M Series two-position Motherboard Data Sheet: 85001-0365

    SIGA-MDM with UIO2R

    Motherboard

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    7

    EST2Analog Control

    To 24 VDC

    From Output of

    Backup Amp

    To Backup Input

    of Next Amp

    Shield Optional

    Output Return

    Class A Only

    Audio Output

    to Speakers or

    Signature device

    Output Voltage

    Selection Jumper

    To Next

    Signature Device

    From Previous

    Signature Device

    From Channel 1

    Signal Source

    1Vrms or 25Vrms

    To Next Amp

    Channel 1 Input

    To Next Amp

    Channel 2 Input

    From Channel 2

    Signal Source

    1Vrms or 25Vrms

    Status LEDs

    Status LEDs

    Intelligent Audio Amplifiers

    Signature Series amplifiers are high-efficiency switch-mode audio amplifiers available in 30 and 50 watt sizes. Ampli-fiers have two input channels supporting dual channel or single channel audio ap-plications. Signature amplifiers are ideally suited for distributed audio applications and small centrally banked applica-tions. The audio output is configurable as 25Vrms or 70Vrms in Class B or Class A wiring configurations. Speakers can connect directly to the output of the amplifier or the amplifier output can run as an audio riser to Signature modules where speaker zone selection is made. Each amplifier has a built-in 1kHz tone generator and provision for a backup amplifier. On-board status LEDs provide quick visual indication of amplifier status.

    SIGA-AA30 30 Watt Intelligent Audio Amplifier Data Sheet: 85010-0089

    SIGA-AA50 50 Watt Intelligent Audio Amplifier Data Sheet: 85010-0089

  • EST2

    Ana

    log Con

    trol

    SUBMIT

    8

    EST2Analog ControlPower SuppliesRemote Booster Power Supply

    The Remote Booster Power Supply is a self-contained 24 Vdc power supply designed to augment fire alarm audible and visual power requirements as well as provide power for auxiliary, access control and security applications. The booster contains all of the necessary circuits to monitor and charge batteries, control and supervise four Class B or two Class A NAC circuits and monitor two controlling inputs from external sources.

    Simple switch selection provides a wide variety of operational configurations. Each remote booster power supply is supplied with its own enclosure providing ample space for additional interface modules and battery compartment.

    When used with Genesis Notification appliances, the booster provides the ability to syn-chronize strobes as well as horn signals. The booster flexibility allows synchronization with upstream devices, or, the booster may be used to synchronize downstream devices, as well as other boosters and their connected devices. Up to 10 boosters deep may be configured while maintaining strobe synchronization.

    BPS notification appliance circuits easily configure for either of two signaling rates: 3-3-3 temporal or continuous. This makes the BPS ideal for applications requiring signaling rates not available from the main panel. It also allows independent setup of a notification appli-ance circuit without interfering with the main panel and its initiating circuits. In addition to the generated signal rates, the BPS can also be configured to follow the signal rate of the main panels notification appliance circuit. This allows seamless expansion of existing NACs.

    For comprehensive configuration and wiring details, refer to the BPS Application Guide, 85001-0582.

    BPS6A 6.5 Amp Booster Power Supply Data Sheet 85005-0125

    BPS6A/230 6.5 Amp Booster Power Supply (220V) Data Sheet 85005-0125

    BPS6CAA 6.5 Amp Booster Power Supply with California rate Data Sheet 85005-0125

    BPS10A 10 Amp Booster Power Supply Data Sheet 85005-0125

    BPS10A/230 10 Amp Booster Power Supply (220V) Data Sheet 85005-0125

    BPS10CAA 10 Amp Booster Power Supply with California rate Data Sheet 85005-0125

    3-TAMP Tamper switch Data Sheet 85005-0125

    Auxiliary Power Supplies

    The Auxiliary Power Supply offers the same advantages as the BPS above, but is supplied with its own extra large enclosure providing space for up to two 24 Ah batteries and additional option modules in a number of mounting configurations. Option modules can be installed on the mounting brackets inside the enclosure or on an MP2L mounting plate at the top of the enclosure. The SIGA-REL, and SIGA-UIO2/6/6R can also be mounted at the top of the enclosure.

    APS6A 6.5 Amp Auxiliary Power Supply Data Sheet 85005-0127

    APS6A/230 6.5 Amp Auxiliary Power Supply (220V) Data Sheet 85005-0127

    APS10A 10 Amp Auxiliary Power Supply Data Sheet 85005-0127

    APS10A/230 10 Amp Auxiliary Power Supply (220V) Data Sheet 85005-0127

    BoosterPower Supply

    Sense NAC

    Parallel ConnectionThe number of boostersthat can be connected

    together is limited by wirerun length and available current

    Parallel ConnectionThe number of boostersthat can be connected

    together is limited by wirerun length and available current

    Series ConnectionUp to ten boosterscan be connectedtogether

    BoosterPower Supply

    Sense NAC

    BoosterPower Supply

    Sense NACNACCircuit

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    9

    EST2Analog Control

    Standard Power Supplies

    All EST2 panels are available with 4.5 amp or 6.4 amp power supplies. These provide the full current rating for notification appliance circuits. Power is provided via two power limited 24Vdc sources. Additional power can be added in 6.4 amp increments. Provisions for notification appliance circuit risers allow for additional multiplex appliance circuits.

    2-PPS 4.5 Amp Power Supply 120Vac Data Sheet: 85005-0097 2-PPS/6A 6.4 Amp Power Supply 120Vac Data Sheet: 85005-0097 2-PPS/220 4.5 Amp Power Supply 220Vac Data Sheet: 85005-0097 2-PPS/6A-220A 6.4 Amp Power Supply 220Vac Data Sheet: 85005-0097

    To Battery

    Ground

    Neutral

    Hot

    24 VDC @ 3.2A

    24 VDC @ 3.2A

    SIGA OUT

    SIGA IN

    Intelligent Auxiliary Power Supplies

    The SIGA-APS is a switch-mode power supply that provides additional power for any fire alarm control panel that includes a Signature Data Circuit. The SIGA-APS mounts with local fire alarm equipment or may be mounted remotely to supply power to signaling devices, amplifiers or system equipment. The power supply communicates with the main control panel over the Signature Data Circuit. This eliminates the need to mount additional monitoring equipment when the power supply is mounted remote from the main control panel.

