14
Énergie Transfert Thermique Technical instructions for Operation & Maintenance A different climate Environmental control solutions Single flow heat pump ULTI+

Technical instructions

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Énergie Transfert Thermique

Technical instructionsfor Operation & Maintenance

A different c l imateEnvironmental control solutions

Single fl ow heat pumpULTI+

2

E n e r g i eT r a n s f e r tT h e r m i q u e

Contents

Information contained in this document has been prepared by qualifi ed ETT specialists.We are doing our best to ensure its completeness and accuracy but it does not constitute a guarantee.This information is given in good faith, any use of the equipment not in accordance with the instructions and warnings is done at the user's own risk.

A. Equipment performance ................................................................................................................................ 3

B. Maintenance intervals ....................................................................................................................................... 3

C. Regulatory requirements ................................................................................................................................. 5

D. Specifi c maintenance recommendations ................................................................................ 7

E. Starting / Stopping the unit ........................................................................................................................... 8

F. Controller operation ............................................................................................................................................. 9

G. Diagnostics and troubleshooting support ...............................................................................10

Technical instructionsfor Operation & Maintenance

3MARK-NOT_20.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

A. Equipment performance• The validity of the guarantee is conditional upon strict compliance with instructions presented in this

document.• Proper operation and maintenance:

> maintain units’ performance; > extend equipment service life; > reduce the risk of unit failure; > allow energy costs management; > ensure regulatory compliance (compulsory checks based on local regulations).

ETT Services is here to help you get the most out of your installation.

+33 (0)2 98 48 02 [email protected]

Contact your local ETT Services adviser.

B. Maintenance intervals

Maintenance intervals: Q (Quarterly), H (Half-yearly), A (Annually)Operations T S A

General control Check casing X

Clean and prime siphons, clean condensate drains X

Read operating time X

Electricity / Control Check controller operation X

Set clock and operating schedule X

Check setpoints X

Electrical connections tightening X

Check temperature probes X

Consumables

Clean or replace fi lters (1)48 mm

X98 mm

X

Replace smoke detector headNota: Maintenance intervals are given as indication only. Replacement may be needed more frequently in polluted atmospheres.

Every 2 years

Replace smoke detection box battery Every 2 years

Replace humidity probe and/or sensor element (if applicable) Every 2 years

Replace CO2 probes (if applicable) Every 2 years

Technical instructionsfor Operation & Maintenance

4MARK-NOT_xx.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

Maintenance intervals: Q (Quarterly), H (Half-yearly), A (Annually)Operations T S A

Ventilation Check servomotors and dampers condition and operation X

Check fans turbines, clean if necessary X

Check air fl ow rates and fans rotation speed (if applicable)(1)

Nota: In case of insuffi cient fl ow rate, apply recommendations described in paragraph Specifi c maintenance recommendations, p. 7

X

Check air ducts (cone connectors, valves etc.) X

Read fans motors currents X

Check ventilation safety devices (fl ow rate, fi lters fouling, fi re contact, smoke detector, post-ventilation, etc.) (1) X

Refrigeration circuits Check oil level, adjust if necessary X

Check compressor(s) currents X

Check pressures: HP and LP X

Control superheat and subcooling X

Check fans turbines, clean if necessary (1) X

Check expansion valves operation, adjust if necessary X

Electronic expansion valves: check parameters X

Check 4-way valve(s) operation X

Check refrigeration safety devices (HP pressure switch, BP pressure switch function, thermostats, etc.) X

Tighten refrigeration pipe clamps: adjust or replace if necessary X

Regulatory controls Leakage checking (based on unit t CO2e) (2) >500 >50 >5

Pressure equipment inspection (2) Every 40 months

Pressure equipment certifi cation (2) Every 10 years

Inspection of air-conditioning systems and heat pumps (2) Every 5 years

Heating (if applicable) Check hot water coil (cleanliness, tightness) X

Check water quality in hot water coil X

Check 3-way valve operation X (3)

Check electric heaters operation X (3)

(1) See Specifi c maintenance recommendations.

(2) See Regulatory requirements.(3) In Heating mode.

Technical instructionsfor Operation & Maintenance

5MARK-NOT_20.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

C. Regulatory requirements

1/ Cooling system register (EN 378-2)

Each system having a refrigerant charge with a CO2 equivalent of 5 tonnes or above requires its own separate log book to be maintained.The logbook shall be prepared by the installer during installation. It shall be updated after every maintenance operation, as indicated in EN 378-4 standard.

