29
Irina Green, Senior Advisor, Regional Transmission, California ISO WECC Modeling and Validation Subcommittee Workshop September 18, 2020 DER Representation in Composite Load Model

DER models in comp load - WECC

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DER models in comp load - WECC

Irina Green, Senior Advisor, Regional Transmission,California ISO

WECC Modeling and Validation Subcommittee Workshop September 18, 2020

DER Representation in Composite Load Model

Page 2: DER models in comp load - WECC

ISO Public

DER Types (NERC Reliability Guideline) Utility-Scale Distributed Energy Resources (U-DER):

directly connected to the distribution bus or through a dedicated, non-load serving feeder. They are three-phase and can range in capacity, for example, from 0.5 to 20 MW

Retail-Scale Distributed Energy Resources (R-DER): offset customer load. Include residential, commercial, and industrial customers. Typically, the residential units are single-phase while the commercial and industrial units can be single- or three-phase facilities.

Distributed Energy Resources may include: Distributed Generation – in front or behind the meter Energy Efficiency – load modifier embedded in load forecast Demand Response – demand or supply side, can be used as

mitigation Energy Storage – can be modeled as aggregated, supply or

demand side•

Page 2

Page 3: DER models in comp load - WECC

ISO Public

DER in Composite Load Model in Power Flow Behind the Meter (BTM) DER are modeled in power flow as a

part of load

Page 3

Aggregated amounts of BTM-PV modeled at each bus by specifying the P and Q values of the PV as separate entries in the power flow load data, including the following values: Pdg - MW output of distributed generation Qdg - MVAr of distributed generation (sign convention

same as generators) Stdg - DG status DGmax – Installed capacity of distributed generation

Interface bus Load = Gross load (Load before PV)

Page 4: DER models in comp load - WECC

ISO Public

Behind the Meter DER in Composite Load Model in Power Flow, GE PSLF

Page 4

11114 BUS 11114Net Load shown

Page 5: DER models in comp load - WECC

ISO Public

DER in Composite Load Model in Dynamic Stability Studies

Page 5

Utility scale DER

Retail scale DER

Currently, DER models in dynamic stability exist only for solar PV. Other types of DER are modeled as generators, or as load modifiers

Page 6: DER models in comp load - WECC

ISO Public

Modeling Behind the Meter (BTM) Distributed Generation DER_A model is available in all major software platforms: GE

PSLF, PSS/E, PowerWorld as stand alone or part of composite load

California ISO uses GE PSLF BTM DER are modeled in power flow as a part of load BTM DER are modeled in dynamic stability as part of the

composite load model CMPLDWG (individual bus model) or _CMPLDW (modular model for climate zones and types of feeders)

DER parameters are modeled in dynamic stability with the _CMP_DER_A model

DER_A model that is used for the utility scale DER is identical to the _CMP_DER_A model that is used for the retail scale DER

Page 6

Page 7: DER models in comp load - WECC

ISO Public

Modeling BTM Distributed Generation in Dynamic Stability

Page 7

Load on the bus 375 MWDER on the bus 311 MWDER capacity 384 MW

Before initialization

After initialization

Page 8: DER models in comp load - WECC

ISO Public

Modeling Retail Scale DER in Dynamic Stability as Part of Load

Page 8

Composite Load When voltage is below specified values, the model trips

fractions of each motor, electronic and static load The fractions of load that are tripped and voltages, at which

they are tripped, are specified by the userDER as part of Composite Load Model

Distributed generation assumed having unity power factor DER also have settings at which voltages and frequencies

they may be tripped or reconnected DER solar PV models are simplified compared to the models

of large solar PV plants

Page 9: DER models in comp load - WECC

ISO Public

DER_A Dynamic Model

Page 9

Page 10: DER models in comp load - WECC

ISO Public

Active Power-Frequency Control

Page 10

Bypassed if low voltage

To freq. relay model

Page 11: DER models in comp load - WECC

ISO Public

Reactive Power-Voltage Control

Page 11

Page 12: DER models in comp load - WECC

ISO Public

Active and Reactive Current Priority Logic

Page 12

Page 13: DER models in comp load - WECC

ISO Public

Fractional Tripping• Represents fractions of DER tripping and recovering for abnormal

voltage or frequency• Use engineering judgement, specific data not available• DER_A model represents aggregate behavior• Vtripflag – voltage tripping, Ftripflag – frequency tripping• Vl – voltage trip thresholds, tvl – tripping timing• Vrfrac – fraction of DER that recovers when voltage recovers• No partial tripping on frequency• Tv- time delay on partial voltage tripping• Can approximately model momentary cessation

Page 13

Page 14: DER models in comp load - WECC

ISO Public

Voltage Source Representation

Page 14

Page 15: DER models in comp load - WECC

ISO Public Page 15

NERC SPIDER (System Planning Impact from DER) WG – DER_A Modeling Guideline

NERC SPIDERWG developed guideline on use of the DER_A model, and its parameter values

The Guideline is approved by NERC Provides detailed understanding of the

model Provides recommendations for

developing parameters for the model and values of DER_A parameters to use

CAISO uses parameters from this guideline: 30% as of IEEE Std 1547-2003 and 70% as of IEEE Std 1547-2018, Category II