    SIGA-APS Intelligent Auxiliary Power Supply 120Vac 50/60Hz Data Sheet: 85010-0087 SIGA-APS-220 Intelligent Auxiliary Power Supply 220Vac 50/60Hz Data Sheet: 85010-0087

    Batteries and Battery CabinetsData Sheet 85010-0127

    12 Volt Batteries 12V4A (4.5 Ah) 12V6A5 (7.2 Ah) 12V10A (11 Ah) 12V17A (18 Ah) 12V1A2 (1.2 Ah) 12V24A (26 Ah) 12V40A (40 Ah) 12V50A (50 Ah) 12V65A (65 Ah)

    6 Volt Batteries 6V8A (8 Ah) 6V10A (12 Ah) Battery Cabinets BC-1 (holds up to two 40 Ah batteries) BC-2 (holds up to two 17 Ah batteries) 3-RCC used as large battery enclosure.

  • EST2

    Ana

    log Con

    trol

    SUBMIT

    10

    EST2Analog Control

    Annunciator Modules

    EST2 provides ample annunciation for any mid-range life safety application. Up to 96 points or zones can be annunciated through software-controlled LEDs. LEDs and switch controls are modular and are available in eight different models that feature a wide selection of LED colors and switch/LED combinations. The same alpha-numeric LCD and annunciator LED modules are used for control and annunciation on both EST2 panels and remote annunciators.

    2-16R 16 Red LEDs Data Sheet: 85005-0097

    2-16Y 16 Yellow LEDs Data Sheet: 85005-0097

    2-16G 16 Green LEDs Data Sheet: 85005-0097

    2-8RY 8 Red and 8 Yellow LEDs Data Sheet: 85005-0097

    2-12R4Y 12 Red LEDs and 4 Yellow LEDs Data Sheet: 85005-0097

    2-16G8S 16 Green LEDs and 8 Two Position Switches Data Sheet: 85005-0097

    2-16R8S 16 Red LEDs and 8 Two Position Switches Data Sheet: 85005-0097

    2-16Y8S 16 Yellow LEDs and 8 Two Position Switches Data Sheet: 85005-0097

    2-8GYS 8 Green LEDs, 8 Yellow LEDs and 8 two Position Switches Data Sheet: 85005-0097

    2-8RYS 8 Red LEDs, 8 Yellow LEDs and 8 two Position Switches Data Sheet: 85005-0097

    Network Annunciators

    EST2 network annunciators provide full global system annunciation and control in remote locations. Up to five network annunciators can be used on a single EST2 network. Each node provides a separate

    RS-485 line that supports a full complement of local printers, LCD displays, and graphic and LED annunciators. Annunciator configurations include LCD display with LED/switch modules in a single enclosure. Message routing to specific displays brings the benefit of flexible custom message applications normally found in cost-prohibitive high-end systems. Annunciator modules can be arranged in any order on the inner door of the annunciator.

    2-LCD Liquid Crystal Display Module Data Sheet: 85005-0101

    2-CPU Network Annunciator CPU Data Sheet: 85005-0101

    2-3ANN/D Door assembly for 6ANN/B or S supports 1 2-LCD and 3 annunciator modules Data Sheet: 85005-0101

    2-6ANN/D Door assembly for 10ANN/B or S supports 1 2-LCD and 6 annunciator modules Data Sheet: 85005-0101

    6ANN/B Flush wallbox for 2-3ANN/D Data Sheet: 85005-0101

    6ANN/B-S Surface wallbox for 2-3ANN/D Data Sheet: 85005-0101

    10ANN/B Flush wallbox for 2-6ANN/D Data Sheet: 85005-0101

    10ANN/B-S Surface wallbox for 2-6ANN/D Data Sheet: 85005-0101

    Display & remote annunciation

    2-6ANN

    2-3ANN

    RJ-11

    RS-485

    RS-485

    IBM compatible PC

    RS-232

    ASCII printer

    24VdcRJ-11

    Download

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    11

    EST2Analog Control

    Smoked Plexiglas c/w Graphic

    Optional 3-EVRMFModule Mounting Frame(7 EIA Panel spaces high)

    BP1

    Flush TrimOptional

    Outer DoorSeparate Hinged

    Mounting Rails

    Feature Plate

    Optional

    or

    Wallbox

    LED Matrix Board

    MountingHinged LED/GRAPHIC

    Extrusion/Mounting

    Driver Board

    Chassis

    24VDC FROM 3-PPS/MOR 3-BPS/M POWER RISER

    FROM PREVIOUS PANELRS-485 NETWORK DATA

    POWER MODULE

    RS-485 NETWORK DATATO NEXT PANEL

    24VDC TO NEXT

    Envoy Graphic Annunciator

    ENVOY graphic annunciators and smoke control panels are designed to present complex status and control information in an easy to understand package. The design of ENVOY products permits users to rapidly deter-mine system status and easily operate associated system controls. The addition of system LCD annunciators and remote microphones can turn ENVOY into a complete fire command station.

    ENVOY graphic annunciators display system information using high in-tensity LEDs mounted behind the smoked Plexiglas panel that displays the artwork. White artwork and text on a dark background is standard. Colored artwork is available as an option, to enhance building areas or individual zones. A variety of LEDs and switches are available to meet any display and control requirement.

    Power ON, Trouble, and Signal Silenced LEDs; System Reset, Silence, Trouble Silence, and Drill push button switches are available as panel fea-

    ture options. Other panel options include system LCD displays and remote microphones.

    ENVOY graphic panels are available in three standard sizes to f i t the needs of most in-stallations. Wall boxes are manufactured from 16-gauge cold rolled steel and finished with a textured black baked enamel. Panels can be surface mount or semi-flush mount. When semi-flush mounting, optional trim kits provide a finished look to the installation.

