CC1N7105en 17.04.2018 Building Technologies 7 105 Burner controls LME7... The burner control LME7... is a microprocessor-based unit with matching system components for the control and supervision of forced draft burners of medium to high capacity. The LME7… and this Data Sheet are intended for use by OEMs which integrate the LME7... in their products. Use LME7… are used for the startup and supervision of multistage or modulating forced draft burners and atmospheric gas burners in intermittent operation The fuel-air ratio can be set either via an air damper actuator - acting on mechanical or pneumatic ratio control - or via pulse width modulated fans and pneumatic ratio control. The flame supervision supervised with ionization probe and with UV flame detector QRA2..., QRA4... or QRA10.... Applications in accordance with EN 267: Gas burners for liquid fuels Applications in accordance with EN 676: Automatic forced draft burners for gaseous fuels Applications in accordance with EN 746-2: Industrial thermoprocessing equipment - Part 2: Safety requirements for combustion and fuel handling systems Type-tested and approved in accordance with DIN EN 298 Notes Caution! All safety, warning and technical notes given in the Basic Documentation of the LME7… (P7105) also apply to this document! If not observed, there is a risk that safety functions will be impaired and that a risk of electric shock will exist!

Siemens LME7 Burner Control Technical Documentation

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Siemens LME7 Burner Control Technical Documentation

CC1N7105en17.04.2018

Building Technologies

7105

Burner controls LME7...The burner control LME7... is a microprocessor-based unit with matching systemcomponents for the control and supervision of forced draft burners of medium tohigh capacity.

The LME7… and this Data Sheet are intended for use by OEMs which integratethe LME7... in their products.

UseLME7… are used for the startup and supervision of multistage or modulating forceddraft burners and atmospheric gas burners in intermittent operation

The fuel-air ratio can be set either via an air damper actuator - acting on mechanical orpneumatic ratio control - or via pulse width modulated fans and pneumatic ratio control.

The flame supervision supervised with ionization probe and with UV flame detectorQRA2..., QRA4... or QRA10....∂ Applications in accordance with EN 267: Gas burners for liquid fuels∂ Applications in accordance with EN 676: Automatic forced draft burners for

gaseous fuels∂ Applications in accordance with EN 746-2: Industrial thermoprocessing equipment -

Part 2: Safety requirements for combustion and fuel handling systems∂ Type-tested and approved in accordance with DIN EN 298

Notes

Caution!All safety, warning and technical notes given in the Basic Documentation of theLME7… (P7105) also apply to this document! If not observed, there is a risk thatsafety functions will be impaired and that a risk of electric shock will exist!

Page 2: Siemens LME7 Burner Control Technical Documentation

2/38

Building Technologies CC1N7105en17.04.2018

Features- Undervoltage detection- Electrical remote reset facility- Accurate control times thanks to digital signal handling- Multicolor indication of fault status and operating state messages- Air pressure supervision with function check of air pressure switch during start and

operation- Repetition limitation- Controlled intermittent operation after max. 24 hours of continuous operation (can

be parameterized via parameter 239) (depending on type of program modulePME7)

- BCI- Unit parameter adjustable either via display or PC software ACS410- Connection for program module PME...

Only LME71.../LME73...:- Indication of program sequence

Integrated in the basic unit LME7... are:∂ Burner control∂ BCI for connection a display or PC∂ Lockout reset button (info button)∂ 3 multi color signal lamp LED for operations and fault notifications∂ Optional: Analog inputs for load controller DC 0...10 V, DC 0/4...20 mA, 0...135 Ω∂ Interface for program module

Only LME71.../LME73...:∂ Optional: 3 x 7 segment display for fault and state information's and parameter

display∂ Control for one actuator

Page 3: Siemens LME7 Burner Control Technical Documentation

3/38

Building Technologies CC1N7105en17.04.2018

Supplementary documentation

Product type Type of documentation Documentation numberPME71.111 User Documentation A7105.1

PME71.112 User Documentation A7105.2

PME71.401 User Documentation A7105.3

PME71.402 User Documentation A7105.4

PME71.901 User Documentation A7105.5

PME72.521 *) User Documentation A7105.11

PME72.541 *) User Documentation A7105.12

PME73.810 User Documentation A7105.21

PME73.811 User Documentation A7105.22

PME73.812 User Documentation A7105.23

PME73.820 User Documentation A7105.24

PME73.830 User Documentation A7105.25

PME73.831 User Documentation A7105.26

PME73.840 User Documentation A7105.27

LME73.000 / PME73.840 User Documentation A7105.28

LME Environmental Product Declaration E7105

LME Product Overview Q7101

LME7 Basic Documentation P7105

PME Environmental Product Declaration E7105.1*) Only on request

Page 4: Siemens LME7 Burner Control Technical Documentation

4/38

Building Technologies CC1N7105en17.04.2018

Standards and certificates

Applied directives:∂ Low-voltage directive 2014/35/EC∂ Directive for pressure devices 2014/68/EC∂ Gas Appliances Regulation (EU) 2016/426∂ Electromagnetic compatibility EMC (immunity) *) 2014/30/EC

*) The compliance with EMC emission requirements must be checked after the burner control is installed in equipment

Compliance with the regulations of the applied directives is verified by the adherence tothe following standards / regulations:∂ Automatic burner control systems for burners and appliances

burning gaseous or liquid fuelsDIN EN 298

∂ Safety and control devices for gas burners and gasburning appliances - Valve proving systems for automaticshut-off valves

DIN EN 1643

∂ Safety and control devices for burners and appliancesburning gaseous and/or liquid fuels — General requirements

DIN EN 13611

∂ Automatic electrical controls for household and similar usePart 2-5:Special requirements on automatic electric burner control andmonitoring systems

DIN EN 60730-2-5

The relevant valid edition of the standards can be found in the declaration ofconformity!

Β Note on DIN EN 60335-2-102Household and similar electrical appliances - Safety - Part 2-102:Particular requirements for gas, oil and solid-fuel burning appliances having electricalconnections. The electrical connections of the LME7 and the PME7 comply with therequirements of EN 60335-2-102.

