  • 7/27/2019 bus bar selection 20338744_0606073419

    1/40

    Technical dataDemag Compact Line DCL

    42211044.eps

    070606 EN/PDF 070606 203 387 44 714 IS 962.2

  • 7/27/2019 bus bar selection 20338744_0606073419

    2/40

    20338744

    .p65/070606

    2

    1 General 31.1 Symbols 31.2 DCL installation 3

    2 Design and installation notes 42.1 Definitions 42.1.1 Arms length 42.1.2 Protection against indirect contact 4

    3 Calculating and selecting the conductor cross-section 53.1 Calculating the conductor cross-section 6

    3.1.1 Calculation method 63.1.2 Graphical method 73.1.3 DCL maximum permissible current I

    35[A] for an ambient temperature

    of 35C 83.2 DCL basic structure 9

    4 General layout 10

    5 Suspension arrangements 115.1 DCL suspension with C-rail bracket 115.1.1 Sliding suspension/fixed suspension 115.1.2 Mounting and operating dimensions 125.2 DCL suspension with M8 threaded pin 145.2.1 Mounting and operating dimensions, sliding suspension/fixed suspension 14

    5.3 Further fitting information 146 Technical data 156.1 DCL straight section 4, 5, 6 und 7 poles 156.2 DCL curved section 4, 5, 6 und 7 poles 176.3 DCL line power feed 4, 5, 6 und 7 poles 196.4 DCL connector end cap as end power feed 216.5 DCL connector end cap as track end cap 226.6 End cap 236.7 Entry/transfer section 246.8 DCL current collector trolley 4, 5, 6 und 7 poles 266.8.1 Current collector technical data 276.9 Towing arm for DCL current collector trolley 286.9.1 Standard towing arm 28

    6.9.2 Towing arm for free transfer sections 296.10 Profile sealing lip 306.10.1 Assembly tool for fitting the profile sealing lip 306.11 Isolating section 31

    7 Component parts 327.1 Straight sections and accessories 327.1.1 Component set for sliding suspension with C-rail bracket 327.1.2 Component set for sliding suspension with threaded pin 327.1.3 Component set for conductor connector 327.1.4 Isolating sections 327.2 Current collectors and current collector trolleys 337.2.1 Sliding contact set 33

    8 Resistance to acids, chemicals and fuels 34

    Fax: Enquiry 35Fax: Order 36

    Table of contents

    Manufacturer Demag Cranes & Components GmbHDrives

    P.O. Box 67 D-58286 WetterTelephone (02335) 92-0 Telefax (0 2335) 92 7298E-mail [email protected]

  • 7/27/2019 bus bar selection 20338744_0606073419

    3/40

    20338744

    .p65/070606

    3

    1 General

    1) The voltage drop must be checked for installations with large power feed sections and high currents.Refer to calculation from chapter 3.

    2) With single-sided thermal effect.

    3) For straight sections with entry/transfer section.

    4) Other line lengths possible.

    5) Copper conductor 10 mm2 on the contact surface plated with stainless steel.Applications and further notes cf. chapter 6.

    The following symbols and recommendations indicate potential safety hazards orcauses of damage or provide useful information.

    Warning against dangerous electrical voltageContact with live parts can result in immediate death. Protective covers (e.g. coversand enclosures) marked with this sign may only be opened by qualified electricians.Before opening, all relevant operating, control, feed or other voltages must be dis-connected.

    Operating hazard for the installation

    This symbol in the operating instructions indicates all warnings which, if not compliedwith, may result in damage to the product.

    1.1 Symbol description

    1.2 DCL installation The DCL is a conductor bar system with PVC-housing.The uniform housing can be effected with 4, 5, 6 or 7 conductors / poles acc. tothe customers requests. The standard material for conductors is copper.

    Alternatively, a stainless steel-plated copper bar is available. The special

    characteristic is the insensitive stainless steel-contact surface compared to

    copper. The stainless steel-plated copper bar is predestined for the use near

    the sea, outdoors, with chemicals or for systems with low application time. An

    oxidising of the sliding contact surface is excluded.

    The available conductor bar cross sections and conductor materials can be found inthe table below.

    enilrotcudnoC

    lairetamerusolcnE CVP

    htgneldradnatS mm 0004

    selop/srotcudnocforebmuN 7...4

    .xamsnoisnepsusneewtebecnatsiD )2 mm 0001 )2 0002/

    UegatloV N CAV 096sib42

    eziS )1 53 06 001 041 002

    )C53otFDC%001(tnerrucelbissimreP )1 A 46 87 001 041 061

    noitcesssorcrotcudnoC mm 01 51 52 83 65

    reppoclairetamrotcudnoC X X X X X

    detalpleetssselniatslairetamrotcudnoC )5 X - - - -

    erutarapmeterusolcnE/erutarepmettneibmA C 07+sib03-

    92506NE/1.T0740EDVNIDssalcnoitcetorP edoC-PI pilgnilaeshtiw42PI/32PI

    suidarmuminimnoitcesevruC mm $ mm008

    noitcetorperiF eerf-negolahton;OV/49LU

    yellortrotcelloctnerruC

    selopforebmuN 7...4

    lairetamtcatnocgnidilS eznorb etihparg etihparg-revlis

    ItnerrucdetaR N )DE%08( A04 A02 A02

    )4,3,2,1(noitcennocrewoprofnoitcesssorcnoitcennoC mm.xam 6 4

    )7,6,5(elbaclortnocrofnoitcesssorcnoitcennoC mm.xam 5,2

    )dradnats(htgnelelbacgnitcennoC )4 mm 0002

    .xamnoitcetorpesuF A 001

    .xamdeepslevarT nim/m 001 )3 002/

  • 7/27/2019 bus bar selection 20338744_0606073419

    4/40

    20338744

    .p65/070606

    4

    2 Design and installation notes

    Conductor lines must be operated in accordance with generally accepted engineer-ing principles. Ensure compliance with DIN VDE/EN, SEV, CSA and UL regulations.We make special reference to the DIN VDE regulations, particularly to DIN VDE 0100.

    Of the many regulations, we refer to the following definitions:

    see DIN VDE 0106, Part 200.

    Arms length is the area which a persons hand may reach in all directions fromnormal locations without any special equipment. Measured from the position where aperson is standing, this area ranges up to at least 2,5 m upwards and at least 1,25 mto the side and downwards (see DIN 31 001 Sheet 1).

    Wherever large or long objects which are not insulated for the operating voltage aremoved, the minimum arms length must be correspondingly increased.

    Protection against direct contact constitutes all measures to protect people fromhazards resulting from contact with live parts of electrical equipment. This may bepartial or full protection.

    Partial protection only provides protection against accidental contact. Protectionagainst accidental contact does not mean any protection against deliberate contact.

    Enclosure type IP 2X to DIN VDE 0470 Part 1 offers protection against accidentalcontact. Complete protection starts from IP 5X to DIN VDE 0470 Part 1.

