RECAPP Facility Evaluation Report

Sherwood Heights Junior High School

B4023ASherwood Park

Elk Island Pub Sch Reg Div #14

Page 2: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 2 of 42

B4023ABuilding Id:

Sherwood Heights Junior HighBuilding Name:

Sherwood ParkLocation:241 Fir Street Address:

6,428.48Gross Area (sq. m): $11,396,917Replacement Cost:0Construction Year:

Evaluation Date: November 2 2006

Kenneth M. Lee ArchitectEvaluation Company:

Ken LeeEvaluator Name:

The original two storey with one storey wing 3,872.91 sq.m. (stucco & metal siding clad, concrete block & wood frameconstruction, combustible & non-combustible ) school was constructed in 1958. In 1959, a two storey 983.07 sq.m. ( brick, stucco & metal siding clad, concrete block & wood frame construction,combustible & non-combustible) addition was constructed. A two storey 358.80 sq.m. addition was added in 1985 and another two storey 563.00 sq.m addition was added in 1992.A one storey 625.83 sq.m. addition was constructed in 1997. The 1985, 1992 and 1997 additions are stucco clad,concrete block and non-combustible construction. Modernization was done to the administration area and library on the main floor of the 1958 original building in 1997.Some upgrading was done to the interior finishes in 1991, 1998, and 1999 which includes the washrooms, scienceclassrooms and art room. The building is non-sprinklered and in good condition. The student capacity is 513.

General Summary:

Structural Summary:The 1958 original building and the 1959 addition have concrete wall foundation with continuous footing. The 1985, 1992 and1997 additions have grade beam on concrete pile foundation. The 2nd floor of the 1958 original building and the 1959, 1985, 1992 additions are concrete floor on steel joists supported byconcrete block walls and wood frame walls. The roof structure of the 1958 original building and the 1959, 1985, 1992 and 1997 additions are a combination of wood deckon wood joists and metal deck on steel joists supported by concrete block walls and wood frame walls. The structure is in acceptable condition.

Envelope Summary:The exterior walls are clad with stucco, metal siding and brick. Windows and entrance doors are aluminum. The roofs are BUR and SBS systems. The building envelope is in acceptable condition.

Interior Summary:Vinyl sheet flooring and vinyl floor tiles are the major floor finishes in the building. Carpet in administration office, offices,staff room, library and drama room. Hardwood floor in gymnasium and stages. Walls are painted gypsum board and concrete block. Some walls have plaster wall finish. Ceilings are acoustic tiles, adhered ceiling tiles, plaster and gypsum board. The interior is in acceptable condition.

Mechanical Summary:Plumbing fixtures and systems are generally acceptable. The heating boilers and distribution pumps were upgraded in 2001 and ventilation systems that serve the 1992 and 1997additions are in good condition. The ventilation systems for the 1958, 1959, and 1985 areas are in poor condition and are not able to meet ventilationstandards. These should be considered a health risk due to the inability to provide even a minimum amount of fresh air tothe classroom spaces. Requirements for upgrades to these systems have been well documented and action shouldproceed immediately.

9.26%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $1,055,050

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Page 3: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 3 of 42

Electrical Summary:1200 Amp 120/208 volt three phase manufactured by Westinghouse, fed from a pad mounted transformer throughunderground cables. Main Distribution Panel is upgraded, and is 60% full. Branch circuit panels are 80% full. Wiring is inconduit. Lighting fixtures have been upgraded in 2004 to T8 lamps and electronic ballasts for interior areas. HPS wallpacks and pole mounted fixtures are used for exterior lighting. Gym has metal halide high bay fixtures. Lighting isswitched using line voltage switches. Exterior lighting is controlled by photo cell. Emergency lighting is provided requiredareas. LED EXIT signs are located at required exits. Fire alarm system is inspected on annual basis. Bells are locatedin hallways. Security system is operational. Main entrance buzzers operate after hours. Clocks in school are 120 volt,stand alone. Telephone handsets are located in offices and library. Intercom switches are located in classrooms. Publicaddress system is complete with CD and tape players and radio. Supernet is in school. Computer network and hardwareis located in server room. Cat5 cabling is used. Televisions, VHS and DVDs are on mobile carts. Rating of acceptable.