EAC Conformity mark (Eurasian Conformity mark)

ISO 9001:2015ISO 14001:2015OHSAS 18001:2007

China RoHSHazardous substances table:http://www.siemens.com/download?A6V10883536

Only AC 120 V versions

Page 5: Siemens LME7 Burner Control Technical Documentation

5/38

Building Technologies CC1N7105en17.04.2018

Life cycleThe burner control LME7... has a designed lifetime* of 250,000 burner startup cycleswhich, under normal operating conditions in heating mode, correspond to approx. 10years of usage (starting from the production date given on the type field).This lifetime is based on the endurance tests in the standard EN 298.A summary of the conditions has been published by the European ControlManufacturers Association (Afecor) (www.afecor.org).

The designed lifetime is based on use of the burner controls according to themanufacturer’s Data Sheet and Basic Documentation. After reaching the designedlifetime in terms of the number of burner startup cycles, or the respective time of usage,the burner control is to be replaced by authorized personnel.

* The designed lifetime is not the warranty time specified in the Terms of Delivery

System overview

The diagram shows the full scope of functions of the LME7… system. The correctfunctions are to be determined based on the respective execution/configuration.

Page 6: Siemens LME7 Burner Control Technical Documentation

6/38

Building Technologies CC1N7105en17.04.2018

Type summary

LME7...Parameterized burner control for the supervision ofmultistage or modulating oil/gas forced draft burners andatmospheric burners of medium to higher capacity, inintermittent operation. With controlled air damper control.See Basic Documentation P7105

Article no.

BP

Z:LM

E71

.000

A1

BP

Z:LM

E71

.000

A2

BP

Z:LM

E72

.000

A2

*)

BP

Z:LM

E73

.000

A1

BP

Z:LM

E73

.000

A2

Type

LME

71.0

00A

1

LME

71.0

00A

2

LME

72.0

00A

2*)

LME

73.0

00A

1

LME

73.0

00A

2

Mains voltage AC 120 V ● --- --- ● ---

Mains voltage AC 230 V --- ● ● --- ●Gas pressure switch-min/POC ● ● ● ● ●Pressure switch valve proving ● ● ● ● ●Air pressure switch ● ● ● ● ●Ionization probe ● ● ● ● ●QRA2... / QRA4... / QRA10... ● ● ● ● ●Load controller analog input signal (0...10 V, 4...20 mA, 0...135 ς) ● ● --- ● ●Load controller input 3-position step input/2-stage ● ● ● ● ●Output actuator control --- --- ● ● ●Input feedback for actuator with potentiometer 0...1 kς --- --- --- ● ●Output PWM control ● ● ● ● ●Onboard LED 7-segment display ● ● --- ● ●BCI bus for AZL2... ● ● ● ● ●

*) On request

Burner control

Page 7: Siemens LME7 Burner Control Technical Documentation

7/38

Building Technologies CC1N7105en17.04.2018

Accessories (must be ordered separately)

PME7...Program module for LME7...With program sequences oil or gas burners for basic unitLME7...See Basic Documentation P7105

PME7... with mains voltage AC 120 V

Article no.

BP

Z:P

ME

71.1

11A

1

BP

Z:P

ME

71.1

12A

1

BP

Z:P

ME

71.4

01A

1

BP

Z:P

ME

71.4

02A

1

BP

Z:P

ME

71.9

01A

1

BP

Z:P

ME

73.8

10A

1

BP

Z:P

ME

73.8

11A

1

BP

Z:P

ME

73.8

12A

1

BP

Z:P

ME

73.8

20A

1

BP

Z:P

ME

73.8

30A

1

BP

Z:P

ME

73.8

31A

1

BP

Z:P

ME

73.8

40A

1

Type

PM

E71

.111

A1

PM

E71

.112

A1

PM

E71

.401

A1

PM

E71

.402

A1

PM

E71

.901

A1

PM

E73

.810

A1

PM

E73

.811

A1

PM

E73

.812

A1

PM

E73

.820

A1

PM

E73

.830

A1

PM

E73

.831

A1

PM

E73

.840

A1

Mains voltage AC 120 V ● ● ● ● ● ● ● ● ● ● ● ●For use with LME71.000A... ● ● ● ● ● --- --- --- --- --- --- ---

For use with LME72.000A... --- --- --- --- --- --- --- --- --- --- --- ---For use with LME73.000A... --- --- --- --- --- ● ● ● ● ● ● ●Gas program forced draft burner ● --- ● ● ● ● ● ● ● ● ● ●Gas program atmospheric burner --- ● --- --- --- --- --- --- --- --- --- ---

1-stage or 1-stage modulating ● ● ● ● ● ● ● ● ● ● ● ●2-stage or 1-stage modulating --- --- ● ● ● ● --- --- ● ● ● ●Pilot burner simultaneously/alternately ● ● --- ● --- --- ● ● --- ● ● ●Modulating via actuator (pneumatic ormechanic gas-air ratio control)

--- --- --- --- --- ● ● ● ● ● ● ●

Modulating via PWM fan (pneumatic ormechanic gas-air ratio control)

--- --- --- --- ● --- --- --- --- --- --- ---

Fan speed control/control via analog signal/3-position step signal

--- --- --- --- ● --- --- --- --- --- --- ---

Actuator control via analog signal/3-positionstep signal for actuator with potentiometer

--- --- --- --- --- ● ● ● --- ● ● ---

3-position signal for actuator withoutpotentiometer

--- --- --- --- --- --- --- --- ● --- ● ●

Control sequence programmable time ● ● ● ● ● ● ● ● ● ● ● ●POC ● ● ● ● ● ● ● ● ● ● --- ●Valve proving --- --- --- --- ● ● ● --- ● ● ● ●Input valve proving ON/Off --- --- --- --- --- --- --- --- --- --- ● ---

Program module

Page 8: Siemens LME7 Burner Control Technical Documentation

8/38

Building Technologies CC1N7105en17.04.2018

Accessories (must be ordered separately) (cont'd)

PME7... with mains voltage AC 230 V

Article no.