    Please note:

    2.1 Definitions2.1.1 Arms length

    2.1.2 Protection against indirectcontact

  • 7/27/2019 bus bar selection 20338744_0606073419

    5/40

    20338744

    .p65/070606

    5

    3 Calculating and selecting the conductor cross-section

    Voltage drop 1. and permissible current 2. must be considered when calculatingpower supply cross-sections.

    1. - Calculate the cross-section considering the max. permissible voltage drop of2,5 % for crane runways + 2,5 % for crane bridge.

    - The relevant value is thestarting current cos

    Aof the largest motor + the rated current cos

    Nof the

    next smaller motor.

    - The currents must be added for motors connected in parallel.

    The calculated cross-sections must be halved for power supplies to solo hoists.

    2. - Calculate the cross-section considering the max. permissible current for cablesto DIN VDE 100 Part 430/523.

    - The relevant value is the sum of all rated currents of all drives.The currents indicated in diagram 1, section 3.1.2 must not be exceeded.

    Permissible voltage drop

    The voltage drop is determined by current IG.

    Current IG

    results from adding the starting - (IA

    cosA) and rated currents (I

    N cos

    N)

    (see table 1 below).The conductor cross-section may be determined according to the calculationmethod described in section 3.1.1 or diagram 1, section 3.1.2.

    Table 1 indicates the number of consumers to be considered for calculating IG

    depending on the number of cranes fed by a conductor line.

    Table 1

    For double drive arrangements correspondingly: 2 IA

    cosA

    or 2 IN

    cosN.

    Exception: For double hoist units with delayed startingIA

    cosA

    + IN

    cosN.

    ybdefsenarcforebmuN

    enilrotcudnoca

    rehtegotnekatsenarcllafO

    )tuptuoforedroni(

    rotomts1 rotomdn2 rotomdr3 rotomht4

    1 IA

    soc A

    IN

    soc N

    - -

    2 I A soc A I N soc N I N soc N -

    3 I A soc A I A soc A - -

    4 I A soc A I A soc A I N soc N -

    5 I A soc A I A soc A I N soc N I N soc N

  • 7/27/2019 bus bar selection 20338744_0606073419

    6/40

    20338744

    .p65/070606

    6

    Abbreviations used in the equations:

    A = Conductor cross-section of the DCL [mm]

    L = cable length [m]

    I = starting current (IA

    cosA) or rated current (I

    N cos

    N) [A]

    IG

    = sum of the currents according to table 1 [A]

    f = frequency in Hertz [Hz]

    = conductibility (for Cu

    = 56) [m/ m]

    U = permissible voltage drop [V]

    U = voltage in volts [V]

    1. Conductor cross-section of the DCL

    2. Required conductor length

    3. Conversion for starting current IA

    cos

    Aor rated current I

    N cos

    N

    fornon-standard voltage U

    4. Conversion for conductor cross-section A

    2for non-standard

    conductor length L2

    5. Permissible voltage drop

    6. Conversion from 400 V, 50 Hz to anew voltage and frequency

    3.1 Calculating the con-ductor cross-section

    3.1.1 Calculation method

    A =IxLx37,1 G

    mm[ 2] xU

    L1 = xU Ax

    Xf2

    ]m[Ix37,1 G f1

    I2 =U1 Ix 1

    ]A[U2

    A2 =L2 Ax 1

    mm[ 2]L1

    U = )V004rof(V01=%5,2

    U =%5,2xU

    ]V[%001

    I wen = I dlo XV004

    Xf wen

    ]A[U wen zH05

  • 7/27/2019 bus bar selection 20338744_0606073419

    7/40

    20338744

    .p65/070606

    7

    Diagram 1

    Calculating the conductor cross-section for the permissible voltage drop.

    The DCL conductor line cross-section and/or voltage drop may be reduced by theposition and quantity of power feeds.

    3.1.2 Graphical method

    42226444.eps

    for

  • 7/27/2019 bus bar selection 20338744_0606073419

    8/40

    20338744

    .p65/070606

    8

    I35 [A]

    25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 10050

    75

    100

    125

    150

    175

    200

    225

    250

    275

    300

    ED [%]

    DCL 35 (10mm )2DCL 60 (15mm )2DCL 60 (15mm )2

    DCL 100 (25mm )2

    DCL 140 (38mm )2

    DCL 200 (56mm )2

    292

    270

    253

    238

    226

    216207

    200 193187

    181176

    172 167 163 160

    140

    100100

    78

    64

    142

    103

    80

    6668707274

    77808387

    9196

    102109

    118

    129

    80838588

    919497101

    106111

    117124

    133

    143

    157

    194

    105108111115

    119123

    128133

    139147

    155

    165

    178

    146149152

    156161

    165171

    177184

    191200

    211

    225

    241

    Check the maximum permissible current for the conductor cross-section as afunction of the cyclic duration factor (CDF) at an ambient temperature of 35 C.

    For other ambient temperatures, the current (IJ) must be calculated with the

    conversion factor (fu) according to the table below.

    The same or the next largest conductor cross-section must be selected.

    Diagram 2

    3.1.3 DCL maximum permissiblecurrent I

    35[A] for an ambient

    temperature of 35C

    42226544.eps

    Cyclic Duration

    Factor

    Perm

    iss

    iblecurren

    t[A]a

    t35Cam

    bien

    ttemp

    era

    ture

    Maximum permissible current I

    = I35

    fu

    Calculating the maximum permissible current I

    [A] for other ambient temperatures

    erutarepmettneibmA ]C[ 02 52 03 53 04 54 05 55 06 56

    rotcafnoisrevnoC fu 02,1 41,1 70,1 00,1 29,0 48,0 47,0 46,0 15,0 53,0

  • 7/27/2019 bus bar selection 20338744_0606073419

    9/40

    20338744

    .p65/070606

    9

    3.2 DCL basic structure

    Model code:

    (Example for ordering a straight section)

    DCL - GS 4 - 60 - PE - 4000

    Section - installation length [mm]

    With protective earth conductor

    Size

    Number of poles

    Component (GS = straight section)

    Line

    Compact

    Demag

    Straight section, section 6.1

    Standard length, section 6.1 Remaining length < 4 m, section 6.1

    Curve section, section 6.2

    Profile sealing lip, section 6.10

    End cap, section 6.6

    Sliding suspension /Fixed suspension,

    section 5.1.1

    Isolating section, section 6.11

    Current collector trolley,

    section 6.8

    Standard towing arm,section 6.9.1

    Transfer towing arm,section 6.9.2

    Bronze contact 40 A,section 6.8.1 1)

    Graphite contact 20 A,section 6.8.1 1)

    C-rail mounting bracket,section 5.1

    Threaded pin bracket,section 5.2

    Entry funnel / Transfer funnel,section 6.7

    Connector cap / End power feed,section 6.5

    Line power feed,section 6.3

    1) The sliding contacts of the control lines (poles 5, 6, 7) optionally are also availableas silver-graphite-sliding contact. Technical data and other notes cf. chapter 6.

