Chiller Plant Optimization Smid

Embed Size (px)

Citation preview

  • 8/11/2019 Chiller Plant Optimization Smid

    1/32

    Mike Smid - TEC

    Vice President Commercial Sales

    Chilled Water Optimization Class

  • 8/11/2019 Chiller Plant Optimization Smid

    2/32

    Agenda

    Objective

    Weather

    Determinants of Chiller Energy Consumption

    SPLV vs. IPLV

    The Life Cycle Point

    Questions

  • 8/11/2019 Chiller Plant Optimization Smid

    3/32

    Objective

    Design and implement a chilled water systemthat reliably delivers real

    and verifiable energy savings, running under the operating conditionsencountered in everyday life.

    Three Pillars:

    System Performance

    Optimize total energy(not sub components)

    System Reliability

    Under normal operating conditions

    Under stress

    Verifiable Energy SavingsAccurate, appropriate metrics

  • 8/11/2019 Chiller Plant Optimization Smid

    4/32

    Agenda

    Objective

    Weather Determinants of Chiller Energy

    Consumption

    SPLV vs. IPLV The Life Cycle Point

    Questions

  • 8/11/2019 Chiller Plant Optimization Smid

    5/32

    Chicago Weather 24 x 7 73.8% of hours have less than 70 F entering condenser water

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    95-90 85-80 75-70 65-60 55-50 45-40

  • 8/11/2019 Chiller Plant Optimization Smid

    6/32

    Chicago Weather 12 x 5 73.3% of hours have less than 70 F entering condenser water

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    0

    200

    400

    600

    800

    1000

    1200

    1400

    95-90 85-80 75-70 65-60 55-50 45-40

  • 8/11/2019 Chiller Plant Optimization Smid

    7/32

    Charlotte Weather 24 x 7

    68% of hours have less than 70.4 F entering condenser water

    7

  • 8/11/2019 Chiller Plant Optimization Smid

    8/32

    Charlotte Weather 12 x 5

    58% of hours have less than 70 F entering condenser water

    8

  • 8/11/2019 Chiller Plant Optimization Smid

    9/32

    Cooling Tower

    As the ambient wet bulb drops colder condenser

    water can be delivered to the chiller(s).

    VFDs on centrifugal chillers track the weather.

  • 8/11/2019 Chiller Plant Optimization Smid

    10/32

    Agenda

    Objective

    Weather

    Determinants of Chiller Energy

    Consumption

    SPLV vs. IPLV The Life Cycle Point

    Questions

  • 8/11/2019 Chiller Plant Optimization Smid

    11/32

    Like pumps, chiller energy consumption is a functionof mass flow and differential pressure.

    kW = Tons Lift

    Compressor Input kW ~

    Mass Flow X Lift

    Load

    Chiller

    Cooling

    Tower

    Compressor/Cycle

    Efficiency

    Chiller Efficiency

  • 8/11/2019 Chiller Plant Optimization Smid

    12/32

    For refrigerant to

    condense, it must bewarmer than leaving

    condenser water.

    95 F + 2F approach = 97F

    To boil, refrigerant must be

    colder than leavingchilledwater.

    44F 2F approach = 42F

    Refrigerant temperatures are based on leavingwatertemperatures!

    54F

    44F

    85F

    95F

    Compressor Work (Lift)

  • 8/11/2019 Chiller Plant Optimization Smid

    13/32

    42 F / 40 PSI

    97 F / 120 PSI

    82F / 90 PSI

    SAT.

    LIQUID

    SAT.

    VAPOR

    Refrigerant Effect

    (Capacity)

    Heat Rejection

    Enthalpy

    SCT

    Reduced Lift

    Pressure

    42

    82

    97

    SST

    Lower Lift = Less Work = Lower kW

    Compressor Work (Lift)

  • 8/11/2019 Chiller Plant Optimization Smid

    14/32

    VFD Driven Chillers take advantage of lift and / or load reductionto reduce energy consumption.

    Mechanicalunloading

    Variablespeedunloading

    Chiller Efficiency

  • 8/11/2019 Chiller Plant Optimization Smid

    15/32

    0102030

    405060708090

    100

    14%20%25%31%37%43%49%56%62%68%75%81%87%Total Building Load %

    Op

    eratingHours

    Individual

    Chiller

    Load %

    Design Day

    85F (29.4C)

    ECWT

    Min Tower

    55F (12.8C)

    ECWT

    92% 100%

    Two Chiller Plant Staging

    Distribution of ton-hours

  • 8/11/2019 Chiller Plant Optimization Smid

    16/32

    VFD Driven Chillers take advantage of lift and/or load reductionto reduce energy consumption.

    One chiller at 100% load

    Two chillers at100% load each

    Two Chiller Plant Efficiency

  • 8/11/2019 Chiller Plant Optimization Smid

    17/32

    Agenda

    Objective

    Weather

    Determinants of Chiller Energy

    Consumption

    SPLV vs. IPLV The Life Cycle Point

    Questions

  • 8/11/2019 Chiller Plant Optimization Smid

    18/32

    Agenda

    Objective

    Weather

    Determinants of Chiller Energy

    Consumption

    SPLV vs. IPLV The Life Cycle Point

    Questions

  • 8/11/2019 Chiller Plant Optimization Smid

    19/32

    19

    Performance Metrics

    Full Load, IPLV

    AHRI 550/590 IPLV

    % Load Weight Condition

    100% 1% 44 F / 85 F

    75% 42% 44F / 75 F

    50% 45% 44F / 65F

    25% 12% 44F / 65F

    ARI 550/590 section D2 states:

    The equation (IPLV) was derived to provide arepresentation of the average part load efficiency for a

    single chil ler only.