BP

Z:P

ME

71.1

11A

2

BP

Z:P

ME

71.1

12A

2

BP

Z:P

ME

71.4

01A

2

BP

Z:P

ME

71.4

02A

2

BP

Z:P

ME

71.9

01A

2

BP

Z:P

ME

72.5

21A

2*)

BP

Z:P

ME

72.5

41A

2*)

BP

Z:P

ME

73.8

10A

2

BP

Z:P

ME

73.8

11A

2

BP

Z:P

ME

73.8

12A

2

BP

Z:P

ME

73.8

20A

2

BP

Z:P

ME

73.8

30A

2

BP

Z:P

ME

73.8

31A

2

BP

Z:P

ME

73.8

40A

2

TypeP

ME

71.1

11A

2

PM

E71

.112

A2

PM

E71

.401

A2

PM

E71

.402

A2

PM

E71

.901

A2

PM

E72

.521

A2

*)

PM

E72

.541

A2

*)

PM

E73

.810

A2

PM

E73

.811

A2

PM

E73

.812

A2

PM

E73

.820

A2

PM

E73

.830

A2

PM

E73

.831

A2

PM

E73

.840

A2

Mains voltage AC 230 V ● ● ● ● ● ● ● ● ● ● ● ● ● ●For use with LME71.000A... ● ● ● ● ● --- --- --- --- --- --- --- --- ---

For use with LME72.000A... --- --- --- --- --- ● ● --- --- --- --- --- --- ---

For use with LME73.000A... --- --- --- --- --- --- --- ● ● ● ● ● ● ●Gas program forced draft burner ● --- ● ● ● ● ● ● ● ● ● ● ● ●Gas program atmospheric burner --- ● --- --- --- --- --- --- --- --- --- --- --- ---

1-stage or 1-stage modulating ● ● ● ● ● ● ● ● ● ● ● ● ● ●2-stage or 1-stage modulating --- --- ● ● ● ● ● ● --- --- ● ● ● ●Pilot burner simultaneously/alternately --- --- --- ● --- --- ● --- ● ● --- ● ● ●Modulating via actuator (pneumatic ormechanic gas-air ratio control)

--- --- --- --- --- ● ● ● ● ● ● ● ● ●

Modulating via PWM fan (pneumatic ormechanic gas-air ratio control)

--- --- --- --- ● --- --- --- --- --- --- --- --- ---

Fan speed control/control via analogsignal/3-position step signal

--- --- --- --- ● --- --- --- --- --- --- --- --- ---

Actuator control via analog signal/3-position step signal for actuator withpotentiometer

--- --- --- --- --- --- --- ● ● ● --- ● ● ---

3-position signal for actuator withoutpotentiometer

--- --- --- --- --- ● ● --- --- --- ● --- ● ●

Control sequence programmable time ● ● ● ● ● --- --- ● ● ● ● ● ● ●POC ● ● ● ● ● ● ● ● ● ● ● ● --- ●Valve proving --- --- --- --- ● --- --- ● ● --- ● ● ● ●Input valve proving ON/Off --- --- --- --- --- --- --- --- --- --- --- --- ● ---

*) Only on request

Page 9: Siemens LME7 Burner Control Technical Documentation

9/38

Building Technologies CC1N7105en17.04.2018

Accessories (must be ordered separately) (cont´d)

AZL21.00x9Article no.: BPZ:AZL21.00x9Display and operating unit, detached, choice of mountingmethods with LCD, 8-digit, 5 buttons, BCI for LME7...,degree of protection IP40.See Data Sheet N7542

AZL23.00x9Article no.: BPZ:AZL23.00x9Display and operating unit, detached, choice of mountingmethods with LCD, 8-digit, 5 buttons, BCI for LME7...,degree of protection IP54.See Data Sheet N7542

Built-in in the LME7...3-colored LED, reset button (info button), 3 other buttons foroperation in connection with 3 x 7-segment display

AGV50.100Article no.: BPZ:AGV50.100Signal cable for AZL2..., with RJ11 connector,cable length 1 m, pack of 10

QRA2…UV flame detector for the supervision of gas flames and yellow-/blue-burning oil flames and for ignition spark proving. Plasticinsulated housing, metalized to prevent static charging causedby the air flow from the fan, lateral illumination.See Data Sheet N7712

QRA4...UV flame detector for the supervision of gas flames and yellow-/blue-burning oil flames and for ignition spark proving, metalhousing, and frontal illumination.See Data Sheet N7711

QRA10…UV flame detector for supervision of gas flames and yellow-/blue-burning oil flames and for ignition spark proving. Die-castaluminum housing with a 1 in. mounting coupling andconnection facility for cooling air.See Data Sheet N7712

Ionization probeTo be provided on site

Display/operating unitsand accessories

Flame detectors

Page 10: Siemens LME7 Burner Control Technical Documentation

10/38

Building Technologies CC1N7105en17.04.2018

Accessories (must be ordered separately) (cont´d)

SQN3…Electromotoric actuators for use with air dampers and controlvalves of oil or gas burners of small to medium capacity.

Holding torque/running time 0,8 Nm/4,5 sup to 3 Nm/30 s

See Data Sheet N7808

SQN7…Electromotoric actuators for air dampers and control valves ofoil and gas burners of small to medium capacity.

Holding torque/running time 0,7 Nm/4 sup to 2,5 Nm/30 s

See Data Sheet N7804

SQM40…/SQM41...Electromotoric actuators for air dampers and control valvesof oil and gas burners of medium to high capacity, with UL-registered.

Holding torque / running time 5 Nm/15 sup to 10 Nm/30 s

See Data Sheet N7817

SQM5...Electromotoric actuators for air dampers and control valvesof oil and gas burners of medium to high capacity, with UL-registered.

Holding torque/running time 10 Nm/15 sup to 40 Nm/60 s

See Data Sheet N7815

QPLx5…The pressure switch is used for monitoring of gas or airpressure.See Data Sheet N7221

Dummy plugFor 6-pole modulating connector (RJ11)Supplier recommendation: Molex,order number: 085 999 3256

Actuators

Pressure switch

Dummy plug for RJ11

Page 11: Siemens LME7 Burner Control Technical Documentation

11/38

Building Technologies CC1N7105en17.04.2018

Accessories (must be ordered separately) (cont´d)

AGG3.710Article no.: BPZ:AGG3.710Connector set completeRAST5 and RAST3.5Single packsSee object list C7105 (74 319 0642 0)

Example: X5-03

AGG3.720Article no.: BPZ:AGG3.72010 standard connector set completeRAST5 and RAST3.5Packing in bags of 10 pieces each connector type.See object list C7105 (74 319 0642 0)

AGG9.xxxThe individual connectors are supplied in packaging units of200 pieces each.

