117213 TABLE OF CONTENTS Page 1Bella Vista Storage Shed 3/6/2017

TABLE OF CONTENTS

DIVISION 03 - CONCRETE

03 30 00 CAST-IN-PLACE CONCRETE

DIVISION 04 - MASONRY

04 20 00 UNIT MASONRY

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 15 00 WOOD DECKING06 17 53 SHOP-FABRICATED WOOD TRUSSES06 20 00 FINISH CARPENTRY

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 21 00 THERMAL INSULATION07 31 13 ASPHALT SHINGLES07 62 00 SHEET METAL FLASHING AND TRIM07 92 00 JOINT SEALANTS

DIVISION 08 - OPENINGS

08 11 13 HOLLOW METAL DOORS AND FRAMES08 33 23 OVERHEAD COILING DOORS08 71 00 DOOR HARDWARE

DIVISION 09 - FINISHES

09 21 16 GYPSUM BOARD ASSEMBLIES09 90 00 PAINTING AND COATING

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 12 16 ASPHALT PAVING

117213 / Alta High Storage Shed 03 30 00 - 1 CAST-IN-PLACE CONCRETE

SECTION 03 30 00CAST-IN-PLACE CONCRETE

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data: Submit manufacturers' data on manufactured products showing compliance withspecified requirements and installation instructions.

B. Sustainable Design Submittal: If any fly ash, ground granulated blast furnace slag, silica fume,rice hull ash, or other waste material is used in mix designs to replace Portland cement, submitthe total volume of concrete cast in place, mix design(s) used showing the quantity of portlandcement replaced, reports showing successful cylinder testing, and temperature on day of pour ifcold weather mix is used; use LEED New Product Content Form.

1.02 QUALITY ASSURANCEA. Perform work of this section in accordance with ACI 301 and ACI 318.B. Follow recommendations of ACI 305R when concreting during hot weather.C. Follow recommendations of ACI 306R when concreting during cold weather.

PART 2 PRODUCTS2.01 FORMWORK

A. Formwork Design and Construction: Comply with guidelines of ACI 347R to provide formworkthat will produce concrete complying with tolerances of ACI 117.

B. Form Materials: Contractor's choice of standard products with sufficient strength to withstandhydrostatic head without distortion in excess of permitted tolerances.

2.02 REINFORCEMENTA. Reinforcing Steel: ASTM A615/A615M, Grade 60 (60,000 psi).

1. Type: Deformed billet-steel bars.2. Finish: Unfinished, unless otherwise indicated.

B. Steel Welded Wire Reinforcement (WWR): Galvanized, plain type, ASTM A1064/A1064M.1. Form: Coiled Rolls.2. WWR Style: 4 x 8-W6 x W10.

C. Reinforcement Accessories:1. Tie Wire: Annealed, minimum 16 gage, 0.0508 inch.2. Chairs, Bolsters, Bar Supports, Spacers: Sized and shaped for adequate support of

reinforcement during concrete placement.2.03 CONCRETE MATERIALS

A. Cement: ASTM C150/C150M, Type I - Normal Portland type. B. Fine and Coarse Aggregates: ASTM C 33.C. Lightweight Aggregate: ASTM C330/C330M.D. Water: Clean and not detrimental to concrete.

2.04 ADMIXTURESA. Do not use chemicals that will result in soluble chloride ions in excess of 0.1 percent by weight

of cement.B. Air Entrainment Admixture: ASTM C260/C260M.

2.05 CONCRETE MIX DESIGNA. Proportioning Normal Weight Concrete: Comply with ACI 211.1 recommendations.

1. Replace as much Portland cement as possible with fly ash, ground granulated blastfurnace slag, silica fume, or rice hull ash as is consistent with ACI recommendations.

Bella Vista Storage Shed

117213 / Alta High Storage Shed 03 30 00 - 2 CAST-IN-PLACE CONCRETE

B. Concrete Strength: Establish required average strength for each type of concrete on the basisof field experience or trial mixtures, as specified in ACI 301.

C. Admixtures: Add acceptable admixtures as recommended in ACI 211.1 and at ratesrecommended or required by manufacturer.

D. Normal Weight Concrete:1. Compressive Strength, when tested in accordance with ASTM C39/C39M at 28 days:

4,000 pounds per square inch.2. Water-Cement Ratio: Maximum 40 percent by weight.3. Total Air Content: 4 percent, determined in accordance with ASTM C173/C173M.

PART 3 EXECUTION3.01 PREPARATION

A. Formwork: Comply with requirements of ACI 301. Design and fabricate forms to support allapplied loads until concrete is cured, and for easy removal without damage to concrete.

3.02 INSTALLING REINFORCEMENT AND OTHER EMBEDDED ITEMSA. Comply with requirements of ACI 301. Clean reinforcement of loose rust and mill scale, and

accurately position, support, and secure in place to achieve not less than minimum concretecoverage required for protection.

