Bus Bar Protection REV 1

Embed Size (px)

Citation preview

  • 7/28/2019 Bus Bar Protection REV 1

    1/18

    BUS BAR PROTECTION AND

    LBB PROTECTION.

    By

    Y. k. Pandharipande.

  • 7/28/2019 Bus Bar Protection REV 1

    2/18

    BUS BAR PROTECTION AND LBBPROTECTION

    PERFORMANCEREQUIREMENTS

    Stability

    High Speed Operation

    Selectivity

    Reliability

    Sensitivity

    Suitable for Use with moderate CT Ratings.

    Extendable to changes in Bus Bar configuration & additionof Circuits.

  • 7/28/2019 Bus Bar Protection REV 1

    3/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTIONCIRCULATING CURRENT DIFFERENTIAL PRINCIPLE

    CURRENT DISTRIBUTION EXTERNAL FAULT

    CURRENT DISTRIBUTION INTERNAL FAULT

  • 7/28/2019 Bus Bar Protection REV 1

    4/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PRIOTECTION

    A. HIGH IMPEDANCETYPE

    Relay Branch made High Impedance to limit differential currentdue to unequal CT saturation on external fault.

    Requires exclusive CT core of identical ratio and rating.

    Simple in design and execution.

  • 7/28/2019 Bus Bar Protection REV 1

    5/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION

    B. LOW IMPEDANCE (BIASED) TYPE

    Through current Bias increases differential pick-up on externalfault to ensure stability.

    Tolerant to CT mismatch and can use shared core. Comparatively more complex in design and execution. Practical schemes provide CT saturation detectors to enhance

    stability.

  • 7/28/2019 Bus Bar Protection REV 1

    6/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION (87)HIGH IMPEDANCE SCHEME

    If B CT fully saturates on external fault,Vs = If/n (Rct + 2Rl) Volts.

    Relay Branch Impedance = Vs/Is, where Is = Setting current of Relay.

    External Stabilising Resistor RST = Vs/Is VA /Is, where VA = RelayVA burden at setting current.

  • 7/28/2019 Bus Bar Protection REV 1

    7/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION (87)HIGH IMPEDANCE SCHEME- Typical Setting Workout.

    Max. Through fault Current (If) = 20,000A (Prim) / 20A(SEC)

    Vs = 20 (5 + 1) = 120V

    Stabilising Resistor (RST) = 120/0.2 1.0/0.2 = 600 - 25 = 575 ,(assuming relay VA burden = 1 VA)

  • 7/28/2019 Bus Bar Protection REV 1

    8/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION

    HIGH IMPEDANCE SCHEME Typical Setting Workout.

    Primary Fault Current setting (assuming number of circuitsconnected to Bus Bar, N=10)

    = CT Ratio (Is + N. Im)

    = 1000 (0.20 + 10 x 0.03) = 500A.

  • 7/28/2019 Bus Bar Protection REV 1

    9/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION (87)HIGH IMPEDANCE SCHEME Need For Metrosils.

    Peak Voltage across CT Secondary for Max. Internal Fault= 2 2 [Vk x (Vp Vk)]

    Vk = 240V, Vp = 20 (575 + 25) = 12000V

    Peak Voltage = 22 [(240 x (12000-240)] = 5300V

  • 7/28/2019 Bus Bar Protection REV 1

    10/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION

    HIGH IMPEDANCE SCHEME Need For Metrosils.

    If Peak voltage exceeds 3000V threatening secondary

    insulation, Metrosils (Non-linear resistors) are used to limitvoltage to safe value (within 1000V) on internal fault.

    Metrosil offers high resistance at lower voltage levelswhich drastically reduces at higher voltages, therebyquenching the voltage across relay branch.

    Typical Metrosil EquationV = C x I ( C = 900 , = 0.25)

  • 7/28/2019 Bus Bar Protection REV 1

    11/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION

    HIGH IMPEDANCE SCHEME -CT SUPERVISION (95)

    Required to detect CT open circuit on load to prevent maloperation. Connected for alarm & short CT bus wires on operation. Time delayed to avoid operation on internal / external faults (3Sec) Voltage relay with sensitive setting (2 -14V) is used. Normally set to detect primary unbalance of 25A or 10% of least loadedcircuit. Also should not operate with normal unbalance on load.

  • 7/28/2019 Bus Bar Protection REV 1

    12/18

    BUS BAR PROTECTION AND LBBPROTECTION

    BUS BAR PROTECTION CT SWITCHING.

  • 7/28/2019 Bus Bar Protection REV 1

    13/18

    BUS BAR PROTECTION AND LBBPROTECTION

    TYPICAL 2 ZONE SCHEME WITH INDEPENDANT CHECK

  • 7/28/2019 Bus Bar Protection REV 1

    14/18

    BUS BAR PROTECTION AND LBBPROTECTION

    TYPICAL 2 ZONE SCHEME WITH INDEPENDANT CHECK

    D.C. CIRCUITS.

    20K resistor on negative side used for cathodic protection.

  • 7/28/2019 Bus Bar Protection REV 1

    15/18

    BUS BAR PROTECTION AND LBBPROTECTION

    LOCAL BREAKER BACKUP (LBB) PROTECTION

    NEED

    Provides local isolation when breaker gets stuck onfault.

    Ensures comparatively faster clearance than remotebackup.

    Avoids wide spread interruption and enables fastrestoration.

  • 7/28/2019 Bus Bar Protection REV 1

    16/18

    BUS BAR PROTECTION AND LBBPROTECTION

    LBB PROTECTION OPRATING PRINCIPLE & CT CKTS.

  • 7/28/2019 Bus Bar Protection REV 1

    17/18

    BUS BAR PROTECTION AND LBBPROTECTION

    LBB PROTECTIOND.C. CKTS USING BUS BAR PROTECTION TRIP LOGIC.

    LBB CURRENT CHECK RELAY (50)Current Setting Range 20-320% or 5 -80%In (Recommended setting - 5%

    for Generator & 20% for Other Circuits)

    LBB TIMER (2/50) Range o.11.0 S (Recommended 0.20S)

  • 7/28/2019 Bus Bar Protection REV 1

    18/18

    BUS BAR PROTECTION AND LBBPROTECTION

    LBB PROTECTION TIMER SETTING CRIETERIA

    TLBB = TCB + TDO + TM TPU,

    Where TCB = C.B. Trip Time, TDO= Current Check relay DO time,TM = Safety margin, TPU = Current Check relay PU Time

    Normally,200ms delay recommended which is faster thanremote backup and allows sufficient time for normal C.B.

    tripping.