BUS-BAR POLYMERIC SUPPORTSSTRICT BUS- BAR
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BARAIZ-10-1L63-4 UHL1-AIZ-10-4L125-4 UHL1
CONDITIONAL DESIGNATION
63-125 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-L...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
AIZ-10-L...-4 UHL1
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1L,2L,3L - 1,2,3 - horizontal flat bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13 The outdoor application bus- bar supports AIZ-10-L are used for fixing the flat rigid bus- bars in horizontal position at 10 (20) kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-L are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
Building height H, mm
Weight, kgQuantity / widthbus- bar mm
Picture
AIZ-10-1L63-4U HL1
AIZ-10-1L80-4U HL1
AIZ-10-1L100-4U HL1
AIZ-10-1L125-4U HL1
AIZ-10-2L63-4U HL1
AIZ-10-2L80-4U HL1
AIZ-10-2L100-4U HL1
AIZ-10-2L125-4U HL1
AIZ-10-3L63-4U HL1
AIZ-10-3L80-4U HL1
AIZ-10-3L100-4U HL1
AIZ-10-3L125-4U HL1
AIZ-10-4L63-4U HL1
AIZ-10-4L80-4U HL1
AIZ-10-4L100-4UHL1
AIZ-10-4L125-4UHL1
1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
4/63
4/80
4/100
4/125
А
А
А
А
C
C
C
C
В
В
В
В
D
D
D
D
318
322
326
328
338
342
346
348
358
362
366
368
378
382
386
388
6,2
6,2
6,3
6,5
6,5
6,5
6,6
6,7
6,7
6,8
6,8
6,9
6,9
7,0
7,0
7,2
Rigid bus- barsupport type
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ10-L...-4 UHL1
H
Рic.В Рic.D
Рic.CРic.А
see table
H
HH
10
12
75
13
nominal voltage, kV10-
292AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR BOX-SHAPED RIGID BUS-BARSAIZ-10-P100-4UHL- AIZ-10-P250-4 UHL
30
10
2
30
29
AIZ-10-P...-4 UHL1
31,5
1480
1
127х4 отв. 13
The outdoor application bus- bar supports AIZ-10-P are used for fixing the box-shaped rigid bus- bars at 10(20) kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231, TS3414-005-59116459-06. The bus- bar supports AIZ-10-P are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
Building height H, mm
Weight, kgWidth of box -bus- bar mm
AIZ-10-P100-4 U HL1
AIZ-10-P125-4 UHL1
AIZ-10-P150-4 UHL1
AIZ-10-P175-4 UHL1
AIZ-10-P200-4 UHL1
AIZ-10-P225-4 UHL1
AIZ-10-P250-4 UHL1
100
125
150
175
200
225
250
412
437
462
487
512
537
562
10,60
10,70
10,80
10,95
11,10
11,30
11,50
Rigid bus- barsupport type
BUS-BAR SUPPORTS FOR BOX-SHAPED RIGID BUS-BARS AIZ-10-P...-4 UHL1
Ø13
4 hol. Ø159
Ø127
10
12
75
13
Н
CONDITIONAL DESIGNATION
100-250 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-P...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
P - the box-shaped rigid bus- bars
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
127х4 hol. 13
nominal voltage, kV10-
293AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR
FOR THE 10KV CURRENT AIZ-10-1M63-4 UHL1-AIZ-10-3M125-4 UHL1 AIZ-10-М...-4 UHL1
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ-10-М...-4 UHL1
The outdoor application bus- bar supports AIZ-10-M are used for fixing the flat rigid bus- bars in vertical position at 10 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
AIZ-10-1M63-4U HL1
AIZ-10-1M80-4 UHL1
AIZ-10-1M100-4 UHL1
AIZ-10-1M125-4 UHL1
AIZ-10-2М63-4 UHL1
AIZ-10-2М80-4 UHL1
AIZ-10-2М100-4 UHL1
AIZ-10-2М125-4 UHL1
AIZ-10-3М63-4 UHL1
AIZ-10-3М80-4 UHL1
AIZ-10-3М100-4 UHL1
AIZ-10-3М125-4 UHL1
1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
A
A
A
A
C
C
C
C
В
В
В
В
362
380
400
425
362
380
400
425
362
380
400
425
5,90
5,96
6,09
6,15
5,92
5,98
6,11
6,17
5,94
6,00
6,13
6,19
Рic.C
H
Рic.А
А
Рic.В
Ø13
4 hol. Ø159
Ø127
CONDITIONAL DESIGNATION
69-125 - width of vertical bus-bar in mm.
