16
CHAPTER(8) Fire Alarm System

Ch8 Fire Alarm System

Embed Size (px)

DESCRIPTION

Design guideline

Citation preview

  • CHAPTER(8)

    Fire Alarm System

  • Chapter (8) Fire Alarm System

    312

    Chapter (8)

    Fire Alarm System

    8.1. Introduction 8.1.1. Why we need fire alarm system? The goal of Fire Safety plans and equipment is to detect and announce fire,

    heat or smoke in real time, so that people may reach safety and buildings

    and information may be protected.

    8.1.2. About the fire Generally, fires are initiated within a single fuel object. The smoke

    produced from the burning objects transported by a smoke plume and

    collects in the upper portion of space as layer. The smoke plume also

    transports the heat produced by the fire into the smoke layer, causing the

    smoke layer to increase in depth and temperature. This smoke layer

    radiates energy back to unburned fuels in the space, causing increase in

    temperature.

    The main combustion products are:

    1. Flame and heat

    2. Smoke

    Smoke considered the most dangerous and is responsible for death

    Cases because it is mainly make oxygen insufficient in indoor fires.

    8.1.3. Classes of fire

    1. Class A fire

    "Class Afire," means a fire involving ordinary combustible as paper,

    wood, cloth, and some rubber and plastic materials.

    2. Class B fire

  • Chapter (8) Fire Alarm System

    312

    "Class B fire" means a fire involving flammable or combustible liquid

    flammable gases, greases and similar materials, and some rubber

    and plastic materials.

    3. Class C fire

    "Class C fire" means a fire involving energized electrical equipment

    where safety to the employee requires the use of electrically

    nonconductive extinguishing media.

    4. Class D fire

    "Class D fire" means a fire involving combustible metals such as

    magnesium, titanium, zirconium, sodium, lithium and potassium.

    8.2. Classification of fire alarm system:

    8.2.1 Household fire alarm system Its tools and instruments that used in houses to give alarm signal for people

    to leave the house in case of fire. In this case, we use a smoke detector, which

    has alarm at the same time. This type operates by batteries and AC current

    and mostly used in kitchens and children rooms.

    8.2.2 Local fire alarm system (for local buildings) The tools and instruments give alarm in manual cases in order to alarm

    people in this building to make the suitable requirements or leaving the

    building.

    8.2.3 Auxiliary fire alarm system It is the system that connecting buildings with fire fighting communication

    center. Moreover, by control circuits we can know place of fire, its

    happening time, and other information. This type widely used in America

    and European countries

  • Chapter (8) Fire Alarm System

    312

    8.3. Basic components of fire alarm system

    1. Initiating devices

    2. Control panel

    3. Signaling devices

    4. Power supply

    These components must be compatible electrically with each other and

    connected by suitable wires to complete system operation as shown in

    figure (8.1);

    Figure (8.1). ''Connection method of fire alarm system components''

  • Chapter (8) Fire Alarm System

    312

    8.4. Types of connecting fire alarm system

    components: 8.4.1. Wire connection

    Class ''A'' type (loop connection); this mean that the wires loop

    connecting control panel to other equipments return to control panel as

    shown in figure(1).

    Class ''B'' type (Zone connection); this mean that the wires loop

    connecting control panel to other equipments don't return to control

    panel, but ended by resistance called ''end line resistance''. The value of

    this resistance do not exceed (1-kilo ohm) and changes due to as shown in

    figure (8.1).

    8.4.2. Wireless connection This type is the latest type of connecting fire alarm components without

    using wires. It has some advantages and disadvantages such as other

    connecting types. However, it has very low economic cost when compared

    with wire connection type

    In our project, we use wire connection classA type because it is

    the most used and available type in wide range.

    8.5. General components (parts) of fire

    alarm system:

    8.5.1. Initiating devices:

    The initiating devices (initiators) have many types we will take about these

    types.

  • Chapter (8) Fire Alarm System

    312

    8.5.1.1. Automatic initiating detectors

    fire alarm system generally depend on area we want to cover it with fire

    alarm system grid .where each fire detector operate approximately in circle

    has radius (8m) , hence we distribute detectors in required area . The

    automatic detectors classified as follows:

    First: Smoke detectors:

    These detectors give alarm when it detects any smoke cutting its

    photoelectric cell .and it has two types;

    Types of Smoke Alarm Sensors:

    There are two primary types of smoke alarm sensors:

    Ionization sensors

    Photoelectric sensors

    Some alarms also include other types of safety sensors, such as heat sensors,

    or carbon monoxide sensors

    1. Ionization Sensors

    Best at detecting fast, flaming fires like grease fires

    Detect combustion particles of .01 to 3 microns (an average human

    hair is about 90 microns)

    Most sensitive to dark or black smoke

    Sensitive to steam, so they may produce false alarms if installed near

    kitchens or bathroom

    Ionization Senor Illustration

  • Chapter (8) Fire Alarm System

    312

    How Ionization Sensors Work?