    Full Load has two components: 100% load and design conditions.

    IPLV is a weighted average of four specific operating points.

  • 8/11/2019 Chiller Plant Optimization Smid

    20/32

    Chicago Weather 24 x 7 73.8% of hours have less than 70 F entering condenser water

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    95-90 85-80 75-70 65-60 55-50 45-40

  • 8/11/2019 Chiller Plant Optimization Smid

    21/32

    21

    Performance MetricsSystem based metrics SPLV (System Part Load Value)

    ARI 550/590 section D2 states:

    The equation (IPLV) was derived to provide a representation of theaverage part load efficiency for a single chiller only. However, it is best

    to use a comprehensive analysis that reflects the actual weather data,

    building load characteristics, operational hours, economizer capabilitiesand energy drawn by auxiliaries such as pumps and cooling towers, whencalculating the chiller and system efficiency. This becomes increasingly

    important with multiple chiller systems because individual chillers

    operating within multiple chiller systems are more heavily loaded than

    single chillers within single chiller systems.

    Actual Local Weather

    Load Profile

    Operating Hours

    Economizer

    Pump, Tower Energy

    Chiller Staging

  • 8/11/2019 Chiller Plant Optimization Smid

    22/32

    22

    Chiller Staging

    Chicago Office Building

    87.5%

    62.5%

    37.5%

    100% Bin

    75% Bin

    50% Bin

    25% Bin

    6

    13

    4

    5

    3 x 400 Ton Chillers: CH-1 (black), CH-2 (Yellow), CH-3 (Blue)

    Minim

    umBuildingLoad

    2

  • 8/11/2019 Chiller Plant Optimization Smid

    23/32

    23

    Performance Metrics

    100% BuildingLoad

    Design Day Weather

    Fully Leased

    Fully Occupied

    Full Solar Load

    Full Equipment and Lighting Load

    Full Ventilation Rates

    < 1% of the operating hours OR MAYBE NEVER

    1

    1

    Are the chillers sized to meet the buildingload exactly or were they maybe

    oversized just a little.

  • 8/11/2019 Chiller Plant Optimization Smid

    24/32

    24

    Performance Metrics

    100% ChillerLoadDesign Leaving Chilled Water

    Design Entering Condenser Water

    No Low Delta T Syndrome!No safety factors when chillers sized

    Tubes fouled to AHRI selection level

    Assumes Chillers not oversized !!!

    Far more ton-hours

    occur at points 3 and 5

    than at point 1

    Variable speed chillershave better 100% load

    efficiency at points 3

    and 5 due to lower lift.

    35 1

    1

    3

    3

    3

    3

    5

    5

    5

    5

    85F70F60F

  • 8/11/2019 Chiller Plant Optimization Smid

    25/32

    25

    Performance Metrics

    SPLV vs. IPLV

    Weighting significantlydifferent.

    SPLV reflects multiple chiller plant stagingSPLV reflects local condenser water temperatures

  • 8/11/2019 Chiller Plant Optimization Smid

    26/32

    26

    Performance Metric

    IPLV weighting issue (multiple chillers)

    IPLV (kW/

    Ton) Single

    Chiller Plant

    Actual Plant

    Chiller A Chiller B Chiller C

    100% 0.640 0.536 0.577

    75% 0.420 0.399 0.39050% 0.280 0.291 0.267

    25% 0.260 0.341 0.301

    IPLV 0.325 0.337 0.314

    SPLV 0.399 0.373 0.362

  • 8/11/2019 Chiller Plant Optimization Smid

    27/32

    2,000 Ton Hotel, with (4) 500 Ton chillers

    Worldwide Study

    75% Load The Life Cycle Point

  • 8/11/2019 Chiller Plant Optimization Smid

    28/32

    75% Load The Life Cycle Point

    2,000 Ton Hotel, with (4) 500 Ton chillers

    Worldwide Study

  • 8/11/2019 Chiller Plant Optimization Smid

    29/32

    600 Ton Office, with (2) 300 Ton chillers

    Carrier Worldwide Study

    75% Load The Life Cycle Point

  • 8/11/2019 Chiller Plant Optimization Smid

    30/32

    30

    Back Up

  • 8/11/2019 Chiller Plant Optimization Smid

    31/32

    31

    System Based Decisions

    Chiller Staging

    Component Calculation

    (1) Chiller at full load* 0.575

    (2) Chillers at 50% load* 0.295

    Delta 0.280

    Capacity (tons) 300

    Savings (per hour) 84 kW

    Compare efficiency at the same temperatures.Compare the AHRI tolerance at the load points

    Compare the pump power consumption

    Consider the minimum evaporator flow rate

    System Calculation

    (1) Chiller at 100% load, 65 F Condenser Water, no AHRI tolerance 0.338 x 1.05% = 0.355

    (2) Chillers at 50% load, 65 F Condenser Water, no AHRI tolerance 0.295 x 1.10% = 0.325

    Capacity (tons) 300

    Chiller Savings 9 kW

    Condenser pump power (750 gpm x 30 ft wg) 6.8 kW

    Evaporator pump power (600 gpm x 20 ft wg)* 3.6 kW

    Extra pump power 10.4 kW

    Net Savings (per hour) -1.4 kW

    * Constant flow application, use minimum flow rate calculation for variable flow systems.

    *Submittal data at 100% and 50%load is often based on two different

    condenser water temperaturesleading to unintended calculation

    error.

    4 Steps to Optimize Chiller staging:

    4

  • 8/11/2019 Chiller Plant Optimization Smid

    32/32

    32

    Questions?