Samaan Short Circuit IEEE PSE09

Embed Size (px)

Citation preview

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    1/21

    Modeling of Wind Power Plants for

    Transmission Network

    Nader Samaan Robert Zavadil J. Charles Smith Jose Conto

    EnerNex Corporation

    Knoxville, TN

    UWIG

    Reston, VA

    ERCOT

    Taylor, TX

    Presented at

    IEEE 2008 Transmission & Distribution Conference & Exposition

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    2/21

    Agenda

    Objective

    Modeling of Type 1 WTG for steady stateshort circuit anal sis

    Calculating equivalent impedance for wind plantto e use n s ort c rcut ana ys s

    t t h w th tr n i nt h vi r f

    Type 1 WTG during fault conditions

    Conclusions

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    3/21

    Objective

    Procedures to calculate the contribution of WindPower Plants (WPP) to short circuits in the MV/HV

    transmission network (steady state analysis)To characterize the asymmetrical induction

    generator short circuit current to identify the

    breakers momentary duty (transient analysis) As the input mechanical power to induction

    generator is almost constant after the fault, the

    s or c rcu curren o n uc on genera or maydecay in a different manner than induction motors

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    4/21

    Type 1 Wind Turbine Generator

    Type 1 wind turbine generator (WTG) is a-

    It is connected directly to the padmount

    Gear Soft starter

    Grid

    SCIG

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    5/21

    Modeling of Type 1 WTG for Steady State Short

    Circuit Analysis Induction generator in short circuit calculations is

    re resented as a volta e source in series with the

    direct axis sub-transient inductance

    That means for a 3LG fault at the WTG LV

    ,symmetrical short-circuit current with a magnitude

    current during the first cycle after the fault

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    6/21

    Procedures for Determining the WPP

    Equivalent Impedance (1)A detailed model for the WPP is needed to determine theplant 3-phase to ground I and single line to ground

    ZZ

    ISLG short circuit currents at the plant main substation

    ne nene

    Isc Feeder

    ne nene

    Isc Feeder

    ZWTGZWTG ZWTG ZWTG

    Isc_9Isc_8 Isc_7 Isc_6

    _

    ZWTGZWTG ZWTG ZWTG

    Isc_9Isc_8 Isc_7 Isc_6

    _

    VG9

    VG8 VG7 VG6VVG9

    VVG8 VVG7 VVG6

    WTG=T

    ZT Impedance of turbine step up transformer

    WTG=T

    ZT Impedance of turbine step up transformer

    d

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    7/21

    Procedures for Determining the WPP

    Equivalent Impedance (2)Using the E/Z simplified method, short-circuit currentsare then used to obtain the equivalent positive sequence

    and zero sequence impedances of the plantLL

    V 3 LNV1 2

    33 * LGI0 1

    SLGI

    WPP +ve -ve se uence

    impedanceszero sequence

    impedance

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    8/21

    eneric Dynamic Model for Squirrel Cage Induction

    Generator with Pitch Angle Controller

    Pitch Angle

    Controller

    AeroDynamics

    -massmodel for

    q e ca einduction

    model

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    9/21

    Case Study

    A 50 MW wind farmconsists of 20 2.5

    MW Type 1 WTG

    n y ower ac orwith 1.35 MVAR

    switched on

    au as s or . sec(12 cycles)

    Grid MVA SC duty 1500 MVA

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    10/21

    Case Study: (3LG Fault at WPP MV Bus)

    Fault Duration

    Injected current from the WPP to the substation MV bus

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    11/21

    Case Study (SLG Fault at WPP MV Bus)

    Faulted phase

    Fault Duration

    Injected current from the WPP to the substation MV bus

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    12/21

    Case Study (Decay of WPP Short Circuit

    Current)No. of

    cycles

    after fault

    Current

    peak

    value

    Percentage of

    rated

    current

    No. of

    cycles

    after

    Current

    peak

    value

    Percentage of

    rated current

    eak value

    peak value(1167 A)

    fault

    (1167 A)

    Max value 6623 A 568%after fault

    instant

    a ter au tinstant

    3 cycles

    3 cycles 3331 A 285%

    6 c cles 1560 A 134%

    6 cycles 2524 A 216%

    9 cycles 780 A 67%9 cycles 1618 A 139%

    3LG Fault SLG Fault

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    13/21

    Case Study (WTG Short circuit current)

    3LG fault

    Generator instantaneous current waveforms

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    14/21

    Case Study (WTG Short circuit current)

    SLG fault

    Generator instantaneous current waveforms

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    15/21

    Case Study (WTG Short circuit current)

    Line to Line fault

    Generator instantaneous current waveforms

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    16/21

    Induction generator highest peak current values

    during the fault-Phase A

    12 3 phase to groundLine to line fault10

    Line to line faultLine to gro und fault

    68

    46

    1 pu

    Short circuit

    current in kA

    020 P re -f a ult Af ter F a ult 3 cy cles 6 cy cles 9 cy cles

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    17/21

    Induction generator highest peak current

    values during the fault-Phase B

    18 3 p h a s e t o g r o u n d

    141618

    Lin e t o l in e f au l tL in e t o g r o u n d f a u l t

    1012

    1 pu

    Short circuit

    current in kA

    468

    024

    P r e-f a ul t A f te r F a ul t 3 c yc l es 6 c yc l e s 9 c yc l es

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    18/21

    Induction generator highest peak current

    values during the fault-Phase C

    18 3 phase to ground

    141618 Line to line fault

    Line to ground fault

    81012

    1 pu

    Short circuit

    current in kA

    468

    024

    Pre f ault After Fault 3 cycles 6 cycles 9 cyclesre-f ault After Fault 3 cycles 6 cycles 9 cycles

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    19/21

    Case Study (Short Circuit Calculations)

    Description Before the After the Fault level

    Description Detailed

    Model

    Equivalent

    Circuit

    SK'' (MVA short- 1616.882 1616.867

    a t on o

    the WPP

    a t on o

    the WPP

    ncrease

    MVA short-

    circuit1500 1617 7.8%

    c rcu power

    Ik(Symmetri

    cal Sub

    PhaseA

    4059 A

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    20/21

    Conclusions

    Procedures have been developed to build anequivalence circuit for wind plant to be used in short

    circuit studies Different comparisons show that the equivalent

    circuit gives the same result as the detailed model

    The contribution of Type 1 WTG during the initialcycle of the fault (asymmetrical current) can be ashigh as 6 or more times the rated machine current

    or c rcu curren ra e o ecay epen s on efault type with the fastest decay rate in the case of a

    - .

  • 7/30/2019 Samaan Short Circuit IEEE PSE09

    21/21

    Questions