    Use a weak radiation source (Americium 241) to ionize the air in a

    detector chamber

    The ionized air conducts an electrical current

    The detector circuit senses this current; if it is present, the alarm does

    not sound

    Smoke particles interfere with the current flow; when the current is

    reduced, the alarm sounds

    2- Photoelectric Sensors

    Best at detecting slow, smoldering fires like furniture ignited by a

    cigarette

    Detect combustion particles of .3 to 10 microns

    Most sensitive to light gray smoke

    Not very sensitive to steam, so they are better for use near kitchens or

    bathrooms

    Higher power requirements than ionization

    How Photoelectric Sensors Work?

    An LED creates a beam of infrared light in the detector chamber

    The detector circuit senses this light; if it is present, the alarm does

    not sound

    Figure (8.2). ''different shapes of smoke detectors

  • Chapter (8) Fire Alarm System

    312

    Smoke particles scatter the light, and reduce the amount that reaches

    the detector; when the amount of light is reduced, the alarm sounds

    There is some types of smoke detectors according to kind of building

    ,some of this detectors are:

    I. addressable smoke detector

    This detector is the most type used in buildings, small and large

    rooms, and passes. This type should not use near air soaker or fan

    II. smoke addressable ducts detector

    This type placed on return duct of central air conditioning in order to

    detect a smoke communing from fire area. If it placed on supply duct,

    it does not detect any smoke because all air communing from air

    conditioner is fresh air .and it is shown in figure (8.3);

    III.receive and transmitter laser beam detector

    This type contains two detectors opposite to each other and third

    apparatus analogy the alarm signal and transmitted it to control panel.

    It used in long paths closed with glass (sky light way).

    Smoke addressable air duct detector multi use detector

    Figure (8.3) ''other shapes of smoke detectors''

  • Chapter (8) Fire Alarm System

    332

    Second: Heat detectors

    The detectors give alarm with increase of temperature rise above certain

    limit. This happened by expansion of a material inside the detector

    therefore, close the fire circuit and giving alarm. it has two types;

    I.addressable fixed heat detector:

    This type depends on fixed temperature. it do not operate unless

    temperature exceed its setting value, so if there is a gradually rise in

    temperature, it do not give alarm. This type is not secure 100%.

    II.Addressable rate of rise heat:

    This type depends on rate of heat change. Moreover, it is the best type

    because it gives alarm with any up normal change in temperature.

    We use the two types of heat detectors in our hotel project when we

    designed fire alarm system

    Third: multi use detectors These detectors operate as heat and smoke detectors in the same time. This

    type used in active places that need the two types of detectors (heat and

    smoke). One detector of this type showed in figure (8.3)

    Fourth: gas detector These types of detectors operate in case of gas pipes. It used on pipes in

    order to detect any Infiltration in gas

    8.5.1.2. Manual initiating detectors;

    These devices operate manually to make fire alarm when any person see

    afire or feel it, or when automatic detectors have any fault or not operate.

    From these devices, manual pull station (break glass) and they have many

    types and shapes as shown in figure (8.4);

  • Chapter (8) Fire Alarm System

    331

    Figure (8.4)''two types of break glass manual detectors ''

    This type operates by giving alarm signal the glass on it is broken by any

    one. It has many types such as firefighter telephone.

    8.6. Control panels of fire alarm system: It is the device that analysis the signals coming from initiating detectors and

    give instructions of (alarms not alarm)to signaling devices. Some of control

    panels have displays from it we can know all information about date and

    time of fire and incorrect alarms. Some shapes of control panels shown in

    figure (8.5)

    There are many methods of connecting control panel with other devices.