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Page 4: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 4 of 42

A1010.01 Wall Foundations (Continuous Footing)

A1020 Special Foundations

A1030 Slab on Grade*

B1010.01 Floor Structural Frame*(Building Frame)

B1010.02 Structural Interior Walls Supporting Floors (or Roof)*

B1010.03 Floor Decks, Slabs, and Toppings*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

100

0

100

100

100

100

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

S1 STRUCTURAL

1958, 1959 sections - Concrete wall foundation with continuous concrete footing.

1985, 1992, 1997 sections - Concrete grade beam on concrete pile.

1958, 1959, 1985, 1992, 1997 sections - Main floor except 2 stages.

1958, 1959 sections - The 2nd floor is concrete floor on steel joists supported by concrete beams, concrete block walls andwood frame walls. The stages are hardwood floor on wood deck supported by wood frame walls. 1985 & 1992 sections - The 2nd floor is concrete floor on steel joists supported by concrete block walls.

1958 & 1959 sections - Concrete block walls and wood frame walls. 1992, 1985, and 1997 sections - Concrete block walls.

1958, 1959, 1985, 1992, 1997 sections - Main floor are concrete slab on grade except 2 stages. 1958, 1959 sections - The 2nd floor is concrete floor on steel joists supported by concrete beams, concrete block walls andwood frame walls. The stages are hardwood floor on wood deck supported by wood frame walls. 1985 & 1992 section - The 2nd floor is concrete floor on steel joists supported by concrete block walls.

Page 5: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 5 of 42

B1010.05 Mezzanine Construction*

B1010.07 Exterior Stairs**

B1020.01 Roof Structural Frame*

B1020.04 Canopies*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1958

1959

0

0

Installed

Installed

Installed

Installed

80

40

100

50

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace exterior concrete stair.

Lifecycle Replacement 2010 $12,000 Low

Replace exterior concrete stair. (1 stair)Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

Mezzanine above stages are plywood deck on wood joists and steel beams supported by concrete block walls.

Exterior concrete stair at east side.

1958 section - Wood deck on wood joists supported by concrete beams, concrete block walls and wood frame walls for thebuilding portion. Wood deck on steel joists supported by concrete beams and concrete block walls for the gymnasium. 1959 sections - Wood deck on wood joists supported by concrete beams, concrete block walls and wood frame walls. 1985, 1992 & 1997 sections - Metal deck on steel joists supported by concrete block walls.

1958, 1959 section - canopies are wood frame. 1985 section - Canopies are concrete frame. 1997 section - Canopies are steel frame.

Page 6: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 6 of 42

B2010.01.02.01 Brick Masonry: Ext. Wall Skin*

B2010.01.02.02 Concrete Block: Ext. Wall Skin*

B2010.01.06.03 Metal Siding**

B2010.01.08 Cement Plaster (Stucco): Ext. Wall*

B2010.01.09 Expansion Control: Exterior Wall Skin*

B2010.01.13 Paints (& Stains): Exterior Wall**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1959

0

1985

0

0

1998

Installed

Installed

Installed

Installed

Installed

Installed

75

75

40

75

75

15

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

S2 ENVELOPE

Brick masonry cladding on north wall.

1958, 1959 sections - Some portions have stucco cladding on concrete block walls. 1985 section - Stucco cladding on concrete block walls. 1992 section - Stucco cladding on metal z bar & rigid insulation on concrete block walls. 1997 section - Stucco cladding on insulation system on concrete block walls.

1958, 1959 sections - Some portions have metal siding cladding.

All phases have stucco cladding.

All phases have original expansion joints.

1958, 1959, 1985 - These phases have painted concrete walls.

