PROPOSED RESIDENCE STORMWATER TO APPROVED DISCHARGE POINT AS PER LOCAL AUTHORITY REQUIREMENTS 1800 GOOD NEIGHBOUR FENCING BY OTHERS 1800 GOOD NEIGHBOUR FENCING BY OTHERS 1800 GOOD NEIGHBOUR FENCING BY OTHERS FFL 11.800 AHD SITE PAD LEVEL 11.500 AHD BUILDER TO CONFIRM PRESENCE & EXTENT OF EXISTING FILL ON SITE PRIOR TO COMMENCEMENT OF CONSTRUCTION WORKS. ALL EXTERNAL LOAD BEARING WALLS MUST BE FOUNDED ON NATURAL GROUND m: 0415 642 727 e: [email protected] w: www.quantumdrafting.com.au P.O. Box 152 Arana Hill Q 4054 QBCC Licence: 1247149 Scale checked by drawn by date project number 1 : 200 11/25/2017 9:46:57 AM 1 SITE PLAN DKMT_A DUAL KEY DESIGN GREG McLAREN 3.5.17 ADH ADH 001 VARIOUS ADDRESSES CONSTRUCTION NOTES ALL WORK TO COMPLY WITH THE BUILDING CODE OF AUSTRALIA REQUIREMENTS (NCC) AND AUSTRALIAN STANDARDS AND THEIR MOST CURRENT AMENDMENTS. ALL LOCAL COUNCIL REQUIREMENTS ARE TO BE MET IN RELATION TO THE CLASS AND TYPE OF CONSTRUCTION. BEFORE COMMENCING CONSTRUCTION ALL DIMENSIONS, EXISTING LEVELS, FINISHED LEVELS AND ALL SITE SERVICES ARE TO BE VERIFIED BY THE BUILDER. NOTIFY THE BUILDING DESIGNER OF ANY VARIATION BETWEEN THE DOCUMENTATION AND SITE CONDITIONS. WRITTEN DIMENSIONS ARE TO TAKE PRECEDENCE OVER SCALING FROM THE DRAWINGS. NOTIFY THE BUILDING DESIGNER OF ANY VARIATIONS OR DISCREPANCIES IN THE DIMENSIONING OF THE PLANS. MANHOLE TO BE POSITIONED TO SUIT TRUSS LAYOUT. POSITION TRUSSES SO AS TO PROVIDE A CLEAR 600mm x 600mm OPENING. MANHOLE POSITION AS INDICATED ON PLAN. TERMITE PROTECTION TO COMPLY WITH AS 3660 AND AS 3660.1 & NCC 2016 VOLUME 2 PART 3.1.3. MASONRY ARTICULATION TO COMPLY WITH AS3700-2011 & TECHNICAL NOTE 61 BY CCAA. WATERPROOFING OF WET AREAS TO COMPLY WITH AS 3740 - 2010 & NCC 2016 VOLUME 2 PART 3.8.1. DAMP PROOFING OF GROUND SLAB/ FLOORS TO COMPLY WITH AS 2870 & NCC 2016 VOLUME 2 PART 3.2.2.6 & 3.2.2.7. ALL BATHROOMS, LAUNDRIES, ENSUITES AND WC'S NOT NATURALLY VENTILATED ARE TO BE MECHANICALLY VENTILATED TO COMPLY WITH 1668.2 AND AS/NZS 3666.1 & NCC 2016 PART 3.8.5. WINDOW FRAME AND GLAZING TO BE INSTALLED IN ACCORDANCE WITH AS1288, NCC 2016 VOLUME 2 PART 3.6 AND MANUFACTURERS REQUIREMENTS. POOL FENCING TO COMPLY WITH AS 1926.1 & 2. SMOKE ALARMS TO COMPLY WITH AS 3786 & NCC 2016 VOLUME 2 PART 3.7.2. & QLD FIRE & EMERGENCY SERVICES ACT 1990, AMENDMENT BILL 2016. STAIRS, HANDRAILS AND BALUSTRADES TO COMPLY WITH Part 3.9.1, 3.9.2 NCC 2016 AND AS1170 INCLUDING AS1288. BALUSTRADES TO HAVE A MINIMUM HEIGHT OF 1000mm ABOVE FINISHED SURFACE LEVEL. ENERGY EFFICIENT LIGHTING AS PER NCC 2016 VOLUME 2 PART 3.12 REQUIREMENTS. ALL SHOWER ROSES TO BE AAA RATED WATER PRESSURE NOT TO EXCEED 500kPa FROM ANY OUTLET DWELLING TO BE FITTED WITH "PRESSURE LIMITING DEVICE" ALL TOILETS TO BE 4.5/3 LITRE DUAL FLUSH CISTERNS. GENERAL NOTES: ALL DIMENSIONS AND LEVELS SHALL BE CHECKED ON SITE PRIOR TO COMMENCEMENT OF THE WORKS. DIMENSIONS SHOWN ARE TO FACE OF EXTERNAL FRAME ONLY. DO NOT SCALE. ANY DISCREPENCIES TO BE REPORTED IMMEDIATELY TO BUILDING DESIGNER. THIS PLAN SHALL BE READ IN CONJUNCTION WITH THE ENGINEER'S SOIL REPORT, SLAB DESIGN AND DETAILS. 6mm VILLABOARD TO WET AREA WALLS. N S E W SUNRISE SUNSET SUMMER WINTER RPD LOT PARISH COUNTY AREA: RP 30377 22 REDCLIFFE STANLEY 405m² Rev. Description Date 1 Preliminary Design 3.5.17

CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

PROPOSED RESIDENCE

STORMWATER TO APPROVED

DISCHARGE POINT AS PER

LOCAL AUTHORITY

REQUIREMENTS

18

00

GO

OD

NE

IGH

BO

UR

FE

NC

ING

BY

OT

HE

RS

1800 GOOD NEIGHBOUR FENCING BY OTHERS

18

00

GO

OD

NE

IGH

BO

UR

FE

NC

ING

BY

OT

HE

RS

FFL 11.800 AHDSITE PAD LEVEL 11.500 AHD

BUILDER TO CONFIRM PRESENCE & EXTENT OF EXISTING FILL ON SITE PRIOR TO COMMENCEMENT OF CONSTRUCTION WORKS. ALL EXTERNAL LOAD BEARING WALLS MUST BE FOUNDED ON NATURAL GROUND

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 200

11/25/2017 9:46:57 AM

1

SITE PLAN

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

001

VARIOUS ADDRESSES

CONSTRUCTION NOTESALL WORK TO COMPLY WITH THE BUILDING CODE OF

AUSTRALIA REQUIREMENTS (NCC) AND AUSTRALIAN

STANDARDS AND THEIR MOST CURRENT AMENDMENTS.

ALL LOCAL COUNCIL REQUIREMENTS ARE TO BE MET IN

RELATION TO THE CLASS AND TYPE OF CONSTRUCTION.

BEFORE COMMENCING CONSTRUCTION ALL DIMENSIONS,

EXISTING LEVELS, FINISHED LEVELS AND ALL SITE SERVICES

ARE TO BE VERIFIED BY THE BUILDER.

NOTIFY THE BUILDING DESIGNER OF ANY VARIATION

BETWEEN THE DOCUMENTATION AND SITE CONDITIONS.

WRITTEN DIMENSIONS ARE TO TAKE PRECEDENCE OVER

SCALING FROM THE DRAWINGS. NOTIFY THE BUILDING

DESIGNER OF ANY VARIATIONS OR DISCREPANCIES IN THE

DIMENSIONING OF THE PLANS.

MANHOLE TO BE POSITIONED TO SUIT TRUSS LAYOUT.

POSITION TRUSSES SO AS TO PROVIDE A CLEAR 600mm x

600mm OPENING. MANHOLE POSITION AS INDICATED ON PLAN.

TERMITE PROTECTION TO COMPLY WITH AS 3660 AND AS

3660.1 & NCC 2016 VOLUME 2 PART 3.1.3.