    EV1 Envoy Graphic Annunciator (maximum 96 LEDs) Data Sheet: 85006-0037

    EV1B EV1 Wallbox: textured black finish Data Sheet: 85006-0037

    EV1T EV1 Semi-Flush Trim: textured black finish Data Sheet: 85006-0037

    EV2 Envoy Graphic Annunciator (maximum 160 LEDs) Data Sheet: 85006-0037

    EV2B EV2 Wallbox: textured black finish Data Sheet: 85006-0037

    EV2T EV2 Semi-Flush Trim: textured black finish Data Sheet: 85006-0037

    EV3 Envoy Graphic Annunciator (maximum 256 LEDs) Data Sheet: 85006-0037

    EV3B EV3 Wallbox: textured black finish Data Sheet: 85006-0037

    EV3T EV3 Semi-Flush Trim: textured black finish Data Sheet: 85006-0037

  • EST2

    Ana

    log Con

    trol

    SUBMIT

    12

    EST2Analog Control

    2-LSRA-C

    Remote Alpha-numeric Annunciators

    EST2 remote alpha-numeric display annunciators provide remote annunciation of system events and custom programmed messages. Annunciators incorporate power saving features that automatically turn off the front panel back lighting after four minutes if there is no switch activity and no unacknowledged messages are waiting. All annunciators include Normal, Alarm, Supervisory, and Trouble LEDs. There are two push-button switches labeled Back and Next/Ack. These acknowledge system event messages and allow the user to scroll through the event buffer. Models are also available with common control features.

    LSRA Series Annunciators

    LSRA annunciators mount in standard North American 2-gang electrical boxes, 4 square electrical boxes, or European 100mm square box enclosures. Annun-ciators come with four feature LEDs (Normal, Alarm, Supervisory, and Trouble) and two push-button Switches (Back and Next/Ack). LSRA-C annunciators support common control functions in addition to the four feature LEDs and the push buttons found on the LSRA. Reset, Alarm Silence, Trouble Silence, and Drill/All Call push button switches provide common control functions. LSRA-C annunciators allow individual programming of front panel switch operation. The controls are enabled by entering a password via the annunciators front switches or by activating an optional remote enable/disable key switch.

    2-LSRA LSRA Remote Display, semi-flush mounting Data Sheet: 85006-0035

    2-LSRA-C LSRA with common control switches and enable/disable functions Data Sheet: 85006-0035

    LSRA-232 Printer/programming port for LSRA series Data Sheet: 85006-0035

    LSRA-RK Remote Enable/Disable keyswitch (mounts in single-gang electrical box) Data Sheet: 85006-0035

    AC POWERDISABLE

    CPU FAILTROUBLE

    ALARMSUPERVISORY GND FAULT

    MONITOR TEST

    RESET

    DRILL

    ALARM SUPVR

    ACK

    TRBLE MONTR

    ALARMSILENCE

    TROUBLESILENCE

    1

    4

    7

    2

    5

    8

    0

    3

    6

    9

    STATUS

    ENABLE

    ACTIVATE RESTORE

    TEST

    PROGRAM

    DISABLE

    REPORTS

    24Vdc 24Vdc 24Vdc

    RS-485 DATA LINE

    3 4 32

    Serial Printer Serial Printer Serial Printer Serial Printer

    2-LSRA(-C) 2-LSRA(-C) 2-LSRA(-C) 2-LSRA(-C)2-SMDN(C) 2-SMDN(C) 2-SMDN(C) 2-SMDN(C)

    2

    24Vdc dedicatedriser (2 wires)

    1

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    13

    EST2Analog Control

    Serial Annunciators

    SAN Series annunciators are 19 rack-mounted control and display modules that may be mounted in the Envoy Graphic An-nunciator or a separate recessed cabinet. Modules are available with a wide range of control switches, buttons and colored LEDs. The front of each SAN module is covered with black LEXAN overlay with a legend pocket for modules requiring switch and LED legends. A legend sheet in a choice of five different colors comes with each module.

    Control Module: SAN modules are connected via ribbon cable to the SAN-CPU controller card. This card is microprocessor-based and includes an RS-485 data line. The SAN-CPU contains LEDs for polling status, and a DIP switch to set the panel address. Each SAN-CPU card will monitor 96 inputs (switches, SIN-16 circuits) and 96 outputs (LEDs, relay drivers). The CPU card requires a 24 Vdc power connection and a RS-485 data (class A or B) connection.

    Common Controls: The 2-SANCOM is a common annunciation and control module. Switches and LEDs are input and output points and may be reconfigured through programming. The Enable/Disable key switch may be set so that the push button switches are be disabled until the keyswitch is placed in the Enable position.

    Microphones: The SAN-MIC II is a SAN module that provides a paging microphone for remote paging applications. The paging microphone is typically connected to the microphone connection of the audio amplifier. It is a high signal output type with a push-to-talk switch. The SAN-MIC II module is a supervised microphone and tone generator module capable of operating at a location remote from the audio control and amplification equipment.

    SAN-CPU CPU card, RS-485 interface, 1 required per 96 inputs and 96 outputs Data Sheet: 270027

    SLU-16R SAN module, 16 Red LEDs Data Sheet: 270027

    SLU-16Y SAN module, 16 Yellow LEDs Data Sheet: 270027

    SWU-8 SAN module, 8 toggle switches with 2 yellow LEDs per switch Data Sheet: 270027

    SWU-8/3 SAN module, 8, 3 position toggle switches with two yellow LEDs per switch Data Sheet: 270027

    SRU-8 SAN module, 8 programmable relays Data Sheet: 270027

    SHO-4 SAN module, 4, 3 position switches, 2 yellow and 1 green LED per switch Data Sheet: 270027

    SDR-32 SAN module, 32 programmable outputs for remote LEDs Data Sheet: 270027

    SDR-32-C SDR-32 circuit card only, no mounting hardware or faceplate Data Sheet: 270027

    SDR-32K SAN module, 32 programmable outputs for remote LEDs or relays Data Sheet: 270027

    SDR-32K-C SDR-32K circuit card only, no mounting hardware or faceplate Data Sheet: 270027

    SIN-16 SAN module, 16 dry contact inputs Data Sheet: 270027

    SIN-16-C SIN-16 circuit card only, no mounting hardware or faceplate Data Sheet: 270027

