http://energy.tycoelectronics.com Energy Division Transmission Surge Arresters

Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Embed Size (px)

Citation preview

Page 1: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

http://energy.tycoelectronics.comEnergy Division

Transmission Surge Arresters

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 1

Page 2: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

2

4P11SR396 Series Parallel Surge Arrester - USA

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 2

Page 3: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

3

Tyco Electronics Energy Divisioncovers a wide range of porcelain andpolymeric transmission surgearresters. The Bowthorpe EMP rangeof arresters has demonstratedreliable performance inenvironments all over the world forover 60 years.

Bowthorpe EMP, unlike othermanufacturers, recognise that somePower Utilities require the need tomaintain the conventional ZnOporcelain surge arrester.

A program of continuous designupdate and development on theporcelain arrester has provided arange of surge arresters to meet thedemands of most system voltages.

Design Evaluated and Type Tested atthe HV Laboratory in Brighton.

Bowthorpe EMP were the firstmanufacturer to develop thepolymeric housed arrester forcommercial operation (1983).

Range of HV surge arresters inservice under the severest climaticconditions up to 550kV system.

Surge Arresters

Porcelain HousedSurge Arrester

MBA Class 2, 10kA (11-150kV)MAA Class 2, 10kA (11-220kV)MCA, Class 3, 10kA (11-400kV)MDA, Class 4, 20kA (11-400kV)

Polymeric HousedSurge Arrester

PSRB,Class 2,10kA (66 -220kV)

Modular Single ColumnPolymeric Surge Arrester

H, 2H & 3H, Class 2, 10kA (11-132kV)

Modular Series ParallelPolymeric Surge Arrester

2PH, Class 3, 10kA (11-150kV)3P, Class 3/4, 10/20kA (66-400kV)4P, Class 4/5, 20kA (110-500kV)5P, Class 5, 20kA (300-500kV)

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 3

Page 4: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

4

H, 2H & 3HModular Single Column Polymeric Surge Arresters

The essential feature of the international construction isthe homogeneous resin and glass fibre bond over thecomplete insulated surface of the ZnO varistor elements.The arrester module has good conductivity even whenhigh cantilever loads are applied and provides a uniformdielectric at the insulated surface of the ZnO elements.

• No air gap therefore no internal ionisation

• Light weight compared to porcelain

• Ease of installation

• Non shattering housing

• Vandal proof

Electrical Performance

Specification: IEC60099-4

Classification: 10kA

Voltage Rating: 3kV to 132kV

High Current Performance: 100kA

Line Discharge Class: 2

Energy Capability:4.5kJ/kV at Ur according to IEC60099-4(Clause 8.4.2 table 5 and 8.5.5)

HSR Rated Voltage to 48kV

2HSR Rated Voltage to 84kV

3HSR Rated Voltage to 126kV

Insulation Material: Silicone Rubber

Typical Applications

• ARC Furnace

• Transformers

• TLA Transmission Line Arresters

• Cable Terminations

• Substations

66kV Surge Arresters - Statkraft, Norway

110kV Surge Arresters - Estonia

Extended Creepage HSREP45 Surge Arrester

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 4

Page 5: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

H, 2H & 3HModular Single Column Polymeric Surge Arresters

5

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 125A 500A 5kA 10kA 20kA 10kAkV crest kV crest kV crest kV crest kV crest kV crest

HSRA(P)6L1E1M0(5) 6 4.8 6.85 12.3 13.0 15.4 16.7 18.5 18.1

HSRA(P)9L1E1M0(5) 9 7.2 10.3 19.6 20.8 24.7 26.8 29.5 29.0

HSRA(P)10.5L1E1M0(5) 10.5 8.4 12.0 22.1 23.4 27.8 30.1 33.2 32.6

HSRA(P)12L1E1M0(5) 12 9.6 13.7 24.5 26.0 30.9 33.5 36.9 36.2

HSRA(P)15L1E1M0(5) 15 12 17.1 29.4 31.2 37.0 40.2 44.3 43.5

HSRB(P)15L1E1M0(5) 15 12 17.1 29.4 31.2 37.0 40.2 44.3 43.5

HSRB(P)18L1E1M0(5) 18 14 20.5 36.8 39.1 46.3 50.2 55.4 54.3

HSRB(P)21L1E1M0(5) 21 17 24.0 41.7 44.3 52.5 56.9 62.8 61.6

HSRB(P)24L1E1M0(5) 24 19 27.4 49.0 52.1 61.7 66.9 73.8 72.5

HSRB(P)27L1E1M0(5) 27 22 30.8 53.9 57.3 67.9 73.6 81.2 79.7

HSRB(P)30L1E1M0(5) 30 24 34.2 58.8 62.5 74.1 80.3 88.6 87.0

HSRC(P)27L1E1M0(5) 27 22 30.8 53.9 57.3 67.9 73.6 81.2 79.7

HSRC(P)30L1E1M0(5) 30 24 34.2 58.8 62.5 74.1 80.3 88.6 87.0

HSRC(P)36L1E1M0(5) 36 29 41.1 71.1 75.5 89.5 97.1 107 105

HSRC(P)39L1E1M0(5) 39 31 44.5 78.5 83.3 98.7 107 118 116

HSRC(P)42L1E1M0(5) 42 34 47.9 83.4 88.5 105 114 126 123

HSRC(P)45L1E1M0(5) 45 36 51.3 88.3 93.7 111 121 133 130

2HSRB(P)30L1E1M0(5) 30 24 34.2 58.8 62.5 74.1 80.3 88.6 87.0

2HSRB(P)45L1E1M0(5) 45 36 51.3 88.3 93.7 111 121 133 130

2HSRB(P)48L1E1M0(5) 48 38.4 54.8 95.6 102 120 131 144 141

2HSRB(P)60L1E1M0(5) 60 48 68.4 118 125 148 161 177 174

2HSRC(P)48L1E1M0(5) 48 38.4 54.7 95.6 102 120 131 144 141

2HSRC(P)60L1E1M0(5) 60 48 68.4 118 125 148 161 177 174

2HSRC(P)72L1E1M0(5) 72 57.6 82.0 142 151 179 194 214 210

2HSRC(P)75L1E1M0(5) 75 60 85.5 147 156 185 201 222 217

2HSRC(P)84L1E1M0(5) 84 67.2 95.8 167 177 210 228 251 246

3HSRC(P)96L1E1M(05) 96 76.8 109 189 201 238 258 284 279

3HSRC(P)108L1E1M0(5) 108 86.4 123 213 227 269 291 321 315

3HSRC(P)120L1E1M0(5) 120 96 137 235 250 296 321 354 348

3HSRC(P)126L1E1M0(5) 126 101 144 248 263 312 338 373 366

Protective Characteristics

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 5

Page 6: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

H, 2H & 3HModular Single Column Polymeric Surge Arresters

6

Total Overall Recommended Recommended Maximum Drawing Data Sheetcreepage height minimum minimum Applied Reference Reference

mm mm phase distance Cantilever(nom) (max) centres line to load

mm Earth N M0 M5mm

600 228 140 33 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA6/HSRAP6

600 228 145 49 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA9/HSRAP9

600 228 160 57 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA10.5/HSRAP10.5

600 228 170 65 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA12/HSRAP12

600 228 200 82 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA15/HSRAP15

930 321 200 82 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB15/HSRBP15

930 321 230 98 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB18/HSRBP18

930 321 255 114 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB21/HSRBP21

930 321 285 130 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB24/HSRBP24

930 321 315 147 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB27/HSRBP27

930 321 340 163 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB30/HSRBP30

1325 476 315 147 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC27/HSRCP27

1325 476 340 163 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC30/HSRCP30

1325 476 400 196 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC36/HSRCP36

1325 476 425 212 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC39/HSRCP39

1325 476 455 228 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC42/HRSCP42

1325 476 480 244 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC45/HSRCP45

1860 642 340 163 1400 BOW-2B-002 BOW-4-004 BOW-EPP-2HSRB-30/2HSRBP-30

1860 642 477 243 1400 BOW-2B-002 BOW-4-004 BOW-EPP-2HSRB-45/2HSRBP-45

1860 642 510 260 1400 BOW-2B-002 BOW-4-004 BOW-EPP-2HSRB-48/2HSRBP-48

1860 642 625 326 1400 BOW-2B-002 BOW-4-004 BOW-EPP-2HSRB-60/2HSRBP-60

2650 952 510 260 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC-48/2HSRCP-48

2650 952 625 326 900 BOW-2B-003 BOW-4-005 BOW-EPP-3HSRC-60/2HSRCP-60

2650 952 735 391 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC-72/2HSRCP-72

2650 952 765 408 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC-75/2HSRCP-75

2650 952 840 456 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC-84/2HSRCP-84

3975 1428 1213 518 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC-96/2HSRCP-96

3975 1428 1326 583 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC-108/2HSRCP-108

3975 1428 1436 648 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC-120/2HSRCP-120

3975 1428 1495 680 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC-126/2HSRCP-126

Mechanical and Reference Information

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 6

Page 7: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

H, 2H & 3HModular Single Column Polymeric Surge Arresters

7

Accessories

Example: 3 HSRC 96 L1 E1 M0

Parallel Paths

Arrester Housing

Voltage

Mounting

Earth Terminal

Line Terminal

E2Earth Clamp to suit cablesup to Ø16 mm

E12 x M10 x 20mmHexagon headedset screws andspring washers

E5Earth Clamp to suit cablesup to Ø35 mm

L5Line Clamp to suit cablesup to Ø35 mm

L2Line Clamp to suit cablesup to Ø16 mm

L6Aluminium StemØ30 x 80mm high

Corona Ring(Above 96kV)

Stainless Steel Terminal Assembly

Die Cast Aluminium Sealing End

Aluminium End Block

ZnO Varistor Element

Glass Fibre Wrap

Silicone Rubber Housing

M54 Hole Pedestal Base127-140 PCD

M3Set of 4 Polyfibre BaseInsulators used with M5

M10Single Polyfibre BaseInsulator

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 7

Page 8: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Series ParallelModular Polymeric Surge Arresters

3P10SR360 - Damhead Creek 400kV - UK

2P4SR168 - 132kV Surge Arresters -Statkraft, Norway

3P6SR252 - Statnet 300kV

The series parallel construction comprises individualsurge arrester modules rated between 30 and 45kVinterconnected by means of corona free aluminium alloycross arm.