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-М...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1M,2M,3M - 1,2,3 - flat vertical bus-bars
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
see table
10
12
75
13
nominal voltage, kV10-
Building height H, mm
Weight, kgQuantity / widthbus- bar mm
PictureRigid bus- barsupport type
294AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR BOX-SHAPED RIGID BUS-BARSAIZ-10-Z-4UHL1 AIZ-10-Z...-4 UHL1
1
POLYMER BUS-BAR SUPPORTS FOR RIDING BUS-BAR AIZ-10-Z....-4 UHL1 The outdoor bus- bar supports AIZ-10-Z are used for aluminum tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-10-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply polymer bus-bar supports with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
Building height H, mm
Weight, kgDiameter
of rigid bus-bar tube, mm
Рic.№Diameter
D, мм
AIZ-10-Z30-4U HL1
AIZ-10-Z40-4 UHL1
AIZ-10-Z50-4 UHL1
AIZ-10-Z70-4 UHL1
AIZ-10-Z80-4 UHL1
AIZ-10-Z90-4 UHL1
AIZ-10-Z100-4 UHL1
AIZ-10-Z110-4 UHL1
AIZ-10-Z120-4 UHL1
AIZ-10-Z130-4 UHL1
AIZ-10-Z140-4 UHL1
AIZ-10-Z150-4 UHL1
AIZ-10-Z170-4 UHL1
AIZ-10-Z200-4 UHL1
AIZ-10-Z250-4 UHL1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
30/25
40/35
50/45
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
30
40
50
70
80
90
100
110
120
130
140
150
170
200
250
359
359
360
370
378
382
394
400
402
415
420
430
450
470
495
12,8
12,9
13,2
13,5
14,7
15,0
15,2
13,5
14,0
18,0
18,0
19,1
20,2
24,3
30,2
Rigid bus- barsupport type
А
D
Рic.1 Рic.2
Ø13
4 hol. Ø159
Ø127
D
Н
А
CONDITIONAL DESIGNATION
Z -rigid connection of aluminium tubular bus-bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-Z...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
30-250- diameter of aluminium tubular bus-bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
295AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARSAIZ-10-SH50-4UHL- AIZ-10-SH250-4 UHL
AIZ-10-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-10-SH are used for hinged fastening of tubular rigid bus-bar at 10 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-10-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply polymer bus-bar supports with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-10-SH50-4U HL1
AIZ-10-SH60-4 UHL1
AIZ-10-SH70-4 UHL1
AIZ-10-SH80-4 UHL1
AIZ-10-SH90-4 UHL1
AIZ-10-SH100-4 UHL1
AIZ-10-SH110-4 UHL1
AIZ-10-SH120-4 UHL1
AIZ-10-SH130-4 UHL1
AIZ-10-SH140-4 UHL1
AIZ-10-SH150-4 UHL1
AIZ-10-SH170-4 UHL1
AIZ-10-SH200-4 UHL1
AIZ-10-SH250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
370
380
405
410
410
415
425
425
435
440
440
460
470
495
15,0
15,0
15,5
16,0
16,4
17,0
17,5
17,5
18,0
18,5
18,7
20,5
22,2
23,9
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIDING BUS-BAR AIZ-10-SH...-4 UHL1
А Ø13
4 hol.
А
Ø159
Ø127
H
D
rotationangle
50-250- rigid fastening aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-SH...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
SH - hinging aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
296AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTAN AIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
AIZ-10-D50-4U HL1
AIZ-10-D60-4U HL1
AIZ-10-D70-4U HL1
AIZ-10-D80-4U HL1
AIZ-10-D90-4U HL1
AIZ-10-D100-4U HL1
AIZ-10-D110-4U HL1
AIZ-10-D120-4U HL1
AIZ-10-D130-4U HL1
AIZ-10-D140-4U HL1
AIZ-10-D150-4U HL1
AIZ-10-D170-4U HL1
AIZ-10-D200-4U HL1
AIZ-10-D250-4U HL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARSAIZ-10-D...-4 UHL1 AIZ-10-D...-4 UHL1
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-10-D...-4 UHL1
The outdoor bus- bar supports AIZ-10-D are used for flexible fitting of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-10-D are included in the integrated rigid bus-bar project of substations.