Log books shall include the following information: > Detailed report of each maintenance or repair operation > Quantity and nature (new, reused, recycled) of refrigerant added during the operation > Quantity of refrigerant transferred during the operation (see also EN 378-4 standard) > Results of reused refrigerant analysis (if such analysis was performed) > Origin of reused refrigerant > System components replaced or modifi ed > Routine or periodic tests results > Signifi cant non-use periods

2/ Leakage checkingIn application of EU regulation No 517/2014 of the European Parliament and of the Council of 16 April 2014 on fl uorinated greenhouse gases and repealing Regulation (EC) No 842/2006 (Text with EEA relevance), equipment containing such refrigerants must be checked periodically for leakage (see Regulatory controls, p. 4) by certifi ed personnel and a tightness control certifi cate must be issued.

Leak check intervals

Checking frequency Once a year Twice a year 4 times a year

Metric tons of CO2 equivalent 5 to 50 50 to 500 > 500

Fluid

R134a Refrigerant charge (kg) 3.5 to 35 kg 35 to 349.7 kg >349.7 kg

R407C Refrigerant charge (kg) 2.82 to 28.2 kg 28.2 to 281.8 kg > 281.8 kg

R410A Refrigerant charge (kg) 2.39 to 23.9 kg 23.9 to 239.5 kg > 239.5 kg

3/ Refrigerant handlingRefrigerant handling must comply with French Decree no. 2007-737 and European legislation:

> Technicians must be trained and must hold the relevant F-gas qualifi cation. > The company employing the technician must hold an F-gas Company Certifi cate authorising its personnel to handle refrigerant. > Refrigerant leaks must be handled and declared according to the installation refrigerant charge.

Technical instructionsfor Operation & Maintenance

6MARK-NOT_xx.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

4/ Monitoring of pressure equipment operationAlthough refrigeration installations fall within the pressure equipment category, they are a special case in terms of in-service monitoring. In 2014, the French safety offi ce of industrial equipment (BSEI) validated a Technical Guidebook (CTP USNEF - Available on-line in French), which authorises waivers from the French decree of 15 March 2000 (amended).

> Refrigeration installations shall be verifi ed within 3 months of commissioning. Initial verifi cation shall be performed by an authorised person, under the responsibility of the operator.

> Refrigeration installations shall be inspected at least every 40 months. Periodic inspection shall be performed by an authorised person, under the responsibility of the operator.

> Refrigeration installations shall be requalifi ed every 10 years. Periodic requalifi cation shall be performed by an authorised body which shall issue a requalifi cation certifi cate. To avoid damage to the installation, the hydraulic test is not required.

5/ Inspection of reversible heat pumps and air-conditioning systemsDecree 2010-349 of 31 March 2010

The inspection shall include documentary controls and an assessment of system effi ciency and sizing compared with the cooling requirements of the building.

The inspection shall be performed: > by an authorised person; > at the owner's initiative; > at least every 5 years.

In case of replacement, the new equipment shall be inspected in the calendar year following replacement.

Technical instructionsfor Operation & Maintenance

7MARK-NOT_20.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

D. Specifi c maintenance recommendations

1/ Heat exchangers cleaningClean them using a bristle scrub brush, a vacuum or a compressed air jet if necessary. Rinse with cold and low pressure water, avoiding spatters on the fan motor. Clean in counter fl ow of the air fl ow way.Increase cleaning frequency if the equipment is exposed to corrosive/saline atmospheres.

2/ FiltrationPoor fi ltration or signifi cant fouling can affect unit effi ciency and damage the refrigeration circuit.

Nota:Filters can be cleaned 2 or 3 times. Beyond 3 regenerations, fi ltration performance is dramatically reduced.Filters should not be regenerated more than three times.If a fi lter cannot be regenerated, replace it.

• Metal fi lters regeneration > Clean the fi lter with warm water and liquid detergent. > Rinse thoroughly and dry using compressed air or air current. > Re-treat fi lter media with "fi lter-coat" or a similar product, to restore original performance. > Check that fi ltering elements are correctly installed when reassembling.

3/ Air fl ow rates control

Insuffi cient air fl ow rates can have several consequences: > The compressor operates out of the permitted operating range.

Ü Risk of compressor breakage > Heat from auxiliary heaters is not evacuated.

Ü Risk of fi re alarm > The setpoints are not reached.

Ü Lower heating capacity

In case of insuffi cient air fl ow rates: > Check supply air dampers operation > Check fi lters for fouling > Check exchangers for fouling > Check air ducts (fi re dampers, fouling in ducts, cone connectors)

Technical instructionsfor Operation & Maintenance

8MARK-NOT_xx.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

4/ Particularities of corrosive/saline atmospheres > Check and clean fans monthly. > Clean heat exchangers with clear water monthly.

