31
AFCI Reaction to Utility Events

AFCI Reaction to Utility Events

  • Upload
    eden

  • View
    31

  • Download
    0

Embed Size (px)

DESCRIPTION

AFCI Reaction to Utility Events. CenterPoint Energy 35 KV Distribution Capacitor Bank – Switched through an automated system. New breaker box built to 2008 NEC requirements with AFCI breakers. Failing vacuum switches on CNP capacitor banks were causing customer AFCI breakers to trip. - PowerPoint PPT Presentation

Citation preview

Page 1: AFCI Reaction to Utility Events

AFCI Reaction to Utility Events

Page 2: AFCI Reaction to Utility Events

CenterPoint Energy 35 KV Distribution Capacitor Bank – Switched through an automated system

Page 3: AFCI Reaction to Utility Events

New breaker box built to 2008 NEC requirements with AFCI breakers

Page 4: AFCI Reaction to Utility Events

Failing vacuum switches on CNP capacitor banks were causing customer AFCI breakers to trip

Page 5: AFCI Reaction to Utility Events

There are 40,000 fires a year caused by problems with house wiring

Page 6: AFCI Reaction to Utility Events

Changes in the 2005 and 2008 National Electric Code call for installation of AFCI breakers on almost all branch circuits

Page 7: AFCI Reaction to Utility Events

Arcing faults can generate temperatures in excess of 9,000 degrees

Page 8: AFCI Reaction to Utility Events

Arcing Fault Circuit Interrupters can sense a downstream arc and trip before starting a fire.

Page 9: AFCI Reaction to Utility Events

AFCIs serve a dual purpose by tripping from an arc or from overload.

Page 10: AFCI Reaction to Utility Events

Arcing faults can occur in series or parallel to the load. Parallel faults involve the greatest amount of energy and are more likely to create a fire hazard.

Page 11: AFCI Reaction to Utility Events

Some loads have arcing inherent in their normal, safe operation.

Page 12: AFCI Reaction to Utility Events

The AFCI is designed to prevent electrical fires that may result from normal wear and tear or aged connections.

Page 13: AFCI Reaction to Utility Events

GFCI prevent electrocution, AFCI prevent fires.

Page 14: AFCI Reaction to Utility Events

Some loads produce arcing during normal use, the AFCI must distinguish between the load arc and an arcing fault.

Page 15: AFCI Reaction to Utility Events

AFCI and GFCI breakers are similar in appearance but much different in design and function

Page 16: AFCI Reaction to Utility Events

Early designs of AFCI breakers would trip when a TVSS would discharge a transient to ground.

Page 17: AFCI Reaction to Utility Events

Centerpoint Energy serves 5000 square miles in and around the greater Houston metropolitan area.

Page 18: AFCI Reaction to Utility Events

Residential load growth within the service area tends to be grouped by time and location.

Page 19: AFCI Reaction to Utility Events

Builders will consolidate construction activity to achieve efficiencies in all steps of the construction.

Page 20: AFCI Reaction to Utility Events

The end result is a grouping of new homes, all built with similar equipment and components manufactured at or near the same time.

Page 21: AFCI Reaction to Utility Events

The end result is a grouping of loads, with similar characteristics. And, if located near distribution equipment there is potential for interaction.

Page 22: AFCI Reaction to Utility Events

Centerpoint Energy electrical design criteria requires multiple capacitor bank installations on every distribution circuit. Which results in many capacitor bank located in and around residential developments.

Page 23: AFCI Reaction to Utility Events

Newer homes should be wired to the 2008 NEC, which requires the installation of AFCI breakers.

Page 24: AFCI Reaction to Utility Events

The interaction of the AFCI with events on the distribution system depends on the design of the AFCI. Its response times and sensitivity.

Page 25: AFCI Reaction to Utility Events

The load served through the AFCI is just as important as the characteristics and design of the AFCI in determining response.

Page 26: AFCI Reaction to Utility Events

Eventually, over time all distribution equipment will be damaged or fail.

Page 27: AFCI Reaction to Utility Events

System maintenance and repair is essential to keep voltages within design criteria specifications.

Page 28: AFCI Reaction to Utility Events

Communication of events, trends and results is essential to insure that all field, dispatch and engineering support are aware of a situation.

Page 29: AFCI Reaction to Utility Events

One failed component does not make a crisis, but is the first step in identifying a root cause which could eventually impact thousands of customers.

Page 30: AFCI Reaction to Utility Events

Advice for the future – learn to listen to your system.

Page 31: AFCI Reaction to Utility Events