Subsynchronous Oscillations (SSO) and PowerWorld Applications at ERCOT Anuj Dixit and Priya Ramasubbu ERCOT Planning and Grid Co-ordination May 21, 2014

WECC ERCOT Presentation

Embed Size (px)

DESCRIPTION

ppt

Citation preview

Page 1: WECC ERCOT Presentation

Subsynchronous Oscillations (SSO) and PowerWorld Applications at

ERCOT

Anuj Dixit and Priya RamasubbuERCOT Planning and Grid Co-ordination

May 21, 2014

Page 2: WECC ERCOT Presentation

The Electric Reliability Council of Texas (ERCOT)

• ERCOT ISO manages the flow of electric power to 23 million Texas customers - representing 85 percent of the state's electric load.

• Performs financial settlement for the competitive wholesale bulk-power market

• Enables retail electric choice for Texas customers

2

Page 3: WECC ERCOT Presentation

Presentation Outline

• *CREZ Network and Resonance• What causes SSO?• Studying and Preventing SSO• How does this impact transmission

planning and operations?• PowerWorld Applications

*Competitive Renewable Energy Zone

3

Page 4: WECC ERCOT Presentation

Definition

Competitive Renewable Energy Zone – a geographic area in the state of Texas initially identified by AWS Truewind (as ERCOT’s consultant) as an area suitable for multiple 100 MW wind development projects. Of the original 25 zones the Public Utility Commission (PUC) chose a small set based on input from potential windfarm developers.

4

Page 5: WECC ERCOT Presentation

CREZ Areas

5

Page 6: WECC ERCOT Presentation

What and Where

New CREZ 345kV lines built both inside ERCOT load-serving areas and far into areas where load is served by SPP.

CREZ will not add any new connections between ERCOT and SPP.

CREZ areas are Panhandle A, Panhandle B, Central, West, and McCamey.

6

Page 7: WECC ERCOT Presentation

CREZ 345kV Lines

7

Page 8: WECC ERCOT Presentation

Series Compensation

• The use of capacitors connected inline with a transmission line.

• Benefits:– Increases power flow by reducing line impedance.– Relieve bottlenecks.– Increases stability and reduces voltage variation.

8

Page 9: WECC ERCOT Presentation

Introduction to Subsynchronous Oscillations9/9/2013 9

Series Compensation:

•CREZ– Tule Canyon – Tesla– Edith Clarke – Clear

Crossing– Dermott – Clear Crossing– West Shackleford – Sam

Switch/Navarro– Big Hill – Kendall– Clear Crossing – Willow

Creek (2016)

•Rio Grande Valley– Lon Hill – Rio Hondo– Lon Hill – Edinburg– Lobo – Edinburg (2016)

•HorseHollow GenTie

Series Compensation in ERCOT

Page 10: WECC ERCOT Presentation

How Resonance Can Occur in Power System

• Complementary Storage Elements creates resonant circuit (e.g. generator & series cap).

• Generator introduces negative damping.• Low frequency power oscillations develop.

Series Capacitor

~~

Generator

Normal EnergyLoad

Normal Energy

~~

Generator Load

Oscillations 10

Page 11: WECC ERCOT Presentation

Mohave SSO Incident (1970)An example of SSO Torsional Interaction

• Mohave generator: 1,580 MW coal-fired in NV.• Gradually growing vibration that eventually

fractured a shaft section.• First investigations incorrectly determined cause. After 2nd failure

in 1971 cause was identified as Subsynchronous Resonance interaction with nearby series capacitors.

• An electrical resonance at 30.5 Hz excited a mechanical resonance at 30.1 Hz.

• Problem was cured by reducing compensation percentage and installing a torsional relay.

D. Baker, G. Boukarim, “Subsynchronous Resonance Studies and Mitigation Methods for Series Capacitor Applications,” IEEE 2005.D. Walker, D. Hodges, “Results of Subsynchronous Resonance Test At Mohave,” IEEE 1975.

11

Page 12: WECC ERCOT Presentation

Introduction to Subsynchronous Oscillations9/9/2013 12

Presentation Outline

• CREZ Network and Resonance

• What causes SSO?

• Studying and Preventing SSO

• How does this impact transmission planning and operations?

• PowerWorld Applications

Page 13: WECC ERCOT Presentation

Introduction to Subsynchronous Oscillations9/9/2013 13

South Texas SSR Event (2009)

• A fault occurred on the Ajo to Nelson Sharpe line.• Fault cleared in 2.5 cycles by opening this line.• The wind farms were then radially connected to the Ajo

to Rio Hondo series compensated transmission line.• Undamped oscillations at 22 Hz.• Voltages at generator doubled in ~150 ms.• Damage to wind generators and series capacitors

occurred.