  • 7/27/2019 bus bar selection 20338744_0606073419

    10/40

    20338744

    .p65/070606

    10

    EKmin.250

    B

    A

    65

    EK

    min.250

    GAFA

    400 2000

    400

    2000 2000 400

    4000 4000 4000

    4001600

    2000 2000

    AKGAGAGAGAAK

    S

    GAGAGA GA

    SS S

    1600

    2000 2000 2000

    400

    4000 4000

    2000

    1600

    min.250

    4001600

    min.250

    Please note

    In place of an AK connector end cap, a track extension, an entry section, or a transfer sectionmay be fitted.

    DCL installations

    - with a line power feed are supplied with an end cap item (8) at both ends.

    A track cannot be extended when an end cap is fitted. An installation with an endcap is exactly 74 mm shorter than the rated length.

    On request also available with connector end cap as track end cap so that thetrack can be extended.

    - with an end power feed are supplied with a connector end cap (7) at both ends.

    An installation with a connector end cap is exactly 130 mm longer than the ratedlength. Allow for clearance to connect the end power feed (approx. 250 mm).

    4 General layout

    42109645.eps

    1)

    1) When large cable cross-sections (from size PG42) are used with a DCL section with a line power feed, athird additional sliding suspension must be fitted close to the power feed enclosure.

    2) Not shown

    3) The 400 mm dimension must not be exceeded.

    61

    2

    3

    45

    87 or

    8

    or 7

    42106144.eps

    (PE)

    Steel structure etc.

    Profile rib(orientationrib)

    Section A - B

    Clearance 250 Clearance 150

    3) 3) 3) 3)

    In place of an AK connector end cap an entry/transfer funnel may be fitted.To do this, an additional suspension must be fitted at 200 mm.

    metI noitangiseD snoisnemiD

    1 noitcesthgiartsLCD SG mm0004

    2 noitcesevrucLCD SB R $ mm008

    3 rotcennoctnioJ S

    4 noisnepsusgnidilS AG

    5 noisnepsusdexiF AF

    6 deefrewopeniL SE mm0004

    7

    pacdnerotcennoCdeefrewopdnesa

    KApacdnerotcennoC

    pacdnekcartsa

    8 pacdnE KE

    yellortrotcelloctnerruC )2

    mragniwoT )2

    snoitcesrefsnartrofmragniwoT )2

    lennufrefsnart/yrtnE )2

  • 7/27/2019 bus bar selection 20338744_0606073419

    11/40

    20338744

    .p65/070606

    11

    5.1 DCL suspension with C-rail bracket5.1.1 Sliding suspension/fixed suspension

    Flange clamp Part no.

    Clamping range 8 to 16 mm 974 548 44Clamping range 16 to 30 mm 974 549 44

    C-rail 40 x 25min. 100max. 165

    C-rail 40 x 40min. 90max. 150

    liar-Crof.ontraP 52x04

    =L 003 44724869=L 005 44481058

    =L 006 44055479

    =L 007 44155479

    =L 029 44355479

    =L 0006 44006312

    Attachment to upper flange I

    Attachment to lower flange II

    42206244.eps

    42211144.eps

    42211544.eps

    42211444.eps

    25 or 40

    min.

    120,m

    ax.1

    80

    Adjusting

    range

    5 Suspension arrangements

    Adjus

    tingrange

    42226044.eps

    25

    or40 04x04liar-CrofontraP

    =L 0001 44455479

    =L 0721 44572056

    =L 0051 44472056

    =L 0281 44125859

    =L 0006 44106312

  • 7/27/2019 bus bar selection 20338744_0606073419

    12/40

    20338744

    .p65/070606

    12

    5.1.2 Mounting and operating dimensions

    42206344.eps

    42211344.eps

    42106344.eps

    42211244.eps

    min. 30max. 90

    C-rail40 x 25

    min. 10max. 75

    C-rail40 x 40

    min. 0max. 60

    Adjus

    tingrange

    Adjus

    tingrange

  • 7/27/2019 bus bar selection 20338744_0606073419

    13/40

    20338744

    .p65/070606

    13

    Mountingarrangement I

    Mounting ar-rangement II

    Mountingbracket

    C-rail clamp section

    Fixed point 1)

    The following information is required for ordering C-rails and flange clamps to fit DCLto I-beams:

    C-rail type and length (see table on page 12). Flange clamps for -beams (see below).

    tekcarbliar-ChtiwnoisnepsusgnidilsroftestnenopmoC .rN-lletseB

    noitcespmalcliar-Cffo1

    44836678tekcarbgnitnuomffo1

    noisnepsusgnidilsffo1

    42106344.eps

    42211344.eps

    Fixed point 1)

    Mountingbracket

    C-rail clamp section

    Sliding supension

    1) Only for fixed suspension. The fixed suspension is a sliding suspension which is fixed on the profile sectionby means of a self-tapping screw. Self-tapping screw 3,5 x 9,5 to DIN 7981.

    htdiwredriG egnargnipmalC .ontraP

    -061 004 mm61-8 44845479

    -524 006 mm03-61 44945479

  • 7/27/2019 bus bar selection 20338744_0606073419

    14/40

    20338744

    .p65/070606

    14

    Mounting angle

    Adjus

    tingrange

    max.

    43

    M8 lock nut

    42207444.eps

    42106444.eps

    Straight sections feature plastic sliding suspensions for connection to C-rail orthreaded pin fittings..

    Line power feeds feature an additional sliding suspension. For C-rail fittings:- The mounting brackets are clipped into the sliding suspensions.- The C-rail clamp section is fitted according to mounting arrangement I or II

    (see section 5.1.2).

    For threaded pin fittings:- The threaded pin fitting with countersunk screw is clipped into the sliding

    suspensions.

    The max. distance between DCL sliding suspensions is 2000 mm for straightsections (see chapter 4).

    Sliding suspensions must be fitted every 500 mm (along the curve) for curvedsections.

    The centre of every DCL installation must be secured by a fixed suspension.To do this, screw the enclosed 3,5 x 9,5 self-tapping screw into the slidingsuspension.For DCL installations with entry/transfer sections, the funnels must be arrested.

    5.3 Further fittinginformation

    Fixed point 1)

    1) Only for fixed suspension. The fixed suspension is a sliding suspension which is fixed on the profile sectionby means of a self-tapping screw. Self-tapping screw 3,5 x 9,5 to DIN 7981.

    5.2 DCL suspension with M8 threaded pin5.2.1 Mounting and operating dimensions, sliding suspension/fixed suspension

    Sliding suspension

    nipdedaerht8MhtiwnoisnepsusgnidilsroftestnenopmoC .ontraP

    gnittifnipdedaerhtffo1

    4473667807x8Mwercsknusretnuocffo1

    8Mtunkcolffo2

    noisnepsusgnidilsffo1

  • 7/27/2019 bus bar selection 20338744_0606073419

    15/40

    20338744

    .p65/070606

    15

    S = Joint connectors are pre-assembled on the conductor enclosures.

    GA = Sliding suspensions: are fitted to the conductor enclosures and have to bepositioned during assembly.

    - Additional sliding suspensions may be fitted.

    - Specify suspension method and order separately.

    - Suspension diagram with dimensions see chapter 4.

    Please observe!Unless the installation is designed otherwise, it must be ensured that all DCL straightand curve sections are fitted in such a way that the protective earth conductor (PE)and the profile rib of the enclosure face towards the track support resp. the steelwork.