Page 7: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 7 of 42

B2010.02.01 Cast-in-place Concrete:Ext.Wall Const*

B2010.02.03 Masonry Units: Ext. Wall Const.*

B2010.02.05 Wood Framing*: Ext. Wall Const.

B2010.06 Exterior Louvers, Grilles, and Screens*

B2010.09 Exterior Soffits*

B2020.01.01.02 Aluminum Windows (Glass & Frame)**

B2030.01.01 Aluminum-Framed Storefronts**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

1988

Installed

Installed

Installed

Installed

Installed

Installed

Installed

100

100

100

30

30

40

30

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

1958, 1959, 1985 section - These phases have cast-in-place concrete exterior walls.

All phases have concrete block walls.

1958, 1959 - These phases have wood frame walls.

All phases have aluminum louvers and grilles.

1958, 1959, 1985 sections - Painted wood soffits. The canopies of the exterior entrances to the gymnasium have stuccofinish for the soffits. 1992, 1997 sections - Pre-finished metal soffits.

1958, 1959 sections - The original windows were replaced with aluminum windows in 1988. 1985, 1992, 1997 sections - Aluminum windows.

1958, 1959 sections - Aluminum doors in aluminum frames for all entrances.

Page 8: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 8 of 42

B2030.05 Other Exterior Doors** Metal Door

B3010.04.01 Built-up Bituminous Roofing (Asphalt & Gravel)**

B3010.04.04 Modified Bituminous Membrane Roofing (SBS)**

B3010.08.02 Metal Gutters and Downspouts**

4 - Acceptable

3 - Marginal

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

0

1986

0

1985

Installed

Installed

Installed

Installed

30

25

25

30

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace BUR roof

Failure Replacement 2009 $150,000 High

The roofs of the 1958 two storey wing and the 1959 addition arevery spongy and deteriorated.

Concern:

According to Roof Inspection Reported in November, 2001,these roofs need re-roofing. Re-roof these roofs with BUR.(1,750.00 sq.m.)

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

1958 section - Hollow metal door in pressed steel frame for mechanical room. Installed in 2003. 1985, 1992, 1997 sections - Hollow metal doors in pressed steel frames.

1958 - BUR. Re-roofed the 2 storey wing in 1986. ( Note: According to Roof Inspection Report dated November, 2001, itneeds re-roofing in 2009.) 1959 - BUR. Re-roofed the 2 storey addition in 1986. ( Note: According to Roof Inspection Report dated November, 2001, itneeds re-roofing in 2009.)

1958 section - The BUR of the gymnasium and the 1 storey west wing was re-roofed with SBS in 2004 according to SchoolBoard's record. 1985 section - The BUR was re-roofed with SBS in 2004. 1992 section - SBS. 1997 section - SBS.

1958 section - Metal downspouts on east exterior wall.

Page 9: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 9 of 42

B3020.01 Skylights**

B3020.02 Other Roofing Openings (Hatch,Vent, etc)*

4 - Acceptable

4 - Acceptable

Rating

Rating

1997

0

Installed

Installed

20

25

Design Life

Design Life

MAR-07

MAR-07

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Three skylights in corridor.

All sections have vents, chimneys, exhaust hoods and hatches on the roof.

Page 10: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 10 of 42

C1010.01 Interior Fixed Partitions*

C1010.04 Interior Balustrades and Screens, Interior Railings*

C1010.05 Interior Windows*

C1010.08 Other Partitions* Glass Block

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

Rating

Rating

Rating

Rating

0

0

0

1997

Installed

Installed

Installed

Installed

50

40

40

50

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

S3 INTERIOR

1958, 1959 sections - Concrete block walls and gypsum board on wood frame partitions. 1985 section - Concrete block walls. 1992, 1997 sections - Concrete blocks walls and gypsum board on metal stud frame partitions.

1958, 1959 sections - Metal balustrades & railings at stairs.

1958 - Georgian wired glass installed in 1997. 1985, 1992, 1997 - Georgian wired glass and tempered glass set in pressed metal frames in vision sidelites at doors andwindows.

