Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

Embed Size (px)

Citation preview

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    1/22

    Schutzvermerk / Copyright-Vermerk

    November 20, 2009

    Sector Energy, Business Unit Medium Voltage Siemens AG 2009

    Special Requirements

    of IEEE C37.013 forGenerator Circuit Breaker Applications

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    2/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 2

    Generator Circuit Breaker Applications

    What is different about generatorcircuit breakers?

    Applicable standards Special considerations Vacuum versus SF6 technology

    Questions.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    3/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 3

    Generator and Distribution Circuit Breakers

    Generator circuit breaker Distribution circuit breaker

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    4/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 4

    Circuit Breakers for Distribution

    Requirements

    Standards:IEEE C37.04 Rating structure for HV circuit breakersIEEE C37.09 Tests for HV circuit breakersIEEE C37.10 Application guide for HV circuit breakers.

    X/R ratio: 17 (60 Hz).

    Time constant of dc decay: 45 ms.

    TRV typical values (15 kV, class S1 cable):Peak voltage (uc) = 25.7 kVTime-to-peak (t3) = 66 sRRRV 0.39 kV/ s.

    Duty cycle: O t CO t CO

    t = 0.3 s for reclosing / 15 s for non-reclosingt = 3 minutes.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    5/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 5

    Circuit Breakers for Generation

    Requirements

    Standards:IEEE C37.013 Generator circuit breaker.

    X/R ratio: 50 (60 Hz).

    Time constant of dc decay: 133 ms.

    TRV typical values (15 kV, 100 MVA machine):Peak voltage (E2) = 1.84 V = 1.84 x 15.0 = 27.6 kVTime-to-peak (T2) = 0.62 V = 0.62 x 15.0 = 9.3 sRRRV 3.5 kV/ s.

    Duty cycle: CO 30 min CO.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    6/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 6

    IEEEC37.04 for distribution circuitbreakers expresses TRV in termsharmonized with IEC with peak voltageuc, andtime-to-peak t3.

    IEEE C37.013 still uses old TRVexpressions with peak voltage E2 andtime-to-peak T2. Peak voltage is notchanged, but t3 is approximately 0.88 xT2.

    The physics are not changed, just therepresentation.

    Notes on TRV Representation

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    7/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 7

    IEEE C37.04-1999 Scope

    IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers

    1. Scope

    This standard establishes a symmetrical current rating structure and construction

    requirements for all indoor and outdoor types of ac high-voltage circuit breakersrated above 1000 V. It is only applicable to three-pole circuit breakers used inthree-phase systems and single-pole circuit breakers used in single-phasesystems.

    This standard does not cover circuit breakers used at frequencies other than50 Hz or 60 Hz, or generator circuit breakers that are covered in IEEEStandard C37.013-1997.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    8/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 8

    IEEE C37.013-1997 Scope

    IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated on aSymmetrical Current Basis

    1. Scope

    This standard applies to all ac high-voltage generator circuit breakers rated on a

    symmetrical current basis that are installed between the generator and thetransformer terminals...

    Note: Since no other national or international standard on generator circuitbreakers exists, this standard is used worldwide.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    9/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 9

    IEEE C37.013 t h e International Standard

    for Generator Circuit Breakers

    IEEE C37.013 Revision PAR (Project) PAR approved by IEEE-SA

    Standards Board, March, 2009 Joint development with IEC SC 17A(HV Switchgear and Controlgear)

    IEEE WG chair is convenor (WG chair) ofIEC working group.

    IEC has no standard for a generator circuit breaker.The IEEE and IEC intent has been that IEEEC37.013 would be the global standard.

    IEC SC 17A WG 52 WG scope: Joint IEC/IEEE revision ofIEEE C37.013: IEEE Standard for AC High-

    Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    10/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 10

    X/R = 17, = 45 ms X/R = 50, = 133 ms

    X/R Ratio Determines %dc Component

    %dc vs Contact Part for X/R = 17 and X/R = 50

    0.0

    20.0

    40.0

    60.0

    80.0

    100.0

    120.0

    0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100

    Contact Part time (ms )

    % d c

    C o m p o n e n

    t

    X/R = 17X/R = 50

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    11/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 11

    X/R Ratio Effect on Asymmetrical InterruptingX/R Ratio Effect on Asymmetrical Interrupting

    -2.00

    -1.50

    -1.00

    -0.50

    0.00

    0.50

    1.00

    1.50

    2.002.50

    3.00

    0

    1 8 0

    3 6 0

    5 4 0

    7 2 0

    9 0 0

    1 0 8 0

    1 2 6 0

    1 4 4 0

    1 6 2 0

    1 8 0 0

    1 9 8 0

    2 1 6 0

    2 3 4 0

    2 5 2 0

    2 7 0 0

    2 8 8 0

    3 0 6 0

    3 2 4 0

    3 4 2 0

    3 6 0 0

    Time (in degrees)

    C u r r e n

    t ( I s c =

    1 . 0

    0 )

    Instantaneous (total) current

    dc component

    S-factor (C37.04-1979)

    dc component (in decimal form) (multiply by 100 for %dc component) (C37.04-1999)

    Symmetrical current (ac component)

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    12/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 12

    X/R Ratio Effect on Asymmetrical Interrupting

    S factor (from IEEE C37.04-1979)