From AEP presentation by Paul Hassink, “Sub-synchronous Control Interaction,” Utility Wind Integration Group Spring Workshop April 15, 2011Also: http://www.elforsk.se/Global/Vindforsk/Konferenser/HF_symposium_111206/Gotia_Power_V309_subsynchronus_resonence.pdf

Page 14: WECC ERCOT Presentation

Introduction to Subsynchronous Oscillations9/9/2013 14

South Texas SSR Event (2009)

• Series capacitors installed on long 345 kV lines to allow full loading.

• 1,000 MW of wind farms connected to Ajo.

345 kV series compensated lines

Page 15: WECC ERCOT Presentation

Introduction to Subsynchronous Oscillations9/9/2013 15

• Wind farms are vulnerable to SSO due to nearby series capacitors.

• Understanding and analysis techniques have advanced considerably.

• Wind farms are now routinely analyzed for risk.• AEP resolved this problem by installing

protection to automatically trip the wind farm.*

Lessons Learned – South Texas 2009

* This solution was site-specific. In other locations, protective tripping may not be appropriate as a first defense.

Page 16: WECC ERCOT Presentation

Who’s At Risk? -- General Observations• More Risk for SSO:

– Electrically closer to series capacitors.– Long shaft / multi-mass generators (Coal, NG Steam,

Combined Cycle).

• Less Risk:– Hydro, CTs, reciprocating engines.– Solar inverters.– HVDC ties.

• Because SSO is a concern for all generation technologies, all generators are reviewed. ERCOT notifies developers whose units might be at risk.

16

Page 17: WECC ERCOT Presentation

Presentation Outline

• CREZ Network and Resonance• What causes SSO?• Studying and Preventing SSO• How does this impact transmission

planning and operations?• PowerWorld Applications• Conclusion.

17

Page 18: WECC ERCOT Presentation

DETAILED STUDY REQUIRED Or rework the proposed interconnection.Or obtain letter from gen. manufacturer.

POWER-FLOW TESTOutage combination solves in steady-state w/ few overloads?

SSO Risk Assessment

ERCOT SSO ScreeningGrid-side frequency scan shows risk?

At 6 or fewer concurrent outages?

TOPOLOGY TESTTEN or less

contingencies to radial?

This simple test is performed by inspection: Does it take ten or fewer outages to make a generator radial to a series cap? This test will clear many projects, especially those far from the series capacitors and those connecting to the lower voltage network.

This tests whether the network electrical characteristics are conducive to resonance. ERCOT performs this test as part of the transmission planning and GINR process.

This tests the affected outage combinations to see whether they solve in a min load case. If the case doesn’t solve or has many overloads, the outage isn’t credible.

If credible SSR risk exists, then a study should be performed. In lieu of a study, generator resources may obtain a letter from their manufacturer or they may also rework their proposed interconnection to reduce risk exposure. 18

Page 19: WECC ERCOT Presentation

How Study for SSO?

• Frequency scans

• Time-Domain Simulation

1 Electromagnetic Transient simulation: A time-domain analysis similar to a dynamic or “stability” analysis but capable of simulating off-nominal frequencies other than 60 Hz. Such simulations generally require more detailed models.

Graph resistance & reactance vs. frequency. Look for dips & crossovers. Less accurate so designed to be conservative.

If frequency scan shows possible exposure risk, EMT1 simulation may be able to dismiss the exposure risk. EMT simulations are more accurate.

-0.05

0.00

0.05

0.10

0.15

0.20

0.25

0.30

5 9 13 17 21 25 29 33 37 41 45 49 53 57

Impe

danc

e (o

hms)

Frequency (Hz)

Network Impedance (N-5)

Resistance

Reactance

19

Page 20: WECC ERCOT Presentation

Introduction to Subsynchronous Oscillations9/9/2013 20

Detailed Study – Results & Action

• Detailed study will determine the system configurations that result in SSO, particularly the number of concurrent outages required.

• Procedural Mitigation: Outage Coordination procedures to avoid scheduling outages that would place a unit at increased risk.

• Structural Mitigation: Redesign, controller tuning, etc.