Each surge arrester module is completely impervious tothe ingress of moisture and utilises the high mechanicalstrength properties of the ZnO varistors bonded bycured resin impregnated glass fibre.

The seismic performance of the 500kV arrester has beenproven in two leading test facilities. Bonneville PowerUSA performed at Portland State University and NELEast Kilbride UK.

• No air gap therefore no internal ionisation• Light weight compared to porcelain• Ease of installation• Non shattering housing• Vandal proof• Tolerance to seismic disturbances• Patented glass fibre core design gives high mechanical

strength and void free construction• Optimised voltage stress grading eliminates need to

oversize stress grading ring, therefore the compactseries parallel can be installed in tight spaces withoutinfringing electrical or surge safety clearances.

• The diameter of the series parallel design has beencalculated to reduce the radial field stress to a mini-mum, even under adverse environmental conditions.

Electrical Performance

Specification: IEC60099-4

Classification: 2PH Class 3 10kA

3P Class 3 & 4 10/20kA

4P Class 4 & 5 20kA

5P Class 5 20kA

High Current Performance: 100kA

Energy Capability:according to IEC60099-4(Clause 8.4.2 table 5 and 8.5.5)

2PH Class 3 7.0 kJ /kV at Ur

3P Class 3 9.4kJ/kV at Ur

3P Class 4 10.8kJ/kV at Ur

4P Class 4 12.5kJ/kV at Ur

5P Class 5 16.4kJ/kV at Ur

Voltage Rating:

2PH Rated Voltage from 15kV to 168 kV

3P Rated Voltage from 60kV to 360 kV

4P Rated Voltage from 96kV to 468 kV

5P Rated Voltage from 288kV to 525 kV

Insulation: Silicone Rubber Housing

Typical Applications• Substations• Capacitor Banks• DC Inter-Connections• Power Transformers• Cable Terminations

8

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 8

Page 9: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Series ParallelModular Polymeric Surge Arresters

9

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 250A 1000A 5kA 10kA 20kA 10kAkV crest kV crest kV crest kV crest kV crest kV crest

2PHSRC30L2E2M4 30 24.0 34.5 59.5 63.3 70.8 75.3 81.4 80.1

2PHSRC36L2E2M4 36 28.8 41.4 71.9 76.4 85.5 90.9 98.3 96.8

2PHSRC39L2E2M4 39 31.2 44.9 79.4 84.3 94.4 100 109 107

2PHSRC42L2E2M4 42 33.6 48.3 84.3 89.6 100 107 115 114

2P2HSRC48L2E2M4 48 38.4 55.2 98.8 105 118 125 136 134

2P2HSRC60L2E2M4 60 48.0 69.0 119 127 142 151 163 160

2P2HSRC75L2E2M4 75 60.0 86.3 149 158 177 188 203 200

2P2HSRC84L2E2M4 84 67.2 96.7 169 179 201 213 231 227

2P3HSRC96L2E2M4 96 76.8 110 193 206 230 245 265 260

2P3HSRC108L2E2M4 108 86.4 124 216 229 257 273 295 291

2P3HSRC120L2E2M4 120 96.0 138 238 253 283 301 326 321

2P4HSRC132L2E2M4 132 106 152 268 285 319 339 366 361

2P4HSRC138L2E2M4 138 110 159 278 295 330 351 380 374

2P4HSRC144L2E2M4 144 115 166 288 306 342 364 393 387

2P4HSRC150L2E2M4 150 120 177 298 316 354 376 407 401

2P4HSRC168L2E2M4 168 134 193 337 358 401 427 461 454

3P3SR96L2E2M7 96 76.8 113 191 201 223 233 253 251

3P3SR108L2E2M7 108 86.4 126 212 224 248 260 282 280

3P3SR120L2E2M7 120 96.0 139 234 248 274 287 311 309

3P4SR132L2E2M7 132 106 157 264 279 308 323 350 347

3P4SR144L2E2M7 144 115 168 283 299 331 347 376 373

3P4SR150L2E2M7 150 120 174 293 309 343 359 389 286

3P4SR168L2E2M7 168 134 197 332 351 388 407 440 437

3P5SR180L2E2M7 180 144 210 354 374 414 433 470 466

3P5SR192L2E2M7 192 154 225 379 400 443 463 502 498

3P5SR198L2E2M7 198 158 232 391 413 457 478 518 515

3P6SR120L2E2M7 120 96.0 139 234 248 274 287 311 309

3P6SR214L2E2M7 214 171 252 425 449 497 520 564 560

3P6SR228L2E2M7 228 182 270 454 480 531 556 602 598

3P6SR240L2E2M7 240 192 278 469 495 548 574 622 617

3P6SR252L2E2M7 252 202 296 498 526 583 610 661 656

3P7SR240L2E2M7 240 192 284 479 506 560 586 635 630

3P7SR264L2E2M7 264 211 315 530 560 620 649 703 698

3P7SR288L2E2M7 288 230 335 564 596 660 691 748 743

3P8SR288L2E2M7 288 230 336 567 598 663 694 751 746

3P8SR300L2E2M7 300 240 348 586 619 685 718 777 772

3P8SR312L2E2M7 312 250 371 625 660 731 765 829 823

3P8SR336L2E2M7 336 269 394 664 702 777 813 881 875

3P9SR336L2E2M7 336 269 392 659 696 771 807 874 868

3P9SR360L2E2M7 360 288 418 703 743 822 861 933 926

3P10SR360L2E2M7 360 288 421 708 748 828 867 939 933

Protective Characteristics 2PH & 3P Class 3

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 9

Page 10: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Series ParallelModular Polymeric Surge Arresters

10

Total Overall Recommended Recommended Maximum Drawing Data Sheetcreepage height minimum minimum Applied Reference Reference