Glass block partitions at administration office.

Page 11: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 11 of 42

C1020.01 Interior Swinging Doors**

C1020.03 Interior Fire Doors*

4 - Acceptable

4 - Acceptable

Rating

Rating

0

0

Installed

Installed

40

50

Design Life

Design Life

MAR-07

MAR-07

Updated

Updated

Replace interior doors and frames

Lifecycle Replacement 2010 $79,000 High

Wood doors with glass inlays do not meet code requirementsfor stairwells.

Concern:

Replace the existing doors and frames in the 1958 building and1959 addition with new doors and frames to meet coderequirement. (71 doors and frames)

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

1958, 1959 sections - Solid core wood doors in wood frame throughout except the main floor area modernized in 1997.French wood doors in wood frames at stairwells and in corridors. 1985 section - Solid core wood doors and hollow metal doors in pressed steel frames. Solid core wood doors in woodframes for phy. ed. offices. 1992 section - Solid core wood doors in pressed steel frames. 1997 section - Solid core wood doors and hollow metal doors in pressed steel frames.

1985 - Mechanical room has hollow metal door in pressed steel frame. 1992 - Mechanical room has solid core wood door in wood frame. Hollow metal doors in pressed steel frames at end ofcorridors. 1997 - Mechanical room has solid core wood door in pressed steel frame. Hollow metal doors in pressed steel frames atend of corridors.

Page 12: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 12 of 42

C1020.03 Interior Fire Doors* Rolling Fire Shutter

C1020.07 Other Interior Doors* Dark Room Door

C1030.01 Visual Display Boards**

C1030.02 Fabricated Compartments(Toilets/Showers)**

C1030.06 Handrails*

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1959

1992

1992

0

0

Installed

Installed

Installed

Installed

Installed

50

15

20

30

50

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

1958, 1959 sections - Rolling fire shutters on main floor corridor and 2nd floor corridor to separate the 1958 building from the1959 addition.

1992 - A special metal rotating door for the dark room.

Whiteboards, chalkboards and tackboards located throughout the school.

1958 section - Floor mounted metal toilet partitions in boy's washrooms and girl's washrooms. Installed in 1991. 1985 section - Floor mounted metal toilet partitions in boy's washroom, girl's washroom and girl's shower room.

1958 section - Metal handrails in stairs from main floor to 2nd floor, in stairs from main floor to gymnasium and in stairs frommain floor to mezzanine above stage. 1959 section - Metal handrails in stairs from main floor to 2nd floor. 1985 section - Metal handrails from main floor to 2nd floor.

Page 13: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 13 of 42

C1030.08 Interior Identifying Devices*

C1030.10 Lockers**

C1030.12 Storage Shelving*

C1030.14 Toilet, Bath, and Laundry Accessories*

C2010 Stair Construction*

C2020.02 Terrazzo Stair Finishes*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1996

0

0

1996

0

0

Installed

Installed

Installed

Installed

Installed

Installed

20

30

20

20

100

60

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Plastic signs in most areas.

1958 & 1959 sections- Single tier metal lockers in main floor corridor and 2nd floor corridor. Installed in 1982. 1985 sections - Two tier metal lockers in boy's change room and girl's change room. 1992 & 1997 sections - Single tier metal lockers in corridor.

Painted and clear finish storage shelving throughout.

Commercial grade mirrors, soap dispensers, paper towel dispensers and toilet holders located in all washrooms.

1958 section - Concrete stairs to 2nd floor. Concrete stairs from main floor to gymnasium. Concrete stairs from main floor tomezzanine above stage. Concrete stair from main floor to music room. Wood stair from music room to stage in music room.1959 section - Concrete stair to 2nd floor. 1985 section - Steel stairs with concrete filled metal pans for treads to 2nd floor.

1958 & 1959 sections - Terrazzo finish on stairs to 2nd floor.