    Version without protective conductor (PE)

    Systems and current collecting trolleys without protective conductor connection (PE)will be supplied as follows.

    Systems

    The green-yellow marking of the protective conductor is not applicable.The conductor / pole is equipped resp. processed and can be used for the power- orfor the control signal transmission. The cross section then corresponds to the

    conductor cross section of the power transmission (valid for sizes starting at 140).

    Current collecting trolley

    In this version the green-yellow core is replaced by a black core. The protectivemarking (PE) is not applied. The sliding contacts are equipped in accordance with theconductor- / poles-quantity.

    When all DCL straight and curve sections have been fitted, one sliding suspensionmust be fixed with a DCL straight section in the middle of the track (fixed point) toprevent the DCL installation moving to the side.

    Fixed point or fixed suspension:

    Screw the enclosed 3,5 x 9,5 self-tapping screws to DIN7981 as there is a risk of

    accidental contact with live parts if longer screws are used.

    6.1 DCL straight section 4, 5, 6 und 7 poles

    42106144.eps

    (PE)

    Steel structureetc.

    Profile rib(orientationrib)

    6 Technical data

    Protective earth symbol(only for conductor line with PE)

    42207544.eps

    Profile rib (orientation rib)

    Suspension method

    Attached to C-rail or suspended fromthreaded pin(must be ordered separate-ly, see sections 5.1.1 and 5.2.1)

    Profile sealing lip: fitted as required.

    May be added to order per meter.42212444.eps

    1) Standard length 4000 mm. Indicate reduced length in order text for part no. Minimum reduced length500 mm. For complete conductor line installations, the entire conductor line length including the powerfeed(s) must be specified in the order text.

    Use only the enclosed 3,5 x 9,5 self-tapping screws to DIN7981 as thereis a risk of accidental contact with live parts if longer screws are used.

  • 7/27/2019 bus bar selection 20338744_0606073419

    16/40

    20338744

    .p65/070606

    16

    selopforebmuN

    eziS

    53 06 001 041 002

    )2C53otpuFDC%001ta)A(tnerrucelbissimreP

    46 87 001 041 061

    mmnoitces-ssorcrotcudnoc3L-1L

    01 51 52 83 65

    4 44046678 44606678 44706678 44806678 44906678

    3L-1LesahP

    rotcudnocEP

    elbaclortnoC

    mm01x3

    mm01x1

    -

    mm51x3

    mm51x1

    -

    mm52x3

    mm52x1

    -

    mm83x3

    mm52x1

    -

    mm65x3

    mm83x1

    -

    5 44146678 44016678 44116678 44216678 44316678

    3L-1LesahP

    rotcudnocEP

    elbaclortnoC

    mm01x3

    mm01x1

    mm01x1

    mm51x3

    mm51x1

    mm01x1

    mm52x3

    mm52x1

    mm01x1

    mm83x3

    mm52x1

    mm01x1

    mm65x3

    mm83x1

    mm01x1

    6 44246678 44416678 44516678 44616678 44716678

    3L-1LesahP

    rotcudnocEP

    elbaclortnoC

    mm01x3

    mm01x1

    mm01x2

    mm51x3

    mm51x1

    mm01x2

    mm52x3

    mm52x1

    mm01x2

    mm83x3

    mm52x1

    mm01x2

    mm65x3

    mm83x1

    mm01x2

    7 44346678 44816678 44916678 44326678 44426678

    3L-1LesahP

    rotcudnocEP

    elbaclortnoC

    mm01x3

    mm01x1

    mm01x3

    mm51x3

    mm51x1

    mm01x3

    mm52x3

    mm52x1

    mm01x3

    mm83x3

    mm52x1

    mm01x3

    mm65x3

    mm83x1

    mm01x3

    The following information is required for ordering a straight section(see model code order text):

    Conductor line type, component DCL-GS

    Number of poles (4, 5, 6, or 7 conductors)

    Size (35, 60, 100, 140, 200)

    protective earth conductor PE (with or without)

    Section and installation length in mm 1)

    Part number table (conductor material copper)

    The combinations of conductor quantity / number of poles and size indicated in theorder table can be purchased as components. As a standard material for theconductor copper is used. Alternatively, the conductor cross section 10 mm2 can beordered in stainless steel plated version.

    The above mentioned part numbers are only valid for the conductor material copper.

    A version with stainless steel plated copper bar (10 mm2

    ) has to be especiallymentioned in the order.

    For straight sections not fitted with a protective earth conductor (PE), this must beindicated in the order section and specified as a part no. with no PE.

    Suspensions DCL with C-rail installation or threaded bolts M8 have to be orderedseparately. Component sets for sliding suspensions with C-rail installation or threadedbolts M8 have to be selected with the corresponding quantity (cf. chapter 7.1).

    Sliding suspensions are pre-mounted for the suspension distance 2000 mm.

    1) Standard length 4000 mm. Indicate reduced length in order text for part no. Minimum reduced length500 mm.

    For complete conductor line installations, the entire conductor line length including the power feed(s)must be specified in the order text.

    2) The permissible current for the conductors must be checked.

    Calculation or tables see chapter 3.

    3) 10 mm2 (L1-L3, PE and / or control line) available upon request as stainless steel plated copper bar.

    Model code Order text, e.g.:

    DCL-GS-6-100-PE-4000

    or DCL-GS-7-60-3500 (no PE, 3500 mm long)

  • 7/27/2019 bus bar selection 20338744_0606073419

    17/40

    20338744

    .p65/070606

    17

    6.2 DCL curved section 4, 5, 6 and 7 poles

    This diagram shows an inside curve

    S = Joint connectors are pre-assembled on the conductor enclosures.

    GA = Sliding suspensions: are fitted to the conductor enclosures and have to be

    positioned during assembly.- Suspensions spaced at a distance of 500 mm along the curve.

    - Specify suspensions and order separately.

    - Suspension diagram with dimensions see chapter 4.

    Please observe!

    Unless the installation is designed otherwise, it must be ensured that all DCL straightand curve sections are fitted in such a way that the protective earth conductor (PE)and the profile rib of the enclosure face towards the track support resp. the steelwork.

    42106144.eps

    (PE)

    Steel structure etc.

    Profile rib(orientationrib)

    42210444.eps

    Profile rib (orientation rib)

    Profile sealing lip: fitted as required.May be added to order per meter.

    stra

    ight straight

    Suspension method

    Attached to C-rail or suspended

    from threaded pin (must beordered separately, see sections5.1.1 and 5.2.1)

    For designing of systems with straight and curve sections the following has to beobserved:

    The straight ends of the curve sections with 178 mm are fixed values and if necessaryhave to be deducted from the total length of the connecting straight section.

  • 7/27/2019 bus bar selection 20338744_0606073419

    18/40

    20338744

    .p65/070606

    18

    The following information is required for ordering a curved section(see model code order text):

    Conductor line type, component DCL-BS

    Number of poles (4, 5,6, or 7 conductors)

    Size (35, 60, 100, 140, 200) 1)

    protective earth conductor PE (with or without)

    Radius (mm)

    Angle (degrees)

    Curve I or curve A 2)

    Model code

    1) The permissible current for the conductors must be checked.