mm mm phase distance Cantilever(nom) (max) centres line to Earth load

mm mm N

1325 488 546 163 4000 BOW-6-019 BOW-EPP-2PHSRC30

1325 488 603 196 4000 BOW-6-019 BOW-EPP-2PHSRC36

1325 488 631 212 4000 BOW-6-019 BOW-EPP-2PHSRC39

1325 488 659 228 4000 BOW-6-019 BOW-EPP-2PHSRC42

1325 970 716 261 2000 BOW-6-019 BOW-EPP-2P2HSRC48

2650 970 828 326 2000 BOW-6-019 BOW-EPP-2P2HSRC60

2650 970 969 408 2000 BOW-6-019 BOW-EPP-2P2HSRC75

2650 970 1054 456 2000 BOW-6-019 BOW-EPP-2P2HSRC84

3975 1454 1347 522 1000 BOW-6-019 BOW-EPP-2P3HSRC96

3975 1454 1460 587 1000 BOW-6-019 BOW-EPP-2P3HSRC108

3975 1454 1572 652 1000 BOW-6-019 BOW-EPP-2P3HSRC120

5300 1936 1685 717 500 BOW-6-019 BOW-EPP-2P4HSRC132

5300 1936 1741 750 500 BOW-6-019 BOW-EPP-2P4HSRC138

5300 1936 1798 782 500 BOW-6-019 BOW-EPP-2P4HSRC144

5300 1936 1854 815 500 BOW-6-019 BOW-EPP-2P4HSRC150

5300 1936 2023 913 500 BOW-6-019 BOW-EPP-2P4HSRC168

3975 1500 1612 522 2000 BOW-7-001 BOW-EPP-3P3S-96

3975 1500 1725 587 2000 BOW-7-001 BOW-EPP-3P3S-108

3975 1500 1838 652 2000 BOW-7-001 BOW-EPP-3P3S-120

5300 2000 1950 717 1875 BOW-7-001 BOW-EPP-3P4S-132

5300 2000 2064 782 1875 BOW-7-001 BOW-EPP-3P4S-144

5300 2000 2120 815 1875 BOW-7-001 BOW-EPP-3P4S-150

5300 2000 2290 913 1875 BOW-7-001 BOW-EPP-3P4S-168

6625 2500 2402 978 1750 BOW-7-001 BOW-EPP-3P5S-180

6625 2500 2515 1043 1750 BOW-7-001 BOW-EPP-3P5S-192

6625 2500 2571 1076 1750 BOW-7-001 BOW-EPP-3P5S-198

7950 3000 1838 650 1625 BOW-7-001 BOW-EPP-3P6S-120

7950 3000 2712 1163 1625 BOW-7-001 BOW-EPP-3P6S-214

7950 3000 2853 1239 1625 BOW-7-001 BOW-EPP-3P6S-228

7950 3000 2966 1304 1625 BOW-7-001 BOW-EPP-3P6S-240

7950 3000 3079 1369 1625 BOW-7-001 BOW-EPP-3P6S-252

9275 3500 2966 1304 1500 BOW-7-001 BOW-EPP-3P7S-240

9275 3500 3192 1435 1500 BOW-7-001 BOW-EPP-3P7S-264

9275 3500 3417 1565 1500 BOW-7-001 BOW-EPP-3P7S-288

10600 4000 3417 1565 1375 BOW-7-001 BOW-EPP-3P8S-288

10600 4000 3530 1630 1375 BOW-7-001 BOW-EPP-3P8S-300

10600 4000 3643 1695 1375 BOW-7-001 BOW-EPP-3P8S-312

10600 4000 3868 1826 1375 BOW-7-001 BOW-EPP-3P8S-336

11925 4500 3868 1826 1250 BOW-7-001 BOW-EPP-3P9S-336

11925 4500 4094 1956 1250 BOW-7-001 BOW-EPP-3P9S-360

13250 5000 4094 1956 1125 BOW-7-001 BOW-EPP-3P10S-360

Mechanical and Reference Information 2PH & 3P Class 3

Transmarr4/05-2.qxd 12.04.2005 16:46 Uhr Seite 10

Page 11: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Series ParallelModular Polymeric Surge Arresters

11

2PH Series Parallel

SiliconeRubberHousedArresterModule

Aluminiumconnectingstrap

E2Earth Clamp to suit cablesup to Ø16 mm

E12 x M10 x 20mmHexagon headedset screws andspring washers

E5Earth Clamp to suit cablesup to Ø35 mm

M4Set of 2 Polyfibre Base Insulators

L5Line Clamp to suit cablesup to Ø35 mm

L3Line Clamp to suit cablesup to Ø16 mm

L2Aluminium StemØ30 x 80mm high

SiliconeRubberHousedArresterModule

Corona Ring

SiliconeAluminiumintersectioncross-arm

CoronaShield

M73 Polyfibre Base Insulatorsconnected to galvanised steel plate

E2Earth Clamp to suit cablesup to Ø16 mm

E12 x M10 x 20mmHexagon headedset screws andspring washers

E5Earth Clamp to suit cablesup to Ø35 mm

3P Series Parallel

L5Line Clamp to suit cablesup to Ø35 mm

L3Line Clamp to suit cablesup to Ø16 mm

L2Aluminium StemØ30 x 80mm high

Example: 3P 8SR 336 L2 E2 M7

Parallel Paths

Series Stages

Voltage

Mounting

Earth Terminal

Line Terminal

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 11

Page 12: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

12

Series ParallelModular Polymeric Surge Arresters

Installations

4P8S260 - Skelton Grange - 275kV

3P9SR360 - Statnett - 400kV 4P13S444 - Indonesia - 500kV

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 12

Page 13: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

13

Series ParallelModular Polymeric Surge Arresters

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 500A 2000A 10kA 20kA 40kA 20kAkV crest kV crest kV crest kV crest kV crest kV crest

3P3SR96L2E2M7-4 96 76.8 115 195 208 233 253 276 271

3P3SR108L2E2M7-4 108 86.4 128 217 233 260 282 308 302

3P3SR120L2E2M7-4 120 96.0 141 240 257 287 311 340 333

3P4SR120L2E2M7-4 120 96.0 141 240 257 287 311 340 333

3P4SR132L2E2M7-4 132 106 159 270 289 323 350 382 375

3P4SR144L2E2M7-4 144 115 170 290 310 347 376 411 403

3P4SR150L2E2M7-4 150 120 176 300 321 359 389 425 417

3P4SR168L2E2M7-4 168 134 200 340 363 407 440 481 472

3P5SR180L2E2M7-4 180 144 213 362 388 433 470 513 503

3P5SR192L2E2M7-4 192 154 228 387 414 463 502 549 538

3P5SR198L2E2M7-4 198 158 235 400 428 478 518 566 555

3P5SR214L2E2M7-4 214 171 257 437 468 523 567 620 607

3P6SR120L2E2M7-4 120 96.0 141 240 257 287 311 340 333

3P6SR214L2E2M7-4 214 171 256 435 465 520 564 616 604

3P6SR228L2E2M7-4 228 182 273 465 497 556 602 658 646

3P6SR240L2E2M7-4 240 192 282 479 513 574 622 680 666

3P6SR252L2E2M7-4 252 202 300 509 545 610 661 722 708

3P7SR240L2E2M7-4 240 192 288 489 524 586 635 694 680

3P7SR264L2E2M7-4 264 211 319 542 580 649 703 768 753

3P7SR288L2E2M7-4 288 230 339 577 617 691 748 818 802

3P8SR300L2E2M7-4 300 240 353 599 641 718 777 850 833

3P8SR312L2E2M7-4 312 250 376 639 684 765 829 906 889

3P8SR336L2E2M7-4 336 269 388 659 706 789 855 935 916

3P9SR336L2E2M7-4 336 269 397 674 722 807 874 956 937

3P9SR360L2E2M7-4 360 288 423 719 770 861 933 1020 1000

3P10SR360L2E2M7-4 360 288 426 724 775 867 939 1027 1007

4P3SR120L2E2M7 120 96.0 139 238 253 284 304 330 324

4P4SR132L2E2M7 132 105 157 268 284 319 342 371 364

4P8SR260L2E2M7 260 208 302 515 548 615 658 715 702

4P8SR330L2E2M7 330 264 383 654 695 780 835 908 891

4P9SR360L2E2M7 360 288 418 714 759 851 911 990 972

4P10SR336L2E2M7 336 269 392 669 711 798 854 928 911

4P10SR360L2E2M7 360 288 421 719 764 857 917 997 979

4P10SR396L2E2M7 396 317 464 793 843 946 1012 1100 1080

4P11SR396L2E2M7 396 317 463 790 840 943 1009 1097 1076

4P11SR420L2E2M7 420 336 494 845 898 1008 1079 1172 1151

4P11SR444L2E2M7 444 355 526 900 956 1073 1148 1248 1225

4P12SR420L2E2M7 420 336 487 833 885 993 1063 1155 1134

4P12SR468L2E2M7 468 374 557 952 1012 1135 1215 1320 1296

5P11SR444L2E2M7 444 355 526 900 956 1073 1148 1248 1225

5P12SR420L2E2M7 420 336 494 833 885 993 1063 1155 1134

5P12SR468L2E2M7 468 374 557 952 1012 1135 1215 1320 1296

Protective Characteristics 3P & 4P Class 4

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 13

Page 14: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Series ParallelModular Polymeric Surge Arresters

Total Overall Recommended Recommended Maximum Drawing Data Sheetcreepage height minimum minimum Applied Reference Reference