    SAN-MIC II Supervised microphone and tone generator module Data Sheet: 270027

    2-SANCOM SAN module, common annunciation and control module Data Sheet: 270027

    SAN-4 Recessed cabinet, provides 4 single SAN module spaces, 1 SAN-CPU space Data Sheet: 270027

    SAN-8 Recessed cabinet, provides 8 single SAN module spaces, 2 SAN-CPU spaces Data Sheet: 270027

    RSAN-6 19 Rack mount unit, provides 6 single SAN module spaces, 1 SAN-CPU space Data Sheet: 270027

    BP-A SAN cabinet filler plate Data Sheet: 270027

  • EST2

    Ana

    log Con

    trol

    SUBMIT

    14

    EST2Analog Control

    LINE BATTERY

    POW

    ER

    ~ ~

    COMMON1 2 3 4 5 6 7 8

    PHONE

    SILENCE

    INPUTSTROUBLE

    SYSTEMRESET

    SERIALPO

    RTIN

    SERIALPO

    RTO

    UT(PROGRAM)

    NCCOM

    NO

    INPUT STATUS LEDS

    1 2 3 4 5 6 7 8

    PWRLINECALLBUSYPAGEDATALOADTRBL

    To Telephone LineTo Telephone

    Interface TroubleContactsTo Optional 12 VDCStandby Battery

    To Printer Port ofInitiating System

    NO or NC Dry Contact Inputor

    0 to 48 VDC Input Signal

    RS-232 Input

    To 24 V AC/DC

    Optional NO Reset Switch

    To Optional NOTrouble Silence Switch

    Alphanumeric Pager Interface

    The API-8/232ME is an interface between alarm and monitoring equipment and personal pager systems or PCS messaging services. The interface ensures that key personnel, regardless of their location, are notified of EST2 status changes. The unit can monitor an ASCII text string from a serial printer port for eight different event types. Each event type is defined by one or two programmable keywords up to 20 characters in length. Should an alarm remain on the system for a predetermined period of time, an alarm escalation feature can be set to re-page the alarm. The system can be programmed to send a restoration page when the input returns to its normal state. The API-8/32ME is supplied in a surface mounted enclosure. Optional battery backup power is available. The unit supervises AC power, the telephone line, and the paging system connection. A trouble relay is provided for connection to an external annunciator.

    API-8/232ME Paging System Interface with programming software Data Sheet: 85006-0045

    City Tie Module Alarm/Supervisory Wiring

    Riser out to next deviceor EOL Relay

    Riser infromPanel

    Data in

    Data out

    Master Box

    MunicipalCircuit

    CC1/MCC1

    2-CTMThe 2-CTM provides a simple way of connecting EST2 to a local energy fire alarm box or City Master Box. One 2-CTM provides either supervisory or alarm signaling. To configure both supervi-sory and alarm signaling, two 2-CTMs are required.

    2-CTM City Tie Module Data Sheet: 85005-0097

    Two-line Dialer

    The DL2 is a Digital Alarm Communicator Transmitter (DACT) or phone dialer. The DL2 dialer automatically transmits to a Central Monitoring Station control panel off-normal conditions and is capable of transmitting 32 unique zones. The DL2 sends a supervisory message every 24 hours to the Central Monitoring Station, verifying phone line operation and message receipt.

    2-DACT EST2 Two-line Dialer Data Sheet: 85005-0087

    Communications

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initiating Devices

    EST2

    Analog C

    ontrol

    15

    EST2Analog Control

    Ground Fault Detection Module

    The GFD module is designed to detect ground fault conditions on either of two independent power or data circuits. Each circuit must be balanced with respect to ground.

    The module will detect when the resistance between any of the monitored conductors and earth ground drops below 10 K Ohms. Two LEDs are provided to indicate the conductor with the ground condition. A normally energized Trouble/Ground Fault relay is provided with NO/NC relay contacts for interfacing with monitoring systems.

    The GFD operates in one of two modes, selectable by jumper posi-tion. Mode One places a ground fault on the common terminal of the relay. When used with a Signature input module, this configuration provides independent indications of ground fault and GFD module trouble conditions at the control panel. Mode Two deactivates the normally energized relay contact upon ground fault or module trouble.

    The ground fault relay activates when any monitored conductor ex-periences a ground fault condition. The trouble relay operates when module power is not available or when the supervisory watchdog timer activates. The module mounts in a two-gang electrical box.

    GFD Ground Fault Detection Module Data Sheet 85010-0115

    RS-232 Optical Isolator Card

    The IOP3A is an optically isolated RS-232 card that electrically isolates the power between the CM1(N), CM2N, FCC, and 3-CPU(1). It also provides power for use with short haul modems and fiber optic drivers. The IOP3A, through its on-card regulator, generates isolated power for the RS-232 drivers. The on-card regulator also provides isolated 12 Vdc power for use with external modems and drivers.

    IOP3A Isolated RS-232 card Data Sheet: 270039

    Reverse Polarity Module

    Provides three reverse polarity transmitters: one for system common alarm; one for system common trouble; and, one for system common supervisory.

    RPM Reverse Polarity Module Data Sheet: 85005-0097

    Desktop Serial Printer

    The PT-1 series printers are high-speed, nine-pin dot matrix type. It is used to perma-nently record life safety system changes of state. All printed entries contain the date, time, event type and a user-defined message for each printed event. The printer is required in proprietary systems and requires a backup UPS power source. In auxiliary, local, or remote station systems, the printer is optional.

    PT-1S Serial Printer Data Sheet: 270020

    PT-1S/220 Serial Printer 220/240Vac Data Sheet: 270020

    From 24 Vdc onfire alarm panel

    To earth ground

    Polarity is not important

    Pair one in Pair one out

    Pair two in Pair two out

    To supervisory module(i.e. Signature SeriesCT1 or CT2 module) or3-IDC traditional zonecard.