Page 14: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 14 of 42

C2020.05 Resilient Stair Finishes**

C2020.11 Other Stair Finishes* Wood

C3010.01 Concrete Wall Finishes* Concrete Block

C3010.02 Wall Paneling** Fibreglass Wall Panel

C3010.03 Plaster Wall Finishes*

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1992

2000

0

1997

0

Installed

Installed

Installed

Installed

Installed

20

10

100

30

60

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

1958 section - Resilient finish on stairs from main floor to music room, on stairs from main floor to gymnasium and on stairsfrom main floor to mezzanine above stage. 1985 section - Resilient finish on stairs from main floor to 2nd floor.

Clear wood finish for stair from music room to stage.

1958 section - Concrete block in south vestibule, gym. storage rooms. 1985 section - Concrete block in mechanical room, phy. ed. offices, stairs to 2nd floor and 2nd floor exercise room, 1992 section - Concrete block in vestibule, corridor, industrial arts room, home economics room, storage rooms. 1997 section - Concrete block in drama room, storage room, work rooms, mechanical room, janitor room, computerclassroom, vestibule, corridor and library.

Fibreglass wall panels on lower portion of wall in drama room.

1958 section - Plaster finish in corridors, stairwells, main entrance lobby, gymnasium and stages. 1959 section - Plaster finish in corridors, stairwell & vestibule.

Page 15: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 15 of 42

C3010.04 Gypsum Board Wall Finishes*

C3010.06 Tile Wall Finishes**

C3010.09 Acoustical Wall Treatment**

C3010.11 Interior Wall Painting**

C3010.12.02 Vinyl Wall Covering

C3010.14 Other Wall Finishes** Texture Wall Coating

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

Rating

Rating

Rating

Rating

Rating

Rating

0

0

2001

2001

1997

1998

Installed

Installed

Installed

Installed

Installed

Installed

60

40

20

10

15

20

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

1958 section - Painted gypsum boards in corridors, classrooms, computer classroom, art room, science classrooms,science prep. rooms, janitor rooms, storage rooms, counseling room, infirmary room, electrical room, library, administrationoffice, offices workmen, staff room, main entrance lobby, music room, kitchen, lounge & storage rooms in the mezzanineabove the stage. 1959 section - Painted gypsum board corridors, classrooms, conference room, staff room and storage room. 1985 section - Painted gypsum board in boy's change room and girl's change room. 1992 section - Painted gypsum board in a few rooms in industrial arts room, home economics room, storage rooms. 1997 section - Painted gypsum in drama room, storage room, workrooms, mechanical room, janitor room, computerclassroom and library.

1958 section - Ceramic wall tiles in boy's washrooms and girl's washrooms. ( Note: These ceramic wall tiles were installedin 1991.) 1985 section - Ceramic wall tiles in boy's washroom, boy's change room, boy's shower room, girl's washroom, girl's changeroom and girl's shower room.

Wall carpet up to 2.135 m high on lower portion of walls in gymnasium.

Concrete block and gypsum board are painted.

Vinyl wall covering on walls of conference room on main floor.

Texture wall coating finish on upper portion of walls in exercise room on 2nd floor.

Page 16: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 16 of 42

C3020.01.02 Paint Concrete Floor Finishes**

C3020.02 Tile Floor Finishes**

C3020.03 Terrazzo Floor Finishes*

C3020.04 Wood Flooring**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2002

0

0

1958

Installed

Installed

Installed

Installed

10

50

75

30

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace hardwood floor.

Lifecycle Replacement 2010 $109,650 Low

Replace the hardwood floor in gymnasium and stages. (498.40sq.m.)

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

1958 & 1997 section - Painted concrete floor in mechanical room. 1985 section - Painted concrete floor in mechanical room and exercise room on 2nd floor. 1992 section - Painted concrete floor in mechanical room, storage room & finishing room in industrial arts room.

1958 section - Ceramic floor tiles in boy's washrooms and girl's washrooms. ( Note: These ceramic floor tiles were installedin 1991.) 1959 - Quarry tile in vestibule and storage room under the stair on main floor. 1985 section - Ceramic floor tiles in boy's washroom, boy's change room, boy's shower room, girl's washroom, girl's changeroom and girl's shower room.

