CC1N7541en 22.06.2006 Building Technologies HVAC Products 7 541 Burner Management System LMV27.1... Burner control with integrated air / fuel ratio control for forced draft burners. The LMV27.1… are designed for intermittent operation. The LMV27.1... and this Data Sheet are intended for use by OEMs which integrate the burner management system in their products! Use The LMV27.1... burner management system is a microprocessor-based unit with matching system components for the control and supervision of forced draft burners of medium to high capacity.

Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

Embed Size (px)

Citation preview

Page 1: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

CC1N7541en 22.06.2006

Building TechnologiesHVAC Products

7541

Burner Management

System LMV27.1...

Burner control with integrated air / fuel ratio control for forced draft burners. The LMV27.1… are designed for intermittent operation. The LMV27.1... and this Data Sheet are intended for use by OEMs which integrate the burner management system in their products!

Use The LMV27.1... burner management system is a microprocessor-based unit with matching system components for the control and supervision of forced draft burners of medium to high capacity.

Page 2: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

2/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Warning notes For additional safety notes, refer to the Basic Documentation of the LMV27.1... system (P7541)! To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! The LMV27.1... is a safety device! Do not open, interfere with or modify the unit. Siemens will not assume responsibility for any damage resulting from unauthor-ized interference! • All activities (mounting, installation and service work, etc.) must be performed by

qualified staff • Before making any wiring changes in the connection area of the LMV27.1…, com-

pletely isolate the unit from the mains supply (all-polar disconnection) • Ensure protection against electric shock hazard by providing adequate protection

for the burner control’s connection terminals • Each time work has been carried out (mounting, installation, service work, etc.),

check to ensure that wiring and parameters is in an orderly state • Fall or shock can adversely affect the safety functions. Such units must not be put

into operation, even if they do not exhibit any damage • For display of the flame on the AZL2…, following general conditions apply:

- Display is subject to various component tolerances so that deviations of ± 10 % can occur - Note that for physical reasons there is no linear relationship between flame display and detector signal values

Mounting notes • Ensure that the relevant national safety regulations are complied with

Additional mounting surfaces

122

Outer contour of housing(103.5)

6.5

103.510

217

M5 x 4

0.3

7541

z298

e/06

06

Installation notes • Always run high-voltage ignition cables separately while observing the greatest

possible distance to the unit and to other cables • Do not mix up live and neutral conductors

Mounting

Page 3: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

3/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Electrical connection of the flame detectors It is important to achieve practically disturbance- and loss-free signal transmission: • Never run the detector cable together with other cables

– Line capacitance reduces the magnitude of the flame signal – Use a separate cable

• Observe the maximum permissible detector cable lengths • The ionization probe is not protected against electric shock hazard. It is mains-

powered and must be protected against accidental contact • Locate the ignition electrode and the ionization probe such that the ignition spark

cannot arc over to the ionization probe (risk of electrical overloads)

Standards and certificates

Conformity to EEC directives - Electromagnetic compatibility EMC (immunity) - Directive for gas appliances - Low-voltage directive

89 / 336 / EEC 90 / 396 / EEC 73 / 23 / EEC

ISO 9001: 2000 Cert. 00739

ISO 14001: 2004 Cert. 38233

• Identification code to EN 298 chapter 4 F T / M C L B B

Service notes • If fuses are blown, the unit must be returned to Siemens

Disposal notes The unit contains electrical and electronic components and must not be disposed of to-gether with domestic waste. Local and currently valid legislation must be observed.

Page 4: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

4/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Mechanical design The LMV27.1... is a microprocessor-based system with matching system components for the control and supervision of forced draft burners of medium to high capacity. The following system components are integrated in the LMV27.1… basic unit: • Burner control with gas valve proving system • Electronic air / fuel ratio control with a maximum of 2 actuators • Modbus interface