3.03 PLACING CONCRETEA. Place concrete in accordance with ACI 304R.

3.04 FLOOR FLATNESS AND LEVELNESS TOLERANCESA. Maximum Variation of Surface Flatness:

1. Exposed Concrete Floors: 1/4 inch in 10 feet.2. Under Seamless Resilient Flooring: 1/4 inch in 10 feet.3. Under Carpeting: 1/4 inch in 10 feet.

B. Correct the slab surface if tolerances are less than specified.C. Interior slab is to slope out as noted. Apron and other slabs shall slope as noted.D. Correct defects by grinding or by removal and replacement of the defective work. Areas

requiring corrective work will be identified. Re-measure corrected areas by the same process.3.05 CURING AND PROTECTION

A. Comply with requirements of ACI 308R. Immediately after placement, protect concrete frompremature drying, excessively hot or cold temperatures, and mechanical injury.

END OF SECTION 03 30 00

Bella Vista Storage Shed

117213 / Bella Vista Storage Shed 04 20 00 - 1 UNIT MASONRY

SECTION 04 20 00UNIT MASONRY

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data: Provide data for masonry units, fabricated wire reinforcement, mortar, andmasonry accessories.

B. Samples: Submit four samples of decorative block units to illustrate color, texture, andextremes of color range.

PART 2 PRODUCTS2.01 CONCRETE MASONRY UNITS

A. Concrete Block: Comply with referenced standards and as follows:1. Size: Standard units with nominal face dimensions of 16 by 8 inches and nominal depth of

8 inches.2. Special Shapes: Provide non-standard blocks configured for corners.3. Load-Bearing Units: ASTM C90, normal weight.

a. Exposed Faces: Special color and texture, as follows: split-faced exterior andbanding.

2.02 MORTAR MATERIALSA. Masonry Cement: ASTM C91/C91M, Type N.

1. Colored Mortar: Premixed cement as required to match Architect's color sample.B. Water: Clean and potable.

2.03 REINFORCEMENT AND ANCHORAGEA. See structural drawings.B. Single Wythe Joint Reinforcement: Truss or ladder type; ASTM A1064/A1064M steel wire, mill

galvanized to ASTM A641/A641M, Class 3; 0.1483 inch side rods with 0.1483 inch cross rods; width as required to provide not more than 1 inch and not less than 1/2 inch of mortar coverageon each exposure.

2.04 LINTELSA. See structural drawings.

2.05 MORTAR MIXESA. Mortar for Unit Masonry: ASTM C270, using the Proportion Specification.

1. Exterior, loadbearing masonry: Type N.B. Colored Mortar: Proportion selected pigments and other ingredients to match Architect's

sample, without exceeding manufacturer's recommended pigment-to-cement ratio.PART 3 EXECUTION3.01 COLD AND HOT WEATHER REQUIREMENTS

A. Comply with requirements of ACI 530/530.1/ERTA or applicable building code, whichever ismore stringent.

3.02 COURSINGA. Establish lines, levels, and coursing indicated. Protect from displacement.B. Maintain masonry courses to uniform dimension. Form vertical and horizontal joints of uniform

thickness.C. Concrete Masonry Units:

1. Bond: Running.2. Coursing: One unit and one mortar joint to equal 8 inches.3. Mortar Joints: Concave.

117213 / Bella Vista Storage Shed 04 20 00 - 2 UNIT MASONRY

3.03 PLACING AND BONDINGA. Lay solid masonry units in full bed of mortar, with full head joints, uniformly jointed with other

work.3.04 REINFORCEMENT AND ANCHORAGE - GENERAL

A. Unless otherwise indicated on drawings or specified under specific wall type, install horizontaljoint reinforcement 16 inches on center.

END OF SECTION 04 20 00

117213 / Bella Vista Storage Shed 06 15 00 - 1 WOOD DECKING

SECTION 06 15 00WOOD DECKING

PART 1 GENERAL1.01 SUBMITTALS

A. Shop Drawings: Indicate deck framing system, loads and cambers, bearing details, and framedopenings.

PART 2 PRODUCTS2.01 WOOD MATERIALS

A. Wood fabricated from old growth timber is not permitted.B. Marking: Mark each piece with producer's stamp indicating compliance with specified

requirements; for pieces exposed to view in completed construction, submit manufacturer'scertificate certifying that products conform to specified requirements in lieu of grade stamping.

C. Plywood Decking: PS 1 veneer plywood; APA Rated Sheathing, Span Rating ____; Exteriorgrade;1 A interior veneer appearance grade; sanded.

2.02 ACCESSORIESA. Fasteners and Anchors:

PART 3 EXECUTION3.01 INSTALLATION - BOARD DECKING

A. Install decking perpendicular to framing members, with ends staggered over firm bearing. Onsloped surfaces, lay decking with tongue upward.