1958 - Terrazzo on 2nd floor stair landings, storage room in one 2nd floor stair landing. 1959 - Terrazzo on 2nd floor stair landing.

Hardwood floor in gymnasium and stages. Re-finished the hardwood floor in gymnasium in 2005.

Page 17: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 17 of 42

C3020.07 Resilient Flooring** - vinyl sheet

C3020.07 Resilient Flooring** - vinyl tiles

C3020.08 Carpet Flooring**

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

0

0

1997

Installed

Installed

Installed

20

20

15

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace vinyl sheet flooring (35m2)

Replace 1980 VAT tiles (890 m2)

Lifecycle Replacement

Lifecycle Replacement

2010

2010

$2,800

$35,600

Low

Low

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

1985 - Vinyl sheet flooring in phy. ed. offices. 1992 - Vinyl sheet flooring in industrial arts room, office in industrial arts room, home economics room and storage rooms inhome economics room.

Vinyl tiles are throughout and were replaced in 1998, except for classrooms and the kitchen in the 1958 section andclassrooms on the second floor in the 1959 section that were installed in 1980.

1958 section - (Main floor of 2 storey wing modernized in 1997) Carpet in counseling rooms, 1 classroom, 1 computer room,library, administration office, offices and staff room. 1958 section - (One storey west wing) Carpet in lounge on mezzanine floor above stage. Installed in 1997. 1959 section - Carpet in conference room and 1 classroom on main floor. Installed in 1997. 1997 section - Carpet in drama room, workrooms, computer room, office, library, administration office, offices and staffroom.

Page 18: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 18 of 42

C3020.14 Other Floor Finishes** Granwood Tile

C3030.02 Ceiling Paneling (Wood)*

C3030.03 Plaster Ceiling Finishes*

C3030.04 Gypsum Board Ceiling Finishes*

2 - Poor

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1958

1958

0

0

Installed

Installed

Installed

Installed

20

60

60

50

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace grandwood tiles

Failure Replacement 2007 $61,500 Unassigned

The granwood tiles are cracked and are a trip hazard.Concern:

Replace all granwood tiles in the 1958 building with vinyl sheetflooring. (815.00 sq.m.)

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

1958 - (Two storey wing) Granwood tile in main floor corridor and 2nd floor corridor. 1958 - (One storey west wing) Granwood tile in corridor and 2 gym.storage rooms. A lot of the granwood tiles are cracked and broken creating a tripping hazzard.

Wood board ceiling in gymnasium.

1958 section - Plaster ceiling finish in corridors, stages, lounge in mezzanine above stages, music room, janitor rooms,stairwells, storage rooms, gym. storage rooms and electrical room. 1959 section - Plaster ceiling finish in corridors, vestibule, stairwell and storage rooms. 1985 section - Plaster ceiling finish in stairwells, vestibules, boy's washroom, boy's change room, boy's shower room, girl'swashroom, girl's change room, girl's shower room, shower rooms in phy. ed. offices.

1958 section - (Main floor area modernized in 1997) Painted gypsum board ceilings in 3 detention rooms, staff washrooms,hub room and storage room in library. 1992 section - (Main floor) Painted gypsum board ceilings in dark rooms, finishing room, 2 storage rooms in industrial artsroom and storage room in home economics room. 1992 section - (2nd floor) Painted gypsum board ceiling in vestibule to mechanical room.

Page 19: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 19 of 42

C3030.06 Acoustic Ceiling Treatment (Susp.T-Bar)**

C3030.07 Interior Ceiling Painting**

C3030.09 Other Ceiling Finishes* Adhered Ceiling Tile

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

0

1996

0

Installed

Installed

Installed

25

20

50

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace adhered ceiling tiles with suspened T-Barsystem with acoustic ceiling tiles.