  Potential Risk

(# of Concurrent Transmission

Outages)

Required Action Responsible Entity

≤ 3 Protection and Structural Mitigation

All affected

≤ 4 Protection All affected4, 5, or 6 Procedural Mitigation All affected and ERCOT

(As proposed in NPRR562)

Page 21: WECC ERCOT Presentation

Protection vs. Mitigation?

• Protection– Involves forced tripping (removal of generator or series capacitor).– Disruptive for a system that is already in a weakened state due to outages

(“double blow”).– Generally recommended as backup means of defense.

• Mitigation– Involves reducing exposure to SSO risk.– Generally allows the resource to continue operating, even when outages place

the unit in stronger electrical coupling with a series capacitor.– In many cases, may completely eliminate risk.

• E.g. Horse Hollow Energy Center installed mitigation which allowed the wind turbines to operate radially to the series-compensated transmission line owned by NextEra.

21

Page 22: WECC ERCOT Presentation

How to Solve SSO Problems?

• Mitigation Options:– Control system upgrades (common for wind).– Re-design of generating unit.– Passive Filters.– Some transmission level options available.

• Protection Options:– Torsional relays

(detect shaft twisting on conventional units).– Subsynchronous Current relays.

22

Page 23: WECC ERCOT Presentation

Presentation Outline

• CREZ Network and Resonance• What causes SSO?• Preventing SSO• How does this impact transmission

planning and operations?• PowerWorld Applications

23

Page 24: WECC ERCOT Presentation

Effect of Outages• Outages are the best indicator for gauging risk for SSR.• Five double-circuit outages make Big Brown radial to

W.Shackelford – Navarro series compensated line.

24

Page 25: WECC ERCOT Presentation

Example Timeline of an SSR EventFor a Generator that is “N-4 Risk”

• SSR can happen very fast.• Action should be taken well ahead of time.

10 days 8 days5 seconds

1st Planned Outage

1st Planned Outage

2nd Planned Outage

2nd Planned Outage

Forced OutageForced Outage

Generator DamagedGenerator Damaged

Take Action!!!Take Action!!!

3rd Planned Outage

3rd Planned Outage

25

Page 26: WECC ERCOT Presentation

Preventing Risk Example

ERCOT Planning identifies all generators that might be at risk.ERCOT Planning identifies all generators that might be at risk.

ERCOT Planning orders detailed studies. ERCOT Planning orders detailed studies.

Detailed studies indicate which outages place a generator at risk.Detailed studies indicate which outages place a generator at risk.EXAMPLE:

For Wise County to be at risk, the following lines must be all out of service: WillowCreek – Hicks, WillowCrk – Parker, and WillowCrk - Jacksboro

EXAMPLE:

For Wise County to be at risk, the following lines must be all out of service: WillowCreek – Hicks, WillowCrk – Parker, and WillowCrk - Jacksboro

ERCOT Outage Coordination ensures that no two combinations of these outages go out at the same time. If unavoidable, takes mitigation action.ERCOT Outage Coordination ensures that no two combinations of these outages go out at the same time. If unavoidable, takes mitigation action.

Outage coordination mitigates risk. Outage coordination mitigates risk.

26

Page 27: WECC ERCOT Presentation

Preventing Risk (Continued)

One of the new SSR Alarms in the Control Room sounds.One of the new SSR Alarms in the Control Room sounds.

Operators follow written mitigation procedures.Operators follow written mitigation procedures.

Example Mitigation Procedure

1.Call TSP. Ask if tripped line can be put back in service.

2.If unable to re-energize, ask TSP to study bypassing series capacitor.

3.TSP studies, sees minor adjustments required (e.g. move switched shunt or enforce a partial wind curtailment).

4.TSP bypasses the series capacitor. SSR risk is averted.

5.When possible, operators look for opportunity to place capacitors back in service and cancel the wind curtailment.

Example Mitigation Procedure

1.Call TSP. Ask if tripped line can be put back in service.

2.If unable to re-energize, ask TSP to study bypassing series capacitor.

3.TSP studies, sees minor adjustments required (e.g. move switched shunt or enforce a partial wind curtailment).

4.TSP bypasses the series capacitor. SSR risk is averted.

5.When possible, operators look for opportunity to place capacitors back in service and cancel the wind curtailment.

Because Outage Coordination is monitoring, SSR is unlikely to become a Real Time issue. However, if it does…

Because Outage Coordination is monitoring, SSR is unlikely to become a Real Time issue. However, if it does…

27

Page 28: WECC ERCOT Presentation

Role of ERCOT Planning in SSR

• ERCOT analyzed risk exposure of all existing and proposed power plants.

