Transcript
Page 1: DL05 - Cable Assembly Instruction

1020-0032, Rev 04

Use the wiring diagram and illustration to assemble a communication cable for use with a KoyoDL05 PLC, DL105 PLC, DL205 Series PLC, DL305 PLC (D3-350 CPU, Port 1), or DL405PLC (D4-450 CPU, Port 2).

C A B L E A S S E M B L Y I N S T R U C T I O N

Controller Model: Koyo DL05, DL105, DL205 Series, DL305

(D3-350 CPU), and DL405 (D4-450 CPU)

Maple OIT Model: MAP320D, MAP340D, OIT3160A, OIT3200B,

OIT3250B, OIT4160A, OIT4400B, OIT4450B,

OIT5400B

Communication Type: RS-232 with RJ-12 at PLC

5

RXD

TXD

Return

2

3

9P

OIT

PLC

Signal Ground1

Data Out

RJ-12

4

Data In3

Solder shield wire to the DE9P connector metal shell. Installheatshrink tubing over the shield wire to avoid shorting.

Twist together 18 AWG green wire and shield wire. Solderwires and insulate with heatshrink to avoid shorting.

NOTES:

1

2

Shield

To Chassis GroundGreen

16

Top1

6

RJ-12 Plug,6 Pos, 6 Contact

DE9P Connector& DE9 Backshell

18 AWG Green wire To Chassis Ground

OIT END

4-40 x 1/2 RetainerScrew, 2 places

PLC END

#6 Crimp Lug

2

1

4 Pair, 24 AWG ShieldedCable, Category 5

Recommended