5/ Actuating detector control > Operation must be controlled periodically, according to regulations applicable to the building. > For type 1 detectors (S6), the secondary source must be controlled every 3 months by holding the "secondary source test" button for at least 5 seconds. > The power indicator should remain lit. > Perform a functional test using an aerosol smoke detector tester. Follow manufacturer's instructions.

E. Starting / Stopping the unit

1/ Unit temporary shutdown > Stop the unit. > Do not shut off power to the compressor crankcase heater (if applicable) if the unit is installed in an area where the temperature is likely to fall below 0°C and if this operation is not handled automatically.

2/ Start-up after temporary shutdownNo special precautions are required. To start the unit, reverse the procedure outlined in Unit temporary shutdown, p. 8.

3/ Unit seasonal shutdown > If the heat pump includes water circuits, drain them. Also drain the connection lines if the unit is installed in an area where the temperature is likely to fall below 0°C. > Open the main power switch. Remove the fuse block or lock the main switch in opened position.

4/ Seasonal start-up > Perform annual maintenance operations according to Maintenance Intervals, p. 3. > Fill the water circuits and bleed the air out as necessary. > Control refrigeration circuit tightness. > Switch on the main power switch. > Acknowledge faults on the detection station, if applicable. > Allow the compressor crankcase heaters to preheat (72 hours), if applicable. > Start the system. > Check operation of all interconnected devices. > Check compressors oil level and refrigeration circuit(s) operating pressures after 15 to 20 minutes of operation.

Technical instructionsfor Operation & Maintenance

9MARK-NOT_20.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

5/ Generating set - EJP (peak load reduction)Equipment that can be powered by a generating set must be correctly stopped at each switch in power supply (mains <-> generating set).This can be managed manually, by dry contact or from the BMS (EJP switch).

Failure to comply with this recommendation could result in major damage to the unit or causecomponents to break (electrical components, compressors). In such circumstances, components are not covered by ETT guarantee.

F. Controller operation

1/ Starting or stopping the unit

Press and hold the ENTER key for 5 seconds.

2/ Acknowledging faults

Press the ALARM key to view the fault.

Correct the fault on the corresponding component (reset smoke detector, fi re thermostat or frost

protection, thermal protection, etc.).

Press and hold the ALARM key for 5 seconds to acknowledge the fault.

3/ Access level 0 - User settingsAccess to menus: - Setpoints - Operating schedule - Alarms history - System information

Hold the UP and DOWN arrow keys simultaneously for 2 seconds.Nota: No password

Use the UP and DOWN arrow keys to scroll through menus.

Press the ENTER key to enter the selected menu.

Use the UP and DOWN arrow keys to scroll through screens.

Press the ENTER key to access mask setpoints.

Use the UP and DOWN arrow keys to select the setpoint to edit.

Press the ENTER key to access the setpoint.

Use the UP and DOWN arrow keys to adjust the setpoint.

Press the ESC key to return to the main screen.

Technical instructionsfor Operation & Maintenance

10MARK-NOT_xx.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

4/ Access level 1 - MaintenanceAccess to menus: - Level 0 - Inputs/Outputs - Meters - BMS communication

Hold the UP and DOWN arrow keys simultaneously for 2 seconds.Password, valid for one calendar year = 1 to 99, to be obtained from ETT Services.

Use the UP and DOWN arrow keys to scroll through menus.

Press the ENTER key to enter the selected menu.

Use the UP and DOWN arrow keys to scroll through screens.

Press the ENTER key to access mask setpoints.

Use the UP and DOWN arrow keys to select the setpoint to edit.

Press the ENTER key to access the setpoint.

Use the UP and DOWN arrow keys to adjust the setpoint.

Press the ESC key to return to the main screen.

G. Diagnostics and troubleshooting support

1/ Smoke fault

Possible reasons Corrective actions

Smoke detection

- Check for smoke or dust - Clean detector head - Replace detector head - Acknowledge the fault (See Acknowledging faults, p. 9)

Fouled detector head

- Check for smoke or dust - Clean detector head - Replace detector head - Acknowledge the fault (See Acknowledging faults, p. 9)

Battery back-up - Replace battery

Technical instructionsfor Operation & Maintenance

11MARK-NOT_20.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

2/ Filter fault

Possible reasons Corrective actions

Fouled fi lters - Clean fi lters - Replace fi lters

Fouled exchangers - Clean exchangers according to the recommendations

3/ Air fl ow fault

Possible reasons Corrective actions

Fouled fi lters - Clean fi lters - Replace fi lters

Leakage on air network - Repair air distribution network

Fouled air network - Clean air distribution network

Blocked pressure tap on fan - Check transparent tubes for water - With textile ducting, check cone diffusers