• All exposed plants are undergoing study.• Several thermal and wind plants are already

moving towards resolution.• Until resolution, series capacitors will not be

energized.*

* If situation involves a new generation resource and existing series capacitors, then the new resource would not be allowed to energize.

28

Page 29: WECC ERCOT Presentation

How does this impact operators?

• List of units prone to SSR may have to be closely monitored under stressful system conditions

• Keeping an eye out for extreme contingencies near the series capacitors

• This will be done with the help of new SCADA displays and alerts

29

Page 30: WECC ERCOT Presentation

Bypassing: The “Emergency Kill Switch”

• Bypassing removes the series capacitor from service but leaves the line still in operation.

• With capacitor removed, no SSR risk.

Series Capacitor

Series Capacitor

Current InterruptCurrent Interrupt

Close to BypassClose to Bypass

30

Page 31: WECC ERCOT Presentation

Bypassing: What effect will it have?

• Line impedance will double, thus less power will flow on line (and more on neighboring lines).

• Bus voltages may change by ~3%.• A new voltage stability limit may appear.

• Because of this, it is recommended to run an STNET and possibly VSAT study before bypassing.– Some generation adjustments may be necessary

(e.g. wind curtailment).

31

Page 32: WECC ERCOT Presentation

Example Display – SSR Alarm

Source: ERCOT Advanced Network Applications32

Page 33: WECC ERCOT Presentation

Example Display – SSR Alarm cont.

Source: ERCOT Advanced Network Applications33

Page 34: WECC ERCOT Presentation

Example Display – SSR Details

Source: ERCOT Advanced Network Applications34

Page 35: WECC ERCOT Presentation

Example Display – SSR Actions

Source: ERCOT Advanced Network Applications35

Page 36: WECC ERCOT Presentation

Presentation Outline

• CREZ Network and Resonance• What causes SSO?• Preventing SSO• How does this impact transmission

planning and operations?• PowerWorld Applications

36

Page 37: WECC ERCOT Presentation

ERCOT System Planning

• ERCOT planning performs coordinated planning studies with input from NERC registered Transmission Planners (TPs), Transmission Owners (TOs) and other stakeholders to address region-wide reliability and economic transmission

• Performs transmission studies/assessment (both near-term and long-term planning horizon) to meet ERCOT and NERC standards (TPL-001-004, PRC-023, FAC-013)

• Assesses resource availability of existing units and future generators

• Load forecasting for the near-term and long-term Planning Horizon37

Page 38: WECC ERCOT Presentation

Regional Transmission Plan (RTP) - Objective

• Regional Transmission Plan is developed annually by ERCOT in coordination with the Regional Planning Group (RPG) and the Transmission Service Providers (TSPs)

• Annual assessment to identify transmission needs of ERCOT system over the next six years

• Projects identified to meet the ERCOT/NERC reliability requirements (Reliability projects) and to reduce system congestion (Economic projects) that meet the ERCOT economic criteria

38

Page 39: WECC ERCOT Presentation

ERCOT RTP Process

39

Page 40: WECC ERCOT Presentation

Use of PowerWorld in RTP

40

Page 41: WECC ERCOT Presentation

Case Building

• Assign ERCOT weather zones to buses and loads

• Update AGC flags for non-conforming loads• Load scaling• Control options for generators (Fast start, AGC,

AVR, Enforce MW Limits)• Geographic onelines

41

Page 42: WECC ERCOT Presentation

SCOPF / Contingency Analyses

• Import cost curves for generators• Load throw over information• Conditional modeling and global actions

for SPSs• SimAuto

42

Page 43: WECC ERCOT Presentation

PowerWorld Settings

43

Page 44: WECC ERCOT Presentation

Options and Settings in PowerWorld• Solution Settings

– Common Options• Enforce Generator MW Limits

– Island Based AGC• Participation Factors

• LP / OPF Settings– Constraint Options

• Maximum Violation Cost– Control Options

• Fast Start

• Areas and Super Areas for OPF

44

Page 45: WECC ERCOT Presentation

Solution Settings

45

Page 46: WECC ERCOT Presentation

Options and Settings in PowerWorld (Contd.)

• Contingency Analysis Options– Basics

• Full Power Flow• Generator Participation Factors

– Advanced Limit Monitoring• Do not report base case violations

• SCOPF Options– Solve base case using optimal power flow

46

Page 47: WECC ERCOT Presentation

SCOPF Options

47

Page 48: WECC ERCOT Presentation

New Feature Recommendation

• N-1-1 capability with system adjustments

48