    Calculation or tables see chapter 3.

    2) Definition of curve type I and curve type A:

    On curve I the protective earth conductor and the profile rib are on the inside of the curved section.

    On curve A the protective earth conductor and the profile rib are on the outside of the curvedsection.

    On curved sections which do not feature a protective earth conductor, the profile rib is only fororientation.

    The view refers to the centre of the radius.

    Order text, e.g.:

    DCL-BS 5-100- PE- R = 1500, = 45, curve A 3)

    3) Profile sealing lip may be added to order per meter. Please specify in the order.

    For curved sections not fitted with a protective earth conductor (PE), this mustbe indicated in the order section and specified as a part no. with no PE.

  • 7/27/2019 bus bar selection 20338744_0606073419

    19/40

    20338744

    .p65/070606

    19

    6.3 DCL line power feed 4, 5, 6 and 7 poles

    S = Joint connectors are pre-assembled on the conductor enclosures.

    GA = Sliding suspensions: are fitted to the conductor enclosures and haveto be positioned during assembly.Line power feeds feature an additional sliding suspension.

    - Additional sliding suspensions may be fitted.- Specify suspension method and order separately, see chapter 5.- Suspension diagram with dimensions see chapter 4.

    M6 slot-head screws

    Prepared

    opening

    Connecting bar

    only for 100 A,140 A and 200 ADCL conductor

    Connecting terminal

    42210544.eps

    42109044.eps

    Profile rib (orientation rib)

    1)

    Profile sealing lip: fitted as required.May be added to order per meter.

    42212444.eps

    2)

    1) Cut off the rubber sleeves to the required cable diameters.- dia. 48 PG 42 only with rubber sleeve max. 43 mm cable diameter,

    PG 36 for PG screw fitting.- dia. 29 PG 21 with rubber sleeve max. 24 mm cable diameter,

    The rubber sleeves are supplied loose inside the line power feed enclosure.2) Standard length 4000 mm. Indicate reduced length in order text for part no.

    Minimum reduced length 1000 mm.

  • 7/27/2019 bus bar selection 20338744_0606073419

    20/40

    20338744

    .p65/070606

    20

    The following information is required for ordering a line power feed(see model code order text):

    Conductor line type, component DCL-ES

    Power feed, number of poles (4, 5, 6, or 7 conductors)

    Size (35, 60, 100, 140, 200)

    protective earth conductor PE (with or without)

    selopforebmuN

    eziS

    53 06 001 041 002

    )1C53otpuFDC%001ta)A(tnerrucelbssimreP

    46 87 001 041 061

    mmnoitces-ssorcrotcudnoc3L-1L

    01 51 52 83 65

    4 44646678 44056678 44156678 44256678 44356678

    EP+3L-1L

    elbaclortnoC

    mm61-5,1x4

    -

    mm61-5,1x4

    -

    mm07-52x4

    -

    mm07-52x4

    -

    mm07-52x4

    -

    5 44746678 44456678 44556678 44656678 44756678

    EP+3L-1L

    elbaclortnoC

    mm61-5,1x4

    mm61-5,1x1

    mm61-5,1x4

    mm61-5,1x1

    mm07-52x4

    mm61-5,1x1

    mm07-52x4

    mm61-5,1x1

    mm07-52x4

    mm61-5,1x1

    6 44846678 44856678 44956678 44066678 44166678

    EP+3L-1L

    elbaclortnoC

    mm61-5,1x4

    mm61-5,1x2

    mm61-5,1x4

    mm61-5,1x2

    mm07-52x4

    mm61-5,1x2

    mm07-52x4

    mm61-5,1x2

    mm07-52x4

    mm61-5,1x2

    7 44946678 44266678 44366678 44466678 44566678

    EP+3L-1L

    elbaclortnoC

    mm61-5,1x7

    mm61-5,1x3

    mm61-5,1x7

    mm61-5,1x3

    mm07-52x4

    mm61-5,1x3

    mm07-52x4

    mm61-5,1x3

    mm07-52x4

    mm61-5,1x3

    Part number table (conductor material copper)

    1) The permissible current for the conductors must be checked.

    Calculation see tables in chapter 3.

    2) 10 mm2 (L1-L3, PE and / or control line) available upon request as stainless steel plated copper bar.

    The combinations of conductor quantity / number of poles and size indicated in theorder table can be purchased as components. As a standard material for theconductor copper is used. Alternatively, the conductor cross section 10 mm2 can beordered in stainless steel plated version.

    The above mentioned part numbers are only valid for the conductor material copper.

    A version with stainless steel plated copper bar (10 mm2

    ) has to be especiallymentioned in the order.

    For line power feeds not fitted with a protective earth conductor (PE), this must beindicated in the order section and specified as a part no. with no PE.

    Suspensions DCL with C-rail installation or threaded bolts M8 have to be orderedseparately. Component sets for sliding suspensions with C-rail installation or threadedbolts M8 have to be selected with the corresponding quantity (cf. chapter 7.1).Sliding suspensions are pre-mounted for the suspension distance 2000 mm.

    Model code Order text, e.g.:

    Line power feed DCL-ES-4-140-PE

    or DCL-ES-7-60 (no PE)

  • 7/27/2019 bus bar selection 20338744_0606073419

    21/40

    20338744

    .p65/070606

    21

    The following information is required for ordering or selecting a connector end cap asa power feed (see model code order text):

    Conductor line type, DCL AK connector end cap

    Connection cross-section 16 mm (IN 60 A)

    Prepared openings

    Open as required andfit rubber sleeve(s).

    1) Not included in the scope of supply.

    Cut off the rubber sleeves to the required cable diameters.

    2) Cable lugs are not included in the scope of supply.

    Rubber sleeves for cabledia. up to 24 mm 1)

    Straight /curved section

    AK = Connector end cap clipped together with the joint connector.

    S = Joint connectors are pre-assembled on the conductor enclosures.

    GA = Sliding suspensions: are fitted to the conductor enclosures and have to be positioned during assembly.

    6.4 DCL connector end cap as end power feed

    42110444.eps

    Connecting point on the conductor lug

    Attach cable lugs to cables up to 16 mm 2)

    Attach the cable lugs to the conductor lugs using M6 nuts andbolts.Clip

    42210644.eps

    Clearance

    Model code Order text, e.g.:

    DCL connector end cap as end power feed DCL-AK-16

    Rubber sleeve PG 21

  • 7/27/2019 bus bar selection 20338744_0606073419

    22/40

    20338744

    .p65/070606

    22

    6.5 DCL connector end cap as track end cap(for DCL conductor line with end power feed or with extended track)

    The following information is required for ordering or selecting a connector end cap astrack end cap (see model code order text):

    Conductor line type, DCL AKconnector end cap

    Straight /curved section

    AK = Connector end cap clipped together with the joint connector.

    S = Joint connectors are pre-assembled on the conductor enclosures.

    GA = Sliding suspensions: are fitted to the conductor enclosures and have to be positioned during assembly.