END OF SECTION 06 15 00

117213 / Bella Vista Storage Shed 06 17 53 - 1 SHOP-FABRICATED WOODTRUSSES

SECTION 06 17 53SHOP-FABRICATED WOOD TRUSSES

PART 1 GENERAL1.01 SUBMITTALS

A. Shop Drawings: Show truss configurations, sizes, spacing, size and type of plate connectors,cambers, framed openings, bearing and anchor details, and bridging and bracing.

1.02 QUALITY ASSURANCEA. Designer Qualifications: Perform design by or under direct supervision of a Professional

Structural Engineer experienced in design of this Work and licensed in the State in which theProject is located.

PART 2 PRODUCTS2.01 TRUSSES

A. Wood Trusses: Designed and fabricated in accordance with TPI 1 and TPI DSB-89 to achievestructural requirements indicated.1. See structural drawings.

2.02 MATERIALSA. Lumber:

1. Moisture Content: Between 7 and 9 percent.2. Lumber fabricated from old growth timber is not permitted.

2.03 ACCESSORIESA. Wood Blocking, Bridging, Plates, and Miscellaneous Framing: Softwood lumber, any species,

construction grade, 19 percent maximum and 7 percent minimum moisture content.PART 3 EXECUTION3.01 ERECTION

A. Install trusses in accordance with manufacturer's instructions and TPI DSB-89 and TPI BCSI 1;maintain a copy of each TPI document on site until installation is complete.

B. Set members level and plumb, in correct position.END OF SECTION 06 17 53

117213 / Bella Vista Storage Shed 06 20 00 - 1 FINISH CARPENTRY

SECTION 06 20 00FINISH CARPENTRY

PART 1 GENERAL1.01 SUBMITTALS

A. Shop Drawings: Indicate materials, component profiles, fastening methods, jointing details, andaccessories.

PART 2 PRODUCTS2.01 FINISH CARPENTRY ITEMS

A. Shelving and Brackets.2.02 WOOD-BASED COMPONENTS

A. Wood fabricated from old growth timber is not permitted.2.03 SHEET MATERIALS2.04 PLASTIC LAMINATE MATERIALS

A. Low Pressure Laminate: Melamine; white color and matte surface texture.2.05 ACCESSORIES

A. Plastic Edge Trim: Extruded convex shaped; smooth finish; self locking serrated tongue; ofwidth to match component thickness; white color.

2.06 FABRICATIONA. Shop assemble work for delivery to site, permitting passage through building openings.B. Apply plastic laminate finish in full uninterrupted sheets consistent with manufactured sizes. Fit

corners and joints hairline; secure with concealed fasteners. Slightly bevel arises. Locatecounter butt joints minimum 2 feet from sink cut-outs.

PART 3 EXECUTION3.01 INSTALLATION

A. Set and secure materials and components in place, plumb and level.B. Carefully scribe work abutting other components, with maximum gaps of 1/32 inch. Do not use

additional overlay trim to conceal larger gaps.END OF SECTION 06 20 00

117213 / Bella Vista Storage Shed 07 21 00 - 1 THERMAL INSULATION

SECTION 07 21 00THERMAL INSULATION

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data: Provide data on product characteristics, performance criteria, and productlimitations.

PART 2 PRODUCTS2.01 APPLICATIONS

A. Insulation in Wood Framed Ceiling Structure: Batt insulation with integral vapor retarder.2.02 BATT INSULATION MATERIALS

A. Where batt insulation is indicated, either glass fiber or mineral fiber batt insulation may be used,at Contractor's option.

B. Glass Fiber Batt Insulation: Flexible preformed batt or blanket, complying with ASTM C665;friction fit.1. Flame Spread Index: 75 or less, when tested in accordance with ASTM E84.2. Smoke Developed Index: 450 or less, when tested in accordance with ASTM E84.3. Combustibility: Non-combustible, when tested in accordance with ASTM E136, except for

facing, if any.4. Thermal Resistance: R-value of 38.5. Thickness: 8 inch.6. Facing: Asphalt treated Kraft paper, one side.

C. Mineral Fiber Batt Insulation: Flexible or semi-rigid preformed batt or blanket, complying withASTM C665; friction fit; unfaced flame spread index of 0 (zero) when tested in accordance withASTM E84.1. Where indicated, provide foil facing on one side; with flame spread index of 25 or less,

when tested in accordance with ASTM E84.2. Smoke Developed Index: 0 (zero), when tested in accordance with ASTM E84.3. Thermal Resistance: R-value of 38.4. Thickness: 8 inch.

2.03 ACCESSORIESA. Tape: Polyethylene self-adhering type, mesh reinforced, 2 inch wide.B. Tape joints of rigid insulation in accordance with roofing and insulation manufacturers'

instructions.C. Nails or Staples: Steel wire; electroplated or galvanized; type and size to suit application.