Example: X5-03

Article no. Type Type of connector TerminalBPZ:AGG9.201 AGG9.201 RAST5 X2-09BBPZ:AGG9.203 AGG9.203 RAST5 X3-02BPZ:AGG9.209 AGG9.209 RAST5 X10-06BPZ:AGG9.301 AGG9.301 RAST5 X2-01BPZ:AGG9.302 AGG9.302 RAST5 X2-03BPZ:AGG9.304 AGG9.304 RAST5 X4-02BPZ:AGG9.306 AGG9.306 RAST5 X5-01BPZ:AGG9.309 AGG9.309 RAST5 X6-03BPZ:AGG9.310 AGG9.310 RAST5 X7-01BPZ:AGG9.311 AGG9.311 RAST5 X7-02BPZ:AGG9.313 AGG9.313 RAST5 X9-04BPZ:AGG9.401 AGG9.401 RAST5 X2-02BPZ:AGG9.403 AGG9.403 RAST5 X5-03BPZ:AGG9.405 AGG9.405 RAST5 X7-04BPZ:AGG9.501 AGG9.501 RAST5 X3-04BPZ:AGG9.504 AGG9.504 RAST5 X10-05BPZ:AGG9.601 AGG9.601 RAST5 X2-09ABPZ:AGG9.822 AGG9.822 RAST3,5 2-poleBPZ:AGG9.831 AGG9.831 RAST3,5 3-poleBPZ:AGG9.841 AGG9.841 RAST3,5 4-pole

Connector set forLME7...

Page 12: Siemens LME7 Burner Control Technical Documentation

12/38

Building Technologies CC1N7105en17.04.2018

Accessories (must be ordered separately) (cont´d)

OCI410Article no.: BPZ:OCI410Interface between burner control and PCFacilitates viewing, handling and recording setting parameterson site in connection with the PC software ACS410.See Data Sheet N7616

ACS410Article no.: BPZ:ACS410PC software for setting the parameters and for visualizing theburner controls.See Software Documentation J7352

Service tools

Page 13: Siemens LME7 Burner Control Technical Documentation

13/38

Building Technologies CC1N7105en17.04.2018

Technical data

Mains voltage AC 120 V AC 230 VMains frequency 50/60 Hz 50/60 HzExternal primary fuse Max. 6.3 A (slow) Max. 6.3 A (slow)Power consumption <10 W, typical <10 W, typicalSafety class I In accordance with DIN EN 60730-1Degree of protection IP00

Β Note:The burner or boilermanufacturer must ensuredegree of protection IP40 forburner controls as perDIN EN 60529 throughadequate installation of theLME7...

Rated surge voltagecategory III (DIN EN 60664)∂ LME7 total unit 4 kV∂ Creepage distances or air gaps 2.5 kV due to voltage limitation

measuresDegree of contamination 2 in accordance with DIN EN 60730-1Software class Class C in accordance with DIN EN

60730-2-5:20112-channel structure

Reaction time in the event of loss offlame

Max. 1 s

Perm. mounting position OptionalWeight Approx. 490 g

Basic unit LME7...

General

Page 14: Siemens LME7 Burner Control Technical Documentation

14/38

Building Technologies CC1N7105en17.04.2018

Technical data (cont’d)

Mains voltage: Input current depending on the operating state of the unitUnder voltage UMains 120 V UMains 230 V∂ Safety shutdown from the operating

position takes place should mainsvoltage drop

≤AC 75 V ≤AC 165 V

∂ Restart is initiated when mainsvoltage exceeds

≥AC 100 V ≥AC 195 V

State inputs, temperature controller, temperature switch, load controller, pressureswitch, air pressure switch, actuator (except safety loop) of the contact feedbacknetwork are used for system supervision and require mains-related input voltage∂ Input safety loop See Terminal rating outputs∂ Input currents and input voltages

- UeMax UN +10% UN +10%- UeMin UN -15% UN -15%- IeMax 1.5 mA peak

(peak value)1 mA peak(peak value)

- IeMin 0.8 mA peak(peak value)

0.5 mA peak(peak value)

∂ Contact material recommended forexternal signal sources (air pressureswitch, pressure switch-min,pressure switch-max, etc.)

Gold-plated silver contacts

∂ Transition/settling behavior/bounce- Perm. bounce time of contacts when switching ON/OFF Max. 50 ms

(after the bounce time, the contact muststay closed or open)

∂ UN AC 120 V AC 230 V∂ Voltage detection

- ON >AC 60 V >AC 120 V- OFF <AC 40 V <AC 80 V

Analog input X65 DC 0...10 V/DC 0/4...20 mA/0...135 Ω

Terminal ratingInputs

Page 15: Siemens LME7 Burner Control Technical Documentation

15/38

Building Technologies CC1N7105en17.04.2018

Technical data (cont´d)

Total contact loading:∂ Rated voltage AC 120 V

50/60 HzAC 230 V50/60 Hz

∂ Unit input current X3-04 (safetyloop) from:- Fan motor contactor- Ignition transformer- Fuel valves

Max. 5 A Max. 5 A

Individual contact loading:Fan motor X2-01 pin 3∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Rated current 2 A

(15 A max. 0.5 s)2 A(15 A for max. 0.5s)

∂ Power factor Cosι ″0.4 Cosι ″0.4Alarm output X2-03 pin 3∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Rated current 1 A 1 A∂ Power factor Cosι ″0,6 Cosι ″0,6Ignition transformer X4-02 pin 3∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Rated current 2 A 2 A∂ Power factor Cosι ″0.4 Cosι ″0.4Output relay contact K2/2 terminal X2-09 pin 7 (auxiliary output)∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Rated current 1 A 1 A∂ Power factor Cosι ″0.4 Cosι ″0.4Fuel valves/pilot valve X7-01 pin 3∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Rated current 1 A 1 A∂ Power factor Cosι ″0.4 Cosι ″0.4Fuel valves 1 X7-04 pin 4/fuel valve 2 X7-02 pin 3∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Rated current

- Valve proving inactive2 A 2 A

- Valve proving active 1 A 1 A∂ Power factor Cosι ″0.4 Cosι ″0.4

Β Note:When activating valve proving (e.g. on shutdown), the load on the valveterminals is restricted. If the load is not reduced, the design lifetime is about100,000 burner start cycles!