    42052444.eps

    Connector end cap

    42210744.eps

    Clearance

    Model code Order text, e.g.:

    DCL connector end cap as track end cap DCL-AK

  • 7/27/2019 bus bar selection 20338744_0606073419

    23/40

    20338744

    .p65/070606

    23

    6.6 End cap(for DCL installations with line power feed or sections subsequently cut to length on site)

    The following information is required for ordering or selecting an end cap (see modelcode order text):

    Conductor line type, DCL

    EKend cap

    Clearance

    Straight /curved section

    EK = End cap screwed together with the conductor enclosure.

    GA = Sliding suspensions: are fitted to the conductor enclosures and have to be positioned during assembly.

    Use only the enclosed 3,5 x 10 oval flat head screws to DIN7981 as there is a risk ofaccidental contact with live parts if longer screws are used.

    42109544.eps

    Oval flat head screw 3,5 x 10 DIN7981

    42210844.eps

    Model code Order text, e.g.:

    End cap DCL-EK

  • 7/27/2019 bus bar selection 20338744_0606073419

    24/40

    20338744

    .p65/070606

    2441761944.eps

    6.7 Entry/transfer section

    Profile rib (orientation rib)

    Profile sealing lip: fitted as required.May be added to order per meter.

    View X View X

    Orientation ribFunnel right-handOrientation rib

    Funnel left-hand

    42279444.eps

    Suspension method

    Attached to C-rail or suspended from threaded pin(must be

    ordered separately, see sections 5.1.1 and 5.2.1)

    aeralennufdaeDenilrotcudnoC mmnoisnemiD

    1

    3422

    3

    4

    5 253

    6342

    7

    EP 431

    42212444.eps

  • 7/27/2019 bus bar selection 20338744_0606073419

    25/40

    20338744

    .p65/070606

    25

    For transfers left-hand and right-hand funnels are required.

    Entry/transfer speed 100 m/min.

    Min. distance between transfer funnels 10 mm.Max. lateral misalignment between the funnels 10 mm.

    Max. vertical misalignment between the funnels 8 mm.

    S = Joint connectors are pre-assembled on the conductor enclosures.

    F = Fixed suspension slides on funnel enclosure to be positioned and secured withself-tapping screw during assembly.

    Use only the enclosed 3,5 x 9,5 self-tapping screws to DIN7981 as there is a risk ofaccidental contact with live parts if longer screws are used.

    Part number table selopforebmuN epyT enilrotcudnoC

    tnemngissa

    .ontraP

    4dnah-thgir

    )EP(7,3-144596678

    dnah-tfel 44007678

    5dnah-thgir

    5)EP(7,3-144696678

    dnah-tfel 44107678

    6dnah-thgir

    6,4)EP(7,3-144796678

    dnah-tfel 44207678

    7dnah-thgir

    6-4)EP(7,3-144896678

    dnah-tfel 44307678

    For transfer sections not fitted with a protective earth conductor (PE), this must beindicated in the order section and specified as a part no. with no PE.

    Note

    The current collector trolley must be prepared for DCL with entry/transfer setions orprofile sealing lip.

    Open the terminal box on the current collector trolley and separate the upper termi-nal box enclosure half on the prepared openings (prepared openings see figure insection 6.8).

    The following information is required for ordering or selecting transfer sections(see model code order text):

    Conductor line type, DCL

    TR Transfer section

    Type (L = left-hand or R = right-hand)

    Number of poles ( 4,5, 6, or 7 conductors)

    protective earth conductor PE (with or without)

    Model code Order text, e.g.:

    Transfer section (funnel right-hand) DCL-TR-4-PE

    or (funnel left-hand) DCL-TL-7 (no PE)

    The combinations of conductor quantity / number of poles and size indicated in the

    order table can be purchased as components. As a standard material for theconductor copper is used. Alternatively, the conductor cross section 10 mm2 can beordered in stainless steel plated version.

    The above mentioned part numbers are only valid for the conductor material copper.A version with stainless steel plated copper bar (10 mm2) has to be especiallymentioned in the order.

  • 7/27/2019 bus bar selection 20338744_0606073419

    26/40

    20338744

    .p65/070606

    26

    6.8 DCL current collector trolley 4, 5, 6 and 7 poles

    42210944.eps

    Guide wheel

    Travel wheel

    Guide roller

    The current collector trolley mustbe prepared for DCL with entry/transfer setions or profile sealing lip.

    Open the terminal box on the cur-rent collector trolley and separatethe upper terminal box enclosurehalf on both terminal box halvesalong the prepared opening.

    41762044.eps

    1

    3

    6

    5

    7

    2

    4

    Preparedopening

    (separate on

    both sides)

    1) Bronze sliding contact material,connecting conductor cross-sectionsL1 - L3 + PE max. 6,0 mm.

    Control conductor connecting cable cross-section 1,5 mm.

    Other cross-sections on request.

    2) Graphite sliding contact material, connectingconductor cross-sections L1 - L3 + PE max.4,0 mm.

    Control conductor connecting cable cross-

    section 2,5 mm.Other cross-sections on request.

    3) Sliding contact materials bronze and silver-graphite, connecting conductors L1 L3 + PE(bronze) max. 6.0 mm2. Connecting conductorsof the control conductors (silver-graphite)2.5 mm2. Other cross section on request.

    noitangiseD .ontraP

    seloP

    I ,N /DE%08

    lairetamtcatnocgnidilS

    elbaccirteM

    /noinu

    ebutdetagurroc

    elbacgnitcennoC

    srotcudnoclatoT EP-2L-1L

    lortnoC

    rotcudnoc

    04-4-WAS-LCD )1 44185678 4 4 0 RB/A04 -

    71WN/52M

    mm6x4

    02-4-WAS-LCD )2 44285678 4 4 0 RB/A02 - mm4x4

    04-5-WAS-LCD )1 44385678 5 4 1 RB/A04 RB/A04 mm)5,2x1+6x4(

    02-5-WAS-LCD )2 44485678 5 4 1 RG/A02 RG/A02 mm)5,2x1+4x4(

    M-04-5-WAS-LCD )3 44777678 5 4 1 RB/A04 RGIS/A02 mm)5,2x1+6x4(

    04-6-WAS-LCD)1

    44585678 6 4 2 RB/A04 RB/A04 mm)5,2x2+6x4(

    02-6-WAS-LCD )2 44685678 6 4 2 RG/A02 RG/A02 mm)5,2x2+4x4(

    M-04-6-WAS-LCD )3 44877678 6 4 2 RB/A04 RGIS/A02 mm)5,2x2+6x4(

    04-7-WAS-LCD )1 44785678 7 4 3 RB/A04 RB/A04 mm)5,2x3+6x4(

    02-7-WAS-LCD )2 44885678 7 4 3 RG/A02 RG/A02 mm)5,2x3+4x4(

    M-04-7-WAS-LCD )3 44977678 7 4 3 RB/A04 RGIS/A02 mm)5,2x3+6x4(

  • 7/27/2019 bus bar selection 20338744_0606073419

    27/40

    20338744

    .p65/070606

    27

    1) Current collector trolleys with graphite sliding contacts must be used in DCL installations operated close tothe sea, outdoors and in chemical environments. Use a higher number of current collector trolleys to ensurecontact reliability.