PART 3 EXECUTION3.01 BATT INSTALLATION

A. Install insulation in accordance with manufacturer's instructions.B. Install in exterior roof spaces without gaps or voids. Do not compress insulation.

END OF SECTION 07 21 00

117213 / Bella Vista Storage Shed 07 31 13 - 1 ASPHALT SHINGLES

SECTION 07 31 13ASPHALT SHINGLES

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data: Provide data indicating material characteristics.B. Shop Drawings: For metal flashings, indicate specially configured metal flashings.C. Samples: Submit two samples of each shingle color indicating color range and finish

texture/pattern; for color selection.PART 2 PRODUCTS2.01 ASPHALT SHINGLES

A. Asphalt Shingles: Asphalt-coated glass felt, mineral granule surfaced, complying with ASTMD3462/D3462M.1. Fire Resistance: Class A.2. Wind Resistance: Class D, when tested in accordance with ASTM D3161/D3161M.3. Algae Resistant.4. Weight: 300 lb/100 sq ft.5. Self-sealing type.6. Style: Laminated overlay.7. Color: to be determined.

2.02 SHEET MATERIALSA. Underlayment: Self-adhering rubber-modified asphalt sheet complying with ASTM

D1970/D1970M; 22 mil total thickness; with strippable release film and woven polypropylenesheet top surface.1. Minimum Requirements: Comply with requirements of ICC-ES AC188 for

non-self-adhesive sheet.2.03 ACCESSORIES

A. Nails: Standard round wire shingle type, of hot-dipped zinc coated steel, 10 wire gage, 0.1019inch shank diameter, 3/8 inch head diameter, of sufficient length to penetrate through roofsheathing or 3/4 inch into roof sheathing or decking.

2.04 METAL FLASHINGSA. Metal Flashings: Provide sheet metal eave edge, gable edge, and other flashing indicated.B. Aluminum Sheet Metal: Prefinished aluminum, 26 gage, 0.017 inch minimum thickness; PVC

coating, color as selected.PART 3 EXECUTION3.01 INSTALLATION - UNDERLAYMENT

A. Provide over the entire roof.3.02 INSTALLATION - SHINGLES

A. Install shingles in accordance with manufacturer's instructions manufacturer's instructions andNRCA (RM) applicable requirements.

B. Place shingles in straight coursing pattern with 5 inch weather exposure to produce doublethickness over full roof area. Provide double course of shingles at eaves.

END OF SECTION 07 31 13

117213 / Bella Vista Storage Shed 07 62 00 - 1 SHEET METAL FLASHING ANDTRIM

SECTION 07 62 00SHEET METAL FLASHING AND TRIM

PART 1 GENERAL1.01 SUBMITTALS

A. Shop Drawings: Indicate material profile, jointing pattern, jointing details, fastening methods,flashings, terminations, and installation details.

PART 2 PRODUCTS2.01 SHEET MATERIALS

A. Pre-Finished Aluminum: ASTM B209 (ASTM B209M); 20 gage (0.032 inch) thick; plain finishshop pre-coated with modified silicone coating.1. Modified Silicone Polyester Coating: Pigmented Organic Coating System, AAMA 2603;

baked enamel finish system.2. Color: As selected by Architect from manufacturer's standard colors.

2.02 ACCESSORIESA. Fasteners: Galvanized steel, with soft neoprene washers.B. Primer: Zinc chromate type.C. Sealant to be Concealed in Completed Work: Non-curing butyl sealant.D. Sealant to be Exposed in Completed Work: ASTM C920; elastomeric sealant, 100 percent

silicone with minimum movement capability of plus/minus 25 percent and recommended bymanufacturer for substrates to be sealed; clear.

E. Plastic Cement: ASTM D4586/D4586M, Type I.2.03 FABRICATION

A. Form sections true to shape, accurate in size, square, and free from distortion or defects.B. Form pieces in longest possible lengths.C. Form material with flat lock seams, except where otherwise indicated. At moving joints, use

sealed lapped, bayonet-type or interlocking hooked seams.2.04 GUTTER AND DOWNSPOUT FABRICATION

A. Gutters: SMACNA (ASMM), Square profile.B. Downspouts: Rectangular profile.C. Gutters and Downspouts: Size for rainfall intensity determined by a storm occurrence of 1 in 10

years in accordance with SMACNA (ASMM).D. Accessories: Profiled to suit gutters and downspouts.

1. Anchorage Devices: In accordance with SMACNA requirements.2. Gutter Supports: Straps.3. Downspout Supports: Straps.

E. Splash Pads: Precast concrete type, of size and profiles indicated; minimum 3000 psi at 28days, with minimum 5 percent air entrainment.