370
380
405
410
410
415
425
425
435
440
440
460
470
495
15,0
15,0
15,5
16,0
16,4
17,0
17,5
17,5
18,0
18,5
18,7
20,5
22,2
23,9
А Ø13
4 hol.
А
Ø159
Ø127
H
D directionmovement
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
CONDITIONAL DESIGNATION
70-250- rigid fastening aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-D...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
D-movable fastening aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10 -
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
297AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BARAIZ-10-К50-4 UHL1 - AIZ-10-К250-4 UHL1
29
AIZ-10-К...-4 UHL1
The outdoor bus- bar supports AIZ-10-K are used for end fixation of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply polymer bus-bar supports with adjusting sizes of bottom flange according clients request.
AIZ-10-К50-4U HL1
AIZ-10-К60-4U HL1
AIZ-10-К70-4U HL1
AIZ-10-К80-4U HL1
AIZ-10-К90-4U HL1
AIZ-10-К100-4U HL1
AIZ-10-К110-4U HL1
AIZ-10-К120-4U HL1
AIZ-10-К130-4U HL1
AIZ-10-К140-4U HL1
AIZ-10-К150-4U HL1
AIZ-10-К170-4U HL1
AIZ-10-К200-4U HL1
AIZ-10-К250-4U HL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
335
338
365
370
370
385
385
390
400
410
440
460
490
495
12,0
12,0
12,1
12,2
12,4
12,7
14,5
14,8
14,9
15,0
15,3
15,5
15,7
15,9
BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-10-К...-4 UHL1
АØ13
4 hol.А
Ø159
Ø127H
D
8AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-К...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
К - end fastening aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
Building height H, mm
Weight, kgDiameter
D, ммRigid busbarsupport type
Diameterof rigid bus-bar
tube, mm
AIZ-10-I50-4U HL1
AIZ-10-I60-4U HL1
AIZ-10-I70-4U HL1
AIZ-10-I80-4U HL1
AIZ-10-I90-4U HL1
AIZ-10-I100-4U HL1
AIZ-10-I110-4U HL1
AIZ-10-I120-4U HL1
AIZ-10-I130-4U HL1
AIZ-10-I140-4U HL1
AIZ-10-I150-4U HL1
AIZ-10-I170-4U HL1
AIZ-10-I200-4U HL1
AIZ-10-I250-4U HL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
18,0
18,0
18,5
19,0
19,4
20,0
20,5
20,5
21,0
21,5
21,7
23,5
25,2
26,9
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBEAIZ-10-I-4UHL1 AIZ-10-I...-4 UHL1 AIZ-10-I...-4 UHL1
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-10-I...-4 UHL1
The outdoor bus- bar supports AIZ-10-I are used for flexible connection of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply polymer bus-bar supports with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
Ø13
4 hol.
А
Ø159
Ø127
А
H
SizeL, мм
360
360
400
400
420
420
450
460
460
460
480
500
520
520
370
380
405
410
410
415
425
425
435
440
440
460
470
495
directionmovement
directionmovement
Diameterof rigid bus-bar
tube, mm
Building height H, mm Weight, kg
DiameterD, мм
Rigid bus- barsupport type
CONDITIONAL DESIGNATION
50-250- rigid fastening aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ -10-I...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
I -movable connection of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
299AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBEAIZ-10-Е50-4 UHL1 - AIZ-10-Е250-4 UHL1
29
AIZ-10-Е...-4 UHL1
The outdoor bus- bar supports AIZ-10-E are used for double fixation of aluminium tube with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply polymer bus-bar supports with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-10-Е50-4U HL1
AIZ-10-Е60-4U HL1
AIZ-10-Е70-4U HL1
AIZ-10-Е80-4U HL1
AIZ-10-Е90-4U HL1
AIZ-10-Е100-4U HL1
AIZ-10-Е110-4U HL1
AIZ-10-Е120-4U HL1
AIZ-10-Е130-4U HL1
AIZ-10-Е140-4U HL1
AIZ-10-Е150-4U HL1
AIZ-10-Е170-4U HL1
AIZ-10-Е200-4U HL1
AIZ-10-Е250-4U HL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
360
370
370
378
394
400
400
402
415
430
430
450
470
470
13,0
13,0
13,1
13,2
13,4
13,7
15,5
15,8
15,9
16,0
16,3
16,5
16,7
16,9
BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-10-Е...-4 UHL1
А Ø13
4 hol.