    ++

    ++

    arthD Power

    Circuit pair 1 Circuit pair 2I IP1

    D1 D2

    T3-2-1

    T

    Trou le F ContactsC C

    13

    1

    1

    3

    1114

    2

    11

    4

    12

    Accessories

  • EST2

    Ana

    log Con

    trol

    SUBMIT

    16

    EST2Analog Control

    2-WB Semi-Flush Wallbox Data Sheet: 85005-0099

    2-WBD Inner and Outer doors for 2-WB Wallbox Data Sheet: 85005-0099

    2-WBS Surface Wallbox Data Sheet: 85005-0099

    2-WBDS Inner and Outer doors for 2-WBS Wallbox Data Sheet: 85005-0099

    2-WB3 Long Surface Wallbox Data Sheet: 85005-0099

    2-WB3D Inner and Outer doors for 2-WB3 Wallbox Data Sheet: 85005-0099

    2-WB3D/DF Outer Door for 2-WB3. No viewing window (red finish) Data Sheet: 85005-0099

    2-LFK Long Semi-Flush Trim Kit for 2-WB3 Wallbox Data Sheet: 85005-0099

    2-WB7 Double wide Surface Wallbox Data Sheet: 85005-0099

    2-WB7D Inner and Outer doors for 2-WB7 Wallbox Data Sheet: 85005-0099

    2-DFK Double Wide Semi-flush Trim Kit for 2-WB7 Wallbox Data Sheet: 85005-0099

    Wallboxes and cabinets

    Wallboxes

    EST2 offers a wide selection of wallboxes that take full advantage of its modular design. Wallboxes provide space for control, monitoring and display modules. Ideal for mounting in lobbies where appearance is important, EST2 wallboxes are available in several sizes that accommodate the full complement of audio and network components. Wallbox doors have viewing windows and are available in gray baked enamel or red baked enamel finishes.

    Remote Audio Closet Cabinet

    The Remote Audio Closet Cabinet provides an economical means of installing equipment in locations such as electrical closets where aesthetics are not paramount. Remote Audio Closet Cabinets are surface mounted and supports mounting of up to two 50 watt distributed amplifiers. They have left-hand hinged doors and are available with red finish only. RCC cabinets can also be used as remote battery cabinets.

    RACCR Remote Audio Closet Cabinet (red finish only) Data Sheet: 85005-0099

    RACCDR Door for RACCR Wallbox Data Sheet: 85005-0099

  • Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initia

    ting

    Devices

    17

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e s

    Test Fire

    Type of DetectorSIGA-IS

    IonSIGA-PS Photo

    SIGA-HRS, SIGA-HFS

    Heat

    SIGA-PHS Photo/ Heat

    SIGA-IPHS Ion/Photo/ Heat

    Open Wood optimum unsuitable optimum very suitable optimumWood Pyrolysis suitable optimum unsuitable optimum optimum

    Smoldering Cotton very suitable optimum unsuitable optimum optimumPolyurethane Foam very suitable very suitable suitable very suitable optimum

    n Heptane optimum very suitable suitable optimum optimumLiquid Fire, no Smoke unsuitable unsuitable optimum very suitable optimumTrue multisensor technology means that a single device can perform optimally under a wider range of conditions than any single-sensor detector.

    EST2s Signature Series intelligent analog-addressable system is an entire family of fire alarm and security detectors as well as mounting bases, multiple-function input and output modules, and user-friendly maintenance and service tools.

    Analog information from equipment connected to Signature de-vices is gathered and converted into digital signals. At the heart of each Signature Series device is an on-board microprocessor that analyses these signals and decides whether or not to input an alarm. The power of this approach, known as distributed intelligence, provides four important benefits: self-diagnostics and history logging; automatic device mapping; stand-alone operation; and, fast, stable communication.

    Self-diagnostics and History Log Signature Series devices constantly run self-checks to provide important maintenance information. The results of these checks are automatically updated and perma-nently stored in the devices non-volatile memory. This informa-tion is accessible for review using the Sys-tem Definition Utility. The information stored in device memory in-cludes:

    device serial num-ber, address, and type;

    date of manufacture, hours of operation, and last maintenance date;

    number of recorded alarms and troubles; and,

    up to 32 possible trouble codes which may be used to specifically diagnose faults.

    Automatic Device Mapping The Signature Loop Controller learns where each devices serial number address is installed relative to other devices on the circuit. The controller keeps a map of all Signature Series devices connected to it. The Sys-tem Definition Utility program also uses this mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or As-Built

    drawing information showing branch wiring (T-taps), device types and their addresses are stored on disk. This takes much of the mystery out of the installation and makes the preparation of As-Built drawings fast and very efficient.

    Device mapping allows the Signature Loop Controller to dis-cover:

    unexpected additional device addresses;

    missing device addresses; and,

    changes to the wiring in the circuit.

    Most Signature modules use a personality code selected by the installer to determine their actual function. Personality codes are downloaded from the controller during system configuration and are indicated during device mapping.

    Fast Stable Communication Built-in intelligence means less information needs to be sent between the device and the Signature Loop Con-troller. Other than rou-tine supervisory polling responses, Signature devices only need to communicate with the controller when they have something new to report. This pro-

    vides very fast control panel response and allows a lower baud rate (speed) to be used for communication on the circuit. The lower baud rate offers several advantages including:

    less sensitivity to circuit wire characteristics;

    less sensitivity to noise glitches on the cable;

    less emitted noise from the analog wiring; and,

    twisted or shielded wiring is not required.

    Testing & Maintenance Automatic self-diagnosis identi-fies when a Signature device is defective and issues a trouble message. The user-friendly maintenance program shows the current state of each device and other pertinent information. Single devices may be turned off temporarily, directly from the control panel.

    Smoke Detectors p. 18

    Detector Bases p. 19

    Duct Detectors p. 20

    Input/Output Modules p. 20

    Input/Output Motherboards p. 24

    Releasing Module p. 25

    Pull Stations p. 26

    Intelligent Audio Amplifiers p. 27

    Intelligent Power Supplies p. 27

    Accessories p. 28

    Signature Series

    Intelligent Analog Initiating Devices

  • Initiating

    Devices

    SUBMIT

    EST2

    Ana

    log Con

    trol

    18

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e s

    Intelligent 4D Multisensor Detector

    Integrates three sensing technologies Ionization, Photoelectric, and Heat into one detector. Select alarm point for any one of five sensitivity settings between 0.67 to 3.70% per foot. Heat detector alarms when it sees a 65 F (35 C) increase in ambient temperature. Mounts to separate Standard, Relay, Isolator, or Sounder detector base.