Safety loop X3-04 pin 2, safety valve X6-03 pin 3, POC or connection PWM motorX2-02 pin 3∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Total current 2 A 2 A∂ Power factor Cosι ″0.4 Cosι ″0.4

Caution!Maximum permissible current load may be exceeded!If terminal X2-02 pin 3 is used as the connection for supplying the PWMmotor, no other motor may be connected on terminal X2-01 pin 3.

Terminal rating Outputs

Page 16: Siemens LME7 Burner Control Technical Documentation

16/38

Building Technologies CC1N7105en17.04.2018

Technical data (cont´d)Mains supply line Max. 100 m (100 pF/m)Display, BCI For use under the burner hood or in a

control panelMax. 1 m (100 pF/m), unshielded

Load controller X5-03 Max. 30 m (100 pF/m) unshieldedSafety Loop Max. 30 m (100 pF/m), unshieldedSafety valve Max. 30 m (100 pF/m), unshieldedFuel valve Max. 30 m (100 pF/m), unshieldedIgnition transformer Max. 30 m (100 pF/m), unshieldedRemote reset (lay separate cable) Max. 30 m (100 pF/m), unshieldedOther lines Max. 30 m (100 pF/m), unshielded

Specification as per EN 60730-1Type of shutdown or interruption of each circuitShutdown with microswitch 1 poleMode of operation Type 2 B

CLOSE/ignition position/OPENX2-09 pin 1, X2-09 pin 2, X2-09 pin 3

1 mio. switchingcycles

1 mio. switchingcycles

∂ Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Rated current 0,1 A 0,1 A∂ Power factor Cosι ″0,6 Cosι ″0,6Output K2/2 X2-09 pin 7 AC 120 V 50/60 Hz AC 230 V 50/60 Hz∂ Nominal current Max. 1 A Max. 1 A∂ Power factor Cosι >0.4 Cosι >0.4Feedback via input X2-09 pin 8 on the LME depending on the current load of theactuator switching contact used (e.g. cam V2)!

The cross-sectional areas of the mains power lines (L, N, and PE) and, if required, thesafety loop (safety limit thermostat, water shortage, etc.) must be sized for ratedcurrents according to the selected external primary fuse.The cross-sectional areas of the other cables must be sized in accordance with theinternal unit fuse (max. 6.3 AT).

Min. cross-sectional area 0.75 mm²(single- or multicore to VDE 0100)

Cable insulation must be suited for the respective temperature and environmentalconditions!

Cable lengths

Actuators

Cross-sectional areas

Page 17: Siemens LME7 Burner Control Technical Documentation

17/38

Building Technologies CC1N7105en17.04.2018

Technical data (cont´d)

Insertion force / contact ′4 NWithdrawal force / contact ″1 NTightening torque / screw 0.5 Nm in accordance with DIN EN

60335-1Contacting with flat pin connector 6.3 x 0.8 mm in accordance with DIN EN

46244Male multipoint connector to RAST5standard

Connection cross-sections conductor screw connection∂ Stranded conductor Cross-section max. 2.5 mm²∂ Stranded conductor with ferrule Cross-section max. 2.5 mm²∂ Stripping length Approx. 8 mm

Connection cross-sections conductor screw connection∂ Stranded conductor fine-wired

(flexible)Cross-sectionMin. 0,14 mm²Max. 1,5 mm²

∂ Stranded conductor fine-wired(flexible) with ferrule

Cross-sectionMin. 0,25 mm²Max. 1 mm²

∂ Stripping length Approx. 7 mm∂ Tightening torque / screw 0,25 Nm

Signal cable Color whiteUnshieldedConductor 4 x 0.141 mm²With jack RJ11

Cable length AGV50.1001 m

Location Under the burner hood (arrangements forSKII EN 60730-1 additionally required)

Dummy plug For 6 pin modular plug (RJ11)Supplier Recommendation: Molex

Order no.: 085 999 3256

Storage DIN EN 60721-3-1Climatic conditions Class 1K3Mechanical conditions Class 1M2Temperature range -40...+70 °CHumidity <95% r.h.Transport DIN EN 60721-3-2Climatic conditions Class 2K3Mechanical conditions Class 2M2Temperature range -40...+70 °CHumidity <95% r.h.Operation DIN EN 60721-3-3Climatic conditions Class 3K3Mechanical conditions Class 3M2Temperature range -40...+60 °CHumidity <95% r.h.Installation altitude Max. 2,000 m above sea level

Warning!Condensation, formation of ice and ingress of water are not permitted!If not observed, there is a risk of impairment of safety functions and ofelectric shock hazard.

RAST5 connectorMechanical data

RAST3.5 connectorMechanical data

Signal cable AGV50...AZL2... ↑ BCI

Dummy plug for RJ11

Environmentalconditions

Page 18: Siemens LME7 Burner Control Technical Documentation

18/38

Building Technologies CC1N7105en17.04.2018

Technical Data (cont´d)

No-load voltage at terminal ionizationprobe (X10–05 pin 2)

AC 300 V

Warning!∂ The ionization probe must be protected against electric shock

hazard!∂ When monitoring ionization currents in earth-free mains, connect

terminal X10-05 pin 1 to burner ground

Short-circuit current Max. AC 1 mARequired detector current Min. DC 1 µA, display approx. 20%Possible detector current Max. DC 40 µA, display approx. 100%Permissible length of detector cable (laidseparately)

30 m (100 pF/m), unshielded

Β

Note:As the detector line capacitance (line length) increases, the voltage at the ionizationprobe und thus the detector current will drop. Extremely long line lengths and veryhigh-ohmic flames might necessitate the use of low-capacitance cable (e.g. ignitioncable). In spite of special electronic circuits designed to compensate possible adverseeffects of the ignition spark on the ionization current, it must be made certain that theminimum detector current required is already available during the ignition phase. Ifthis is not the case, the primary ignition transformer connections must beinterchanged and/or the electrodes relocated.

