1020-0032, Rev 04
Use the wiring diagram and illustration to assemble a communication cable for use with a KoyoDL05 PLC, DL105 PLC, DL205 Series PLC, DL305 PLC (D3-350 CPU, Port 1), or DL405PLC (D4-450 CPU, Port 2).
C A B L E A S S E M B L Y I N S T R U C T I O N
Controller Model: Koyo DL05, DL105, DL205 Series, DL305
(D3-350 CPU), and DL405 (D4-450 CPU)
Maple OIT Model: MAP320D, MAP340D, OIT3160A, OIT3200B,
OIT3250B, OIT4160A, OIT4400B, OIT4450B,
OIT5400B
Communication Type: RS-232 with RJ-12 at PLC
5
RXD
TXD
Return
2
3
9P
OIT
PLC
Signal Ground1
Data Out
RJ-12
4
Data In3
Solder shield wire to the DE9P connector metal shell. Installheatshrink tubing over the shield wire to avoid shorting.
Twist together 18 AWG green wire and shield wire. Solderwires and insulate with heatshrink to avoid shorting.
NOTES:
1
2
Shield
To Chassis GroundGreen
16
Top1
6
RJ-12 Plug,6 Pos, 6 Contact
DE9P Connector& DE9 Backshell
18 AWG Green wire To Chassis Ground
OIT END
4-40 x 1/2 RetainerScrew, 2 places
PLC END
#6 Crimp Lug
2
1
4 Pair, 24 AWG ShieldedCable, Category 5