Example: Modulating gas burner The system components (display and operating unit, actuators) are connected directly to the LMV27.1…basic unit. All safety-related digital inputs and outputs of the system are monitored by a contact feedback network (CFN). For intermittent operation in con-nection with the LMV27.1..., an ionization probe or optical flame detector type QRB… or QRC… is used. The burner management system is operated and parameterized with the help of the AZL2… display and operating unit or a PC tool. The AZL2... features an LCD and me-nu-driven operation, offering straightforward operation and targeted diagnostics. To simplify diagnostics, the display shows the operating states, the type of fault and the point in time the fault occurred. The different parameter setting levels for the burner / boiler manufacturer and the heating engineer are protected by passwords. Basic set-tings that the plant operator can make on site do not demand a password. There is also a communication interface COM from which higher level systems such as building auto-mation (GA). Using the BCI and OCI410… interfaces, a PC with ACS410 software can be connected. Among other features, the software affords convenient readout of set-tings and operating states, parameterization of the LMV27.1..., and trend logging. The burner / boiler manufacturer can choose from a number of different fuel trains and has a wide variety of parameter setting choices (program times, configuration of inputs and outputs, etc.) to ensure optimum adaptation to the relevant application. The SQM3... and SQN1… actuators are driven by stepper motors and offer high-resolution positioning. The characteristics and settings of the actuators are defined by the LMV27.1... basic unit.

Page 5: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

5/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Type summary Microprocessor-based burner control for single-fuel burners of any capacity, electronic air / fuel ratio control, up to 2 actuators, integrated gas valve proving system.

TSA Type reference Mains voltage Parameter set Type of flame detector Gas Oil

LMV27.100A2 AC 230 V Europe QRA2… / QRA4… (USA) / QRA10… / QRB… / QRC… / ION

3 s 5 s

Technical data Mains voltage AC 230 V -15 % / +10 % Mains frequency 50 / 60 Hz ±6 % Power consumption < 30 W (typically) Safety class I, with parts according to II and III to

DIN EN 60 730-1 Degree of protection IP00

Note: The burner or boiler manufacturer must ensure degree of protection IP40 to DIN EN 529 for burner controls by adequate installation of the LMV2…

• Perm. mains primary fuse

(externally) max. 16 AT

• Unit fuse F1 (internally) 6.3 AT (DIN EN 60 127 2 / 5) • Mains supply: Input current depending on the operating state of the unit Undervoltage • Safety shutdown from operating

position at mains voltage approx. AC 186 V

• Restart on rise in mains voltage approx. AC 195 V Status inputs: Status inputs (with the exception of the safety loop) of the contact feedback network (CFN) are used for system supervision and require mains-related input voltage • Input safety loop refer to «Terminal loading outputs» • Input currents and input voltages

- UeMax - UeMin - IeMax - IeMin

UN +10 % UN -15 % 1.5 mA peak 0.7 mA peak

• Contact material recommendation for external signal sources (LP, DWmin, DWmax, etc.)

gold-plated silver contacts

• Transition / settling behavior / boun-ce - Perm. bounce time of contacts when switching on / off

max. 50 ms (after the bounce time, the contact must stay closed or open)

• UN AC 230 V • Voltage detection

- On - Off

AC 180...253 V < AC 80 V

LMV27.1… basic unit

Terminal loading «Inputs»

Page 6: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

6/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Technical data (cont’d)

Total contact loading: • Nominal voltage AC 230 V, 50 / 60 Hz • Unit input current (safety loop) from:

- Fan motor contactor - Ignition transformer - Valves - Oil pump / magnetic clutch

max. 5 A

Individual contact loading: Fan motor contactor • Nominal voltage AC 230 V, 50 / 60 Hz • Nominal current 2 A • Power factor cosϕ > 0.4 Alarm output • Nominal voltage AC 230 V, 50 / 60 Hz • Nominal current 1 A • factor cosϕ > 0.4 Ignition transformer • Nominal voltage AC 230 V, 50 / 60 Hz • Nominal current 2 A • Power factor cosϕ > 0.2 Fuel valves • Nominal voltage AC 230 V, 50 / 60 Hz • Nominal current 2 A • Power factor cosϕ > 0.4 Operation display • Nominal voltage AC 230 V, 50 / 60 Hz • Nominal current 0.5 A • Power factor cosϕ > 0.4

• Mains line AC 230 V max. 100 m (100 pF / m) • Display, BCI max. 3 m (100 pF / m)

for used outside the burner cover or the control panel in assessment: max. 10 m (100 pF / m) for used outside the burner cover

• Load controller LR max. 20 m (100 pF / m) • External lockout reset button max. 20 m (100 pF / m) • Other lines max. 3 m (100 pF / m)

Specification as per EN 60730-1 Type of shutdown or interruption of each circuit Shutdown with microswitch 1-pole Mode of operation type 2 B

Terminal loading «Outputs»

Cable lengths

Page 7: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

7/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Technical data (cont’d) The cross-sectional areas of the mains power lines (L, N, and PE) and, if required, the safety loop (safety limit thermostat, water shortage, etc.) must be sized for nominal cur-rents according to the selected external primary fuse. The cross-sectional areas of the other cables must be sized in accordance with the in-ternal unit fuse (max. 6.3 AT).