Threshold values when flame is supervised by ionization- Start prevention (extraneous light) - Intensity (parameter 954) approx. 12%- Operation - Intensity (parameter 954) approx. 13%

ION input

Ionization current in µA

Flam

ein

tens

ityin

%

100

90

80

70

60

50

40

30

20

10

0

Flame supervision withionization probe

Page 19: Siemens LME7 Burner Control Technical Documentation

19/38

Building Technologies CC1N7105en17.04.2018

Technical Data (cont´d)

Ionization probe

LME7...M

C ION

X10-05/2

X10-05/1

Legend

C Electrolytic condenser 100...470 µF; DC 10...25 VION Ionization probeM Microammeter Ri max. 5,000 ς

Warning!Simultaneous operation of QRA... and ionization probe is not permitted!If not observed, there is a risk of impairment of safety functions.

Measuring circuit fordetector currentmeasurement

Page 20: Siemens LME7 Burner Control Technical Documentation

20/38

Building Technologies CC1N7105en17.04.2018

Technical Data (cont´d)

Caution!If flame detectors QRA2… / QRA4... / QRA10... are used for flame supervisionwith the LME7..., it must be ensured that the burner control is permanentlyconnected to power (conforming to EN 298), thus enabling the system to detectflame detector failures during startup and shutdown.Generally, the system works with flame detectors QRA... in intermittentoperation. If this is not observed, there is a risk of loss of safety functions.Technical Data see Data Sheet N7712, flame detector QRA2.../QRA10…!Technical Data see Data Sheet N7711, flame detector QRA4...!

Threshold values when flame is supervised by QRA...- Start prevention (extraneous light) - Intensity (parameter 954) approx. 12%- Operation - Intensity (parameter 954) approx. 13%

Operating voltage AC 280 V ±15%Mains frequency 50...60 Hz °6%Required detector current in operation Min. 70 µAPossible detector current in operation Max. 700 µAPerm. length of detector cable(normal cable, laid separately) ¹)

Max. 100 m, unshielded

¹) Multicore cable not permitted

Flame detector QRA...

QRA...

Legend

A Exposure to lightC Electrolytic condenser 100...470 µF; DC 10...25 VM Microammeter Ri max. 5,000 ς

Warning!∂ Input QRA... is not short-circuit-proof!

Short-circuits of X10-06 pin 2 against earth can destroy the QRA... input∂ Simultaneous operation of flame detector QRA... and ionization probe is not

permitted. If not observed, there is a risk of impairment of safety functions∂ To ensure that the age of the UV tubes can be determined, the LME basic

unit must always be connected to mains supply. If this is not observed, thesafety functions may be impaired.

Flame supervision withQRA2... / QRA4... /QRA10...

Measuring circuit fordetector currentmeasurement

Page 21: Siemens LME7 Burner Control Technical Documentation

21/38

Building Technologies CC1N7105en17.04.2018

Connection diagram AGG9 connector ↑ LME71...

X56

AG

G9.

822

831

841

7105

d109

en/0

316

GND

Cod

ing

Con

nect

orm

arki

ng

NTNL

LME7

1.00

0...

LED

K7 K5 FS

V2

FSV

1

K4

K1K

2/1

DC24VoutputPWMsignaloutput

Hallsignalinput

GND

µC

BCI

Out

putf

uelv

alve

V2

Out

puta

larm

Notused

Analoginput

K2/2

+ - A

/rese

t

Not

used

Option

Not

e!*)

IfP

OC

notu

sed,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

ΒB

CI

AGG9. 310 405 304 504 209

03K34 03K66 05K37 02K43

05K30 03K57 03K105 02K02 03K54 03K30

04K77

AGG9. 302 501 309 401 301 403 203 306 313

03K15 04K22 04K01

Page 22: Siemens LME7 Burner Control Technical Documentation

22/38

Building Technologies CC1N7105en17.04.2018

Connection diagram AGG9 connector ↑ LME73...

X56

AG

G9.

822

831

841

7105

d110

en/0

316

GND

Cod

ing

Plug

mar

king

NTNL

LME7

3.00

0...

LED

K12

K11

K9

K2/

2

K7

K5 FS

V2

FSV1

K4

K1K

2/1

SA-

NL

SA-C

LOS

E

Notused

LR-IN(analog)µC

+ - A

BC

I

Out

putp

ilotv

alve

(PV

)

Out

puta

larm

Inpu

tval

vepr

ovin

g(L

T)O

N/O

FF

Out

putf

uelv

alve

(V1

/V2)

**)

GNDLRinput

5VpowersupplySignalGND

Not

activ

e

PLT

/rese

t

Valv

epr

ovin

gO

N/O

FF

Not

e!*)

Ifva

lve

prov

ing

isno

tuse

,w

irelin

kD

br1

can

beco

nnec

ted!

**)D

epen

ding

onfu

eltra

in.

Β

BC

I

03K34 03K66 05K37 02K43

05K30 03K57 03K105 02K02 03K54 03K30

04K77

AGG9. 302 501 309 401 301 403 203 306 313

03K15 04K22 04K01

03K10

AGG9. 601 201 311 310 405 304 504 209

08K24

Page 23: Siemens LME7 Burner Control Technical Documentation

23/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME71... for PME71.111...

7105

d88e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LME7

1.00

0...

LED

K2/2

K7

K5 FSV2

FSV

1

K4

K1K2

/1

X76 Notused

X66

X65

Notused

Notused

µC

+ - A

Out

puta

larm

Feed

back

inpu

tPO

C

Out

putp

ilotv

alve

PV

BCI

Dbr2fordirectignition

/rese

t

Not

activ

e

Hin

wei

s!*)

IfP

OC

isno

tuse

dan

dpa

ram

eter

237

=1,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

ΒBC

I

Page 24: Siemens LME7 Burner Control Technical Documentation

24/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME71... for PME71.112...