MASONRY ARTICULATION TO COMPLY WITH AS3700-2011 &

TECHNICAL NOTE 61 BY CCAA.

WATERPROOFING OF WET AREAS TO COMPLY WITH AS 3740 -

2010 & NCC 2016 VOLUME 2 PART 3.8.1.

DAMP PROOFING OF GROUND SLAB/ FLOORS TO COMPLY WITH

AS 2870 & NCC 2016 VOLUME 2 PART 3.2.2.6 & 3.2.2.7.

ALL BATHROOMS, LAUNDRIES, ENSUITES AND WC'S NOT

NATURALLY VENTILATED ARE TO BE MECHANICALLY

VENTILATED TO COMPLY WITH 1668.2 AND AS/NZS 3666.1 &

NCC 2016 PART 3.8.5.

WINDOW FRAME AND GLAZING TO BE INSTALLED IN

ACCORDANCE WITH AS1288, NCC 2016 VOLUME 2 PART 3.6

AND MANUFACTURERS REQUIREMENTS.

POOL FENCING TO COMPLY WITH AS 1926.1 & 2.

SMOKE ALARMS TO COMPLY WITH AS 3786 & NCC 2016

VOLUME 2 PART 3.7.2. & QLD FIRE & EMERGENCY SERVICES

ACT 1990, AMENDMENT BILL 2016.

STAIRS, HANDRAILS AND BALUSTRADES TO COMPLY WITH Part

3.9.1, 3.9.2 NCC 2016 AND AS1170 INCLUDING AS1288.

BALUSTRADES TO HAVE A MINIMUM HEIGHT OF 1000mm

ABOVE FINISHED SURFACE LEVEL.

ENERGY EFFICIENT LIGHTING AS PER NCC 2016 VOLUME 2

PART 3.12 REQUIREMENTS.

ALL SHOWER ROSES TO BE AAA RATED

WATER PRESSURE NOT TO EXCEED 500kPa FROM ANY

OUTLET

DWELLING TO BE FITTED WITH "PRESSURE LIMITING DEVICE"

ALL TOILETS TO BE 4.5/3 LITRE DUAL FLUSH CISTERNS.

GENERAL NOTES:

ALL DIMENSIONS AND LEVELS SHALL BE CHECKED ON SITE PRIOR

TO COMMENCEMENT OF THE WORKS.

DIMENSIONS SHOWN ARE TO FACE OF EXTERNAL FRAME ONLY.

DO NOT SCALE. ANY DISCREPENCIES TO BE REPORTED

IMMEDIATELY TO BUILDING DESIGNER.

THIS PLAN SHALL BE READ IN CONJUNCTION WITH THE

ENGINEER'S SOIL REPORT, SLAB DESIGN AND DETAILS.

6mm VILLABOARD TO WET AREA WALLS.

N

S

EW

SUNRISE

SUNSET

SUMMER

WINTER

RPD

LOT

PARISHCOUNTY

AREA:

RP 3037722

REDCLIFFESTANLEY

405m²

Rev. Description Date

1 Preliminary Design 3.5.17

Page 2: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

2

3

4

1

1

300

1

300

2

300

2

300

PT

YR

EF

SP

AC

E

PT

YR

EF

SP

AC

E

7480 5235

2400

4060

1280

1790

1180

1790

2740

5470

1000

800

6310

3190

1280

4660

4670

600 1270 2930 3855 3460

230 2700 190 2700 70 1055 70 3000 230

70 1200 70 1730 230

230 3970 190 1700 70 930 70 1055 70 3000 70 530 230

930 230 2670 70 900 190 2100 70 530 70 1055 70 3000 230 600

600 230 3000 70 900 190 7495 230

230 4570 70 530 70 1780 230

230 7020 230

230

3000

7015

0070

3000

7030

0070

4200

230

2400

800

230

5400

7010

0070

1780

7013

2070

4400

230

1000

230

5400

7010

0070

3000

7015

0070

3000

7036

0023

023

030

9070

1320

1670

1330

230

1180

230

1330

1670

70

930 230 2670 70 900 190

Bed 1Carpet

GarageConcrete

WIRCarpet

Ens.Tiles

Bed 2Carpet

BathTiles

WCTiles

L'dryTiles

Bed 3Carpet

GarageConcrete

Bed 1Carpet

BathTiles

Bed 2Carpet

L'dryTiles

LivingLam. Flooring K

itch

en

Lam

. F

loo

rin

g

LivingLam. Flooring

Kitch

en

Lam

. F

loo

rin

g

NOTE:MECHANICAL VENTILATION REQUIRED TO

ALL BATHROOMS AND WC's

FLOORING PATTERN & LAYOUT SHOWN IS

FOR INDICATIVE PURPOSES ONLY

820

21.24

21.24

820

820

21

.12

720

21

.12

820

820

820

720 720

820

21

.12

21

.12

820

720

720

21

.12

820

21.36 SGD

21

.12

21.36 SGD 18.06 DH

15.1

2A

WN

15.1

2A

WN

18.15 AWN

15.1

2A

WN

15.1

2A

WN

06.0

9S

W

600

NOMINATED TILE

FINISH TO PORCH

NOMINATED TILE

FINISH TO PORCH

1990

2200

W/M TUB

TUB W/M

DP

DP

DP

DP

DP

DP

820

820

RO

BE

RO

BE

RO

BE

RO

BE

LIN

EN

LIN

EN

MB

MB

HOUSE 1

HOUSE 2

3890 2990 4300

Room?

BROOMED CONCRETE

ALFRESCO SLAB

BROOMED CONCRETE

ALFRESCO SLAB

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 100

11/25/2017 9:46:58 AM

1

FLOOR PLAN

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

100

VARIOUS ADDRESSES

Area Schedule

House 1 113 m²

House 2 88 m²

Alfresco 10 m²

Alfresco 9 m²

221 m²

Door Schedule

1 820 SCFD

2 21.24 PLD

3 21.24 PLD

4 820

5 820 HC

6 21.12 PRD

7 720 HC

8 820 HC

9 21.12 PRD

10 820 CSD

11 21.12 PRD

12 820 HC

13 820 HC

14 720 HC

15 720 HC

16 21.12 PRD

17 820 CSD

18 820 HC

19 21.12 PRD

20 820 HC

21 21.12 PRD

22 820 HC

23 720 HC

24 720 HC

Window Schedule

1 18.15 AW XO

2 15.12 AW XO

3 06.09 SW OX OBS TOUGH

4 15.12 AW XO

5 21.36 SGD OXXO

6 18.06 DH

7 21.36 SGD OXXO

8 15.12 AW XO

9 15.12 AW XO

DOOR KEY

SCFD

SC1/3

SOLID CORE EXT FEATURE DOOR

NOTE: FOR SPECIFIC FINISH REFER SPECIFICATION.INTERNAL DOORS 2040mm HIGH, PAINT GRADE, WIDTH AS NOTED.

HC HOLLOW CORE INT. DOOR

HC-2

CSD CAVITY SLIDING DOOR

FSD FACE SLIDING DOOR

SOLID CORE EXT 1/3 GLASS

HOLLOW CORE INT. DOUBLE DOOR

MRD MIRROR ROBE DOOR

PLD PANEL LIFT DOOR

WINDOW KEY

OBS

OBS TGH

OBSCURE GLASS

NOTE: FOR SPECIFIC FINISH REFER SPECIFICATION.

FG FIXED GLASS

LW

SW SLIDING WINDOW

DH DOUBLE HUNG

OBSCURE TOUGHENED GLASS

LOUVRE WINDOW

BF BOTTOM PANEL FIXED

AW AWNING WINDOW

N

S

EW

SUNRISE

SUNSET

SUMMER

WINTER

Rev. Description Date

1 Preliminary Design 3.5.17

© QUANTUM DRAFTING SOLUTIONS 2017.

THESE DRAWINGS REMAIN THE PROPERTY OF QUANTUM

DRAFTING SOLUTIONS & ANY REPRODUCTION EITHER IN FULL

OR IN PART CONSTITUTES A BREACH OF COPYRIGHT ACT 1968.