    SIGA-IPHS Intelligent 4D Multisensor Detector, White Data Sheet: 85001-0245

    SIGA-IPHSB Intelligent 4D Multisensor Detector, Black Data Sheet: 85001-0245

    Intelligent 3D Multisensor Detector

    Integrates two sensing technologies Photoelectric and Heat into one detector. Select alarm point for any one of five sensitivity settings between 0.67 to 3.77% per foot. Heat detector alarms at 135 F (57 C) ambient temperature. Mounts to separate Standard, Relay, Isolator, or Sounder detector base.

    SIGA-PHS Intelligent 3D Multisensor Detector, White Data Sheet: 85001-0247

    Intelligent Photoelectric Detector

    Select alarm point for any one of five sensitivity settings between 0.67 to 3.77% per foot. Mounts to separate Stan-dard, Relay, Isolator, or Sounder detector base.

    SIGA-PS Intelligent Photoelectric Detector, White Data Sheet: 85001-0269

    Intelligent Ionization Detector

    Select alarm point for any one of five sensitivity settings between 0.61 to 1.91% per foot. Mounts to separate Stan-dard, Relay, Isolator, or Sounder detector base.

    SIGA-IS Intelligent Ionization Detector, White Data Sheet: 85001-0291

    Intelligent Rate-of-Rise/Fixed Temperature Heat Detector

    Includes 15 F (9 C) per minute rate-of-rise and 135 F (57 C) fixed temperature sensor. Mounts to separate Standard, Relay, Isolator, or Sounder detector base.

    SIGA-HRS Intelligent Rate-of-Rise/Fixed Temperature Heat Detector, White Data Sheet: 85001-0243

    Intelligent Fixed Temperature Heat Detector

    Includes 135 F (57 C) fixed temperature sensor. Mounts to separate Standard, Relay, Isolator, or Sounder base. SIGA-HFS Intelligent Fixed Temperature Heat Detector, White Data Sheet: 85001-0243

    Expander Signature Data Circuit, p. 5; Remote LED, p. 28.

    Signature Series

    Detectors and BasesSignature Series products are intelligent devices that have significantly lower communications requirements than those of sensor type devices. Because of the low Signature communica-tions rate there are no special wiring requirements for Signature circuits. This permits Signature devices to use existing wiring, as long as the wiring is in good shape, free of electrical noise, When existing wiring is used, the Signature devices will properly map the circuit, function as designed, and provide overall network response time of less than three seconds. For new installations, twisted-pair wiring is all that is recommended.

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initia

    ting

    Devices

    19

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e s

    SIG+ SIG-DATA-OUT

    DATA-IN

    DATA+IN/OUT

    +

    -

    +

    -

    +

    -

    +

    -

    Volume setting

    24 Vdc inFrom power supply

    or previous base

    Data inFrom Signature controller

    or previous device

    Tone setting

    24 Vdc outTo next baseor EOL relay

    Data outTo next Signaturedevice

    Audible (Sounder) Detector Base

    The Signature Series AB4G sounder base adds an audible output function to any Signature Series detector. The base can operate as an independent local alarm, or as part of a zone or system alarm with synchronized audible output. The AB4G may be configured in the field for either steady or temporal output and either high or low dB output.

    SIGA-AB4G Audible (Sounder) Base Data Sheet: 85001-0581

    Standard Detector Base

    Signature detector base provides roomside wiring terminals. Mounts to North American one-gang box, 3 or 4-inch octagon boxes, or 4-inch square electric box. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the electric box and provide a finished appearance.

    SIGA-SB SIGA-SB4 (with trim skirt) Standard Detector Base Data Sheet: 85001-0245

    Isolator Detector Base

    Signature detector base provides room-side wiring terminals and includes a built-in line fault isolator. Models with integral switches allow the detector to be removed from its base without causing the isolator to operate. Mounts to North American one-gang box, 3 or 4-inch octagon boxes, or 4-inch square electrical boxes. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the electrical box and provide a finished appearance.

    SIGA-IB SIGA-IB4 (with trim skirt) Isolator Detector Base Data Sheet: 85001-0245

    Relay Detector Base

    This base includes a relay. Normally-open or closed operation is selected dur-ing installation. The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relays position is supervised to avoid accidentally jarring it out of position. The relay base does not support the SIGA-LED remote LED. It mounts to North American one-gang boxes, 3 or 4-inch octagon boxes, or 4-inch square electrical boxes. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the electrical box and provide a finished appearance.

    SIGA-RB SIGA-RB4 (with trim skirt) Relay Detector Base Data Sheet: 85001-0245

    Trim skirt, p. 28; Detector Guard, p. 28; Detector Mounting Plate, p. 28.

  • Initiating

    Devices

    SUBMIT

    EST2

    Ana

    log Con

    trol

    20

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e s

    Signature Series intelligent input/output modules feature multiple user-set personality codes that define the modules behavior.

    Signature Series input/output modules are extremely flexible and power-ful devices that gather analog information from the slave devices connected to them and convert this data into digital signals. They are available in models that mount in standard one- or two-gang electrical boxes, as well as versions that plug into UIO motherboards. The actual function of each module is determined by its installer-selected personality code. This is downloaded to the module from the Signature Loop Controller during system configuration. Because they are intelligent devices, all decisions are made at the module. This allows lower communication speed but very fast control panel response time and less sensitivity to line noise and loop wiring properties. As a result, twisted or shielded wire is not required.