    2) If 2 current collector trolleys are connected in parallel, twice the rated current can be expected to occur.

    If 3 current collector trolleys are connected in parallel, the rated current will be increased by a factor of3 - 10%.

    3) Single conductors in the corrugated tube. Maximum cable length 2000 mm Other lengths on request.

    Minimum length: 500 mm / maximum length: 10000 mm.

    The following information is required for ordering a current collector trolley (see mod-el code order text):

    Conductor line type, DCL

    Current collector trolley

    Number of poles ( 4,5, 6, or 7 sliding contacts)

    Permissible current (20 or 40 A)

    Protective earth conductor PE (with or without)

    6.8.1 Current collector technicaldata

    For current collecting trolleys not fitted with protective earth conductor (marking PEis not applied) this must be indicated in the order section and specified as a part no.with no PE. In this version the green-yellow core is replaced by a black core. Themarking (PE) is not applied.

    For the transmission of control signals and at low voltages (24 48 V, IN# 1 A) the

    use of silver-graphite-sliding contacts in connection with stainless steel plated copperbars is recommended.If necessary, the use of at least 2 current collecting trolleys can be reasonable.

    Model code Order text, e.g.:

    DCL-SAW-4-40-PE

    or DCL-SAW-7-20-3500 (no PE, 3500 mm connecting cable)

    lairetamtcatnocgnidilS eznorB etihparG )1 etihparG-revliS )1

    egnarnoitacilppA ylppusygrenEylppusygrenE

    noissimsnartataDnoissimsnartataD

    egataloVelbissimreP V096ot42 .

    tnerrucsuounitnoC )2

    FDC%08htiw A04 A02 A02

    FDC%06htiw A54 A02 A02

    FDC%04htiw A05 A52 A52

    elbacgnitcennoC )3EP+3L-1L mm0002xmm6 mm0002xmm4

    elbaClortnoC DE%08,A52.xam,mm5.2

    deepslevarT

    noitcesthgiartS nim/m002.xam

    noitcesevruCnim/m001.xam

    srefsnarT

    Rrofgnitaitogen-evruC $ mm008

    Connecting cable length (mm)

  • 7/27/2019 bus bar selection 20338744_0606073419

    28/40

    20338744

    .p65/070606

    28

    6.9 Towing arm for DCL current collector trolley6.9.1 Standard towing arm (not for transfer sections)

    42225844.eps

    42206144.eps

    Detail X

    Model code Order text, e.g.:

    Towing arm DCL-MIT

  • 7/27/2019 bus bar selection 20338744_0606073419

    29/40

    20338744

    .p65/070606

    29

    6.9.2 Towing arm for free transfer sections

    42225944.eps

    42226344.eps

    Model code Order text, e.g.:

    Towing arm for transfer section DCL-MIT

  • 7/27/2019 bus bar selection 20338744_0606073419

    30/40

    20338744

    .p65/070606

    30

    6.10 Profile sealing lip

    42212444.eps

    Order text, e.g.:DCL profile sealing lip 876 508 44 1)DCL assembly tool for profile sealing lip 876 509 44Cyacrylat glue (super glue), 20 gr. 000 383 44 2)

    6.10.1 Assembly tool for fitting theprofile sealing lip Disconnect the DCL installation from the power supply before fitting the

    profile sealing lip.

    Cable slider

    42262144.eps

    Handle

    Roller pair

    DCL assembly tool

    The profile sealing lip is supplied on rolls in lengths measuring 40 m.

    Profile sealing lip sections have to be bonded together using cyanoacrylate glue(super glue)2) for longer DCL tracks. Ensure the bonding surfaces are clean and fittogether.

    Profile sealing lip length = 2 x DCL installation length

    The profile sealing lips are individually pushed into both sides of the DCL conductorenclosure (see also assembly instructions 214 399 44, section 3.11.1).

    If profile sealing lips are used with the DCL, the teminal box enclosure halveson the current collector trolley must be prepared. (see note in section 6.8).

    1) Profile sealing lip may be added to order per meter. Please specify in the order.2) Order, if required.

    Model code

  • 7/27/2019 bus bar selection 20338744_0606073419

    31/40

    20338744

    .p65/070606

    31

    6.11 Isolating section

    98

    5,5

    5

    ,5

    5,5

    5,5

    5,5

    205

    5,5

    5,5

    5,5

    42145244.eps

    For control purposes, the DCL conductor line can be interrupted by means ofisolating sections on straigth sections or line feeds.

    The isolating sections can only be combined with 100 A copper conductors.

    The isolating section can be fitted in the factory or on site.

    If the isolating sections are fitted in the factory, the following detailed information isrequired:

    - postition of the isolating section/sections in the installation

    - conductor no.

    - length of each isolating section

    Isolating

    sectionU

    off,isolatin

    gsection

    S

    Isolatingsecti

    onS

    Cucondu

    ctor

    100A

    Cucondu

    ctor

    100A

    Cucondu

    ctor

    100A

    Cucondu

    ctor

    100A

    Model code Order text, e.g.:

    Isolating section U 876 676 44

    Isolating section S 876 678 44

  • 7/27/2019 bus bar selection 20338744_0606073419

    32/40

    20338744

    .p65/070606

    32

    7 Component parts

    7.1 Straight sections andaccessories

    7.1.1 Component set for slidingsuspension with C-rail bracket

    noitangiseD .ontraP

    noisnepsusgnidilS

    44736678gnittifnipdedaerhT

    )ffo2(8MtunkcoL

    07x8MwercsknusretnuoC

    noitangiseD .ontraP

    noisnepsusgnidilS

    44836678tekcarbgnitnuoM

    noitcesgnipmalcliar-C

    1) Clamp section not required for 100 A, 140 A and 200 A conductors.

    2) off, isolating section S = 97 mm isolating distance

    off, isolating section S + off, isolating section U = 205 mm isolating distance

    The isolating distance can be extended by adding further isolating sections (isolating section U)(see assembly instructions 214 399 44, section 4.12).

    7.1.2 Component set for slidingsuspension with M8 threadedpin

    noitangiseD ytitnauQ .ontraP

    noitcesUrotcennocrotcudnoC 1

    44396678

    gulrotcennocrotcudnoC 2

    02x6MwercsdaehdnuoR 2

    6MtunkcoL 2

    noitcespmalC )1 2

    22x6MwercsdaehdnuoR 2

    7.1.3 Component set for conductorconnector

    noitangiseD .ontraP

    UnoitcesgnitalosI )2 44676678

    I noitcesgnitalos S )2 44876678

    7.1.4 Isolating sections

  • 7/27/2019 bus bar selection 20338744_0606073419

    33/40

    20338744

    .p65/070606

    33

    stestcatnocgnidilS

    7+6/5-WAS-LCD

    etihparg-revlis,A02/eznorb,A04 )3

    noitangiseD .ontraP

    A02/A04elop-5testcatnocgnidilS

    )WASelop-5rof( 33627678A02/A04elop-7testcatnocgnidilS

    )WASelop-7+6rof(33727678

    7.2.1Current collector andcurrent collector trolley

    The parts listed below are subject to a greater or lesser amount of wear while acurrent collector trolley is in operation.

