Uninterruptible Power Supply 1ph - 3ph from 10 to 20 kVA Applications Networks and servers Industrial control and process automation Building automation Highlights On-line double conversion Transformer free Full IGBT technology Paralleling up to 120 kVA B8031FXS - B8033FXS 11

B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

  • Upload
    others

  • View
    7

  • Download
    7

Embed Size (px)

Citation preview

Page 1: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

Uninterruptible Power Supply1ph - 3ph from 10 to 20 kVA

Applications• Networks and servers• Industrial control and process automation• Building automation

Highlights• On-line double conversion • Transformer free • Full IGBT technology • Paralleling up to 120 kVA

B8031FXS - B8033FXS

11

Page 2: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

12

Main options● Isolation transformer.

● Transformers/autotransformers for voltage adjustment.

● Battery voltage temperature compensation.

● External maintenance bypass wall-mounted box.

● Battery fuse switch wall-mounted box.

● Associated battery cabinets for long autonomy times.

● Parallel kit for load sharing.

● Load-sync for single UPS units.

● Input terminals for remote EPO, external manual bypass auxiliary contact, diesel mode.

● Separate bypass input for B8033FXS.

● Cold start.

Features and benefits● High double conversion efficiency and ECO mode for low running costs and environmental impact.

● Transformer free design for light small size layout.

● Removable power modules architecture and built-in diagnostics for easy maintenance and very low MTTR.

● Hot connection/disconnection of parallel units for easy system resizing.

● Full IGBT technology and electronic PFC, ensuring 0.99 input PF and low THDi for maximum upstream sources compatibility.

● Wide range of configurations with internal batteries for low TCO compact solutions.

● High power battery charger, suiting long autonomy applications.

● Dual DSP plus microcontroller logics for top performance and reliability.

● CAN-bus based distributed parallel control ensuring high load sharing accuracy and no single point of failure.

● Comprehensive set of communication options for total remote monitoring of equipment operation.

● Included bypass contactor for complete backfeed protection and operators’ safety without additional installation costs.

● Fully compliant with all international product standards for maximum quality guarantee.

Autonomy time in minutes with different types of internal batteries

20 kVA

15 kVA

10 kVA

0 5 10 15 20 25 30 35 40 45 50

B8031FXSB8033FXSUninterruptible Power Supply 1ph - 3ph from 10 to 20 kVA

Page 3: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

13

Environmental

UPS operating temperature range 0°C to +40°C

UPS storage temperature range -10°C to +70°C

Altitude (AMSL) < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m

Audible noise at 1 m (dBA) <52

Standards and certifications

Quality assurance, ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 environment, health and safety

Safety IEC/EN 62040-1

EMC IEC/EN 62040-2

Environmental aspects IEC/EN 62040-4

Test and performance IEC/EN 62040-3

Protection degree IEC 60529

Marking CE

B8031FXS - B8033FXS technical data Rating (kVA) 10 15 20

Nominal power (kW) 9 13.5 18

UPS dimensions WxDxH (mm) 450x670x1200

UPS weight (kg) 100 110 110

UPS weight with internal Max.285 Max.275 Max.275

battery (kg)

External battery module 500x670x1200

dimensions WxDxH (mm)

Battery configuration Internal or external, 360 to 372 cells, VRLA (other options)

Max autonomy with int. battery 70% load (min) 49 24 12

Input B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA)

Connection type Hardwired 4w (rectifier), 2w (bypass) Hardwired 4w

Nominal voltage 400 Vac 3-phase with neutral (rectifier) 400 Vac 3-phase with neutral (rectifier)

220/230/240 Vac 1-phase (bypass) 380/400/415 Vac 3-phase with neutral (bypass)

Voltage tolerance -20%, +15% (rectifier); ±10% (bypass)

Frequency and range 50/60 Hz, 45 to 65 Hz

Power factor 0.99

Current distortion (THDi) <4%

Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA)

Connection type Hardwired 2w Hardwired 4w

Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase with neutral

Frequency 50/60 Hz

Voltage regulation

Static: ±1%; dynamic: IEC/EN 62040-3 Class 1

Power factor Up to 0.9, lagging or leading without power derating

Overload capacity

Inverter: 125% for 10 min, 150% for 30 s, >150% for 10 s; bypass: 150% continuous, 1000% for 1 cycle

Efficiency (AC/AC)* Up to 98%

Classification as per IEC/EN 62040-3 VFI-SS-111

Connectivity and function extensions

Front panel Graphic display, mimic LED panel and keyboard, local EPO

Remote communication

Included: serial RS232 and USB; terminal block for battery breaker auxiliary contact. Optional: input terminal block (remote emergency power off, external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software