7105

d90e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03X2-02

04K22 04K01

Cod

ing

Plu

gm

arki

ng

NTNL

LME7

1.00

0...

LED

K2/2

K7

K5 FS

V2

FSV1

K4

K1

K2/1

X76 Notused

X66

X65

Notused

Notused

µC

+ - A

Out

puta

larm

Feed

back

inpu

tPO

C

Out

putp

ilotv

alve

PV

BC

IDbr2fordirectignition

/rese

t

Not

activ

e

Not

e!*)

IfP

OC

isno

tuse

dan

dpa

ram

eter

237

=1,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

ΒB

CI

Page 25: Siemens LME7 Burner Control Technical Documentation

25/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME71... for PME71.401...

7105

d31e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LME7

1.00

0...

LED

K7

K5 FS

V2

FSV

1

K4

K1K2

/1

X76 Notused

X66

X65

µC

BCI

Out

putf

uelv

alve

V2a

Out

puta

larm

Feed

back

inpu

tPO

C

Notused

Notused

K2/

2

+ - A

/rese

t

Not

activ

e

Not

e!*)

IfP

OC

isno

tuse

d,w

irelin

kD

BR

1m

ustb

eco

nnec

ted!

**)F

or2-

stag

eop

erat

ion

(with

outl

oad

cont

rolle

rOP

EN

),w

irelin

kD

br5

mus

tbe

conn

ecte

d!

ΒB

CI

Page 26: Siemens LME7 Burner Control Technical Documentation

26/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME71... for PME71.402...

7105

d41e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LED

K7 K5 FS

V2

FSV

1

K4

K1K2

/1

X76 Notused

X66

X65

µC

BC

I

Out

putp

ilotv

alve

PV

Out

puta

larm

Feed

back

inpu

tPO

C

Notused

Notused

K2/2

LME7

1.00

0... + - A

/rese

t

Dbr2fordirectignition

Not

e!*)

IfP

OC

notu

sed,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

Β

BC

I

Page 27: Siemens LME7 Burner Control Technical Documentation

27/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME71... for PME71.901...

7105

d56e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Con

nect

orm

arki

ng

NTNL

LME7

1.00

0...

LED

K7

K5 FS

V2

FSV

1

K4

K1K2

/1

X76

DC24VoutputPWMsignaloutput

Hallsignalinput

GND

X66

X65

µC

BCI

Out

putf

uelv

alve

V2

Out

puta

larm

Notused

Analoginput

K2/

2

+ - A

/rese

t

Not

used

Option

Not

e!*)

IfP

OC

notu

sed,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

ΒB

CI

Page 28: Siemens LME7 Burner Control Technical Documentation

28/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME72... for PME72.521...

7105

d84e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LED

K12

K11

K9K2/2

K7 K5 FS

V2

FSV

1

K4

K1K2

/1

SA-

NL

SA-C

LOS

E

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65

µC

BCI

Out

putf

uelv

alve

V2a

Out

puta

larm

Feed

back

inpu

tPO

C

Out

putf

uelv

alve

V2

Notused

Notused

Not

activ

e

LME7

2.00

0... + - A

/rese

t

Not

e!*)

IfP

OC

isno

tuse

d,w

irelin

kD

br1

mus

tbe

conn

ecte

d!**

)With

appl

icat

ions

with

outa

ctua

torS

QM

4...,

wire

link

Dbr

4m

ustb

eco

nnec

ted.

Β

BCI

Page 29: Siemens LME7 Burner Control Technical Documentation

29/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME72... for PME72.541...

7105

d86e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plu

gm

arki

ng

NTNL

LME7

2.00

0...

LED

K12

K11

K9

K2/2

K7

K5 FS

V2

FSV

1

K4

K1K2

/1

SA-N

L

SA-C

LOSE

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65

µC

BCI

Out

putp

ilotv

alve

PV

Out

puta

larm

Fee

dbac

kin

putP

OC

Out

putf

uelv

alve

V2

Notused

Notused

Not

activ

e

Dbr3Dbr2fordirectignition

+ - A

/rese

t

Not

activ

e

Not

activ

e

Not

e!*)

IfP

OC

isno

tuse

d,w

irelin

kD

br1

mus

tbe

conn

ecte

d!**

)With

appl

icat

ions

with

outa

ctua

torS

QM

4...,

wire

link

Dbr

4m

ustb

eco

nnec

ted.

Β

BC

I

Page 30: Siemens LME7 Burner Control Technical Documentation

30/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME73... for PME73.810...

7105

d43e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plu

gm

arki

ng

NTNL

LME7

3.00

0...

LED

K12

K11

K9

K2/2

K7

K5 FS

V2

FSV

1

K4

K1K2

/1

SA-N

L

SA-

ZU

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65 LR-IN(analog)

µC

+ - A

BCI

Out

putf

uelv

alve

V2a

Out

puta

larm

Fee

dbac

kin

putP

OC

Out

putf

uelv

alve

V2

GNDLRinput

5VpowersupplySignalGND

Not

activ

e

/rese

t

Not

e!*)

IfPO

Cis

notu

sed,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

Β

BC

I

Page 31: Siemens LME7 Burner Control Technical Documentation

31/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME73... for PME73.811...

7105

d101

e/09

14

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LME7

3.00

0...

LED

K12

K11

K9K2/2

K7 K5 FS

V2

FSV

1

K4

K1K2

/1

SA-

NL

SA

-CLO

SE

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65 LR-IN(analog)

µC

+ - A

BC

I

Out

putf

uelv

alve

PV

Ausg

ang

alar

m

Feed

back

inpu

tPO

C

Out

putf

uelv

alve

V2

GNDLRinput

5VpowersupplySignalGND

Dbr2fordirectignitionDbr3

/rese

t

Not

activ

e

Not

e!*)

IfP

OC

isno

tuse

dan

dpa

ram

eter

237

=1,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

ΒB

CI

Page 32: Siemens LME7 Burner Control Technical Documentation

32/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME73... for PME73.812...

7105

d96e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LME7

3.00

0...