mm mm phase distance Cantilever(nom) (max) centres line to Earth load

mm mm N

3975 1500 1612 522 2000 BOW-7-001 BOW-EPP-3P3S-96cl.4

3975 1500 1725 587 2000 BOW-7-001 BOW-EPP-3P3S-108cl.4

3975 1500 1838 652 2000 BOW-7-001 BOW-EPP-3P3S-120cl.4

5300 2000 1838 652 1875 BOW-7-001 BOW-EPP-3P4S-120cl.4

5300 2000 1950 717 1875 BOW-7-001 BOW-EPP-3P4S-132cl.4

5300 2000 2064 782 1875 BOW-7-001 BOW-EPP-3P4S-144cl.4

5300 2000 2120 815 1875 BOW-7-001 BOW-EPP-3P4S-150cl.4

5300 2000 2290 913 1875 BOW-7-001 BOW-EPP-3P4S-168cl.4

6625 2500 2402 978 1750 BOW-7-001 BOW-EPP-3P5S-180cl.4

6625 2500 2515 1043 1750 BOW-7-001 BOW-EPP-3P5S-192cl.4

6625 2500 2571 1076 1750 BOW-7-001 BOW-EPP-3P5S-198cl.4

6625 2500 2712 1163 1750 BOW-7-001 BOW-EPP-3P5S-214cl.4

7950 3000 1838 652 1625 BOW-7-001 BOW-EPP-3P6S-120cl.4

7950 3000 2712 1163 1625 BOW-7-001 BOW-EPP-3P6S-214cl.4

7950 3000 2853 1239 1625 BOW-7-001 BOW-EPP-3P6S-228cl.4

7950 3000 2966 1304 1625 BOW-7-001 BOW-EPP-3P6S-240cl.4

7950 3000 3079 1370 1625 BOW-7-001 BOW-EPP-3P6S-252cl.4

9275 3500 2966 1304 1500 BOW-7-001 BOW-EPP-3P7S-240cl.4

9275 3500 3192 1435 1500 BOW-7-001 BOW-EPP-3P7S-264cl.4

9275 3500 3417 1565 1500 BOW-7-001 BOW-EPP-3P7S-288cl.4

10600 4000 3530 1630 1375 BOW-7-001 BOW-EPP-3P8S-300cl.4

10600 4000 3643 1695 1375 BOW-7-001 BOW-EPP-3P8S-312cl.4

10600 4000 3868 1826 1375 BOW-7-001 BOW-EPP-3P8S-336cl.4

11925 4500 3868 1826 1250 BOW-7-001 BOW-EPP-3P9S-336cl.4

11925 4500 4094 1956 1250 BOW-7-001 BOW-EPP-3P9S-360cl.4

13250 5000 4094 1956 1125 BOW-7-001 BOW-EPP-3P10S-360cl.4

3975 1838 1848 652 2875 BOW-8-001 BOW-EPP-4P3S-120

5300 1951 1925 717 2750 BOW-8-001 BOW-EPP-4P4S-132

10600 3154 3156 1413 2250 BOW-8-001 BOW-EPP-4P8S-260

10600 3812 3814 1793 2250 BOW-8-001 BOW-EPP-4P8S-330

11925 4575 4095 1956 2125 BOW-8-001 BOW-EPP-4P9S-360

13250 5075 3870 1826 2000 BOW-8-001 BOW-EPP-4P10S-336

13250 5075 4096 1956 2000 BOW-8-001 BOW-EPP-4P10S-360

13250 5075 4435 2152 2000 BOW-8-001 BOW-EPP-4P10S-396

14575 5575 4435 2152 1875 BOW-8-001 BOW-EPP-4P11S-396

14575 5575 4660 2282 1875 BOW-8-001 BOW-EPP-4P11S-420

14575 5575 4885 2413 1875 BOW-8-001 BOW-EPP-4P11S-444

15900 6075 4660 2282 1750 BOW-8-001 BOW-EPP-4P12S-420

15900 6075 5110 2543 1750 BOW-8-001 BOW-EPP-4P12S-468

14575 5575 5089 2413 2200 BOW-25-001 BOW-EPP-5P11S-444

15900 6075 4863 2283 2000 BOW-25-001 BOW-EPP-5P12S-420

15900 6075 5315 2543 2000 BOW-25-001 BOW-EPP-5P12S-468

Mechanical and Reference Information 3P & 4P Class 4

14

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 14

Page 15: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

15

Series ParallelModular Polymeric Surge Arresters

Silicone RubberHoused ArresterModule

Silicone Aluminiumintersection cross-arm

Corona Ring

Corona Shield

4P Series Parallel

E2Earth Clamp to suit cablesup to Ø16 mm

E12 x M10 x 20mmHexagon headedset screws andspring washers

E5Earth Clamp to suit cablesup to Ø35 mm

L5Line Clamp to suit cablesup to Ø35 mm

L3Line Clamp to suit cablesup to Ø16 mm

L2Aluminium StemØ30 x 80mm high

Example: 4P 8SR 336 L2 E2 M7

Parallel Paths

Series Stages

Voltage

Mounting

Earth Terminal

Line Terminal

M74 Polyfibre Base Insulatorsconnected to galvanised steel plate

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 15

Page 16: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters

16

Aluminium End Flange

Pressure Relief Diaphragm

Dry Air

Porcelain Housing

ZnO Varistor Block

Locating Ring

Aluminium Spacer

Four Vent Ports

Compression Spring

UK - 132kV System - Gapped Silicon Carbide

Kuwait - 300kV system - ZnO

Porcelain surge arresters are available for applicationsup to 400kV systems.

Porcelain housing designs have been used by us forover 55 years.

From 1945 we produced porcelain surge arresters to thegapped silicone carbide pattern and since 1980 we haveproduced arresters to the gapless ZnO design.

The design consists of porcelain housing whichconforms to IEC-815 with an Aero Dynamic shed profile.

The varistors, spacers and locating rings are assembledunder compression with pressure relief diaphragms ateither end. The air void is evacuated and replaced withdry air, then sealed.

Routine tests are carried out to show that themanufacturing conforms to the current Internationalstandard.

Electrical Performance

Specification: IEC60099-4

Classification: MAA Class 2 10kA

MBA Class 2 10kA

MCA Class 3 10kA

MDA Class 4 20kA

High Current Performance:100kA

Pressure Relief: MAA 40 kA

MBA 25 kA

MCA 65 kA

MDA 65 kA

Energy Capability:according to IEC60099-4(Clause 8.4.2 table 5 and 8.5.5)

MAA Class 2 5kJ/kV at Ur

MBA Class 2 5kJ/kV at Ur

MCA Class 3 8.75kJ/kV at Ur

MDA Class 4 10kJ/kV at Ur

Voltage Rating:

MAA Rated Voltage from 3kV to 198kV

MBA Rated Voltage from 3kV to 156kV

MCA Rated Voltage from 3kV to 360kV

MDA Rated Voltage from 3kV to 360kV

Typical Applications

• Substations

• Power Transformers

• Cable Termination

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 16

Page 17: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters

17

MBA Surge Arrester Accessories MAA, MCA & MDA Surge Arrester Accessories

Grading Ring(None <120kV)(Ø610 120-150kV)(Ø710 >150kV)

Glazed Porcelain Housing

Die CastAluminiumEnd Flangewith integralvent ports

BaseDiaphragmDeflector Plate

Corona Ring(150kV and above

GalvanisedSteel Top Cap

Grading Ring(None <120kV)(Ø610 120-150kV)(Ø710 151-228kV)(Ø915 >228kV)

Glazed Porcelain Housing

Die CastAluminiumEnd Flangewith integralvent ports

BaseDiaphragmDeflector Plate

M4Base Plate with4 Polyfibre Insulators

E2Earth Clamp to suit cablesup to Ø16 mm

E12 x M10 x 20mmHexagon headedset screws andspring washers

L12 x M10 x 20mmHexagon headedset screws andspring washers

L5Line Clamp to suit cablesup to Ø35 mm

L3Line Clamp to suit cablesup to Ø16 mm

L2Aluminium StemØ30 x 80mm high

E2Earth Clamp to suit cablesup to Ø16 mm

E12 x M10 x 20mmHexagon headedset screws andspring washers

Example: MCA4.2 198 L2 E1 M2

Arrester Housing

Voltage

Mounting

Earth Terminal

Line Terminal

L12 x M10 x 20mmHexagon headedset screws andspring washers

L5Line Clamp to suit cablesup to Ø35 mm

L3Line Clamp to suit cablesup to Ø16 mm

L2Aluminium StemØ30 x 80mm high

Corona Ring(150kV and above

GalvanisedSteel Top Cap

M3Base Plate with4 Polyfibre Insulators

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 17

Page 18: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MAA Series

18

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 125A 500A 5kA 10kA 20kA 10kAkV crest kV crest kV crest kV crest kV crest kV crest

MAA03L2E1M2 3.0 2.40 3.4 7.43 7.89 9.38 10.1 11.1 10.8

MAA06L2E1M2 6.0 4.80 6.9 12.3 13.0 15.4 16.7 18.5 18.1

MAA012L2E1M2 12 9.60 13.7 24.5 26.0 30.9 33.5 36.9 36.2

MAA015L2E1M2 15 12.0 17.1 29.4 31.2 37.0 40.2 44.3 43.5

MAA018L2E1M2 18 14.4 20.5 36.8 39.1 46.3 50.2 55.4 54.3

MAA021L2E1M2 21 16.8 24.0 41.7 44.3 52.5 56.9 62.8 61.6

MAA024L2E1M2 24 19.2 27.4 49.0 52.1 61.7 66.9 73.8 72.5

MAA027L2E1M2 27 21.6 30.8 53.9 57.3 67.9 73.6 81.2 79.7

MAA030L2E1M2 30 24.0 34.2 58.8 62.5 74.1 80.3 88.6 87.0

MAA124L2E1M2 24 19.2 27.4 49.0 52.1 61.7 66.9 73.8 72.5

MAA127L2E1M2 27 21.6 30.8 53.9 57.3 67.9 73.6 81.2 79.7

MAA130L2E1M2 30 24.0 34.2 58.8 62.5 74.1 80.3 88.6 87.0

MAA136L2E1M2 36 28.8 41.1 71.1 75.5 89.5 97.1 107 105

MAA139L2E1M2 39 31.2 44.5 78.5 83.3 98.7 107 118 116

MAA142L2E1M2 42 33.6 47.9 83.4 88.5 105 114 126 123

MAA230L2E1M2 30 24.0 34.2 58.8 62.5 74.1 80.3 88.6 87.0

MAA260L2E1M2 60 48.0 68.5 118 125 148 161 177 174

MAA275L2E1M2 75 60.0 85.6 147 156 185 201 222 217

MAA396L2E1M2 96 76.8 110 189 201 238 258 284 279

MAA3108L2E1M2 108 86.4 123 213 227 269 291 321 315

MAA3120L2E1M2 120 96.0 137 235 250 296 321 354 348

MAA3126L2E1M2 126 101 144 248 263 312 338 373 366

MAA3132L2E1M2 132 106 151 260 276 327 355 391 384

MAA4150L2E1M2 150 120 171 297 316 375 403 444 433

MAA31150L2E1M2 150 120 171 297 316 375 403 444 433

MAA32150L2E1M2 150 120 171 297 316 375 403 444 433

MAA33150L2E1M2 150 120 171 297 316 375 403 444 433

MAA40150L2E1M2 150 120 171 297 316 375 403 444 433

MAA41198L2E1M2 198 158 226 394 418 497 534 589 573

MAA42198L2E1M2 198 158 226 394 418 497 534 589 573

MAA43198L2E1M2 198 158 226 394 418 497 534 589 573

MAA44198L2E1M2 198 158 226 394 418 497 534 589 573

Protective Characteristics

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 18

Page 19: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MAA Series

19

Total Overall Recommended Recommended Drawing Data Sheetcreepage height minimum minimum Reference Reference