А
Ø159
Ø127
H
D
10AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-Е...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
Е - double-grip aluminum tube
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
Diameterof rigid bus-bar
tube, mm
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
AIZ-10-С50-4U HL1
AIZ-10-С60-4U HL1
AIZ-10-С70-4U HL1
AIZ-10-С80-4U HL1
AIZ-10-С90-4U HL1
AIZ-10-С100-4U HL1
AIZ-10-С110-4U HL1
AIZ-10-С120-4U HL1
AIZ-10-С130-4U HL1
AIZ-10-С140-4U HL1
AIZ-10-С150-4U HL1
AIZ-10-С170-4U HL1
AIZ-10-С200-4U HL1
AIZ-10-С250-4U HL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
620
630
655
660
660
665
675
685
685
690
690
710
740
780
30,5
31,6
32,0
33,0
34,2
35,0
35,5
47,0
40,0
41,0
42,0
45,0
111,0
119,0
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBESAIZ-10-S...-4 UHL1 AIZ-10-S...-4 UHL1
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ-10-S...-4 UHL1
The outdoor bus- bar supports AIZ-10-S are used for installation of two aluminium tubes with 10 kV voltage on opened distribution devices of electric power stations and substations.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Please indicate and fill data shit if it is necessary to install tubes with different diameter.The factory can supply polymer bus-bar supports with adjusting sizes of bottom flange according clients request.
870
870
870
870
870
870
870
870
870
870
870
870
870
870
D
А
Ø134 hol.
АØ159
Ø127
H
L
Installation choices for bus- bar. The arrows indicate the axis of the aluminum tubes rigid bus- bar.
directionmovement
directionmovement
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameter of rigid bus-bar
tube, mm
SizeL, мм
CONDITIONAL DESIGNATION
50-250- rigid fastening aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ -10-C...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
S - for the installation of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
2911AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
29
AIZ-10-GL...-4 UHL1
12
L HNumber
of wires of flexible bus- bar
Flat bus- barmm
AIZ-10-GL2/8-2/100-2 UHL1
AIZ-10-GL2/12-3/125-2 U HL1
AIZ-10-GL2/12-4/125-2 U HL1
AIZ-10-GL2/16-3/125-2 U HL1
AIZ-10-GL2/16-4/125-2 U HL1
AIZ-10-GL2/20-3/125-2 U HL1
AIZ-10-GL2/20-4/125-2 U HL1
2+8
2+12
2+12
2+16
2+16
2+20
2+20
2bus- bar( 100*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
400
470
470
590
590
590
590
360
400
400
400
400
400
400
The outdoor bus- bar supports AIZ-10-GL are used for transition from flexible to flat horizontal bus-bars with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ-10-GL...-4 UHL1
Ø13
4 hol.
А
Ø159
Ø127
А
А
L
Н
Built braceAIZ type-2 to maintainwires
Flat bus- barhorizontal
Contact plateto move
POLYMER BUS-BAR SUPPORTS INTENDED FOR TRANSITION FROM FLEXIBLE BUS-BARS AIZ-10-GL2/8-2/100-4 UHL1 - AIZ-10-GL2/24-4/125-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Rigid bus- barsupport type
CONDITIONAL DESIGNATION
2/8-2/100 - modification of the cross section of bus- bar and wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ -10-GL...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armaTSre spacingcorrespondence
Quality and thickness of armaTSre’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, sm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
GL - go with a flexible busbar on flat bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
see table
10
12
75
13
nominal voltage, kV10-