Standard offer applications: Fans, blowers, ventilators Pumps: water pumps, heat
pumps, etc. Compressors Elevators Automatic gates,
roof window openers Wood machines: fixed drilling
machines, saws, etc. Tool machines Conveyors
Standard offerStarters
TeSys LE
Direct On Line or reversing startersIP65 degree of protection
Functions
> Protection from overloads (thermal relay to be ordered separately)
> Local control
Check for the presence of short-circuit protection in the main electrical switchboard.
Switch disconnectors
TeSys Vario
3-pole switch disconnectorsIP55 degree of protection
Functions
> Local isolation, for maintenance
> Padlockable rotary handle
The motor control and protection devices are located in the main electrical switchboard.
Manual motor starters
TeSys GV
Manual Direct On Line startersIP55 or IP65 degree of protection(according to the version)
Functions
> Protection from short circuits and overloads
> Local manual control
> Emergency stop switch (special version)
> Disconnection locking (option)
Circuit breaker to be ordered separately.
Safety offer applications:Machines whose electrical equipment should comply with IEC 60204 (dangerous machines)
Wood machines Metalworking machines
Plastics machines Material handling machines,
including conveyors
AS-Interface offer applications: Conveyors
Safety offer AS-Interface offerSafety starters
TeSys LG, LJ
Direct On Line or reversing startersIP55 degree of protection
Functions
> Protection from short circuits and overloads
> Protection from voltage drops (depending on the model, undervoltage release unit to be ordered separately)
> Emergency stop switch
> Local manual control
> Disconnection locking
AS-Interface starters
TeSys LF
Direct On Line or reversing startersIP54 degree of protection
Functions
> Motor control and monitoring by AS-Interface
> Protection from short circuits and overloads
> Disconnection locking
> Local manual control (special version)
Manual motor starters
TeSys GV
Manual Direct On Line startersIP55 degree of protection
Functions
> Protection from short circuits and overloads
> Local manual control
> Emergency stop switch (special version)
> Disconnection locking
Circuit breaker to be ordered separately.
TeSys GV Manual motor starters
Motor power AC-3 400 V
Max. motor current Ie max
For standard applications
For high performances applications
kW References
0.06 0.25 GV2ME02 GV2P02
0.09 0.4 GV2ME03 GV2P03
0.12 0.63 GV2ME04 GV2P04
0.18 0.63 GV2ME04 GV2P04
0.25 1 GV2ME05 GV2P05
0.37 1.6 GV2ME06 GV2P06
0.55 1.6 GV2ME06 GV2P06
0.75 2.5 GV2ME07 GV2P07
1.1 4 GV2ME08 GV2P08
1.5 4 GV2ME08 GV2P08
2.2 6.3 GV2ME10 GV2P10
3 9 GV2ME14 GV2P14
4 9 GV2ME14 GV2P14
5.5 13 GV2ME16 GV2P16
7.5 17 GV2ME20 GV2P20
9 21 GV2ME21 GV2P21
11 23 GV2ME22 GV2P22
15 29 GV3P32
18.5 35 GV3P40
22 41 GV3P50
30 55 GV3P65
Enclosures for GV2ME circuit breakers References
Degree of protection Mushroom head Emergency Stop Surface mounting Flush mountingIP41 without GV2MC01 GV2MP01IP55 without GV2MC02 GV2MP02
with - turn to release, padlockable GV2MCK04IP55 < +5°C without GV2MC03
Add-on blocksDescription Mounting Voltage References
Undervoltage trips* right side 380…415 V 50 Hz GVAX38560 Hz GVAX386
*Can be mounted only on GV2ME
Enclosures for GV2P/GV3P circuit breakers References
Circuit-breaker Degree of protection Mounting Red BlackGV2P IP65 surface mounting GV2PC01 GV2PC02GV3P IP65 surface mounting GV3PC01 GV3PC02
Thermal-magnetic circuit breakers
TeSys LE Starters
Dots must be replaced by the control circuit voltage code:Control circuit voltages*
Volts ~ 50/60 Hz 220 230 240 380 400 415
Voltage code LE1M35, LE•D09… D35 M7 P7 U7 Q7 V7 N7
LE•D40A… D65A - P7 - Q7 - -
* Other voltages: please consult our catalogue
Enclosed starters Enclosed starters for high-performance applications
(1) Thermal relay included
Motor power AC-3 400 V
Max. motor current Ie max
Direct On Line starters(1)
kW References
0.25 0.8 LE1M35••05
0.37 1.2 LE1M35••06
0.55 1.8 LE1M35••07
0.75 2.6 LE1M35••08
1.1 3.7 LE1M35••10
1.5 3.7 LE1M35••10
2.2 5.5 LE1M35••12
3 8 LE1M35••14
4 11.5 LE1M35••16
5.5 14 LE1M35••21
7.5 16 LE1M35••22
Motor power AC-3 400 V
Max. motor current Ie max
Direct On Line starters
Reversing starters
Thermal overload relays (class 10 A)
kW Ref. Ref. Ref.