Optional function extensions

Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit; load-sync for single UPS; other options on request

System

Protection degree IP 20

Colour RAL 7016

Installation layout 10 cm wall-gap, side by side installation allowed

Accessibility Front and top access, bottom cable entry

*according to IEC/EN 62040-3

Other features

Page 4: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

14

B8031FXS - B8033FXS series options Description When do I use it

Parallel kit When the unit is to be paralleled for load sharingLOAD

3-phase input isolation transformer for B8033FXSin extended cabinet

To galvanically isolate UPS from load or to change system’s earth arrangement

1-phase output isolation transformer for B8031FXSin extended cabinet

To galvanically isolate UPS from load or to change system’s earth arrangement

TRANSFORMEROUTPUT

TRANSFORMER CABINET

QRA

Battery fuse switch in wall-mounted box To disconnect and protect an external battery pack

Backfeed protection bypass contactor To be fully protected against backfeed energy upon static bypass failure

Included

Included

Load-sync for single units To synchronize single units’ output for no-break load transfers by downstream static transfer switches

LOAD A LOAD B

Internal battery temperature probe When the unit has internal batteries, for charging voltage compensation with temperature

External battery temperature probe

Internal battery + UPS temperature probe

When the unit has external batteries, for charging voltage compensation with temperature (10 m cable length)

When the unit has internal batteries, for charging voltage compensation with temperature and

UPS temperature monitoring

Input terminal block for remote EPO When the Emergency Power Off (EPO) has to be commanded by a remote control button

Input terminal block for external manual bypass switch auxiliary contact

Input terminal block for diesel mode contact

Input terminal block for external battery switch auxiliary contact

When there is an external maintenance bypass switch, for state monitoring

When battery recharge has to be inhibited over genset operation

When there is an external battery switch, for state monitoring

Dry contact relay card

Remote monitoring panel

RS485 ModBus-RTU port

Web/SNMP Adapter

To send UPS status to PLC’s, SCADA’s or AS400’s by voltage free SPDT contacts

To monitor UPS status by a LED panel from a remote control room (relay card required)

To send UPS status to BMS’s by RS485 connection and ModBus-RTU protocol.

For telemonitoring and teleservice

To send UPS status to BMS’s by Ethernet connection and SNMP or ModBus over IP protocol. To monitor UPS status by any

internet browser from workstations. To receive SMS or e-mail alerts from the UPS on any portable device

Page 5: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

15

INGENIO COMPACTUninterruptible Power Supply

3ph from 10 to 20 kVA

Highlights• On-line double conversion• Transformer free• Full IGBT technology• Parallel redundant configuration• Built-in batteries

Applications• Networks and servers• Small and medium data centers• Telecommunication

Page 6: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

16

Main options● Isolation transformer.

● Transformers/autotransformers for voltage adjustment.

● Battery voltage temperature compensation.

● External maintenance bypass wall-mounted box.

● External battery cabinets for long autonomy times.

● Parallel kit.

● Common battery.

Features and benefits● On-line double conversion mode for total load protection.

● ECO mode for low running costs and environmental impact.

● Full rated output power, ensuring optimal UPS sizing and utilization.

● Transformer free design for light small size layout.

● Full IGBT technology and electronic PFC, ensuring 0.99 input PF and low THDi for maximum upstream sources compatibility.

● Wide input voltage range to save battery life.

● Wide range of configurations with internal and external batteries for low TCO compact solutions.

● Parallel-redundant up to six units, to increase system redundancy.

● Innovative design allows for fast installation.

● Removable tray design for easy battery maintenance.

● Comprehensive set of communication options for total remote monitoring of equipment operation.

● Fully compliant with all international product standards for maximum quality guarantee.

INGENIOCOMPACTUninterruptible Power Supply 3ph from 10 to 20 kVA

20 kVA

10 kVA

0 2 4 6 8 10 12 14 16 18 20

Autonomy time in minutes with different typesof internal batteries

Page 7: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

INGENIO COMPACT technical data Rating (kVA) 10 20

Nominal power (kW) 10 20

UPS dimensions WxDxH (mm) 440x800x800

UPS weight (kg) 75 76

UPS weight with internal battery (kg) 150 165

External battery module 500x650x1200

dimensions WxDxH (mm)

Battery configuration Internal (standard): 180 cells; external: 156/240 cells Internal (standard): 216 cells; external: 192/240 cells