mm mm phase distance(nom) (max) centres line to Earth

mm mm

540 440 308 16 BOW-14-001 BOW-EPP-MAA0-3

540 440 336 33 BOW-14-001 BOW-EPP-MAA0-6

540 440 393 65 BOW-14-001 BOW-EPP-MAA0-12

540 440 421 81 BOW-14-001 BOW-EPP-MAA0-15

540 440 449 98 BOW-14-001 BOW-EPP-MAA0-18

540 440 477 114 BOW-14-001 BOW-EPP-MAA0-21

540 440 506 130 BOW-14-001 BOW-EPP-MAA0-24

540 440 534 147 BOW-14-001 BOW-EPP-MAA0-27

540 440 562 163 BOW-14-001 BOW-EPP-MAA0-30

1150 610 506 130 BOW-14-002 BOW-EPP-MAA1-24

1150 610 534 147 BOW-14-002 BOW-EPP-MAA1-27

1150 610 562 163 BOW-14-002 BOW-EPP-MAA1-30

1150 610 618 195 BOW-14-002 BOW-EPP-MAA1-36

1150 610 647 212 BOW-14-002 BOW-EPP-MAA1-39

1150 610 675 228 BOW-14-002 BOW-EPP-MAA1-42

2390 980 562 163 BOW-14-003 BOW-EPP-MAA2-30

2390 980 844 326 BOW-14-003 BOW-EPP-MAA2-60

2390 980 985 407 BOW-14-003 BOW-EPP-MAA2-75

3820 1330 1182 521 BOW-14-004 BOW-EPP-MAA3-96

3820 1330 1295 586 BOW-14-004 BOW-EPP-MAA3-108

3820 1330 1295 586 BOW-14-004 BOW-EPP-MAA3-120

3820 1330 1464 684 BOW-14-004 BOW-EPP-MAA3-126

3820 1330 1521 717 BOW-14-004 BOW-EPP-MAA3-132

5000 1680 2022 814 BOW-14-005 BOW-EPP-MAA4-150

4970 1940 2022 814 BOW-14-006 BOW-EPP-MAA3.1-150

6210 2310 2022 814 BOW-14-006 BOW-EPP-MAA3.2-150

7640 2665 2352 814 BOW-14-006 BOW-EPP-MAA3.3-150

5540 2120 2352 814 BOW-14-006 BOW-EPP-MAA4.0-150

6150 2295 2570 1075 BOW-14-006 BOW-EPP-MAA4.1-198

7390 2665 2570 1075 BOW-14-006 BOW-EPP-MAA4.2-198

8820 3015 2570 1075 BOW-14-006 BOW-EPP-MAA4.3-198

10000 3365 2570 1075 BOW-14-006 BOW-EPP-MAA4.4-198

Mechanical and Reference Information

Housing Max Overall Total Nett MaximumType kV height creepage weight safe load

Rating mm mm kg cantilever(max) (nom) N.m

MAA0 30 440 540 24 6800MAA1 54 610 1150 39 6800MAA2 96 980 2390 48 6800MAA3 138 1330 3820 80 6800MAA4 156 1680 5000 100 6800

Mechanical and Dimensional Characteristics

NOTE: Add 5mm to over all height for 2 Unit ArrestersAdd 10mm to over all height for 3 Unit Arresters

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 19

Page 20: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MBA Series

20

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 125A 500A 5kA 10kA 20kA 10kAkV crest kV crest kV crest kV crest kV crest kV crest

MBA03L2E1M1 3.0 2.40 3.42 7.43 7.89 9.38 10.1 11.1 10.8

MBA06L2E1M1 6.0 4.80 6.85 12.3 13.0 15.4 16.7 18.5 18.1

MBA012L2E1M1 12 9.60 13.7 24.5 26.0 30.9 33.5 36.9 36.2

MBA015L2E1M1 15 12.0 17.1 29.4 31.2 37.0 40.2 44.3 43.5

MBA018L2E1M1 18 14.4 20.5 36.8 39.1 46.3 50.2 55.4 54.3

MBA021L2E1M1 21 16.8 24.0 41.7 44.3 52.5 56.9 62.8 61.6

MBA024L2E1M1 24 19.2 27.4 49.0 52.1 61.7 66.9 73.8 72.5

MBA127L2E1M1 27 21.6 30.8 53.9 57.3 67.9 73.6 81.2 79.7

MBA130L2E1M1 30 24.0 34.2 58.8 62.5 74.1 80.3 88.6 87.0

MBA136L2E1M1 36 28.8 41.1 71.1 75.5 89.5 97.1 107 105

MBA139L2E1M1 39 31.2 44.5 78.5 83.3 98.7 107 118 116

MBA251L2E1M1 51 40.8 58.2 102 108 128 138 152 148

MBA260L2E1M1 60 48.0 68.5 118 125 148 161 177 174

MBA275L2E1M1 75 60.0 85.6 147 156 185 201 222 217

MBA360L2E1M1 60 48.0 68.4 118 125 148 161 177 174

MBA396L2E1M1 96 76.8 110 189 201 238 258 284 279

MBA3108L2E1M1 108 86.4 123 213 227 269 291 321 315

MBA3120L2E1M1 120 96.0 137 235 250 296 321 354 348

MBA3126L2E1M1 126 101 144 248 263 312 338 373 366

MBA3132L2E1M1 132 106 151 260 276 327 355 391 384

MBA4150L2E1M1 150 120 171 297 316 375 403 444 433

MBA31150L2E1M1 150 120 171 297 316 375 403 444 433

MBA32150L2E1M1 150 120 171 297 316 375 403 444 433

MBA33150L2E1M1 150 120 171 297 316 375 403 444 433

MBA40120L2E1M1 120 96.0 137 235 250 296 321 354 348

MBA41120L2E1M1 120 96.0 137 235 250 296 321 354 348

MBA40150L2E1M1 150 120 171 297 316 375 403 444 433

Protective Characteristics

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 20

Page 21: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MBA Series

21

Total Overall Recommended Recommended Drawing Data Sheetcreepage height minimum minimum Reference Reference

mm mm phase distance(nom) (max) centres line to Earth

mm mm

620 446 268 16 BOW-13-001 BOW-EPP-MBA0-3

620 446 296 33 BOW-13-001 BOW-EPP-MBA0-6

620 446 353 65 BOW-13-001 BOW-EPP-MBA0-12

620 446 381 81 BOW-13-001 BOW-EPP-MBA0-15

620 446 409 98 BOW-13-001 BOW-EPP-MBA0-18

620 446 437 114 BOW-13-001 BOW-EPP-MBA0-21

620 446 466 130 BOW-13-001 BOW-EPP-MBA0-24

960 568 494 147 BOW-13-002 BOW-EPP-MBA1-27

960 568 522 163 BOW-13-002 BOW-EPP-MBA1-30

960 568 578 195 BOW-13-002 BOW-EPP-MBA1-36

960 568 607 212 BOW-13-002 BOW-EPP-MBA1-39

2220 970 719 277 BOW-13-003 BOW-EPP-MBA2-51

2220 970 804 326 BOW-13-003 BOW-EPP-MBA2-60

2220 970 945 407 BOW-13-003 BOW-EPP-MBA2-75

3320 1330 804 326 BOW-13-004 BOW-EPP-MBA3-60

3320 1330 1142 521 BOW-13-004 BOW-EPP-MBA3-96

3320 1330 1255 586 BOW-13-004 BOW-EPP-MBA3-108

3320 1330 1368 651 BOW-13-004 BOW-EPP-MBA3-120

3320 1330 1424 684 BOW-13-004 BOW-EPP-MBA3-126

3320 1330 1481 716 BOW-13-004 BOW-EPP-MBA3-132

3915 1670 2022 814 BOW-13-005 BOW-EPP-MBA4-150

4280 1903 2022 814 BOW-13-006 BOW-EPP-MBA3.1-150

5540 2305 2022 814 BOW-13-006 BOW-EPP-MBA3.2-150

6640 2665 2022 814 BOW-13-006 BOW-EPP-MBA3.3-150

4535 2121 1738 651 BOW-13-006 BOW-EPP-MBA4.0-120

4875 2243 1738 651 BOW-13-006 BOW-EPP-MBA4.1-120

4535 2121 2022 814 BOW-13-006 BOW-EPP-MBA4.0-150

Mechanical and Reference Information

Housing Max Overall Total Nett MaximumType kV height creepage weight safe load

Rating mm mm kg cantilever(max) (nom) N.m

MBA0 39 446 620 18 3540MBA1 54 568 960 26 3540MBA2 96 970 2220 40 3540MBA3 150 1330 3320 53 3540MBA4 180 1670 3915 65 3540