0.06 0.25 LE1D09•• LE2D09•• LRD02
0.09 0.4 LE1D09•• LE2D09•• LRD03
0.12 0.63 LE1D09•• LE2D09•• LRD04
0.18 0.63 LE1D09•• LE2D09•• LRD04
0.25 1 LE1D09•• LE2D09•• LRD05
0.37 1.6 LE1D09•• LE2D09•• LRD06
0.55 1.6 LE1D09•• LE2D09•• LRD06
0.75 2.5 LE1D09•• LE2D09•• LRD07
1.1 4 LE1D09•• LE2D09•• LRD08
1.5 4 LE1D09•• LE2D09•• LRD08
2.2 6 LE1D09•• LE2D09•• LRD10
3 7 LE1D09•• LE2D09•• LRD12
4 9 LE1D09•• LE2D09•• LRD14
5.5 12 LE1D12•• LE2D12•• LRD16
7.5 16 LE1D18•• LE2D18•• LRD21
11 22 LE1D25•• LE2D25•• LRD22
15 29 LE1D35•• LE2D35•• LRD32
18.5 40 LE1D40•• LE2D40•• LRD21
22 50 LE1D50•• LE2D50•• LRD22
30 65 LE1D65•• LE2D65•• LRD32
TeSys LG, LJ Safety starters
Motor power AC-3 400 V
Max. motor current Ie max
Direct On Line starters Reversing starters
Emergency stop by switch (rotary handle)
Emergency stop by mushroom head pushbutton
Emergency stop by mushroom head pushbutton
kW References
0.06 0.25 LG1K065••02 LG7K06••02 LG8K06••02
0.09 0.4 LG1K065••03 LG7K06••03 LG8K06••03
0.12 0.63 LG1K065••04 LG7K06••04 LG8K06••04
0.18 0.63 LG1K065••04 LG7K06••04 LG8K06••04
0.25 1 LG1K065••05 LG7K06••05 LG8K06••05
0.37 1.6 LG1K065••06 LG7K06••06 LG8K06••06
0.55 1.6 LG1K065••06 LG7K06••06 LG8K06••06
0.75 2.5 LG1K065••07 LG7K06••07 LG8K06••07
1.1 4 LG1K065••08 LG7K06••08 LG8K06••08
1.5 4 LG1K065••08 LG7K06••08 LG8K06••08
2.2 6 LG1K065••10 LG7K06••10 LG8K06••10
3 9 LG1K095••14 LG7K09••14 LG8K09••14
4 9 LG1K095••14 LG7K09••14 LG8K09••14
5.5 12 LG1D122••16 LG7D12••16 LG8D12••16
7.5 17 LG1D182••20 LG7D18••20 -
9 18 LG1D182••21 LG7D18••21 -
Dots must be replaced by the control circuit voltage code:Control circuit voltages*
Volts ~ 50/60 Hz 220/230 380/400
Voltage code M7 Q7
* Other voltages: please consult our catalogue
Enclosed starters
TeSys LF AS-Interface starters
TeSys Vario Switch disconnectors
Power AC-23 400 V
Thermal current Ithe
References
kW A
4 10 VCFN12GE
5.5 16 VCFN20GE
7.5 20 VCFN25GE
11 25 VCFN32GE
15 32 VCFN40GE
Overview
TeSys
enclosed
starters:
Motor power AC-3 400 V
Maximum motor current Ie max
Direct On Line starters
Reversing starters
kW References
0.06 0.25 LF3P02E LF4P02E
0.09 0.4 LF3P03E LF4P03E
0.12 0.63 LF3P04E LF4P04E
0.18 0.63 LF3P04E LF4P04E
0.25 1 LF3P05E LF4P05E
0.37 1.6 LF3P06E LF4P06E
0.55 1.6 LF3P06E LF4P06E
0.75 2.5 LF3P07E LF4P07E
1.1 4 LF3P08E LF4P08E
1.5 4 LF3P08E LF4P08E
2.2 6.3 LF3P10E LF4P10E
3 9 LF3P14E LF4P14E
4 9 LF3P14E LF4P14E
5.5 12 LF3P16E LF4P16E
Enclosed starters Enclosed switch disconnectors
TeSys range: TeSys GV, TeSys GK, TeSys GS, TeSys DF, TeSys K, TeSys D, TeSys F, TeSys B, TeSys LR, TeSys LT, TeSys T, TeSys Vario, TeSys U, TeSys LE, TeSys LG.
To discover the TeSys range, go to: www.schneider-electric.com/tesys
To download TeSys Enclosed Motor Starter Solution Guide
03-2014
35, rue Joseph MonierCS 30323F- 92506 Rueil Malmaison CedexFrance
RCS Nanterre 954 503 439Capital social 896 313 776 € www.schneider-electric.com
This document has been printed on ecological paper.
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
© 2
014
- Sch
neid
er E
lect
ric -
All
right
s re
serv
ed
Publication: Schneider Electric Industries SASPhoto: © Fotosearch - Schneider Electric Industries SASPrinted:
Make the most of your energy™
www.schneider-electric.com
Schneider Electric Industries SAS
EDCED114012EN