LED

K12

K11

K9K2/2

K7 K5 FS

V2

FSV

1

K4

K1K2

/1

SA-N

L

SA-

CLO

SE

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65 LR-IN(analog)

µC

+ - A

BC

I

Out

putp

ilotv

alve

PV

Ausg

ang

alar

m

Feed

back

inpu

tPO

C

SA-Z

L

GNDLRinput

5VpowersupplySignalGND

Dbr2fordirectignitionDbr3

/rese

t

Not

activ

e

Not

e!*)

IfP

OC

isno

tuse

dan

dpa

ram

eter

237

=1,

wire

link

Dbr

1m

ustb

eco

nnec

ted!

ΒBC

I

Page 33: Siemens LME7 Burner Control Technical Documentation

33/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME73... for PME73.820...

7105

d44e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plu

gm

arki

ng

NTNL

LME7

3.00

0...

LED

K12

K11

K9K2/2

K7 K5 FS

V2

FSV

1

K4

K1K2

/1

SA-N

L

SA

-CLO

SE

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65

µC

+ - A

BC

I

Out

putf

uelv

alve

V2a

Out

puta

larm

Feed

back

inpu

tPO

C

Out

putf

uelv

alve

V2

Not

activ

e

Notused

Notused

/rese

t

Not

e!*)

IfP

OC

isno

tuse

d,w

irelin

kD

br1

mus

tbe

conn

ecte

d!**

)With

appl

icat

ion

with

outa

ctua

tor

SQM

4...,

wire

link

Dbr

4m

ustb

eco

nnec

ted.

Β

BC

I

Page 34: Siemens LME7 Burner Control Technical Documentation

34/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME73... for PME73.830...

7105

d26e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LME7

3.00

0...

LED

K12

K11

K9K2/2

K7 K5 FS

V2

FSV1

K4

K1K2

/1

SA-N

L

SA-C

LOSE

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65

LR-IN(analog)

µC

+ - A

BCI

Out

putp

ilotv

alve

PV

Out

puta

larm

Feed

back

inpu

tPO

C

Out

putf

uelv

alve

V2

GNDLRinput

5VpowersupplySignalGND

Dbr3

Not

activ

e

PLT

Dbr2fürDirectignition

/res

et

Not

e!*)

IfP

OC

isno

tuse

d,w

irelin

kD

br1

mus

tbe

conn

ecte

d!Β

BCI

Page 35: Siemens LME7 Burner Control Technical Documentation

35/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME73... for PME73.831...

7105

d66e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LME7

3.00

0...

LED

K12

K11

K9

K2/2

K7 K5 FSV2

FSV

1

K4

K1K2

/1

SA-N

L

SA-C

LOS

E

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65 LR-IN(analog)

µC

+ - A

BCI

Out

putp

ilotv

alve

(PV

)

Out

puta

larm

Inpu

tval

vepr

ovin

g(L

T)O

N/O

FF

Out

putf

uelv

alve

(V1

/V2)

**)

GNDLRinput

5VpowersupplySignalGND

Not

activ

e

PLT

/rese

t

Valv

epr

ovin

gO

N/O

FF

Not

e!*)

Ifva

lve

prov

ing

isno

tuse

,w

irelin

kD

br1

can

beco

nnec

ted!

**)D

epen

ding

onfu

eltra

in.

Β

BC

I

Page 36: Siemens LME7 Burner Control Technical Documentation

36/38

Building Technologies CC1N7105en17.04.2018

Connection diagram LME73... for PME73.840...

7105

d59e

/091

4

X7-01

03K34

X4-02

03K66

X10-05

05K37

X10-06

02K43

X3-04

05K30

X6-03

03K57

X2-01

03K105

X3-02

02K02

X5-01

03K54

X9-04

03K30

X56

GND

X7-04

04K77

X2-03

03K15

X5-03

03K105

X2-02

04K22 04K01

Cod

ing

Plug

mar

king

NTNL

LME7

3.00

0...

LED

K12

K11

K9

K2/2

K7 K5 FSV2

FSV1

K4

K1K2

/1

SA-

NL

SA-

Z

X7-02

03K10

X2-09

08K24

X76 Notused

X66

X65

µC

+ - A

BCI

Out

putp

ilotv

alve

PV

Out

puta

larm

Feed

back

inpu

tPO

C

Out

putf

uelv

alve

V1

Dbr3

Not

activ

e

PLT

Dbr2fordirectignition

Notused

Dbr4**)

Notused

/rese

t

Not

e!*)

IfPO

Cno

tuse

d,th

ew

irelin

kD

br1

mus

tbe

conn

ecte

d!**

)For

appl

icat

ins

with

outa

ctua

torS

QM

4...,

the

wire

link

Dbr

4m

ustb

eco

nnec

ted!

Β

BCI

Page 37: Siemens LME7 Burner Control Technical Documentation

37/38

Building Technologies CC1N7105en17.04.2018

Legend

AL Alarm deviceAUX Auxiliary outputDbr Wire link

/reset (EK1)Lockout reset button (info button)

EK2 Remote lockout reset buttonFSV Flame signal amplifierION Ionization probeK... Relay contactLED 3-color signal lampLP Air pressure switchLR Load controllerLR-OPEN Load controller OPEN positionLR-CLOSE Load controller CLOSE positionM Fan motorNT Power supply unitP LT Pressure switch valve provingPmax Pressure switch-maxPmin Pressure switch-minPOC Proof of closurePV Pilot valveQRA... Flame detectorR Control thermostat or pressurestatSA ActuatorSA-KL Actuator low-fireSA-NL Actuator high-fireSA-R Actuator feedbackSA-CLOSED Actuator CLOSESA-ZL Actuator ignition loadSL Safety loopSTB Safety limit thermostatSV Safety valveV1 Fuel valveV2 Fuel valveV2a Fuel valveW Limit thermostat or pressure switchZ Ignition transformer

µC µC controller

Input/output signal 1 (ON)Input/output signal 0 (OFF)Input permissible signal 1 (ON) or 0 (OFF)

Page 38: Siemens LME7 Burner Control Technical Documentation

38/38

Building Technologies CC1N7105en17.04.2018

DimensionsDimensions in mm

nfo+-A

7105m02en/0316

LME7…

2018 Siemens AG Building Technologies, Berliner Ring 23, D-76437 RastattSubject to change!