Mechanical and Dimensional Characteristics

NOTE: Add 5mm to over all height for 2 Unit ArrestersAdd 10mm to over all height for 3 Unit Arresters

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 21

Page 22: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MCA Series

22

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 250A 1000A 5kA 10kA 20kA 10kAkV crest kV crest kV crest kV crest kV crest kV crest

MCA03L2E1M2 3 2.40 3.69 10.6 11.4 13.1 14.1 15.5 14.8

MCA06L2E1M2 6 4.80 7.38 21.3 22.8 26.1 28.2 31.0 29.6

MCA012L2E1M2 12 9.60 14.8 31.9 34.2 39.2 42.3 46.5 44.4

MCA015L2E1M2 15 12.0 18.5 37.0 39.7 45.8 49.5 55.0 52.8

MCA021L2E1M2 21 16.8 25.8 49.5 53.2 61.4 66.3 73.7 70.8

MCA024L2E1M2 24 19.2 29.5 53.7 57.7 66.6 72.0 80.0 76.8

MCA127L2E1M2 27 21.6 33.2 61.6 66.2 76.4 82.6 91.7 88.1

MCA130L2E1M2 30 24.0 36.9 66.6 71.4 81.7 88.2 97.1 92.7

MCA136L2E1M2 36 28.8 44.3 77.0 82.7 95.4 103 115 110

MCA139L2E1M2 39 31.2 48.0 83.1 89.3 103 111 124 119

MCA260L2E1M2 60 48.0 73.8 123 132 153 165 183 176

MCA275L2E1M2 75 60.0 92.3 151 162 187 202 223 216

MCA360L2E1M2 60 48.0 73.8 123 132 153 165 183 176

MCA396L2E1M2 96 76.8 118 192 206 238 257 286 274

MCA3108L2E1M2 108 86.4 133 216 232 267 289 321 308

MCA3120L2E1M2 120 96.0 148 236 254 293 317 352 338

MCA3126L2E1M2 126 101 155 250 268 309 334 372 357

MCA4144L2E1M2 144 115 177 282 303 350 378 420 403

MCA4150L2E1M2 150 120 185 296 318 366 396 440 422

MCA31150L2E1M2 150 120 1 85 296 318 366 396 440 422

MCA32150L2E1M2 150 120 185 296 318 366 396 440 422

MCA40150L2E1M2 150 120 185 296 318 366 396 440 422

MCA41198L2E1M2 198 158 244 387 415 477 515 573 550

MCA42198L2E1M2 198 158 244 387 415 477 515 573 550

MCA43198L2E1M2 198 158 244 387 415 477 515 573 550

MCA43240L2E1M2 240 192 295 466 500 573 619 688 661

MCA44240L2E1M2 240 192 295 466 500 573 619 688 661

MCA44288L2E1M2 288 230 354 557 598 690 746 829 796

MCA333336L2E1M2 336 269 413 649 699 804 870 967 924

MCA333360L2E1M2 360 288 443 694 744 857 928 1031 990

MCA444360L2E1M2 360 288 443 694 744 857 928 1031 990

Protective Characteristics

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 22

Page 23: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MCA Series

23

Total Overall Recommended Recommended Drawing Data Sheetcreepage height minimum minimum Reference Reference

mm mm phase distance(nom) (max) centres line to Earth

mm mm

540 440 308 16 BOW-14-008 BOW-EPP-MCA0-3

540 440 336 33 BOW-14-008 BOW-EPP-MCA0-6

540 440 393 65 BOW-14-008 BOW-EPP-MCA0-12

540 440 421 81 BOW-14-008 BOW-EPP-MCA0-15

540 440 477 114 BOW-14-008 BOW-EPP-MCA0-21

540 440 506 130 BOW-14-008 BOW-EPP-MCA0-24

1150 610 534 147 BOW-14-009 BOW-EPP-MCA1-27

1150 610 562 163 BOW-14-009 BOW-EPP-MCA1-30

1150 610 618 195 BOW-14-009 BOW-EPP-MCA1-36

1150 610 647 212 BOW-14-009 BOW-EPP-MCA1-39

2390 980 844 326 BOW-14-010 BOW-EPP-MCA2-60

2390 980 985 407 BOW-14-010 BOW-EPP-MCA2-75

3820 1330 844 326 BOW-14-011 BOW-EPP-MCA3-60

3820 1330 1182 521 BOW-14-011 BOW-EPP-MCA3-96

3820 1330 1295 586 BOW-14-011 BOW-EPP-MCA3-108

3820 1330 1408 651 BOW-14-011 BOW-EPP-MCA3-120

3820 1330 1464 684 BOW-14-011 BOW-EPP-MCA3-126

5000 1680 1965 783 BOW-14-012 BOW-EPP-MCA4-144

5000 1680 2022 814 BOW-14-012 BOW-EPP-MCA4-150

4970 1945 2022 814 BOW-14-013 BOW-EPP-MCA3.1-150

6210 2315 2022 814 BOW-14-013 BOW-EPP-MCA3.2-150

5540 2125 2022 814 BOW-14-013 BOW-EPP-MCA4.0-150

6150 2295 2571 1075 BOW-14-013 BOW-EPP-MCA4.1-198

7390 2665 2571 1075 BOW-14-013 BOW-EPP-MCA4.2-198

8820 3015 2571 1075 BOW-14-013 BOW-EPP-MCA4.3-198

8820 3015 3171 1303 BOW-14-013 BOW-EPP-MCA4.3-240

10000 3365 3171 1303 BOW-14-013 BOW-EPP-MCA4.4-240

10000 3365 3622 1563 BOW-14-013 BOW-EPP-MCA4.4-288

11490 3970 4074 1826 BOW-14-014 BOW-EPP-MCA3.3.3-336

11490 3970 4299 1954 BOW-14-014 BOW-EPP-MCA3.3.3-360

15000 5050 4299 1954 BOW-14-014 BOW-EPP-MCA4.4.4-360

Mechanical and Reference Information

Housing Max Overall Total Nett MaximumType kV height creepage weight safe load

Rating mm mm kg cantilever(max) (nom) N.m

MCA0 30 440 540 26 6800

MCA1 45 610 1150 42 6800

MCA2 90 980 2390 55 6800

MCA3 126 1330 3820 90 6800

MCA4 168 1680 5000 115 6800

Mechanical and Dimensional Characteristics

NOTE: Add 5mm to over all height for 2 Unit ArrestersAdd 10mm to over all height for 3 Unit Arresters

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 23

Page 24: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MDA Series

24

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 500A 2000A 10kA 20kA 40kA 20kAkV crest kV crest kV crest kV crest kV crest kV crest

MDA03L2E1M2 3 2.40 3.63 11.0 11.9 14.1 15.5 17.6 16.6

MDA06L2E1M2 6 4.80 7.26 22.0 23.7 28.2 31.0 35.1 33.1

MDA012L2E1M2 12 9.60 14.5 31.9 34.7 41.3 45.9 52.5 49.7

MDA015L2E1M2 15 12.0 18.2 37.1 40.3 48.0 53.3 61.0 57.7

MDA018L2E1M2 18 14.0 21.8 44.0 47.4 56.4 62.0 70.2 66.2

MDA021L2E1M2 21 16.8 25.4 46.4 50.4 60.0 66.7 76.2 72.2

MDA024L2E1M2 24 19.2 29.0 55.0 59.3 70.4 77.6 87.8 82.8

MDA127L2E1M2 27 21.6 32.7 60.0 65.1 77.5 86.2 98.5 93.3

MDA130L2E1M2 30 24.0 36.3 66.0 71.1 84.5 93.3 107 101

MDA136L2E1M2 36 28.8 43.6 76.9 83.0 98.6 109 123 116

MDA139L2E1M2 39 31.2 47.2 80.0 86.8 103 115 131 124

MDA142L2E1M2 42 33.6 50.8 87.9 94.8 113 124 140 132

MDA260L2E1M2 60 48.0 72.6 121 131 156 173 198 188

MDA275L2E1M2 75 60.0 90.8 150 163 194 215 246 233

MDA396L2E1M2 96 76.8 116 190 206 246 273 312 295

MDA3108L2E1M2 108 86.4 131 210 228 271 302 345 327

MDA3120L2E1M2 120 96.0 145 232 252 300 333 381 361

MDA3126L2E1M2 126 101 152 242 262 312 347 396 375

MDA3132L2E1M2 132 106 160 256 277 330 367 420 397

MDA4150L2E1M2 150 120 182 290 315 375 416 476 451

MDA31150L2E1M2 150 120 182 290 315 375 416 476 451

MDA32150L2E1M2 150 120 182 290 315 375 416 476 451

MDA33150L2E1M2 150 120 182 290 315 375 416 476 451

MDA33240L2E1M2 240 192 290 460 499 595 661 755 715

MDA40150L2E1M2 150 120 182 290 315 375 416 476 451

MDA41198L2E1M2 198 158 240 380 412 491 546 624 591

MDA42198L2E1M2 198 158 240 380 412 491 546 624 591

MDA43210L2E1M2 210 168 254 403 437 512 578 660 626

MDA44288L2E1M2 288 230 348 550 597 711 790 903 855

MDA333336L2E1M2 336 269 407 640 694 827 919 1051 995

MDA333360L2E1M2 360 288 436 680 738 879 976 1117 1057

Protective Characteristics

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 24

Page 25: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Station ClassPorcelain Surge Arresters MDA Series