THE ORIGINAL DESIGNER REMAINS THE OWNER OF ANY

COPYRIGHTS IN THE ARCHITECTURAL DESIGN, EVEN IF THE

CONTRACTOR OR OWNER PAID FOR THE DESIGN.

Page 3: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

SELECTED FACE

BRICK AS PER SPEC

COLORBOND CORRUGATED ROOF

SHEETING @ 7.5° PITCH FIXED TO

MANUF SPEC

FASCIA & GUTTER IN SELECTED

COLOUR FIXED TO MANUF SPEC

PANEL LIFT GARAGE DOOR -

COLOUR AS PER SELECTION

NEWPORT CLADDING

FIXED TO MANUF SPEC

Ceilin

g Heig

ht

2550

DPDP DP DPDP

TIMBER FRAMED

DOORS AS PER SPEC

Ceilin

g Heig

ht

2550

SELECTED FACE

BRICK AS PER SPEC

COLORBOND CORRUGATED ROOF

SHEETING @ 5° PITCH FIXED TO

MANUF SPEC

FASCIA & GUTTER IN SELECTED

COLOUR FIXED TO MANUF SPEC

NEWPORT CLADDING

FIXED TO MANUF SPEC

COLORBOND CORRUGATED ROOF

SHEETING @ 7.5° PITCH FIXED TO

MANUF SPEC

DPDPDPDP

HC

MB

HC

ARTICULATION JOINT IN ACCORDANCE

WITH AS3700 - 2011 & TN61 BY CCAA

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 100

11/25/2017 9:47:00 AM

1

ELEVATIONS 1 & 2

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

200

VARIOUS ADDRESSES

1 : 100

ELEVATION 11

1 : 100

ELEVATION 22

Rev. Description Date

1 Preliminary Design 3.5.17

Page 4: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

SELECTED FACE

BRICK AS PER SPEC

COLORBOND CORRUGATED ROOF

SHEETING @ 7.5° PITCH FIXED TO

MANUF SPEC

FASCIA & GUTTER IN SELECTED

COLOUR FIXED TO MANUF SPEC

NEWPORT CLADDING

FIXED TO MANUF SPEC

COLORBOND CORRUGATED ROOF

SHEETING @ 5° PITCH FIXED TO

MANUF SPEC

DPDP

Ceilin

g Heig

ht

2550

SELECTED FACE

BRICK AS PER SPEC

COLORBOND CORRUGATED ROOF

SHEETING @ 5° PITCH FIXED TO

MANUF SPEC

FASCIA & GUTTER IN SELECTED

COLOUR FIXED TO MANUF SPEC

NEWPORT CLADDING

FIXED TO MANUF SPEC

ARTICULATION JOINT IN ACCORDANCE

WITH AS3700 - 2011 & TN61 BY CCAA

COLORBOND CORRUGATED ROOF

SHEETING @ 7.5° PITCH FIXED TO

MANUF SPEC

DPDPDP

HCHC

MB

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 100

11/25/2017 9:47:01 AM

1

ELEVATIONS 3 & 4

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

201

VARIOUS ADDRESSES

1 : 100

ELEVATION 31

1 : 100

ELEVATION 42

Rev. Description Date

1 Preliminary Design 3.5.17

Page 5: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

11/25/2017 9:47:02 AM

1

PERSPECTIVES

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

202

VARIOUS ADDRESSES

3D View 11

3D View 22

Rev. Description Date

1 Preliminary Design 3.5.17

Page 6: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

COLORBOND CORRUGATED ROOF SHEETING

IN SELECTED MEDIUM COLOUR FIXED TO

MANUF SPEC @ 5° PITCH

ALUMINIUM FASCIA & GUTTER FIXED TO

MANUF SPEC IN SELECTED COLOUR

ROOF TRUSSES TO TRUSS

MANUFACTURER'S DETAIL

Ceilin

g Heig

ht

2550

Joine

ry He

ight

2100

R3.5 INSULATION IN CEILING

SPACE

R2.0 INSULATION &

FOILBOARD TO EXTERNAL

WALLS

GarageLiving Bed 1BathBed 2

HOUSE 2

REINFORCED CONCRETE SLAB &

FOOTINGS TO ENGINEER'S DETAIL

COLORBOND CORRUGATED ROOF SHEETING

IN SELECTED MEDIUM COLOUR FIXED TO

MANUF SPEC @ 7.5° PITCH

ALUMINIUM FASCIA & GUTTER FIXED TO

