AIR HANDLING UNITS WITH HEAT RECOVERY
DescriptionThe air handling units are the fully featured ventila-tion units with heat recovery for air filtration, fresh air supply and stale air extract. During operation the extract air heat is transferred to the supply air stream by the highly efficient plate heat exchanger. The units are designed for energy efficient ventilation of cottages and flats and are compatible with round air ducts (Ø 150 mm).
Casing The casing is made of expanded polypropylene (EPP) with high heat and sound insulation characteristics.
FilterTwo built-in filters with filtration class G4 and F7 provide efficient supply air filtration. Extract air is cleaned by the integrated G4 filter.
MotorThe units are equipped with high-efficient EC motors with an external rotor and a centrifugal impeller with forward curved blades. These state-of-the-art motors offer the very best in energy efficiency today. EC mo-tors are characterised with high performance and opti-mum control across the entire speed range. In addition to that, the efficiency of the electronically commutat-ed motor reaches very impressive levels of up to 90 %.
Heat exchangerThe VUT 180 P5B EC units are equipped with a coun-ter-flow polystyrene heat exchanger. In the cold season the extract air heat is captured and transferred to the supply air stream which reduces the ventilation-gen-erated heat losses. This can lead to formation of con-densate that is collected in a special drain pan and dis-charged into the sewage system. In the warm season the ambient air heat is transferred to the exhaust air stream. This allows for a considerable reduction of the supply air temperature which, in turn, reduces the air conditioning load.
The VUE 180 P5B EC units are equipped with a counter-flow heat exchanger with an enthalpy mem-brane at the core. In the cold season the extract air heat and moisture are transferred to the supply air stream through the enthalpy membrane reducing the heat losses from ventilation. Consequently, it is the ambient air heat and moisture transferred to the exhaust air stream through the enthalpy membrane in the warm season. This allows for a considerable re-duction of the supply air temperature and humidity which, in turn, reduces the air conditioning load.
BypassThe units are equipped with a bypass for summer ventilation (cooling of the premise with a cool out-side air).
Control and automationThe VUT/VUE 180 P5B EC units are equipped with an A14 automation.The VUT/VUE 180 P5B EC A14 models have the A14 sensor control panel with LED indication.
Freeze protection
Supply fan stopping. The heat exchanger freeze protection operates as follows: in case of freezing danger determined by the temperature sensor the supply fan is turned off to let extract air warm up the heat exchanger. After freezing danger is no longer imminent, the unit reverts to the standard operation mode.
Installation The unit is designed for suspended ceiling, wall hori-zontal or vertical mounting using mounting brackets. While installing the unit, ensure convenient access for subsequent maintenance and repair.
Air handling units in heat- and sound-insulated casing. Air flow up to 220 m3/h. Heat recovery efficiency
up to 98 %
Designation key
Series Rated air flow [m3/h] Installation type Casing design Bypass Motor type Control
VUT: ventilation with heat recovery
VUE: ventilation with energy recovery
180 P: suspended 5: expanded polypropylene B: bypass