25

Total Overall Recommended Recommended Drawing Data Sheetcreepage height minimum minimum Reference Reference

mm mm phase distance(nom) (max) centres line to Earth

mm mm

540 440 308 16 BOW-14-015 BOW-EPP-MDA0-3

540 440 336 33 BOW-14-015 BOW-EPP-MDA0-6

540 440 393 65 BOW-14-015 BOW-EPP-MDA0-12

540 440 421 81 BOW-14-015 BOW-EPP-MDA0-15

540 440 449 98 BOW-14-015 BOW-EPP-MDA0-18

540 440 477 114 BOW-14-015 BOW-EPP-MDA0-21

540 440 506 130 BOW-14-015 BOW-EPP-MDA0-24

1150 610 534 147 BOW-14-016 BOW-EPP-MDA1-27

1150 610 562 163 BOW-14-016 BOW-EPP-MDA1-30

1150 610 618 195 BOW-14-016 BOW-EPP-MDA1-36

1150 610 647 212 BOW-14-016 BOW-EPP-MDA1-39

1150 610 675 228 BOW-14-016 BOW-EPP-MDA1-42

2390 980 844 326 BOW-14-017 BOW-EPP-MDA2-60

2390 980 985 407 BOW-14-017 BOW-EPP-MDA2-75

3820 1330 1182 521 BOW-14-018 BOW-EPP-MDA3-96

3820 1330 1295 586 BOW-14-018 BOW-EPP-MDA3-108

3820 1330 1408 651 BOW-14-018 BOW-EPP-MDA3-120

3820 1330 1464 684 BOW-14-018 BOW-EPP-MDA3-126

3820 1330 1521 717 BOW-14-018 BOW-EPP-MDA3-132

5000 1680 2022 814 BOW-14-019 BOW-EPP-MDA4-150

4970 1945 2022 814 BOW-14-020 BOW-EPP-MDA3.1-150

6210 2315 2022 814 BOW-14-020 BOW-EPP-MDA3.2-150

7640 2665 2022 814 BOW-14-020 BOW-EPP-MDA3.3-150

7640 2665 3171 1303 BOW-14-020 BOW-EPP-MDA3.3-240

5540 2125 2022 814 BOW-14-020 BOW-EPP-MDA4.0-150

6150 2295 2571 1075 BOW-14-020 BOW-EPP-MDA4.1-198

7390 2665 2571 1075 BOW-14-020 BOW-EPP-MDA4.2-198

8820 3015 2684 1141 BOW-14-020 BOW-EPP-MDA4.3-210

10000 3365 3622 1563 BOW-14-020 BOW-EPP-MDA4.4-288

11490 4000 4074 1826 BOW-14-021 BOW-EPP-MDA3.3.3-336

11490 4000 4299 1954 BOW-14-021 BOW-EPP-MDA3.3.3-360

Mechanical and Reference Information

Housing Max Overall Total Nett MaximumType kV height creepage weight safe load

Rating mm mm kg cantilever(max) (nom) N.m

MDA0 30 440 540 26 6800

MDA1 51 610 1150 42 6800

MDA2 96 980 2390 55 6800

MDA3 138 1330 3820 90 6800

MDA4 180 1680 5000 115 6800

Mechanical and Dimensional Characteristics

NOTE: Add 5mm to over all height for 2 Unit ArrestersAdd 10mm to over all height for 3 Unit Arresters

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 25

Page 26: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

PSRB single columnPolymeric Housed Surge Arresters

26

The PSRB surge arrester is available for applications upto 220kV systems.

The design utilises a housing construction, which is aresin and glass fibre strengthening sleeve over mouldedwith Silicone Rubber outer insulating housing fitted withaluminium flanges.

High cantilever mechanical strength is achieved on thisdesign with the internal assembly similar to that of theporcelain Housed Surge Arrester.

The design has been tested to IEC and demonstrates a63kA short circuit performance.

Routine tests are carried out to show that themanufacturing conforms to the current internationalstandard.

Electrical Performance

Specification: IEC60099-4

Classification: Class 2 10kA

High Current Performance: 100kA

Pressure Relief 63 kA

Energy Capability:5.0kJ/kV at Ur according to IEC60099-4(Clause 8.4.2 table 5 &8.5.5)

Voltage Rating: 60kV to 228kV

Typical Applications

• Substations

• Power Transformers

• Cable Termination

PSRB3180 - Brazil - 220kV

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 26

Page 27: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

27

PSRB single columnPolymeric Housed Surge Arresters

Product Code Rating Max cont. Temporary Max residual voltage kV crest with current wave Steep

voltage operating over-voltage current

kV voltage capabilitySwitching surge Lightning current residual

(COV) kV for 1 sec30/60 µS 8/20 µS voltage

(TOV) kV 250A 1000A 5kA 10kA 20kA 20kAkV crest kV crest kV crest kV crest kV crest kV crest

PSRB160L2E1M3 60 48.0 69.6 119 126 150 161 178 173

PSRB175L2E1M3 75 60.0 87.0 149 158 188 202 222 216

PSRB296L2E1M3 96 76.8 111 193 205 244 262 289 281

PSRB2108L2E1M3 108 86.0 125 218 232 275 296 326 317

PSRB2120L2E1M3 120 96.0 139 238 253 300 323 356 346

PSRB2132L2E1M3 132 106 153 263 279 332 356 393 383

PSRB2138L2E1M3 138 110 160 275 292 347 373 411 400

PSRB2150L2E1M3 150 120 174 297 316 375 403 445 433

PSRB2168L2E1M3 168 134 195 335 355 422 454 500 487

PSRB3198L2E1M3 198 158 230 397 421 500 538 593 577

PSRB3228L2E1M3 228 182 265 454 482 572 615 678 660

Protective Characteristics Class 2

Total Overall Recommended Recommended Drawing Data Sheetcreepage height minimum minimum Reference Reference

mm mm phase distance(nom) (max) centres line to Earth

mm mm

2378 1000 764 326 BOW-18-004 BOW-EPP-PRSB1-60

2378 1000 905 407 BOW-18-004 BOW-EPP-PRSB1-75

4756 2025 1103 522 BOW-18-005 BOW-EPP-PRSB2-96

4756 2025 1216 587 BOW-18-005 BOW-EPP-PRSB2-108

4756 2025 1738 652 BOW-18-005 BOW-EPP-PRSB2-120

4756 2025 1851 717 BOW-18-005 BOW-EPP-PRSB2-132

4756 2025 1908 750 BOW-18-005 BOW-EPP-PRSB2-138

4756 2025 2020 815 BOW-18-005 BOW-EPP-PRSB2-150

4756 2025 2290 913 BOW-18-005 BOW-EPP-PRSB2-168

7134 3025 2572 1076 BOW-18-006 BOW-EPP-PRSB3-198

7134 3025 2854 1239 BOW-18-006 BOW-EPP-PRSB3-228

Mechanical and Reference Information Class 2

Transmarr4/05-2.qxd 12.04.2005 16:47 Uhr Seite 27

Page 28: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

PSRB single columnPolymeric Housed Surge Arresters

28

Example: PSRB2 138 L2 E1 M3

Arrester Housing

Voltage

Mounting

Earth Terminal

Line Terminal

Corona Ring (150kV and above)

Grading Ring (None <120kV)(Ø610 120-150kV)(Ø710 151-228kV)

Silicone Rubber Housed Arrester Unit

Die Cast Aluminium End Flange

M3 Diaphram Deflector Plate with3 M16 Polyfibre Base Insulatorsequally spaced on 178 PCD

E2Earth Clamp to suit cablesup to Ø16 mm

E12 x M10 x 20mmHexagon headedset screws andspring washers

L5Line Clamp to suit cablesup to Ø35 mm

L3Line Clamp to suit cablesup to Ø16 mm

L2Aluminium StemØ30 x 80mm high

L1 (as E1) 2 x M10 x 20mmHexagon headed set screws andspring washers

Transmarr4/05-2.qxd 12.04.2005 16:48 Uhr Seite 28

Page 29: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

Surge Counters SC12, SC13 designed to be usedwith Surge Arresters

Meter – 6 digit cyclometer at least5 counts/second

Minimum count current – 200 amps 8/20 microsecondwave

Maximum High Current – 100kA 4/10 microsecondWithstand wave

Nominal Residual – 5kV peakVoltage at 100kA with4/10 Microsecond Wave

Meter scale – 0 - 30mA (bilinear scale)Ref SC13

SC13 leakage – 0 - 50mA (bilinear scale)Ref SC13L

Both SC12/SC13 counters can be supplied with anauxiliary contact rated 0.5 amps 250V for connection toremote signalling equipment. If required put suffix ACe.g. SC12/AC

Surge Counters

Transmission Line Arrester “TLA”

TLA4 -150

Transmission Line surge arresters for systems up to 230 kV.