Page 16: DER models in comp load - WECC

ISO Public

DER_A Default Parameters (SPIDER Guideline)Active Power-Frequency Control

Page 16

Page 17: DER models in comp load - WECC

ISO Public

DER_A Default Parameters (SPIDER Guideline)Reactive Power-Voltage Control

• Kqv=0, no voltage control• With dynamic voltage control, SPIDER Guideline recommended• Kqv=5, Dbd1= -0.12, Dbd2=0.1

Page 17

Page 18: DER models in comp load - WECC

ISO Public

DER_A Default Parameters (SPIDER Guideline)Active-Reactive Current Priority Logic

• If DER is a generator (Ipmin = 0), storage (Ipmin=-Ipmax)

• Pqflag = 0 – Q priority, =1- P priority• Inverters prior to IEEE 1547-2018

Standard not required to have voltage control – P priority

• After the approval of IEEE 1547-2018 -voltage control, Q priority

Page 18

Page 19: DER models in comp load - WECC

ISO Public

Why do we need to model DER?Growth of DER, as Modeled in the CAISO Cases

(BTM)

Page 19

PG&E Example Daily Load

Existing DER as of 2019 – 8,661 MW (all)

Page 20: DER models in comp load - WECC

ISO Public

Behind the Meter DER Sensitivity Studies

In addition to the studies of the Transmission Planning Process, CAISO performed numerous sensitivity studies of the BTM DER parameters

The latest studies included : Voltage regulation from DER Impact of the DER on frequency regulation DER parameters as Category II compared with Category

III according to the IEEE Standard 1547-2018 Also performed studies with DER netted with load The studies concluded that modeling DER makes significant

difference in the study results DER parameters have large impact on the system

performance and the simulation results.

Page 20

Page 21: DER models in comp load - WECC

ISO Public Page 21

Study Example: Hypothetical Summer Peak, Behind the Meter DER dispatched at 80% installed capacity

Behind the meter DER installed capacity at CAISO 18,600 MW, dispatched 14,880 MW

PG&E (Northern California) Load 31,654 MW gross, 24,240 MW net Behind the meter DER installed capacity 9,270 MW Behind the meter DER dispatched 7,416 MW

Fresno zone, Load MW 2,846 MW gross,1,634 MW net Behind the meter DER installed capacity 1,515 MW Behind the meter DER dispatched 1,212 MW

Page 22: DER models in comp load - WECC

ISO Public Page 22

Contingency Studied, power flow case with 80% Behind-the-Meter DER dispatched

Fresno area, Gates- Midway 230 kV line outage

Why 230 kV? Larger difference in DER performance

3- fault on the sending end with normal clearance (6 cycles, 0.1 s)

DER cases studied: Category II, No voltage control, Category III, No voltage control Category II, Voltage control, Category III, Voltage control DER netted with load

Cases with voltage control, kqv=5, dead-band +0.1/-0.12

Page 23: DER models in comp load - WECC

ISO Public

Behind the Meter DER Parameters in this Study

Page 23

Assumed hot summer day, DER dispatched at 80% of installed capacity The peak case has high load, thus stalling of single-phase air-conditioners with faultsDER_A parameters as recommended by SPIDER Modeling Guideline for inverters according to IEEE 1547-2018

Page 24: DER models in comp load - WECC

ISO Public Page 24

Results Summary for the Cases Studied No criteria violations with this contingency

Loss of Composite Load and DER with Contingency

Page 25: DER models in comp load - WECC

ISO Public

Comparison of the five cases. Voltage at feeder end

Page 25

Higher recovery voltage with Cat III and voltage control

Lowest voltage with Cat II and no voltage control

With netted DER higher transient voltage because of lower induction motor load due to netting

Significantly better performance with Cat III settings

Page 26: DER models in comp load - WECC

ISO Public

Comparison of load and DER on a 70 kV bus close to fault

Page 26

NET LOAD DER OUTPUT

This DER tripped, except for Cat. III with voltage control

Page 27: DER models in comp load - WECC

ISO Public

Load and DER on another bus

Page 27

DER recovered for Cat. III with or without voltage control, but did not recover for Cat II

Net load: blue –no DER, red and brown Cat II, green and purple Cat III

Page 28: DER models in comp load - WECC

ISO Public

Conclusions from the IEEE 1547 Std setting studies DER ride-through capability and adequate trip settings lead to a

significant reduction of DER trip There is less load reduction if DER have Category III requirements

and settings, than with Category II If DER have Category III requirements and settings, system

performance is significantly better than with Category II. Some DER trip for low voltage with faults and don’t recover when

voltage recovers. There are fewer DER that trip and don’t recover with Category III.

In addition, voltage regulation on the Behind the Meter DER can provide some additional help with faults ride through and may allow the induction motors not to stall. There is less load reduction if DER have voltage control If DER have voltage control, their active power output during

transient period will be lower because of the reactive current priority

Page 28

Page 29: DER models in comp load - WECC

ISO Public

QUESTIONS?COMMENTS?

Please send your comments to Irina [email protected]

Page 29