Min. cross-sectional area 0.75 mm² (single- or multi-core to VDE 0100)

Cable insulation must meet the relevant temperature requirements and environmental conditions. Fuses used in the LMV27.1... basic unit - F1 6.3 AT DIN EN 60 127 2 / 5

Standard signal cable standard length 0.3 m and 2 m Location under the burner cover or in the control

panel Delivery Specification H 72385 0000 0 Supplier Hütter

http://www.huetter.co.at/telefonkabel.htm Storage DIN EN 60 721-3-1 Climatic conditions class 1K3 Mechanical conditions class 1M2 Temperature range -20...+60 °C Humidity < 95 % r.h. Transport DIN EN 60 721-3-2 Climatic conditions class 2K2 Mechanical conditions class 2M2 Temperature range -30...+60 °C Humidity < 95 % r.h. Operation DIN EN 60 721-3-3 Climatic conditions class 3K3 Mechanical conditions class 3M3 Temperature range -20...+60 °C Humidity < 95 % r.h. Condensation, formation of ice and ingress of water are not permitted!

Cross-sectional areas

Connecting cable display → BCI

Environmental conditions

Page 8: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

8/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Technical data (cont’d) No-load voltage at ION terminal (X10–05 terminal 2)

approx. UNetz

Caution! Protect the ionization probe against electric shock hazard!

Short-circuit current max. AC 1 mA Required detector current min. DC 4 µA, flame display approx. 30 % Possible detector current max. DC 16…40 µA, flame display

approx. 100 % Max. perm. length of detector cable (laid separately)

3 m (wire – ground 100 pF / m)

Note: With increasing detector cable capacitance (cable length), the voltage at the ionization probe, and thus the current, drops. Long cable lengths plus very highly resistive flames might necessitate low-capacitance detector cables (e.g. ignition cable). In spite of technical measures taken in the circuitry aimed at compensating potential adverse effects of the ignition spark on the ionization current, it must be made certain that the minimum detector current required will already be reached during the ignition phase. If this is not the case, the connections on the primary side of the ignition transformer must be changed and / or the electrodes relocated. No-load voltage at QRB... terminal (X10–05 terminal 3)

approx. DC 5 V

Max. perm. length of QRB... detector cable (laid separately)

3 m (wire – wire 100 pF / m)

Note: A detector resistance of RF < 500 Ω is identified as a short-circuit and leads to safety shutdown in operation as if the flame had been lost. For this reason, before considering the use of a highly sensitive photoresistive detector (QRB1B... or QRB3S), it should be checked whether this type of flame detector is really required! Increased line capacitance between QRB... connection and mains live wire L has an adverse effect on sensitivity and increases the risk of damaged flame detectors due to overvoltage. Always run detector cables separately! Threshold value flame supervision QRB… with LMV2… Start prevention (extraneous light) with RQRB

< 400 kΩ intensity > 10 %

Operation with RQRB < 230 kΩ intensity > 16 %

Short-circuit detection with RQRB < 0.5 kΩ

Flame detectors

Ionization probe

Photoresistive detectors QRB…

Page 9: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

9/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Technical data (cont’d)

Caution! If flame detectors type QRA2… / QRA4… are used for flame supervision with the LMV2…, it must be ensured that the detector is permanently connected to power (conforming to EN 230), thus enabling the system to detect flame detector failures during startup.

Aquivalent threshold value: Operation approx. 20 µA

(measured with DC 15 V / 4.5 kΩ series resistor)

For system-specific reasons, the display of flame intensity is limited to a maximum of approximately 55 %.