Lifecycle Replacement 2010 $68,500 Low

Replace the adhered ceiling tiles in the 1958 building and 1959addition with suspended T-Bar system with acoustic ceilingtiles. (1,540.00 sq.m.)

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

1958 section - Main floor: Suspended T-Bar system with acoustic ceiling tile in administration office, offices, staff room,workroom, storage rooms, library, classroom & computer room in library. 2 storey wing modernized in 1997. 1958 section - Main floor of 2 storey wing: Suspended T-Bar system with acoustic ceiling tiles in science classrooms,science prep. room, boy's washroom, girl's washroom, 2 counseling rooms, 1 storage room, main entrance lobby and southvestibule. 2nd floor of 2 storey wing: Suspended T-Bar system with acoustic ceiling tiles in boy's washroom, girl'swashroom and art room. 1959 section - Main floor: Suspended T-Bar system with acoustic ceiling tiles in conference room. 1985 section - Main floor: Suspended T-Bar system with acoustic ceiling tiles in phy. ed. Offices. 2nd floor: Suspended T-Bar system with acoustic ceiling tiles in exercise room. 1992 section - Main floor: Suspended T-Bar system with acoustic ceiling tiles in office & drafting room in industrial artsroom vestibule, corridor, home economics room. 1997 section - Suspended T-bar system with acoustic ceiling tiles in drama room, storage room of drama room, workroom,computer classroom, office & workroom in computer classroom, vestibule and corridor.

Gypsum board ceilings are painted. Painted in 1996.

1958 section - (Main floor of 2 storey wing) Adhered ceiling tiles in 3 classrooms and infirmary room. 1958 section - (2nd floor of 2storey wing) Adhered ceiling tiles in computer classroom, science classroom and 8classrooms. 1959 section - (Main floor) Adhered ceiling tiles in 4 classrooms. 1959 section - (2nd floor) Adhered ceiling tiles in 4 classrooms, 1 storage room and staff room.

Page 20: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 20 of 42

C3030.09 Other Ceiling Finishes* Steel Deck

5 - GoodRating

1992Installed

50Design Life

MAR-07Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

1992 - (Main floor) Steel deck ceiling in industrial arts room. 1992 - (2nd floor) Steel deck ceilings in mechanical room and electrical room.

Page 21: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 21 of 42

D2010.01 Water Closets**

D2010.02 Urinals** - 1985 section

D2010.02 Urinals** 1958/59 section

D2010.03 Lavatories**

D2010.04 Sinks**

5 - Good

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

2001

1985

2001

2001

1992

Installed

Installed

Installed

Installed

Installed

35

35

35

35

30

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

S4 MECHANICAL

Floor mounted flush valve water closets used in the student's washrooms. Standard units have elongated bowls with openfront seats. Each washroom includes one handicapped water closet with elongated bowl. Flush tank water closets are used in staff washrooms and gymnasium office washrooms. These are 5 gallon flush modelsand most have elongated bowls and open seats.

Floor mounted urinals with flush valves.

Wall mounted urinals with flush valves.

Vanity mounted porcelain enameled steel with ribbed handle faucets.

Single compartment stainless steel sinks for science labs complete with goose neck faucets and bottle traps. Single and double compartment stainless steel sinks with swing spouts in the Home Economics classrooms. One two-compartment stainless steel sink for staff room with swing spout. Art room custom stainless steel sinks have plaster traps. Photo sinks provided in industrial arts area. There is a semicircular, fibreglass wash fountain in the shop area. Three floor mounted janitor's sinks.

25

4

8

16

22

Capacity Size

Capacity Size

Capacity Size

Capacity Size

Capacity Size

number

number

number

number

number

Capacity Unit

Capacity Unit

Capacity Unit

Capacity Unit

Capacity Unit

Page 22: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 22 of 42

D2010.05 Showers**

D2010.08 Drinking Fountains / Coolers**

D2020.01.01 Pipes and Tubes: Domestic Water*

D2020.01.03 Piping Specialties (Backflow Preventors)**

D2020.02.02 Plumbing Pumps: Domestic Water**

D2020.02.06 Domestic Water Heaters**

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

1985

2001

0

1992

1996

1996

Installed

Installed

Installed

Installed

Installed

Installed

30

35

40

20

20

20

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Wall mounted showers in boys' change rooms with push button mixing valves. Six shower stalls in girls' change room. Private showers in Phys. Ed. offices. Thermostatic tempering valve in Phys Ed office.