    Wear depends on various factors and is not determined by the current collector trolleyoperating period alone.Preventive maintenance is therefore required.

    Worn current collector trolleys or other components must be replaced immediately.

    stestcatnocgnidilS

    -7+6/5+4-WAS-LCD eznorb,A04 )1

    noitangiseD .ontraP

    )WASelop-5+4rof(A04elop-5testcatnocgnidilS 33517678

    )WASelop-7+6rof(A04elop-7testcatnocgnidilS 33617678

    stestcatnocgnidilS

    -7+6/5+4-WAS-LCD etihparg,A02 )2

    noitangiseD .ontraP

    )WASelop-5+4rof(A02elop-5testcatnocgnidilS 33717678

    )WASelop-7+6rof(A02elop-7testcatnocgnidilS 33817678

    Sliding contact set Bronze or Graphite

    7.2 DCL Spare part-sets

    Line power feed set

    noitangiseD .ytQ .ontraP

    LCD07edisnoitcennoC

    )straptnorferusolcne(2

    33235678

    )strapediserusolcne(trapretneC 2

    12GPtuopsyrtnE 1

    24GPtuopsyrtnE 1

    6Mtun.xeH 2

    21x6Mwercs.lyC 2

    End power feed set

    Sliding contact set Bronze / Silver-Graphite

    noitangiseD .ytQ .ontraP

    pacdnE 2

    3343567861-KA-LCDpacnoitcennoC 2

    12GPtuopsyrtnE 4

    5.9x5.3TSwercsgnippat-fleS 6

    1) Sliding contacts power + control conductor: bronze

    2) Sliding contacts power + control conductor: graphite

    3) Sliding contacts power: bronzeSliding contacts control conductor: silver-graphite

  • 7/27/2019 bus bar selection 20338744_0606073419

    34/40

    20338744

    .p65/070606

    34

    + resistant resitant to a limited extent

    - not resistant

    8 Resistance to acids, chemicals and fuels

    8.1 Acids

    8.2 Fuels, oil, grease etc.

    8.3 Chemicals

    Applies to all chemicals:

    Conductors (Cu) subject to increasedoxidation (corrosion)

    Resistance information only valid forroom temperature (20 C).

    muideM krameR

    dicA .cnoC

    dicacimorhC %04 .tcatnoctceriddiovAdicaciruflus-cimorhC %02

    dicacirtiN %01 +

    stcatnocgnidilsforaewdesaercnI

    dicacirufluS %01 +

    dicacionahtE %5 +

    dicacinobraC %01 +

    dicacielO +

    dicaciratrat-D %01 +

    dicacimroF %02 +

    C03+erutarepmet.xaM

    C06+otC03+morf

    srotcelloctnerrucforaewdesaercnI

    dicacinesrA %02 +

    dicaciroB %01 +

    dicaciroulfordyH +

    dicacitcaL %01 +

    dicacirohpsohP %05 +

    dicacilaxO %01 +

    dicacirolhcordyH %02

    dicacirtiC %01 +

    muideM krameR

    tiripsmuelorteP

    tcatnoctceriddiovA

    lortepralugeR

    lortepedargrepuS

    enisoreK

    tiripsmuelortepetihW

    lioleseiD

    elozneB -

    )scitamoramorfeerf(esaerg,liO +

    tcatnoctceriddiovAliognillirD

    lioekarbETA

    sffutsdooF +

    retawaeSmk5ecnatsid +

    muideM krameR

    snoitulosenilaklA%1< +

    %1> / m5ecnatsidmuminiMretawainommA -

    lohoclA +

    snobracordyHcitahppila -

    citamora -

    stnevloscirolhC -

    retsE -

    enoteK -

    enelyhterolhcirT -

    stnevlosenilaclA .yawlareneganiderewsnaebtonnaC

    etatecalyhtE

    lonatuB -

    etatecalytuB -

    lonahteM -

    louluT -

    enelyX -

    edirolhcartetnobraC

    enotecA -

    eylgnihcaelB

  • 7/27/2019 bus bar selection 20338744_0606073419

    35/40

    20338744

    .p65/070606

    35

    EnquiryDemag Compact Line

    Demag-Compact-Line O DCL - _____ - _____ PE - PVC

    Selected/dimensioned by O Customer O Demag Wetter / Deutschland

    Type _____ Number of poles _____ A (rated current)

    Length _____ m

    Rated voltage/frequency _____ V _____ Hz

    Control voltage _____ V

    Protective earth conductor PE O Yes O No

    Complete DCL track O Yes _____ number of DCL tracks

    O No O Spare parts see remark

    Track layout O straight O curved

    according to enclosed drawing

    Electrical power feed point O Line power feed _____ number of

    O End power feed _____ number of

    Current collector trolley _____ number of _____ mm cable length

    O Bronze sliding contacts

    O Graphite sliding contacts

    O Including standard towing arm (not for transfer sections)

    Suspension method O C-rail O M 8 threaded pin

    Accessories O Yes, the following: O No

    Address and reference of the customer

    _______________________________________________________________________

    Remarks:

    Project no.

    Page 11 page(s)

  • 7/27/2019 bus bar selection 20338744_0606073419

    36/40

    20338744

    .p65/070606

    36

    OrderDemag Compact Line

    Demag-Compact-Line O DCL - _____ - _____ PE - PVC

    Selected/dimensioned by O Customer O Demag Wetter / Deutschland

    Type _____ Number of poles _____ A (rated current)

    Length _____ m

    Rated voltage/frequency _____ V _____ Hz

    Control voltage _____ V

    Protective earth conductor PE O Yes O No

    Complete DCL track O Yes _____ number of DCL tracks

    O No O Spare parts see remark

    Track layout O straight O curved

    according to enclosed drawing

    Electrical power feed point O Centre power feed section _____ number of

    O End power feed _____ number of

    Current collector trolley _____ number of _____ mm cable length

    O Bronze sliding contacts

    O Graphite sliding contacts

    O Including standard towing arm (not for transfer sections)

    Suspension method O C-rail O M 8 threaded pin

    Accessories O Yes, the following: O No

    Address and reference of the customer

    _______________________________________________________________________

    Remarks:

    Project no.

    Page 11 page(s)

    Reproduction in whole or in part only with prior consent of Demag Cranes & Components GmbH, D-58286 Wetter Not l iable for errors or omissions. Subject to change.Prin

    tedinGermany

    DZS/120

    0/2T/PDF080704

  • 7/27/2019 bus bar selection 20338744_0606073419

    37/40

    20338744

    .p65/070606

    37

    Notes

  • 7/27/2019 bus bar selection 20338744_0606073419

    38/40

    20338744

    .p65/070606

    38

    Notes

  • 7/27/2019 bus bar selection 20338744_0606073419

    39/40

    20338744

    .p65/070606

    39

    Notes

  • 7/27/2019 bus bar selection 20338744_0606073419

    40/40

    Demag Cranes & Components GmbHAntriebstechnik