    Signature Series

    Input/Output Modules

    Standard two-gang mount

    Plug-in UIOs with motherboard

    SIGA-SD Intelligent SuperDuct Detector Data Sheet: 85001-0584

    Sampling Tubes SD-T8 (8) SD-T18 (18) SD-T24 (24) SD-T36 (36) SD-T42 (42) SD-T60 (60) SD-T78 (78) SD-T120 (120)

    Remote Test Stations SD-TRM (magnetic) SD-TRK (keyed) SIGA-LED (Remote alarm LED)

    Accessories SD-GSK (cover gasket kit) SD-MAG (Test magnet kit) SD-VTK (Air velocity test kit, stoppers only) SIGA-SDPCB (PCB/Signature sensor kit)

    SuperDuct Duct Detectors

    Less than two inches deep, SuperDuct intelligent smoke detectors are ideal for installation in ductwork, where space is always at a premium. Offering the most advanced and most reliable performance in its class, SuperDuct represents the perfect balance of practical design and ad-vanced technology.

    SuperDuct detectors feature a unique design that speeds installation and simplifies maintenance. Removable dust filters, conformally coated circuit boards, and optional water-resistant gaskets keep contaminants away from components, ensuring years of trouble-free service. When cleaning is required, the assemblies come apart easily and snap back together in seconds.

    Returnair

    Duct smokedetector

    Supplyair

    Duct smokedetector

    Remotetest station

    FACP

    HVACunit

    Alarm relay output

    Alarm relay output

    Remotetest station

    Application ModuleVoice messages Digital Messaging ModuleWaterflow Switches Waterflow/Tamper ModuleClass A indicating and initiating circuits, two-wire smoke detectors

    Universal Class A/B Module

    Class B Initiating Circuits: Door Closers, Fans, Dampers

    Class B Input Module Monitor ModuleControl Relay ModuleProgrammable I/O Module

    Telephone Power and Audible/Visual Signal Power Selector, Strobe Synchronization

    Signal Module

    Sounder Base power Reversal Relay ModuleSupervision of Telephone and Signal Power Riser Monitor ModuleFire Suppression Releasing ModuleFault detection Isolator Module

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initia

    ting

    Devices

    21

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e sModule mounting and installation options

    Signature Series input/output modules are available in models that feature two mounting options: standard mount and plug-in.

    Standard mount models are installed to North American two-gang or one-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module.

    Plug-in UIO modules mount to UIO motherboards. Two- and six-module UIO motherboards are available, making them ideal for instal-lations where more than one module is required. Motherboards can accommodate individual risers for each on-board module, or shared risers in any combination with their UIO modules. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in either cabinets, or standard electrical enclosures.

    Digital Message Module

    The SIGA-MDM Digital Message Module provides custom pre-recorded voice messaging. Two standard factory pre-recorded messages are included. Each module can store two 30 second messages in its non-volatile EEPROM memory. A microphone/line-level audio input stereo jack and output stereo jack, as well as record and playback switches are conveniently located on top of the module. Programming in the Signature Data Controller provides all control instructions; extra wiring for monitoring or controlling circuits is not required. Up to 47 modules can be cascaded together. The SIGA-MDM is available as a plug-in module only.

    SIGA-MDM Intelligent Digital Message Module Data Sheet: 85001-0363

    4321

    4321

    1 2 3 4

    1 2 3 4

    1 2 3 4

    1 2 3 4

    P1 P2

    TB1 TB2TB7

    TB8 TB9

    TB15PLAY

    REC.

    LINE

    IN

    HEAD

    PHONES

    MSG 1MSG 2

    CLIP

    MIC.LINE

    SDC

    NORMAL

    ACTIVE

    PLAY

    REC.

    LINE

    IN

    HEAD

    PHONES

    MSG 1MSG 2

    CLIP

    MIC.LINE

    SDC

    NORMAL

    ACTIVE

    IN OUTAudio Preamp Riser

    24 Vdc ToOther Loads

    24 VdcFrom Power Supply

    First DownstreamJumper

    To OtherSIGA Devices

    To SignatureLoop

    Controller(SLC)

    _

    _

    +

    +

    Expander Signature Data Circuit p. 5; UIO Motherboards, p. 24

    Universal Class A/B Module

    The Universal Class A/B Module is used to connect initiating, appliance, or two-wire smoke circuits in either Class A or Class B configurations. The plug-in version can also be used as a Class A dry contact initiating device circuit. The actual function of this module is determined by the personality code selected by the installer. Up to fifteen personalities are available.

    SIGA-UM Universal Class A/B Module (Two-gang standard mount) Data Sheet: 85001-0275

    SIGA-MAB Universal Class A/B UIO (Plug-in) Module Data Sheet: 85001-0275

    SIGA-UM

    Class B Input Module

    The Class B Input Module is used to connect Class B normally-open Alarm, Supervisory, or Monitor type dry contact initiating device circuits. The standard-mount version is available with either one or two input connections. The plug-in version accepts two input connections. The actual function of this module is determined by the personality code selected by the installer. A total of four personalities are available.

    SIGA-CT1 Single Input Module (One-gang standard mount) Data Sheet: 85001-0241

    SIGA-CT2 Dual Input Module (One-gang standard mount) Data Sheet: 85001-0241

    SIGA-MCT2 Dual Input UIO (Plug-in) Module Data Sheet: 85001-0241

    SIGA-CT1/CT2

    SIGA-MCT2

    SIGA-MAB

    Standard mount (one- or two-gang)

    FIREALAR

    M

    MODULE

    UIO Motherboard

    Plug-in (UIO)Module

    Cabinet or electrical enclosure

    Plug-in UIO

  • Initiating

    Devices

    SUBMIT

    EST2

    Ana

    log Con

    trol

    22

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e sSignal ModuleThe Signal Module is used to connect, upon command from the loop controller, supervised Class B signal or telephone circuits to their respective power inputs. Models are available with one or two power inputs. These may be either polarized 24 Vdc to operate audible and visual signal appliances, or 25 and 70Vrms to operate audio evacuation speakers and firefighters telephones. The actual function of this module is determined by the personality code selected by the installer. A total of three personalities are available.

    SIGA-CC1 Single Input Signal Module (Two-gang standard mount) Data Sheet: 85001-0237

    SIGA-MCC1 Single Input Signal UIO (Plug-in) Module Data Sheet: 85001-0237

    SIGA-CC2 Dual Input Signal Module (Two-gang standard mount) Data Sheet: 85001-0237

    SIGA-MCC2 Dual Input Signal UIO (Plug-in) Module Data Sheet: 85001-0237

    Control Relay ModuleThe Control Relay Module provides a Form C dry relay contact to control external appliances such as door closers, fans, dampers etc. This device does not provide supervision of the state of the relay contact. Instead, the on-board microprocessor ensures that the relay is in the proper ON/OFF state. Upon command from the loop controller, the relay activates the normally open or normally-closed contact. This module supports only one personality: no user configuration is required.