PART 3 EXECUTION3.01 INSTALLATION

A. Secure flashings in place using concealed fasteners. Use exposed fasteners only wherepermitted.

B. Slope gutters 1/4 inch per 10 feet, minimum.END OF SECTION 07 62 00

117213 / Bella Vista Storage Shed 07 92 00 - 1 JOINT SEALANTS

SECTION 07 92 00JOINT SEALANTS

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data for Accessory Products: Submit manufacturer's technical data sheet for eachproduct to be used, including physical characteristics, installation instructions, andrecommended tools.

PART 2 PRODUCTS2.01 JOINT SEALANT APPLICATIONS

A. Scope:1. Exterior Joints: Seal open joints, whether or not the joint is indicated on the drawings,

unless specifically indicated not to be sealed. Exterior joints to be sealed include, but arenot limited to, the following items.a. Wall expansion and control joints.b. Joints between doors, and other frames and adjacent construction.c. Joints between different exposed materials.d. Openings below ledge angles in masonry.e. Other joints indicated below.

2. Interior Joints: Do not seal interior joints unless specifically indicated to be sealed. Interiorjoints to be sealed include, but are not limited to, the following items.a. Joints between doors, and other frames and adjacent construction.b. Other joints indicated below.

3. Do not seal the following types of joints.a. Intentional weepholes in masonry.b. Joints indicated to be treated with manufactured expansion joint cover or some other

type of sealing device.c. Joints where sealant is specified to be provided by manufacturer of product to be

sealed.d. Joints where installation of sealant is specified in another section.e. Joints between suspended panel ceilings/grid and walls.

B. Exterior Joints: Use non-sag non-staining silicone sealant, unless otherwise indicated.C. Interior Joints: Use non-sag polyurethane sealant, unless otherwise indicated.

1. Wall and Ceiling Joints in Non-Wet Areas: Acrylic emulsion latex sealant.2.02 JOINT SEALANTS - GENERAL

A. Sealants and Primers: Provide products having lower volatile organic compound (VOC) contentthan indicated in SCAQMD 1168.

2.03 NONSAG JOINT SEALANTSA. Non-Staining Silicone Sealant: ASTM C920, Grade NS, Uses M and A; not expected to

withstand continuous water immersion or traffic.1. Movement Capability: Plus and minus 50 percent, minimum.2. Non-Staining To Porous Stone: Non-staining to light-colored natural stone when tested in

accordance with ASTM C1248.3. Dirt Pick-Up: Reduced dirt pick-up compared to other silicone sealants.

B. Polyurethane Sealant: ASTM C920, Grade NS, Uses M and A; single or multi-component; notexpected to withstand continuous water immersion or traffic.1. Movement Capability: Plus and minus 25 percent, minimum.

C. Type ___ - Acrylic Emulsion Latex: Water-based; ASTM C834, single component, non-staining,non-bleeding, non-sagging; not intended for exterior use.

117213 / Bella Vista Storage Shed 07 92 00 - 2 JOINT SEALANTS

2.04 ACCESSORIESA. Backer Rod: Cylindrical cellular foam rod with surface that sealant will not adhere to,

compatible with specific sealant used, and recommended by backing and sealantmanufacturers for specific application.

B. Backing Tape: Self-adhesive polyethylene tape with surface that sealant will not adhere to andrecommended by tape and sealant manufacturers for specific application.

PART 3 EXECUTION3.01 INSTALLATION

A. Perform work in accordance with sealant manufacturer's requirements for preparation ofsurfaces and material installation instructions.

B. Perform installation in accordance with ASTM C1193.C. Install bond breaker backing tape where backer rod cannot be used.D. Install sealant free of air pockets, foreign embedded matter, ridges, and sags, and without

getting sealant on adjacent surfaces.E. Nonsag Sealants: Tool surface concave, unless otherwise indicated; remove masking tape

immediately after tooling sealant surface.END OF SECTION 07 92 00

117213 / Alta High Storage Shed 08 11 13 - 1 HOLLOW METAL DOORS ANDFRAMES

SECTION 08 11 13HOLLOW METAL DOORS AND FRAMES

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data: Materials and details of design and construction, hardware locations,reinforcement type and locations, anchorage and fastening methods, and finishes.

B. Shop Drawings: Details of each opening, showing elevations, frame profiles, and any indicatedfinish requirements.

1.02 DELIVERY, STORAGE, AND HANDLINGA. Comply with NAAMM HMMA 840 or ANSI/SDI A250.8 (SDI-100) in accordance with specified

requirements.PART 2 PRODUCTS2.01 DESIGN CRITERIA

A. Requirements for Hollow Metal Doors and Frames:1. Steel used for fabrication of doors and frames shall comply with one or more of the

following requirements; Galvannealed steel conforming to ASTM A653/A653M, cold-rolledsteel conforming to ASTM A1008/A1008M, or hot-rolled pickled and oiled (HRPO) steelconforming to ASTM A1011/A1011M, Commercial Steel (CS) Type B for each.