MANUF SPEC IN SELECTED COLOUR

ROOF TRUSSES TO TRUSS

MANUFACTURER'S DETAIL

Bath Bed 3Bed 1 WC

R3.5 INSULATION IN CEILING

SPACE

R2.0 INSULATION &

FOILBOARD TO EXTERNAL

WALLS

COLORBOND CORRUGATED ROOF SHEETING

IN SELECTED MEDIUM COLOUR FIXED TO

MANUF SPEC @ 5° PITCH

REINFORCED CONCRETE SLAB &

FOOTINGS TO ENGINEER'S DETAIL

CORE FILLED REINFORCED CONCRETE BLOCK

PARTY WALL TO ACHIEVE FRL 60/60/60 min.

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 100

11/25/2017 9:47:03 AM

SECTION 1 & 2

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

300

VARIOUS ADDRESSES

1 : 100100

Section 11

1 : 100100

Section 22

Rev. Description Date

Page 7: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

GARAGE DOOR REBATE

50mm

STEP

LINE OF REBATE

LIN

E O

F R

EB

AT

E

NOTE:EXTERNAL SLABS TO BE POURED SEPARATELY TO HOUSE SLAB

GARAGE DOOR REBATE

2011

0

12715

HB

SHR

WC

SHR

HB

BATH

WC

TUB

HB

SHR

WC HB

SK

TUB

SK

5255

1290

800

1000

5470

2740

1790

1180

1790

1280

4060

600

930

600

7480 5235

600

600

2400

2270

2400

4660

1280

3190

6310

23477

035

85 HB

4335

SHR

4660 WC

084

15 HB

9220 WC

1284

0

SK

1550

0

TUB

1882

0

SK

069

65

SHR

8053 HB

8978

BATH

9520

TUB

013

040

HB

012

390

SHR

1300

0

WC

LIN

E O

F R

EB

AT

E

REINFORCED CONCRETE SLAB & FOOTINGS TO ENGINEER'S DETAILS

0 600 1870 4800 8655 12115

LINE OF REBATE

330

695

1630

05390

HB

6660SHR

7025

HB

04915

WC

6795BATH

06725TUB

05745

SK

9355

HB

10225

WC

11090

SHR

0630

TUB

2225

SK

160

160

160

160

160

50mm

STEP

160

160 160

160

160

160

600 3890 2990 4300 935

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 100

11/25/2017 9:47:03 AM

SLAB PLAN

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

400

VARIOUS ADDRESSES

Rev. Description Date

Page 8: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

FALL

FALL

COLORBOND CORRUGATED ROOF

SHEETING IN SELECTED MEDIUM

COLOUR FIXED TO MANUF SPEC @

7.5° PITCH

ALUMINIUM FASCIA & GUTTER FIXED TO

MANUF SPEC IN SELECTED COLOUR

COLORBOND CORRUGATED ROOF

SHEETING IN SELECTED MEDIUM

COLOUR FIXED TO MANUF SPEC @ 5°

PITCH

DP

DP

DP

DP

DP

DP

DP

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 100

11/25/2017 9:47:04 AM

ROOF PLAN

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

401

VARIOUS ADDRESSES

Roof Quantities

265.72 m²

Fascia Quantities

93.74 m

Grand total 93.74 m

Gutter Quantities

40.20 m

Grand total 40.20 m

DOWNPIPE - 90mm Ø PVCGUTTER PROFILE - AS PER SPECCROSS SECTION - ≥ 8100mm²

Rev. Description Date

Page 9: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

PROVIDE WATER & ELECTRICITY

CONDUIT TO KITCHEN ISLAND BENCHES

SINGLE GPO IN CEILING

FOR PANEL LIFT DOOR

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 100

11/25/2017 9:47:05 AM

ELECTRICAL PLAN

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

600

VARIOUS ADDRESSES

ELECTRICAL LEGEND

ROUND FLUORESCENT

DOWNLIGHT - 240V FLUORESCENT

DOWNLIGHT - 240V INCANDESCENT

DOWNLIGHT - 12V

PENDANT LIGHT

WALL MOUNTED BUNKER (HT AFL)

