High Impedance Bus Bar Protection

Embed Size (px)

Citation preview

  • 8/13/2019 High Impedance Bus Bar Protection

    1/16

    Agenda

    Extension of existing ( OLD) BUS BAR PROTECTION

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    TIME SYNCHRONISATION OF RELAYS

    DISTRUBANCE RECORD WORK STATION

    TEST PLUGS & TEST EQUIPMENTS

  • 8/13/2019 High Impedance Bus Bar Protection

    2/16

    HV Application: Busbar Protection

    Kirchhoffs Principle applied to a healthy system

    I = 0

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    I1 = I2 + I3I1 - I2 - I3 = 0

    I1 I3I2

  • 8/13/2019 High Impedance Bus Bar Protection

    3/16

    Without Busbar Protection (1)

    F2F1

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    There are fewer faults on busbars than on other parts of the power system

    No dislocation of system due to accidental operation of busbar protection.

    Slow fault clearance.Busbar faults at F1 and F2 are cleared by remote time delayed protection oncircuits feeding the faults:

    Time Delayed Overcurrent orTime Delayed Distance Protection

  • 8/13/2019 High Impedance Bus Bar Protection

    4/16

    Busbar Faults Are Usually Permanent

    CAUSES : Insulation failures Circuit breaker failures Falling debris Isolators operated outside their ratings Safety earths left connected

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    urrent trans ormer a ures

    THEREFORE :Circuit breakers should be tripped and locked

    out by busbar protection

  • 8/13/2019 High Impedance Bus Bar Protection

    5/16

    Busbar Protection must be:

    RELIABLE

    Failure could cause widespread damage to the substation

    STABLE

    False tripping can cause widespread interruption ofsupplies to customers

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    DISCRIMINATING

    Should trip the minimum number of breakers to clear thefault

    FAST

    To limit damage and possible power system instability

  • 8/13/2019 High Impedance Bus Bar Protection

    6/16

    1 Breaker Scheme

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

  • 8/13/2019 High Impedance Bus Bar Protection

    7/16

    1 Breaker Bus Protection

    87

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    87

  • 8/13/2019 High Impedance Bus Bar Protection

    8/16

    Double Bus Protection

    Z1

    Z3

    Z2

    Z4

    BS

    BC1 BC2F1 F2 F3 F4

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    BCM1

    BCM2

    FM1

    FM2

    FM3

    FM4

    BSM

    Z1Z3

    ZCK

    Z2Z4

    ZCK

    Z1 Z2 Z4Z3 ZCK

  • 8/13/2019 High Impedance Bus Bar Protection

    9/16

    Effect of C.T. Location onBusbar Protection Performance

    Circuitprotection

    Interlockedovercurrentrelay

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    Busbarprotection

    protection

    Busbarprotection

    Overlapping C.T.s

    Circuitprotection

    Busbarprotection

    Interlockedovercurrentrelay

    All C.T.s on line sideof circuit breaker

    All C.T.s on Busbar sideof circuit breaker

  • 8/13/2019 High Impedance Bus Bar Protection

    10/16

    High Impedance Protection

    Simple system to apply andextend.

    High sensitivity for phase and

    earth faults.

    Extremely stable for externalfaults.

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    CT requirements: Equal ratiosClass X

    May require stabilising resistors,RST.

    May require non-linear resistors

    (Metrosils).

    RST

    METROSIL

    87

  • 8/13/2019 High Impedance Bus Bar Protection

    11/16

    Isolator Auxiliary Switches

    R

    M

    A B C D

    Auxiliary switches should :1) Close before the isolator

    closes

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    a b c d

    rm

    Buswires

    2) Open after the isolatoropens

    In order to maintain stabilityon switching.

  • 8/13/2019 High Impedance Bus Bar Protection

    12/16

    Differential Relay CircuitABCN

    Zone bus wires

    95X

    95X

    95X

    Bus wire short contacts

    Supervisionrelay

    95

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    Stabilising

    resistors

    87 87 87

    v v v

    Metrosil

    resistors

  • 8/13/2019 High Impedance Bus Bar Protection

    13/16

    Typical Trip Relay Arrangement

    Double Busbar System

    In Out

    CSS - M1

    CSS - M2

    87M1 - 1

    87M2 - 1

    -

    M1 RM2

    a1

    c196E

    96D2

    96D1

    -+87CH - 1

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    CSS - R

    b1

    c2

    D.C. Buswires

    80T

    96H2

    96H1

    96G

    96F2

    96F1

  • 8/13/2019 High Impedance Bus Bar Protection

    14/16

  • 8/13/2019 High Impedance Bus Bar Protection

    15/16

    Single Bus Protection

    F1 F2 F3 F4

    Z2Z1

    BS

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    FM1

    FM2

    FM3

    FM4BSM

    Z1

    ZCK

    Z2

    ZCK

    ZCKZ1 Z2

  • 8/13/2019 High Impedance Bus Bar Protection

    16/16

    Double Bus Protection

    Z1

    Z3

    Z2

    Z4

    BS

    BC1 BC2F1 F2 F3 F4

    ALSTOM 2010. All rights reserved. Information contained in this document is indicative only. No representation or warranty is given or should be relied on that it is complete or correct or will apply to anyparticular project. This will depend on the technical and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or disclosure to third parties, withoutexpress written authority, is strictly prohibited.

    BCM1

    BCM2

    FM1

    FM2

    FM3

    FM4

    BSM

    Z1Z3

    ZCK

    Z2Z4

    ZCK

    Z1 Z2 Z4Z3 ZCK