Input

Connection type Hardwired 4w

Nominal voltage 400 Vac 3-phase with neutral

Voltage tolerance -20%, +15% (rectifier); ±10% (bypass)

Frequency and range 50/60 Hz, 40 to 70 Hz

Power factor 0.99

Current distortion (THDi) <3%

Output

Connection type Hardwired 4w

Nominal voltage 380/400/415 Vac 3-phase with neutral

Frequency 50/60 Hz

Power factor 1

Overload capacity 110% for 60 min, 125% for 10 min, 150% for 1 min

Efficiency (AC/AC)* Up to 98%

Connectivity and function extensions

Front panel Touch screen display

Remote communication Included: serial RS232; backfeed protection monitoring contact, remote EPO contact. Optional: 2 slots for SNMP adapter, ModBus-RTU, contact relay card

Optional function extensions

Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit; other options on request

System

Protection degree IP 20

Colour RAL 9005

Installation layout 30 cm wall-gap

Accessibility Positioning casters; bottom cable entry

17

Environmental

UPS operating temperature range 0°C to +40°C

UPS storage temperature range -10°C to +70°C

Altitude (AMSL) < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m

Audible noise at 1 m (dBA) <52

Standards and certifications

Quality assurance, ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 environment, health and safety

Safety IEC/EN 62040-1

EMC IEC/EN 62040-2

Environmental aspects IEC/EN 62040-4

Test and performance IEC/EN 62040-3

Protection degree IEC 60529

Marking CE

*according to IEC/EN 62040-3

Other features

Page 8: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

18

INGENIO COMPACT series options Description When do I use it

LOAD

Internal battery temperature probe When the unit has internal batteries, for charging voltage compensation with temperature

Input isolation transformerin extended cabinet

To galvanically isolate UPS from load or to change system’s earth arrangement

Backfeed protection contactor To be fully protected against backfeed energy upon static bypass failure

Input terminal block for remote EPO When the Emergency Power Off (EPO) has to be commanded by a remote control button

Dry contact relay card

RS485 ModBus-RTU port

Web/SNMP Adapter

To send UPS status to PLC’s, SCADA’s or AS400’s by voltage free SPDT contacts

To send UPS status to BMS’s by RS485 connection and ModBus-RTU protocol.

For telemonitoring and teleservice

To send UPS status to BMS’s by Ethernet connection and SNMP or ModBus over IP protocol. To monitor UPS status by any

internet browser from workstations. To receive SMS or e-mail alerts from the UPS on any portable device

Included

Parallel kit When the unit is to be paralleled for load sharing

Page 9: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

19

INGENIO PLUS

Highlights• On-line double conversion• Transformer free• Full IGBT technology• Paralleling up to 960 kVA

Applications• Small and medium data centers• Networks and servers• Industrial control and process automation• Medical equipment• Building automation

Uninterruptible Power Supply3ph from 30 to 160 kVA

Page 10: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

20

Main options● Isolation transformer.

● Transformers/autotransformers for isolation or voltage adjustment.

● Battery voltage temperature compensation.

● External maintenance bypass wall-mounted box.

● Battery fuse switch wall-mounted box.

● Battery cabinets for long autonomy times.

● Parallel kit for load sharing.

● Load-sync for single UPS units, load-sync box for two sets of paralleled UPS.

● Common battery.

● Tripping coil for bypass disconnector.

● Separate rectifier and bypass input for INGENIO PLUS 30-40 kVA.

● Ultra High Efficiency Mode (UHE).

● Cold start.

● Touch screen display (only on 60-160 kVA range).

Features and benefits● Green Conversion technology, high efficiency even at light load and the lowest TCO in its category.

● Full rated output power, ensuring optimal UPS sizing and utilization.

● Transformer free design for compact, light and sustainable systems.

● Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi<3% for maximum upstream sources compatibility.

● Internal battery configurations up to 80 kVA for less floor space and maximum flexibility.

● Dynamic Charging Mode (DCM) for maximum versatility in long autonomy and low charging time applications.

● Green Conversion Battery Care (GCBC), for extended battery service life.

● Comprehensive set of communication options for total remote monitoring of equipment operation.

● Fully compliant with all international product standards for maximum quality guarantee.