WALL MOUNTED UP/DOWN (HT AFL)

WALL MOUNTED VANITY (HT AFL)

SYMBOL DESCRIPTION

LIGHTING/ FAN

BOLLARD

SPOTLIGHT

BATTEN FLUORESCENT DOUBLE

CEILING FAN

CEILING FAN WITH LIGHT

EXHAUST FAN

EXHAUST FAN DUCTED

DRAFTSTOPPA

SWITCH - SENSOR

DOUBLE GPO

WEATHER PROOF SINGLE GPO

WEATHER PROOF DOUBLE GPO

DATA SOCKET

HEATER (2), LIGHT, FAN COMBO

POWER/ SWITCH

SWITCH

SURGE PROTECTED DOUBLE GPO

ELECTRICAL METER BOX

INTERNAL SWITCH BOARD

HEATER (4), LIGHT, FAN COMBO

TV POINT

PHONE POINT

OTHERS

SMOKE DETECTOR

HOT WATER SYSTEM

GAS HOT WATER SYSTEM

CEILING OYSTER

BATTEN LIGHT (NO FITTING)

F

I

1800

1800

2100

2

+

2

S

HWS

G

WALL MOUNTED RECESSED LIGHT

2

TV FOXTEL POINT

SINGLE GPO

DOORBELL

EXHAUST FAN WITH LIGHT

SPOTLIGHT WITH SENSOR

DOWNLIGHT - 12V SENSOR

ELECTRICAL POINT HEIGHTS

DESCRIPTION

GPO - STANDARD

ABOVE FFL

GPO - FRIDGE/ FREEZER

GPO - DISHWASHER

GPO - RANGEHOOD

GPO - WM / DRYER

GPO - REMOTE GAR. DOOR

METER BOX TEMP POWER

PHONE OUTLET - WALL

PHONE OUTLET - TYPICAL

TELEVISION OUTLET

LIGHT SWITCHES

300, 500 TO CNR

1100

1700

AS REQUIRED

CEILING -3m BACK

IN METER BOX

1400

300

300

AS REQUIRED

AS REQUIRED

GPO - ABOVE BENCHES

1100

SWITCH - SENSOR 2000

DOORBELL 1100

Rev. Description Date

Electrical Fixture Schedule

Elec - GPO: GPO - DOUBLE 23

Elec - GPO: GPO - SINGLE 4

Elec - GPO: GPO - WEATHER PROOF DOUBLE 2

Elec - Meter Box: METER BOX - ELECTRICAL 2

Elec - Phone Point: PHONE POINT 2

Elec - Smoke Detector: SMOKE DETECTOR 7

Elec - Switch: SWITCH 20

Elec - TV Point: TV POINT 2

Lighting Fixture Schedule

Elec - Batten Fluro: BATTEN FLUORO SINGLE 2

Elec - Downlight - 12V: DOWNLIGHT 12V FIXED 27

Elec - Exhaust Fan: EXHAUST FAN 1

Elec - Heater-Fan-Light: Elec - Heater-Fan-Light 3

Elec - Wall Light - Up Down: WALL MOUNTED

UP/ DOWN

4

Page 10: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

7002

1100 800

1100

2200

1100

2100

450

750

900

CT

UBO

RHREF

SPACE

250

1850

630 2836 934

700

4

TUB

W/M

SPACE

900

600

200

10mm WATERSHIELD

PLASTERBOARD

INTERNAL LINING

7006

7

SHOWER

MIRROR

BATH

HB2000

1200

6mm VILLABOARD

INTERNAL WALL LINING TO

BATHROOM WALLS typ.