EC: synchronous electronically commutated
motor
A14: sensor control panel with LED indication
motor
Series VENTS
VUT/VUE 180 P5B EC
WWW.VENTILATION-SYSTEM.COMWWW.VENTILATION-SYSTEM.COM
ModelDimensions [mm]
Ø D B B2 L H
VUT/VUE 180 P5B EC 150 600 326 900 264
Overall dimensions
Unit design
Functions
A14
Control functions
Switching the unit on and off +
Low, Medium or High speed selection +
Filter maintenance indicator +
Emergency indicator +
Bypass control manual
Speed setting from 0 to 100% +
Built-in humidity sensor option
Normally open contacts for a kitchen hood, a humidity sensor and a CO2 sensor +
Normally closed contacts for a fire alarm panel +
Air damper contacts +
L
HL1
BB2
øD
EC supply fan
G4 extract filter
G4 supply air filter F7 supply air filter
Control unitEC extract fan
Heat exchanger
Bypass damper
Supply air
Exhaust air
Intake air
Extract air
Technical data
AIR HANDLING UNITS WITH HEAT RECOVERY
VUT 180 P5B EC A14 VUE 180 P5B EC A14
Unit voltage [V/50 (60) Hz] 1~ 230
Maximum power [W] 87
Maximum current [A] 0.71
Maximum air flow [m3/h] 220
RPM [min-1] 2200
Sound pressure level at 3 m distance [dBA] 33
Transported air temperature [°C] -25…+60
Casing material expanded polypropylene
Insulation EPP 30-15 mm
Extract filter G4
Supply filter G4, G7
Connected air duct diameter [mm] Ø150
Weight [kg] 14 14
Heat recovery efficiency [%] from 86 up to 98 from 79 up to 94
Heat exchanger type counter-flow
Heat exchanger material polystyrene enthalpy membrane
Energy efficiency class for A14 A+ A+
Mod
el
G4
supp
ly p
anel
filte
r
F7 s
uppl
y pa
nel fi
lter
Built
-in h
umid
ity s
enso
r
Out
door
CO
2 sen
sor w
ith
indi
catio
n
Out
door
CO
2 sen
sor
Out
door
hum
idity
sen
sor
U-t
rap
kit
Air
dam
per
Elec
tric
act
uato
r
VUT 180 P5B EC A14 SF186x214x18 G4
SF186x214x48 F7 HV2 CO2-1 CO2-2 HR-S SH-32 KRV 150 LF230
VUE 180 P5B EC A14
Accessories for air handling units
WWW.VENTILATION-SYSTEM.COM
0 10 20 30 40 50 60
75
80
85
90
95
100
0 50 100 150 200 250
0 10 20 30 40 50 60
707580859095
100
0 50 100 150 200 250
0 10 20 30 40 50 60
0
50
100
150
200
250
300
0 50 100 150 200 250
0.8 W/l/s1.0 W/l/s1.2 W/l/s1.4 W/l/s1.6 W/l/s1.8 W/l/s2.0 W/l/s
VUT 180 P5B EC
VUT 180 P5B EC
VUE 180 P5B EC
3
2
1
4
5
6
98
7
VENTS VUT/VUE 180 P5B EC
Sound power level, A – weighted Octave-frequency band [Hz] LpA, 3 m
dBALpA, 1 m
dBAHz Gen. 63 125 250 500 1000 2000 4000 8000
LwA to supply inlet dBA 59 27 46 54 55 53 48 44 35
LwA to supply outlet dBA 60 27 46 54 55 52 49 44 35
LwA to exhaust inlet dBA 55 25 41 50 51 44 42 39 30
LwA to exhaust outlet dBA 55 26 41 51 51 44 42 39 31
LwA to environmet dBA 54 18 36 47 49 48 43 37 33 33 43
Stat
ic p
ress
ure
ΔP
[Pa]
Air flow [l/s]
Air flow [l/s]
Air flow [l/s]
Hea
t rec
over
y effi
cien
cy [%
]H
eat r
ecov
ery
effici
ency
[%]
Air flow [m3/h]
Air flow [m3/h]
Air flow [m3/h]
Calculation of air temperature downstream of the heat exchanger:
t=toutd+khr*(textr-toutd)/100,
where
toutd – outdoor air temperature [°C]
textr – extract air temperature [°C]
khr – heat exchanger efficiency (according to the diagram) [%]
PointPower [W] Sound pressure level
at 3 m (1 m) distance [dBA]
VUT/VUE 180 P5B EC VUT/VUE 180 P5B EC
1 77 33 (43)
2 64 33 (43)
3 53 32 (42)
4 31 29 (39)
5 30 28 (38)
6 26 27 (37)
7 14 23 (33)
8 13 21 (31)
9 12 19 (29)
AIR HANDLING UNITS WITH HEAT RECOVERY
Application options
Ceiling plenum with an anemostat
Air handling unitFlexiVent air duct
Collector