4/ Fire fault

Possible reasons Corrective actions

Insuffi cient air fl ow - Check fi lters - Check fan

Faulty thermostat - Check thermostat

5/ Antifreeze fault

Possible reasons Corrective actions

Insuffi cient air fl ow - Check fi lters - Check fan

Faulty thermostat - Check thermostat

Lack of hot water - Check boiler house and pumpNota: Water must keep fl owing in the hot water coil circuit.

6/ Supply air fan fault

Possible reasons Corrective actions

Drive fault - Check the type of fault on the maintenance terminal.

Nota: Switch off the power supply, wait for 2 minutes then switch it on again. If the fault persists, consult ETT Services.

Technical instructionsfor Operation & Maintenance

12MARK-NOT_xx.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

7/ Low pressure fault

Possible reasons Corrective actions

Poor air fl ow - Refer to Air fl ow fault, p. 11

Low pressure switch malfunction - Check low pressure switch parameters - Check LP probe connections

Fouled fi lters - Clean fi lters - Replace fi lters

Expansion valve malfunction - Check expansion valve (status, settings, operation) - Check overheating control parameters

Ineffi cient defrosting - Check refrigeration circuit probes - Check 4-way valve - Check defrost settings

Refrigerant charge problem - Leakage checking

8/ High pressure fault

Possible reasons Corrective actions

Poor air fl ow - Refer to Air fl ow fault, p. 11

High pressure switch malfunction - Check pressure switch operation - Check pressure switch connections

Fouled fi lters - Clean fi lters - Replace fi lters

Outside T° out of application range - The unit is not designed to operate in such conditions.

Poor air distribution - Check air distribution network

9/ Refrigeration circuit fault

9.1/ The compressor does not start.

Possible reasons Corrective actions

Electrical protection faults - Check protections

Control security - Check control parameters - Check securities - Reset controller if authorised

Abnormal supply voltage - Check phases - Check voltage drop at unit start-up - Check power supply chain (wire, connections, contactors, etc.)

Fan fault - Check fans

Technical instructionsfor Operation & Maintenance

13MARK-NOT_20.00-EN

ETT may change equipment’s data & design without prior notice.Specifi cations given in this document are for information only and are not contractual.

9.2/ The compressor stops.

Possible reasons Corrective actions

Low pressure fault - Refer to Low pressure fault, p. 12

High pressure fault - Refer to High pressure fault, p. 12

Ipsotherm fault - Check ipsotherm probe, if applicable - Check fi lters for fouling

Thermal fault - Check compressor's absorbed current - Check voltage drop at start-up

Power supply chain interruption - Check power supply chain (wire, connections, contactors, etc.).

Fan fault - Check fans

9.3/ The compressor is noisy.

Possible reasons Corrective actions

Knocks - Check compressor suction pressure

Slugging - Check charge (subcooling) - Check superheat - Check overheating control probe fastening

Grunts - Check supply voltage - Check phases - Galling → broken part

9.4/ The compressor does not stop.

Possible reasons Corrective actions

Temperature setpoint too far from recommended temperatures - Check temperature setpoints

Stuck contactor - Check contactor

9.5/ Lack of capacity.

Possible reasons Corrective actions

Evaporation temperature too low - Check overheating control parameters - Check charge

Severe overheating - Check overheating control parameters - Check charge - Check fl ow rates (Refer to Air fl ow fault, p. 11)

Pre-expansion - Check drier fi lter

Wrong fl ow rates - Check fl ow rates (Refer to Air fl ow fault, p. 11) - Check setpoints

www.ett.fr

Reference: MARK-NOT_20.00-EN56 Route de Brest - BP26 - 29830 PLOUDALMEZEAU - FranceTel: +33 (0)2 98 48 14 22 - Fax: +33 (0)2 98 48 09 12Export Contact: +33 (0)2 98 48 00 70 - ETT Services: +33 (0)2 98 48 02 22

Des

ign:

ETT

- D

ocum

ent p

rinte

d b

y an

env

ironm

enta

lly fr

iend

ly p

rinte

r usin

g ve

geta

ble-

base

d in

ks o

n PE

FC p

aper

cre

ated

from

sust

aina

bly-

man

aged

fore

sts.

A different c l imateEnvironmental control solutions

Énergie Transfert Thermique