Flame detectors QRA2… / QRA4… (U.S.) / QRA10…

Blue-flame detectors QRC…

Page 10: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

10/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Block diagram inputs / outputs

5 4 3 2 1

X74

AK 1550/5-3.5-gr

5 4 3 2 1

X64

AK 1550/5-3.5-gr

5 46 3 2 1

X53

3521 06 / RAST2.5

5 46 3 2 1

X54

3521 06 / RAST2.5

4 3 2 1

X92

3521 04/RAST2.5

43

21

X56

12

3

X5-0

2

03K

31

L

P

max

PE

12

3

X5-0

1

03K

54

12

31

23

L

P

min

PE

L

P

X9-0

4

03K

30

X7-0

2

03K

10

L

PE

NV3

12

3

X4-0

2

03K

66

12

31

23

X6-0

3

03K

57

X3-0

5

03K

80

L

PE

NSV

L

PE

N

Z

12 X3

-03

02K

15

LL

L

Burner flange

Motor

Alarm

Motor continuous

L

PE

N

X3-0

4

54

32

1

05K

30

L Safety loop

L

PE

N

X7-0

1 32

103K

34 V2

X3-0

2 2102

K02 L

X10-

06 2102

K43

+

L

PE

GND

X10-

05

54

32

1

05K

37

ION

QRB....

X75 2

102K

37 Signal input

Voltage

Lum

berg

cod

eS

iem

ens

mar

king

Sie

men

s m

arki

ngLu

mbe

rg c

ode

Lumberg codeSiemens marking

Name PTRSiemens marking

LTPE

X8-0

2

43

21

04K

80

L

PEN

V1

X8-0

4 2102

K13

X5-0

3

43

21

04K

01

L2

3

ResetL

Reserve

24 V

ext

erna

l inp

ut

GN

D e

xter

nal

Ana

log

outp

ut

Load output

U A

CT

GN

D

AC

T1 O

utpu

t A

AC

T1 O

utpu

t B

AC

T1 In

put A

AC

T1 In

put B

U A

CT

GN

D

AC

T0 O

utpu

t A

AC

T0 O

utpu

t B

AC

T0 In

put A

AC

T0 In

put B

U B

us

TXD

1

RX

D1

GN

D

ActuatorAir

ActuatorFuel

COM

U Display

TXD0

RXD0

GND

Dis

play

/ BC

I

B4

GP max

GP min

GP LT

QRA...

pa LP

b

On/off

Fuel counter

7541

a14e

/060

6

Page 11: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

11/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Inputs / outputs (cont’d)

X3-03

X3-05

X6-03

X4-02

X7-02

X9-04

X5-01

X5-02

FUSE

1

X7-

01X

5-03

X8-

04X

8-02

X75

X10

-05

X10

-06

X3-

02

VSD X74

X64 1

1

COM X92 FUEL X54 AIR X53

BCIX56

111

X3-

04N

PE

LT6.3

IEC

601

27-2

/V

7541

z297

/050

6

Page 12: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

12/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Connection diagram

X3-04.3

X3-04.5 Power supply phase conductor (L)

X3-04.4 Power supply neutral conductor (N)

Protective earth (PE)

X3-04.2 Power signal for safety loop

X3-04.1 Safety loop

X3-03.2 Power signal for end switch burner flange

X3-03.1 End switch burner flange(component of safety loop)

X3-05.2 Alarm

X3-05.1 Fan motor contactor

IgnitionX4-02.3

Fuel valve SVX6-03.3

Fuel valve V2X7-01.3

Fuel valve V3X7-02.3

Fuel valve V1X8-02.1

Wiring point for series valvesX8-02.2

X3-05.3

X4-02.2

X6-03.2

X7-01.2

X7-02.2

X8-02.3

STB AUX Watershortage

L1-L3

Fan

PE

N

L1F 6.3AT L1'

LMV2...LMV2...

3

Air pressure switch (LP)X3-02.1

P

X3-02.2Power signal for airpressure switch (LP)

X8-04.1 Reset / manual locking

X5-03.1

X5-03.2

X5-03.3X5-03.4

Controller (on / off)

Controller closing / stage 3

Controller opening / stage 2Power signal forcontroller

On/Off

2

3

X5-01.2P

X5-02.2

min

max

Pressure switch-min

Pressure switch-max

X9-04.2X9-04.3

LT

Power signal forpressure switch

Pressure switch-DK-fas / LT orvalve closing contact (CPI)

(CPI)

L1'

P

P

Protective earth (PE)X10-05.1

GND X10-05.4

X10-05.5 Power signal (L)

X10-05.3 QRB... / QRC... signal voltage

X10-05.2 Ionization probe (ION)

QRB... / 1) only QRC...