2. Accessibility: Comply with ICC A117.1 and ADA Standards.3. Exterior Door Top Closures: Flush end closure channel, with top and door faces aligned.4. Door Edge Profile: Manufacturers standard for application indicated.5. Typical Door Face Sheets: Flush.6. Hardware Preparations, Selections and Locations: Comply with NAAMM HMMA 830 and

NAAMM HMMA 831 or BHMA A156.115 and ANSI/SDI A250.8 (SDI-100) in accordancewith specified requirements.

2.02 HOLLOW METAL DOORSA. Exterior Doors: Thermally insulated.

1. Based on SDI Standards: ANSI/SDI A250.8 (SDI-100).a. Level 3 - Extra Heavy-duty.b. Physical Performance Level A, 1,000,000 cycles; in accordance with ANSI/SDI

A250.4.c. Model 1 - Full Flush.d. Door Face Metal Thickness: 16 gage, 0.053 inch, minimum.

2. Door Thermal Resistance: R-Value of 6.0 minimum, for installed thickness of polystyrene.3. Door Thickness: 1-3/4 inch, nominal.

2.03 HOLLOW METAL FRAMESA. Comply with standards and/or custom guidelines as indicated for corresponding door in

accordance with applicable door frame requirements.B. Exterior Door Frames: Full profile/continuously welded type.

1. Frame Metal Thickness: 16 gage, 0.053 inch, minimum.2. Weatherstripping: Separate, see Section 08 71 00.

2.04 FINISHESA. Primer: Rust-inhibiting, complying with ANSI/SDI A250.10, door manufacturer's standard.

PART 3 EXECUTION3.01 INSTALLATION

A. Install doors and frames in accordance with manufacturer's instructions and relatedrequirements of specified door and frame standards or custom guidelines indicated.

Bella Vista Storage Shed

117213 / Alta High Storage Shed 08 33 23 - 1 OVERHEAD COILING DOORS

SECTION 08 33 23OVERHEAD COILING DOORS

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data: Provide general construction, electrical equipment, and component connectionsand details.

B. Shop Drawings: Indicate pertinent dimensioning, anchorage methods, hardware locations, andinstallation details.

1.02 QUALITY ASSURANCEA. Products Requiring Electrical Connection: Listed and classified by UL (DIR) as suitable for the

purpose specified and indicated.PART 2 PRODUCTS2.01 COILING DOORS

A. Exterior Coiling Doors: Steel slat curtain.1. Capable of withstanding positive and negative wind loads of 20 psf, without undue

deflection or damage to components.2. Sandwich slat construction with insulated core of foamed-in-place polyurethane insulation;

minimum R-value of 8.1.3. Nominal Slat Size: 2 inches wide x required length.4. Finish: Factory painted, ________ color.5. Guides: Angles; galvanized steel.6. Hood Enclosure: Manufacturer's standard; primed steel.7. Electric operation. 8. Mounting: Surface mounted.

2.02 MATERIALSA. Curtain Construction: Interlocking slats.B. Steel Slats: Minimum thickness, ___ gage, ___ inch; ASTM A653/A653M galvanized steel

sheet.C. Guide Construction: Continuous, of profile to retain door in place with snap-on trim, mounting

brackets of same metal.D. Steel Guides: Formed from galvanized steel sheet, ___ gage, ___ inch thick; ___ inch wide;

complying with ASTM A653/A653M.1. Galvanizing: Minimum G90/Z275 coating.

E. Hood Enclosure: Internally reinforced to maintain rigidity and shape.F. Lock Hardware:

1. For motor operated units, additional lock or latching mechanisms are not required.G. Perimeter Seal:

1. Provide full perimeter seal , all sides of coiling door to prevent intrusion by vermin.2.03 ELECTRIC OPERATION

A. Operator, Controls, Actuators, and Safeties: Comply with UL 325; provide products listed byITS (DIR), UL (DIR), or testing agency acceptable to authorities having jurisdiction.1. Provide interlock switches on motor operated units.

B. Electric Operators:1. Mounting: Side mounted.2. Motor Enclosure:

a. Exterior Doors: NEMA MG 1, Type 4; open drip proof.3. Motor Rating: 3/4 hp; continuous duty.4. Motor Voltage: ____ volt, three phase, 60 Hz.

Bella Vista Storage Shed

117213 / Alta High Storage Shed 08 33 23 - 2 OVERHEAD COILING DOORS

5. Motor Controller: NEMA ICS 2, full voltage, reversing magnetic motor starter.6. Controller Enclosure: NEMA 250, Type 1.7. Opening Speed: 12 inches per second.8. Brake: Adjustable friction clutch type, activated by motor controller.9. Manual override in case of power failure.