    The following figures (6, 7, and 8) show how to connect fire alarm system

    components;

    Figure (8.5)some shapes of control panels

  • Chapter (8) Fire Alarm System

    333

    8.7. Fire Alarm system Power Sources: AC power (hard wired) linked to normal AC wiring system

    Most have a battery backup in case AC power fails

    Batteries

    9-volt carbon zinc (general purpose)

    9-volt alkaline

    9-volt lithium (ten year battery)

    Large rechargeable lead-acid or gel cells

    AC Power

    Most dependable (at least if backup batteries are maintained

    properly)

    Cost-competitive with battery power for new construction but

    expensive to retrofit in older buildings

    Normally used as the primary power source for centrally controlled

    alarm systems

  • Chapter (8) Fire Alarm System

    332

    Battery (DC) Power

    Fairly dependable if batteries are checked and replaced consistently

    Inexpensive and easy to install, even in older buildings

    Often used as the primary power source for self-contained

    independent alarms

    Limited power for horns and auxiliary function

    8.8. Fire alarm system Maintenance: Fire alarm system requires regular maintenance, which includes:

    Maintenance of Power Supply

    Cleaning of Sensor and Air Passages

    Regular Testing

    Replacement of outdated Sensors or Alarms

    8.8.1. Power Supply Maintenance:

    For AC powered alarms:

    Check AC power supply monthly (or more often)

    Replace backup batteries as recommended by the alarm

    manufacturer

    For battery powered alarms:

    Test alarm weekly (or as directed by manufacturer)

    Replace batteries:

    Every six months for general purpose or alkaline batteries

    When alarm signals low battery or fails test for lithium batteries

    8.8.2. Fire Alarm system Testing:

    AC powered alarms should be tested monthly, or more often if the

    manufacturer or codes require

    Battery powered alarms should be tested weekly, unless the

    manufacturer recommends otherwise

    One of the most common reasons for failed smoke alarms is a lack of

    regular testing

    8.8.3. Replacing Outdated Alarms:

  • Chapter (8) Fire Alarm System

    332

    The recommended service life for most smoke alarms is ten years

    After that point, electronic failure becomes likely

    If an alarm system has separate sensors, the sensors and other

    manufacturer-recommended components should be replaced

    If the alarm is self-contained, the entire alarm should be replaced

    8.8.8. Nuisance Alarms:

    Nuisance alarms occur when the alarm sounds without a fire being

    present

    Often called false alarms, but in most cases theyre not the alarm

    does detect something

    Usually caused by exposing the alarm to smoke, combustion products

    or steam

    From tobacco smokers

    From wood-burning stoves or fireplaces

    From kitchens and bathrooms

    8.8.6. Reducing Nuisance Alarms:

    Locate alarms and sensors away from areas where they will be

    exposed to smoke, other combustion products or steam

    Clean the alarm regularly

    Maintain the alarm power supply (low power can sometimes trigger

    a true false alarm)

    Avoid activities that trigger the alarm

    8.8.7. Other Problems with fire alarm system:

    Lack of Power

    Usually due to failure to test alarm and replace battery as needed

    Electronic failure

    Rare, but it happens testing is important!

    Deliberately disabled alarms

    Usually due to nuisance alarms, but may also be done to get alarm

    battery

  • Chapter (8) Fire Alarm System

    332

    Type of Alarm Selection:

    If you want to use an alarm with a long life lithium battery, you will

    have to use an alarm with an ionization sensor. because Photoelectric

    alarms require more power and are not currently offered with lithium

    batteries

    If the power source is not a limitation, use the type of alarm most

    suitable for the site

    Photoelectric alarms work best in or near kitchens, bathrooms,

    laundry rooms and other areas where steam may be present

    Both sensor types work well in other areas

    Use hardwired (AC powered) linked alarms in new construction

    8.9. How to select the suitable alarm system? If you want to use an alarm with a long life lithium battery, you will

    have to use an alarm with an ionization sensor

    Photoelectric alarms require more power and are not currently

    offered with lithium batteries

    If the power source is not a limitation, use the type of alarm most

    suitable for the site

    Photoelectric alarms work best in or near kitchens, bathrooms,

    laundry rooms and other areas where steam may be present

    Both sensor types work well in other areas

    Use hardwired (AC powered) linked alarms in new construction

    8.10. Alarm Location: Installing smoke alarms in proper locations is important

    Alarms that are installed in the wrong location may:

    Not provide adequate warning of fire or smoke

    Fail prematurely due to heat, cold, etc.

    Produce nuisance alarms

    You may need to install alarms inside a bedroom in special

    circumstances, such as where a resident smokes in bed

  • Chapter (8) Fire Alarm System

    332

    Install at least one alarm on each occupied level of the house

    including the basement, if it is regularly occupied

    Do not install smoke alarms

    In or near kitchens, bathrooms or laundry rooms, if the alarm has an

    ionization sensor

    In attics, cellars or other areas that become very hot, cold or dusty

    On un-insulated exterior walls or ceilings that are not insulated from

    the roof (the alarm will get too hot and/or cold)

    Do not install smoke alarms

    In the dead air zones that occur within two feet of any corner of a

    room or hallway

    8.11. An Example showing distribution of

    fire detectors on basement floor;

  • Chapter (8) Fire Alarm System

    332