    Ratio of rms asymmetrical current to rms symmetrical current

    Assume contact part time of 55 ms, and 50 kA symmetrical current

    X/R = 17 %dc = 29.5 S = 1.084 I = 54.2 kA

    X/R = 50 %dc = 66.1 S = 1.369 I = 68.5 kAover 26% higher

    )100/(%21 dc I

    I S

    l symmetrica

    total +==

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    13/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 13

    Short-Circuit Currents

    Consider system shown:

    Transformer 1,000 A full load (self-cooled)impedance = 10%

    Generator 1,000 A full load Xd (subtransient reactance) = 20%

    For fault at F2, circuit breaker sees transformerfault current, roughly 1,000 A / 0.10 = 10 kA

    For fault at F1, circuit breaker sees generatorfault current, roughly 1,000 A / 0.20 = 5 kA

    Note:

    Fault current for generatorsource fault is only about50% of fault current forsystem (transformer)source fault

    F1

    F2

    G

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    14/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 14

    Generator Circuit Breaker Ratings

    32.24.5 / 4.5 / 4.51.4 / 1.8 / 1.8

    27.63.5 / 4.51.6 / 1.8

    kVkV/ skV/ s

    TRV parameters Peak voltage (1.84 V) RRRV transformer source RRRV generator source

    30 / 30 / 3040 / 30msDelayed current zero*

    75 / 65 / 6573 / 61%%dc component

    50 / 63 / 7225 / 31.5 / 3640 / 6320 / 31.5kAkA

    Short-circuit current

    Transformer source Generator source

    50 / 11038 / 95kV/kVDielectric 60 Hz / BIL

    17.515.0kVMaximum voltage

    Fixed-Mounted

    Drawout(Metal-Clad)

    UnitCharacteristic

    * Higher values may be available

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    15/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 15

    Generator Circuit Breakers

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    16/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 16

    Generator Circuit Breakers

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    17/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 17

    Out-of-Phase Switching

    Circuit Breakers for Standard Applications:

    IEEE C37.04 (clause 5.12):

    Out-of-phase switching is optional, not required for general purpose circuitbreakers

    If a rating is assigned, the preferred rating is 25% of the rated symmetricalinterrupting rating, with recovery voltage of (250% rated voltage / 1.732).Therefore, out-of-phase ratings are not typically assigned to general purposecircuit breakers rated per IEEE C37.04 and tested to IEEE C37.09.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    18/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 18

    Out-of-Phase Switching

    Circuit Breakers for Generator Switching Applications:

    IEEE C37.013 (clause 6.2.9):

    Out-of-phase switching is optional, not required for generator circuit breakersIf a rating is assigned, the assigned rating is shall be 50% of the rated

    symmetrical interrupting rating (transformer or system source).Out-of-phase switching recovery voltage values are based on a maximumout-of-phase condition of 90 degrees between generator and system. This isreasonable as more extreme angles would result in damage to the machine.The likelihood of out-of-phase switching is influenced by generator inertia, i.e.,low-inertia machines are more likely to be subject to out-of-phase switchingconditions.Generator circuit breakers should have an assigned out-of-phase switchingrating.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    19/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 19

    Other Differences

    Reclosing:Reclosing duty not required for generator circuit breakers.

    Short-time current duration:Normal circuit breakers

    3 seconds (metal-clad switchgear = 2 seconds)

    Generator circuit breakers1.0 second (typically test to 3 seconds).

    Closing & latching rating:Normal circuit breakers

    Peak current 260% of symmetrical short-circuit (60 Hz)With X/R = 17, real peak is 259.3%

    Generator circuit breakersPeak current 274% of symmetrical short-circuit (60 Hz)

    With X/R = 50, real peak is 274.2%.

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    20/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 20

    Delayed Current Zero Example C37.013

    -4.000

    -3.500

    -3.000

    -2.500

    -2.000

    -1.500

    -1.000

    -0.500

    0.000

    0.500 0 1

    0 2 0

    3 0

    4 0

    5 0

    6 0

    7 0

    8 0

    9 0

    1 0 0

    1 1 0

    1 2 0

    1 3 0

    1 4 0

    1 5 0

    1 6 0

    Time (ms)

    C u r r e n

    t ( u n

    i t i z e

    d )

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    21/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 21

    Delayed Zero Test Example

    20.6 ms 30.0 ms

    40.1 ms 57.7 ms

  • 8/10/2019 Special Requirement of IEEE C37.013 for Generator Circuit Breaker Applications

    22/22

    Sector Energy, Business Unit Medium Voltage

    Siemens AG 2009November 09Folie 22

    Generator Circuit Breaker Technologies

    VacuumWell-suited to smaller units(up to 6,000 A or so)

    Most economic for small units

    Derived from proven distribution unitoperators and interrupters

    High experience-base

    Very low arc voltage (20 - 50 V)Little affect on X/R ratioLower arc voltage = less arc energy =

    lower contact erosion

    Extremely rapid recovery of dielectricstrength between contacts afterinterruption good for extreme TRV levels

    SF 6Only option for very large units

    VERY expensive

    Unlike distribution products

    Lower experience-base

    SF 6 low arc voltage (several 100 V)Somewhat higher impact on X/R ratioHigher arc voltage = higher arc energy =

    greater contact erosion

    Less able to cope with high TRV levels