    SIGA-CR Control Relay Module (One-gang standard mount) Data Sheet: 85001-0239

    SIGA-MCR Control Relay UIO (Plug-in) Module Data Sheet: 85001-0239

    Polarity Reversal Relay ModuleThe Polarity Reversal Relay Module provides a Form C dry relay contact to power and activate a series of SIGA-AB4 Audible Sounder Bases. Upon command from the Signature loop controller, the SIGA-CRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop. This module supports only one personality: no user configuration is required.

    SIGA-CRR Polarity Reversal Relay Module (One-gang standard mount) Data Sheet: 85001-0239

    SIGA-MCRR Polarity Reversal Relay UIO (Plug-in) Module Data Sheet: 85001-0239

    Expander Signature Data Circuit p. 5; UIO Motherboards, p. 24; AB4G Sounder Base, p. 19.

    SIGA-CC1/CC2

    SIGA-MCC1/MCC2

    SIGA-CR

    SIGA-MCR

    SIGA-CRR

    SIGA-MCRR

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initia

    ting

    Devices

    23

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e sWaterflow/Tamper Module

    The SIGA-WTM Waterflow/Tamper Module is a two circuit intelligent module. Circuit 1 is for Class B normally-open waterflow alarm switches. When the input contact is closed for approximately 16 seconds, an alarm signal is sent to the loop controller. Circuit 2 is for Class B normally open dry contact supervisory and tamper switches. When the input contact is closed, an active signal is sent to the loop controller. Conditions on both circuits are latched at the module.

    SIGA-WTM Waterflow/Tamper Module (One-gang standard mount) Data Sheet: 85001-0297

    Isolator Module

    The SIGA-IM Isolator Module is an intelligent device that allows part of the Signature data loop to continue operating in the event of a short circuit. The module can be wired into a Class A data loop at any point. A maximum of 96 isolator modules can be installed on one circuit. If a fault occurs, the isolator cuts power to all devices beyond the isolator on the loop. Once activated, the line fault isolator continuously checks the faulted side of the loop to determine if the short still exists. When the fault is cleared, the module automatically restores the entire data loop to its normal condition.

    SIGA-IM Fault Isolator Module (Two-gang standard mount) Data Sheet: 85001-0271

    Monitor Module

    The SIGA-MM1 is a single-circuit intelligent module that includes a Class B normally-open dry contact. This is used for monitoring input from devices such as fans, dampers, and doors. When the input contact is closed, an active signal is sent to the loop controller. The active condition is not latched at the module.

    SIGA-MM1 Monitor Module (One-gang standard mount) Data Sheet: 85001-0297

    SIGA-IM

    SIGA-WTM

    SIGA-MM1

  • Initiating

    Devices

    SUBMIT

    EST2

    Ana

    log Con

    trol

    24

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e s

    Related Equipment

    MFC-A Multi-function Cabinet (for UIO and Releasing modules)

    27193-11 Surface Mount Box - Red, One-gang

    27193-16 Surface Mount Box - White, One-gang

    27193-21 Surface Mount Box - Red, Two-gang

    27193-26 Surface Mount Box - White, Two-gang

    235196P Bi-polar Transient Protector (use with all Signal Modules)

    SIGA-MP1 Signature Module Mounting Plate, 1 footprint

    SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint

    SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint

    Riser 2 Input

    common to

    all SIGA-UIO

    Modules

    Jumpers Connect

    Riser Input #1

    Between Modules

    Individual Riser 1 Input to each SIGA-UIO module

    Module Input/Output Wiring

    Signature

    Data

    Circuit

    Data In

    Data Out

    Universal Input/Output (UIO) Motherboards

    Signature Series Universal Input/Output Module Motherboards provide mounting and wiring terminations for up to six Signature Series plug-in UIO (SIGA-M se-ries) modules. UIO motherboards snap into a rigid extruded track (included) with mounting pads for convenient mounting into a variety of equipment enclosures. UIO modules plug into the board and are held securely in place with captive machine screws. All field wiring connects to terminal blocks on the motherboard, which permits rapid removal and replacement of modules for troubleshooting.

    The SIGA-UIO2R provides mounting and wiring terminations for up to two UIO modules, and the SIGA-UIO6R provides mounting and wiring terminations for up to six UIO modules. Both motherboards feature a riser #1 input and a riser #2 input bus. Jumpers on riser #1 input (between modules), facilitate sharing a single riser among more than one module. This significantly reduces wiring requirements. Re-moving the jumpers provides

    separate riser inputs to each adjacent module. Riser #2 input is fixed to each module position and cannot be split.

    The SIGA-UIO6 provides mounting and wiring terminations for up to six UIO modules. This moth-erboard provides two riser inputs that are common to all modules.

    UIO motherboards mount inside the MFC-A cabinet or other suitable UL-listed electrical enclosure. Each MFC-A will hold one UIO2R motherboard or one UIO6 or UIO6R motherboard complete with their full complement of modules.

    SIGA-UIO2R Universal Input/Output Module Board with Riser Inputs 2 Module Positions Data Sheet: 85001-0365

    SIGA-UIO6R Universal Input/Output Module Board with Riser Inputs 6 Module Positions Data Sheet: 85001-0365

    SIGA-UIO6 Universal Input/Output Module Board 6 Module Positions Data Sheet: 85001-0365

    UIO6R

    UIO2R

  • SUBMIT

    Notification

    Appliances

    Hazard

    ous Lo

    cation

    Devices

    Door H

    olders & Relays

    Initia

    ting

    Devices

    25

    EST2I n t e l l i g e n t I n i t i a t i n g D e v i c e sReleasing Module

    The Signature Series Releasing Module (SIGA-REL) is an analog addressable module that works with fire suppression systems designed to release extinguish-ing gas such as Halon. Its primary function is the