200

1200 200 HIGH SKIRTING

TILE typ.BATH

HB HB

700 9

10

2000 200

900

SHOWER

HB

MIRROR

6mm VILLABOARD

INTERNAL WALL LINING TO

BATHROOM WALLS typ.

SHOWER

HB

WC

2000

200

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 50

11/25/2017 9:47:06 AM

INTERNAL ELEVATIONS

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

700

VARIOUS ADDRESSES

NOTE:TILE LAYOUT IS INDICATIVE ONLY.TILE SET OUT TO BE AGREED ON SITE PRIOR TO COMMENCEMENT OF TILING.

Rev. Description Date

1 : 50

House 1 Kitchen1

1 : 50700

House 1 Kitchen2

1 : 50

House 1 Laundry3

1 : 50700

House 1 Laundry4

1 : 50

House 1 Bathroom5

1 : 50700

House 1 Bath 16

1 : 50700

House 1 Bath 27

1 : 50

House 1 Ensuite8

1 : 50700

Ensuite 19

1 : 50700

Ensuite 210

Page 11: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

701 2

REF

SPACE

630 1526 934

UBO

CT

RH

2100

600

600

900

250

1850

701

4W/M

SPACE

TUB

900

600

701

6

MIRROR

WC

SHOWER

HB

900

200

900

2000

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

1 : 50

11/25/2017 9:47:07 AM

INTERNAL ELEVATIONS

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

701

VARIOUS ADDRESSES

Rev. Description Date

1 : 50

House 2 Kitchen1

1 : 50701

House 2 Kitchen2

1 : 50

House 2 Laundry3

1 : 50701

House 2 Laundry4

1 : 50

House 2 Bathroom5

1 : 50701

House 2 Bathroom6

Page 12: CONSTRUCTION NOTES - Bartercardwaterproofing of wet areas to comply with as 3740 - 2010 & ncc 2016 volume 2 part 3.8.1. damp proofing of ground slab/ floors to comply with as 2870

CORE FILLED REINFORCED

CONCRETE BLOCK PARTY WALL

FRL 60/60/60 minROOF BATTENS MAY PASS

OVER SEPARATING WALL

MINERAL FIBRE OR OTHER SUITABLE

FIRE-RESISTING MATERIAL

NON-COMBUSTIBLE

ROOF CLADDING

ROOF FRAME TO TRUSS

MANUFACTURER'S DETAILS

CEILING

DWELLING UNIT DWELLING UNIT

INTERNAL PLASTERBOARD

LINING FIXED TO BATTENS

R3.5 INSULATION IN CEILING

SPACE

REINFORCED CONCRETE SLAB &

FOOTINGS TO ENGINEER'S DETAIL

SELECTED FACE BRICK AS

PER BUILDERS RANGE

TIMBER STUD WALL FRAME AS

PER FRAMING SCHEDULE /

ENGINEER'S DETAILS

160

SLAB EDGE REBATE -

REFER SLAB PLAN

35

STUDS TO BE TRENCHED

INTO BOTTOM PLATE

G.I. Stirrup cast in concrete

to manufacturer's spec.

2/M16 Bolts

H3 treated HWD Posts as

specified. Refer to Floor Plan &

Elevations

100mm Thick Reinforced

Concrete Slab SL82 Mesh 40

Cover Top

450Ø x 900dp BORED

PIERS typ.

200

300

900

MIN BEARING

100KPa IN STIFF

NATURAL GROUND

7512

012

0

450 Ø

N12 'L' BAR

m: 0415 642 727

e: [email protected]

w: www.quantumdrafting.com.au

P.O. Box 152 Arana Hill Q 4054

QBCC Licence: 1247149

Scale

checked by

drawn by

date

project number

As indicated

11/25/2017 9:47:07 AM

DETAILS

DKMT_A

DUAL KEY DESIGN

GREG McLAREN

3.5.17

ADH

ADH

800

VARIOUS ADDRESSES

Rev. Description Date

1 : 50

Party Wall Detail1

1 : 20

Slab Edge Detail2

1 : 20

Post Footing Detail3