ION

Flame

X5-02.3

X5-01.3

Fan

Indication oil / gasX8-04.2

Continuous fan operation

QRA... (+)X10-06.2

QRA... (-)X10-06.1QRA...+

7541a15e/0606

1)

Page 13: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

13/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Connection diagram (cont´d)

X56.2

X56.3

Signal reference GND

X56.1

X56.4

DC 5 V

TXD0

RXD0

U Display

TXD0

RXD0

GND

AZL2... /OCI...

LMV2...

X75.2

X75.1

LMV2...

Power supplyfor fuel counter

Input fuel counter

Fuel counter input

+

-

DC 0 / 1...10 V

Signal reference

Load output

X74.2

X74.3

DC 24 V external X74.1

UAC_SA

GND

SHIELD

FE

SQM3...

X92.2

X92.3

Signal reference GND

X92.1

X92.4

DC 5 V

TXD1

RXD1

U Display

TXD1

RXD1

GND

GA

ACT0_OUT_B

ACT0_OUT_A

ACT0_IN_B

ACT0_IN_A

UAC_SA

GND

SHIELD

FE

SQM3...

ACT1_OUT_B

ACT1_OUT_A

ACT1_IN_B

ACT1_IN_A

X54.1

X54.3

X54.4

X54.5

X54.6

X54.2

X53.1

X53.3

X53.4

X53.5

X53.6

X53.2

Fuel actuator

Air actuator

Functional earthfor shield connection

Functional earthfor shield connection

Display

GA

7541a37e/0606

+ 24 V

+ Mains supply input 0...10 V

-

VDS

Page 14: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

14/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Fuel train applications (examples)

SV V1 V2

Direct ignitionGProgram

7541s01e/0505

SADWmax

DWmin

DWDK

SV V1

SAV2

Program Gp1 Gas pilot

7541s02e/0505

PV

DWmin

DWDK

DWmax

SV

DWmax SA

V2

Program Gp2 Gas pilot

7541s03e/0505

DWmin

PV

V1

DWDK

Gas (always modulating)

Direct trafo

G

PV V1 V2

TSA1

TSA2

Operation

*)

Pilot ignition 1

Gp1

PV V1 V2

Pilot ignition 2

Gp2

PV V1 V2

7541

f01e

/050

5

Legend for fuel trains: *) Not used 1) Series connection of two 115 V- valves (each requiring approx. 25 VA control power) 2) Preheating device V Fuel valve DK Gas valve proving DW Pressure switch HE Heating element HO Heavy fuel oil LO Light fuel oil SA Actuator No Normally Open SV Shutoff valve (outside the building) PV Pilot valve

Direct gas ignition

Gas pilot ignition 1

Gas pilot ignition 2

Fuel valve control program

Page 15: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

15/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Fuel train applications (examples)

DWmin

V1

7541s04/0305

LOProgram

1-stage burner

V1

V2

7541s05/0305

DWmin

LOProgram

2-stage burner

V1

V2

7541s06/0305

DWmin

V3

LOProgram

3-stage burner

Direct ignition with light fuel oil, multistage

Page 16: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

16/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Fuel train applications (examples)

DWmax

1)

M

DWmin

V1

7541s07e/0505

1)

LOProgram

Modulating burner (without shutdown facility for

adjustable head)

1)

V1

M

7541s08e/0505

DWmin

DWmax

LOProgram

Modulating burner (with shutdown facility for

adjustable head)

LO

V1 V2 V3

TSA1

TSA2

Operation

V3

V2

MIN

LK posi

tion

stage operation7541f02e/0606

MAX

Light fuel oil (Trafo direct ignition)

Direct ignition with light fuel oil, modulating

Fuel valve control program

Page 17: Burner Management LMV27.1 System - burners.ovk-kom.ruburners.ovk-kom.ru/Siemens/Burners/n7541en_LMV27.pdf · CC1N7541en 22.06.2006 Building Technologies HVAC Products 7541 Burner

17/17

Building Technologies CC1N7541en HVAC Products 22.06.2006

Dimensions Dimensions in mm

230202

192141

82,522,8

10,2

16,5

39,3

118,

512

213

5

217202

172128,5

82,527,2

12,5 23,5

R100

6019

,5

19,7

7541m08/0506

25,5

53,6

76,6

100,

811

8,5

LMV27.1...

©2006 Siemens Building Technologies HVAC Products GmbH Subject to change!