Specification: IEC60099-4Classification: 10kAVoltage Rating: 15kV to 192 kVHigh Current Performance: 100kALine Discharge Class: 2Energy Capability:4.5kJ/kV at Ur according to IEC60099-4(Clause 8.4.2 table 5 and 8.5.5)TLA1 15 - 45 kVTLA2 48 - 96 kVTLA3 108 - 144kVTLA4 150 - 192 kVInsulation Material: Silicone Rubber

Vibration tested at National Engineering Laboratory - UK

TLA Applications

• Towers that have high footing resistance to impedance earth can causeback flashover on to the line.

• Transmission lines with or without shielding wire which have abnormallightning activity

29

Transmarr4/05-2.qxd 12.04.2005 16:48 Uhr Seite 29

Page 30: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

30

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Additional Ranges

Other products in our range

DC traction surge arresters

CSPA surge arresters

DC Traction surge arresters for system voltages 0.7 – 4kV (HE60MC)to EN50123-5.AC surge arresters for system voltages 15-25kV singlephase (HSR) to IEC 60099-4 &EN50123-5.

Cable sheath surge arresters for available forprotection of underground cables. Surge arrestermodules used for direct burried or installed in a linkbox. (CSPA/CPA) to IEC60099-4.

Airfield lighting control circuits are vulnerable tolightning surges as they have an attractive lowimpedance path. Protection of 4kV DC lightingcircuits. (2DCAFL4) to IEC60099-4.

Replaceable spark gap device with sparkover voltage450 – 900V. Mainly used on railway networks toprotect earthing in conjunction with signalling (SPG).

Portable earthing kit designed to ESI standards usedto protect utility engineers working on distribution ortransmission lines from accidental line switching.

Hydraulic Cable Spiker used to prove that adisconnected underground cable is not live before sitework commences. 25 year product reliability (CSTE).

Airfield lighting box

Spark gap

Portable earth kits

Cable spiker kit

Transmarr4/05-2.qxd 12.04.2005 16:48 Uhr Seite 30

Page 31: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

31

Energy Division is a worldwide leader with innovative solutions from the power plant to the end user.

Other products and brochures available from Energy Division

Asset protection

Low-voltage surge arresters

Insulation enhancement systems for substations andoverhead. Designed to prevent unplanned outagesdue to accidential bridging.

LV arresters are used to provide protection for LVoverhead lines, consumer in-house supplies,distribution tranformers and other applicances.

Metal oxide varister, distribution arresters for indoorand outdoor applications for protection of overheadlines, DC locomotives and switchgear applications.

Porcelain and polymeric series parallel and single column contructed arresters for protection oftransmission systems up to 550 kV.

Insulators and insulating components/housings providing reliable solutions for power utilities andrailway customers with installations in high pollutionenvironments and applications up to 400 kV.

Insulators for applications up to system voltages of132 kV. This range of insulators offers a cost-effectivesolution for low and medium polluted environments.

Medium-voltage surge arresters

High-voltage surge arresters

Polymeric insulators

Porcelain insulators

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Contact us at: [email protected]

Transmarr4/05-2.qxd 12.04.2005 16:48 Uhr Seite 31

Page 32: Transmission Surge Arresters - yerenergo.am · polymeric transmission surge arresters. The Bowthorpe EMP range ... MCA, Class 3, 10kA (11-400kV) MDA, Class 4, 20kA (11-400kV) Polymeric

© T

yco

Ele

ctro

nic

s B

OW

-EP

P-00

01-0

2-05

For further information contact [email protected]

Tyco Electronics Bowthorpe EMPStevenson Road, Brighton, East Sussex, England BN2 0DFPhone: +44 (0) 1273 692591, Fax: +44 (0) 1273 601741http://www.bowthorpe-emp.com

Tyco Electronics Raychem GmbH, Energy DivisionFinsinger Feld 1, 85521 Ottobrunn/Munich, GermanyPhone: +49-89-6089-0, Fax: +49-89-6096345

Energy Division – a pioneer in the development of economical solutions forthe electrical power industry. Our product range includes: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls,insulators & insulation enhancement and surge arresters.

For more information and your country contact person, please visit us at: http://energy.tycoelectronics.com

All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable.Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particularquality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forthin our standard terms and conditions of sale. ALR, AMP, AXICOM, B&H, BOWTHORPE EMP, DORMAN SMITH, DULMISON, GURO, HELLSTERN, LA PRAIRIE, MORLYNN, RAYCHEM, andSIMEL are trademarks. CROMPTON is a trademark of Crompton Parkinson Ltd. and is used by Tyco Electronics under licence.

Additional Product Lines:

http://energy.tycoelectronics.comEnergy Division

Transmission Line Arrester “TLA”

http://energy.tycoelectronics.comEnergy Division

Polymeric DC TractionSurge Arrester

http://energy.tycoelectronics.comEnergy Division

Spark Gap Type SPG1

The SPG1 Spark Gap is designed for use with tractioncircuits to provide virtually instantaneous protection ofboth equipment and personnel from power systemfaults. The unit also provides protection againstlightning generated voltages which would otherwisecause damage to signalling and cable circuits.

The SPG1 is constructed in stainless steel of ruggeddesign allowing the SPG to be installed in harshenvironments such as track side locations withoutadditional weather protection.

Suitable for use on circuits where standing/inducedvoltages do not exceed 110v RMS.

Fast operation – Typical 5 microseconds with 11kA faultcurrent.

Internal spark gap module unit easily replaced afterfault current operation.

Fail safe feature ensures safety to personnel andequipment.

Service proven performance.

High internal impedance with low capacitance – doesnot interfere with track signalling circuits.

Transmission Line Arrester‘TLA’• Switching over voltages are

absorbed over the length ofthe line reducing the severityof surge at the substation.

• Transmission systems can beoperated even where sub-soilgives poor tower footingresistance.

Polymeric DC Traction Surge Arresters• Rolling Stock• Track Side

Spark Gap Type SPG1• Protection between overhead

catenary structure earth andsystem earth

• Protection of single bondedpower cable circuits

• Protection of low voltage DCpower supplies

• Protection of cathodic protectionpower supplies.

http://energy.tycoelectronics.comEnergy Division

Safety, Connectors and Earthing Equipment

http://energy.tycoelectronics.comEnergy Division

Airfield Lighting Box Type 2DCAFL4

There are few places more exposed to direct lightningstrikes than an airfield. In such situations lightningstrikes within the vicinity of the airfield can result inpermanent damage to electrical equipment.

Airfield lighting circuits are particularly vulnerable asthe associated cable networks present an attractive lowimpedance path for lightning surge currents to earth.The result of a nearby lightning strike can bepermanent damage to the control circuits unless asuitable lightning arrester is fitted to the lightingcontrol equipment.

The Lightning Arrester Type 2DCAFL4 is designed toprotect airfield lighting control equipment from theeffects of direct or indirect lightning strikes.

The arrester is provided with two metal oxide activeelements which are connected in parallel with thesupply cables. Installation requires only the cutting ofthe supply cables at a convenient place close to thecontrol equipment and connection of the arrester to agood electrical earth.

Arrester 2DCAFL4 can be fitted to new equipment butis primarily designed to be quickly installed on existingcircuits.

Safety, Connectors andEarthing Equipment.• Portable Earth Kits• InsulatedPoles• Pole Heads• Earthing Clamps• Line Taps and Shrouds• Cable Spiker

Airfield Lighting Box Type 2DCAFL4• Protection of airfield lighting

control equipment.

http://energy.tycoelectronics.comEnergy Division

Surge CountersType SC12 & SC13

The Bowthorpe EMP range of SurgeArrester monitoring instruments arefully tested for use with anymanufacturers surge arrester. TheSC12 is a Surge Counter only, whilstthe SC13 provides the additionalmeasurement of total leakagecurrent. The analogue instrumentprovides a means of monitoring thecurrent through the arrester and theleakage current over the surface ofthe arrester housing. Significantchanges after installation mayindicate a deterioration in thearrester or a build up of surfacecontamination.These instruments, which require noauxiliary supply, are designed forinstallation in the earth connectionsof a single surge arrester oralternatively the SC12 may be usedwith the common earth of a threephase set. Fully weatherproofed andsealed for life they are housed in aone piece gravity die cast aluminiumcase coated to enhance its alreadyhigh degree of resistance to surfacecorrosion. The glass viewing windowis sealed in place, using a siliconrubber adhesive, and a desiccator isenclosed to ensure any residualmoisture trapped during sealing isabsorbed for the service life of thecounter. Mounting is effected bymeans of an integrally cast lug at the

rear of the case providing a singleclearance hole for the galvanisedsteel M12 bolt supplied.

The SC12 and SC13 are serviceproven and require no specialmaintenance or servicing apart fromgeneral cleaning of the glassviewing window and the mouldedepoxy resin line terminal bushing.

Surge Counters Type SC12 &Sc13• Used in series with HV

Surge Arrester• SC12 Surge Counter• SC13 Combined Surge Counter

with Leakage Current Meter.