INGENIO PLUSUninterruptible Power Supply 3ph from 30 to 160 kVA

Autonomy time in minutes with different types of internal batteries

80 kVA

60 kVA

40 kVA

30 kVA

0 5 1510 20

Page 11: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

Environmental

UPS operating temperature range 0°C to +40°C

UPS storage temperature range -10°C to +70°C

Altitude (AMSL) < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m

Audible noise at 1 m (dBA) <60

Standards and certifications

Quality assurance, ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 environment, health and safety

Safety IEC/EN 62040-1

EMC IEC/EN 62040-2

Environmental aspects IEC/EN 62040-4

Test and performance IEC/EN 62040-3

Protection degree IEC 60529

Marking CE

21

INGENIO PLUS technical data Rating (kVA) 30 40 60 80 100 125 160

Nominal power (kW) 30 40 60 80 100 125 160

UPS dimensions WxDxH (mm) 460x650x1230 560x940x1800

UPS weight (kg) 120 140 250 300 320 360 380

UPS weight with int. battery (kg) 365 385 800 850 - - -

Battery configuration Internal or external, 360 to 372 cells, External 360 to 372 cells, VRLA (other options)

VRLA (other options)

Max autonomy with int. battery 11 7

16 11 - - -

70% load (min)

Input

Connection type Hardwired 4w Hardwired 4w (rectifier), 4w (bypass)

Nominal voltage

400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass)

Voltage tolerance -20%, +15% (rectifier); ±10% (bypass)

Frequency and range 50/60 Hz, 45 to 65 Hz

Power factor >0.99

Current distortion (THDi) <3%

Output

Connection type Hardwired 4w

Nominal voltage 380/400/415 Vac 3-phase with neutral

Frequency 50/60 Hz

Voltage regulation Static: ±1%; dynamic IEC/EN 62040-3 Class 1

Power factor Up to 1, without power derating

Overload capacity*

Inverter: 125% for 10 min, 150% for 30 s, >150% for 0.1 s; bypass: 150% continuous, 1000% for 1 cycle

Efficiency (AC/AC)** Up to 99%

Classification as per VFI-SS-111

IEC/EN 62040-3

Connectivity and function extensions

Front panel Graphic display, mimic LED panel and keyboard, local EPO

Remote communication

Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software

Optional function extension

Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request

System

Protection degree IP 20

Colour RAL 9005

Installation layout 10 cm wall-gap, Wall and side by side installation allowed, side by side installation allowed 80 cm clearance on one side only with internal battery

Accessibility Front and top access, Front access, side access (only with internal battery), bottom cable entry bottom cable entry

*conditions apply **according to IEC/EN 62040-3Other features

Page 12: B8031FXS - B8033FXS...Output B8031FXS (10-15-20 kVA) B8033FXS (10-15-20 kVA) Connection type Hardwired 2w Hardwired 4w Nominal voltage 220/230/240 Vac 1-phase 380/400/415 Vac 3-phase

22

LOAD

INGENIO PLUS series options

Parallel kit When the unit is to be paralleled for load sharing

Description When do I use it

Load-sync for single units To synchronize single units’ output for no-break load transfers by downstream static transfer switches

Load-sync box for two sets of paralleled UPSTo synchronize the output of two paralleled UPS systems

for no-break load transfers by downstream static transfer switches

Tripping coil for bypass disconnector To be fully protected against backfeed energy upon static bypass failure. Detection circuit is included

Input transformerto be installed internally or in extended cabinet

To galvanically isolate UPS from load or to change system’s earth arrangement

Battery fuse switch in wall-mounted box To disconnect and protect an external battery pack

LOAD A LOAD B

LOAD SYNCBOX

LOAD A LOAD B

Internal battery temperature probe When the unit has internal batteries, for charging voltage compensation with temperature

External battery temperature probe When the unit has external batteries, for charging voltage compensation with temperature (10 m cable length)

Dry contact relay card

Remote monitoring panel

RS485 ModBus-RTU port

Web/SNMP Adapter

To send UPS status to PLC’s, SCADA’s or AS400’s by voltage free SPDT contacts

To monitor UPS status by a LED panel from a remote control room (relay card required)

To send UPS status to BMS’s by RS485 connection and ModBus-RTU protocol.

For telemonitoring and teleservice

To send UPS status to BMS’s by Ethernet connection and SNMP or ModBus over IP protocol. To monitor UPS status by any

internet browser from workstations. To receive SMS or e-mail alerts from the UPS on any portable device

Input terminal block for remote EPO When the Emergency Power Off (EPO) has to be commanded by a remote control button

Input terminal block for external manual bypass switch auxiliary contact

Input terminal block for diesel mode contact

Input terminal block for external battery switch auxiliary contact

When there is an external maintenance bypass switch, for state monitoring

When battery recharge has to be inhibited over genset operation

When there is an external battery switch, for state monitoring