C. Control Station: Standard three button (OPEN-STOP-CLOSE) momentary control for eachoperator.1. 24 volt circuit.2. Surface mounted next to door.

D. Safety Edge: Located at bottom of curtain, full width, electro-mechanical sensitized type, wiredto stop operator upon striking object, hollow neoprene covered.

PART 3 EXECUTION3.01 INSTALLATION

A. Install units in accordance with manufacturer's instructions.B. Fit and align assembly including hardware; level and plumb, to provide smooth operation.C. Coordinate installation of electrical service with Section 26 27 17.D. Complete wiring from disconnect to unit components.

END OF SECTION 08 33 23

Bella Vista Storage Shed

117213 / Alta High Storage Shed 08 71 00 - 1 DOOR HARDWARE

SECTION 08 71 00DOOR HARDWARE

PART 1 GENERAL1.01 ADMINISTRATIVE REQUIREMENTS

A. Convey Owner's keying requirements to manufacturers.1.02 SUBMITTALS

A. Product Data: Manufacturer's catalog literature for each type of hardware, marked to clearlyshow products to be furnished for this project.

B. Keys: Deliver with identifying tags to Owner by security shipment direct from hardware supplier.1.03 WARRANTY

A. Provide five year warranty for door closers.PART 2 PRODUCTS2.01 DOOR HARDWARE - GENERAL

A. Provide hardware specified or required to make doors fully functional, compliant with applicablecodes, and secure to the extent indicated.

B. Provide products that comply with the following:1. Applicable provisions of federal, state, and local codes.2. Hardware Preparation for Steel Doors and Steel Frames: BHMA A156.115.

C. Finishes: Provide door hardware of the same finish unless otherwise indicated.1. Primary Finish: Satin chrome plated over nickel on brass or bronze, 626 (approx US26D).2. Secondary Finish: Satin chrome plated over nickel on brass or bronze, 626 (approx

US26D).3. Finish Definitions: BHMA A156.18.4. Exceptions:

a. Where base metal is specified to be different, provide finish that is an appearanceequivalent according to BHMA A156.18.

2.02 LOCKS AND LATCHESA. Locks: Provide a lock for every door, unless specifically indicated as not requiring locking.

1. Hardware Sets indicate locking functions required for each door.2. Trim: Provide lever handle or pull trim on outside of all locks unless specifically stated to

have no outside trim.3. Lock Cylinders: Provide key access on outside of all locks unless specifically stated to

have no locking or no outside trim.B. Lock Cylinders: Manufacturer’s standard tumbler type, seven-pin standard core.C. Keying: Grand master keyed.

2.03 HINGESA. Hinges: Provide hinges on every swinging door.

1. Provide five-knuckle full mortise butt hinges unless otherwise indicated.2. Provide ball-bearing hinges at all doors having closers.3. Provide hinges in the quantities indicated.4. Provide non-removable pins on exterior outswinging doors.

B. Butt Hinges: Comply with BHMA A156.1 and BHMA A156.7; standard weight, unless otherwiseindicated.

2.04 CYLINDRICAL LOCKSETSA. Locking Functions: As defined in BHMA A156.2, and as follows.

1. Always-Locked: F86, key required to lock, may not be left unlocked.2. Always exit.

117213 / Alta High Storage Shed 08 71 00 - 2 DOOR HARDWARE

2.05 CLOSERSA. Closers: Complying with BHMA A156.4.

2.06 GASKETING AND THRESHOLDSA. Gaskets: Complying with BHMA A156.22.

1. On each exterior door, provide weatherstripping gaskets, unless otherwise indicated; top,sides.

2. On each exterior door, provide door bottom sweep, unless otherwise indicated.B. Thresholds: Complying with BHMA A156.21.

1. At each exterior door, provide a threshold unless otherwise indicated.C. Provide bottom sweep seal to prevent intrusion of vermin.

2.07 PROTECTION PLATES AND ARCHITECTURAL TRIMA. Drip Guard: Provide projecting drip guard over all exterior doors unless they are under a

projecting roof or canopy.PART 3 EXECUTION3.01 INSTALLATION

A. Install hardware in accordance with manufacturer's instructions and applicable codes.B. Use templates provided by hardware item manufacturer.

3.02 ADJUSTINGA. Adjust hardware for smooth operation.

HARDWARE SETS4.01 HARDWARE SETS - GENERAL4.02 SWING DOORS -- MAY NOT BE LEFT UNLOCKED

A. HW-01: Always-Locked, Non-Fire-Rated:1. Lockset, Always-Locked.2. Exterior Outswing Doors: Lock Guard.3. Can always exit.

END OF SECTION 08 71 00

Bella Vista Storage Shed

117213 / Bella Vista Storage Shed 09 21 16 - 1 GYPSUM BOARD ASSEMBLIES

SECTION 09 21 16GYPSUM BOARD ASSEMBLIES

PART 1 GENERAL1.01 SUBMITTALS

A. Product Data: Provide data on gypsum board, accessories, and joint finishing system.PART 2 PRODUCTS2.01 GYPSUM BOARD ASSEMBLIES

A. Provide completed assemblies complying with ASTM C840 and GA-216.2.02 BOARD MATERIALS

A. Ceiling Board: Special sag resistant gypsum ceiling board as defined in ASTM C1396/C1396M;sizes to minimize joints in place; ends square cut.1. Application: Ceilings, unless otherwise indicated.2. Thickness: 5/8 inch.3. Edges: Tapered.

2.03 ACCESSORIESA. Joint Materials: ASTM C475/C475M and as recommended by gypsum board manufacturer for

project conditions.1. Tape: 2 inch wide, coated glass fiber tape for joints and corners, except as otherwise

indicated.2. Ready-mixed vinyl-based joint compound.

B. Screws for Fastening of Gypsum Panel Products to 0.033 inch wood Members: ASTM C1002;self-piercing tapping screws, corrosion resistant.

PART 3 EXECUTION3.01 BOARD INSTALLATION

A. Comply with ASTM C840, GA-216, and manufacturer's instructions. Install to minimize butt endjoints, especially in highly visible locations.

B. Single-Layer Non-Rated: Install gypsum board in most economical direction, with ends andedges occurring over firm bearing.

3.02 JOINT TREATMENTA. Finish gypsum board in accordance with levels defined in ASTM C840, as follows:

1. Level 4: Walls and ceilings to receive paint finish or wall coverings, unless otherwiseindicated.

3.03 TEXTURE FINISHA. Apply finish texture coating by means of spraying apparatus in accordance with manufacturer's

instructions.END OF SECTION 09 21 16

117213 / Alta High Storage Shed 09 90 00 - 1 PAINTING AND COATING

SECTION 09 90 00PAINTING AND COATING

PART 1 GENERAL1.01 SECTION INCLUDES

A. Scope: Finish all interior and exterior surfaces as noted, unless fully factory-finished 1.02 SUBMITTALS

A. Product Data: Provide complete list of all products to be used, with the following information foreach:

B. Samples: Submit three paper "draw down" samples, 8-1/2 by 11 inches in size, illustratingrange of colors available for each finishing product specified.1. Where sheen is specified, submit samples in only that sheen.

PART 2 PRODUCTS2.01 MANUFACTURERS

A. Provide all paint and coating products used in any individual system from the samemanufacturer; no exceptions.

2.02 PAINTS AND COATINGS - GENERALA. Paints and Coatings: Ready mixed, unless intended to be a field-catalyzed coating.

1. Supply each coating material in quantity required to complete entire project's work from asingle production run.

2. Do not reduce, thin, or dilute coatings or add materials to coatings unless such procedureis specifically described in manufacturer's product instructions.

B. Volatile Organic Compound (VOC) Content: 1. Provide coatings that comply with the most stringent requirements specified in the

following:a. 40 CFR 59, Subpart D--National Volatile Organic Compound Emission Standards for

Architectural Coatings.2. Determination of VOC Content: Testing and calculation in accordance with 40 CFR 59,

Subpart D (EPA Method 24), exclusive of colorants added to a tint base and water addedat project site; or other method acceptable to authorities having jurisdiction.

2.03 PAINT SYSTEMS - EXTERIORA. Ferrous Metals (Bollards), Primed, Latex, 2 Coat:

1. Touch-up with rust-inhibitive primer recommended by top coat manufacturer.2. Semi-gloss: Two coats of latex enamel; ____.

PART 3 EXECUTION3.01 PREPARATION

A. Clean surfaces thoroughly and correct defects prior to coating application.B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best

result for the substrate under the project conditions.3.02 APPLICATION

A. Apply products in accordance with manufacturer's instructions.B. Do not apply finishes to surfaces that are not dry. Allow applied coats to dry before next coat is

applied.END OF SECTION 09 90 00

117213 / Alta High Storage Shed 32 12 16 - 1 ASPHALT PAVING

SECTION 32 12 16ASPHALT PAVING

PART 1 GENERAL1.01 PERFORMANCE REQUIREMENTS

A. Design paving and subbase for patching parking area.PART 2 PRODUCTS2.01 MATERIALS

A. Match existing material, asphalt, and base.2.02 ASPHALT PAVING MIXES AND MIX DESIGN

A. Use dry material to avoid foaming. Mix uniformly.PART 3 EXECUTION3.01 PLACING ASPHALT PAVEMENT - SINGLE COURSE

A. Place asphalt within 24 hours of applying primer or tack coat.END OF SECTION 32 12 16

Bella Vista Storage Shed