China, wall hung water fountains in corridors.

Copper piping throughout. Much of the original piping was replaced during the 2001 renovation. Some 1985 piping remains.

Backflow prevention devices have been provided on the boiler feed systems.

Armstrong inline circulator used for domestic hot water recirculation in main mechanical room.

John Wood model JWE402NA-04 natural gas fired, tank type water heater located in the main mechanical room. Unitsserve the washrooms in the two story classroom areas.

16

6

2

9.3

Capacity Size

Capacity Size

Capacity Size

Capacity Size

number

number

number

kW

Capacity Unit

Capacity Unit

Capacity Unit

Capacity Unit

Page 23: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 23 of 42

D2020.02.06 Domestic Water Heaters** - 1985

D2020.03 Water Supply Insulation: Domestic*

D2030.01 Waste and Vent Piping*

D2040.01 Rain Water Drainage Piping Systems*

D2040.02.04 Roof Drains**

3 - Marginal

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1985

2001

1959

1959

1992

Installed

Installed

Installed

Installed

Installed

20

30

50

50

40

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Replace Domestic Water Heater

Operating Efficiency Upgrade 2008 $6,000 High

Unit is oversized for the application.Concern:

Replace the water heater with a smaller capacity unit.Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

A.O Smith model BT500H-774S natural gas fired, tank type water heater is located in the gymnasium mechanical room.Unit serves the the 1985 gymnasium locker room addition.

Fiberglass insulation on all domestic hot and cold domestic water lines. Insulation has been recovered with canvas inexposed areas.

Cast iron and copper DWV used throughout. Some repairs and minor revisions use ABS piping. Cast iron piping uses bell& spigot and MJ clamps.

Cast iron with MJ clamps.

Deep sump open flow roof drains with cast aluminum strainers.

146

18

Capacity Size

Capacity Size

kW

number

Capacity Unit

Capacity Unit

Page 24: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 24 of 42

D3010.02 Gas Supply Systems*

D3020.02.01 Heating Boilers and Accessories: H.W.**

D3020.02.01 Heating Boilers and Accessories: H.W.** CTS

D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler**

D3020.02.03 Water Treatment: H. W. Boiler*

5 - Good

5 - Good

4 - Acceptable

4 - Acceptable

5 - Good

Rating

Rating

Rating

Rating

Rating

2001

2001

1992

2001

2001

Installed

Installed

Installed

Installed

Installed

60

35

35

30

30

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Gas meter is located in main mechanical room adjacent to the main entrance. Gas is regulated from 15# to low pressurefor distribution. A branch line runs from the main mechanical room to the CTS mechanical room to serve gas firedappliances in the 1992 addition. This gas line runs exposed in the corridor. Gas piping is welded steel throughout. Pipingsupports are adequate.

Two RBI, model 33HB2800 natural gas fired, atmospheric copper-tube hot water heating boilers provide heating to perimeterradiation, unit heaters, and reheat coils throughout the 1958 and 1959 portions of the facility. Each boiler has a high altitudeoutput of about 605 kW. A Taco air separator and two steel expansion tank have been provided.

Two Allied Superhot, model AAE840 natural gas fired, atmospheric steel finned-tube hot water heating boilers provideheating to perimeter radiation, unit heaters, and heating coils in the 1992 CTS addition at the south end of the facility. Eachboiler has a high altitude output of about 177 kW. An Extrol AX-120 bladder type expansion tank has been provided.

B-vent up through the roof. Combustion air with insulated trap.

Water treatment is provided for both heating systems including side stream filter, chemical pot feeder.

1210

354

Capacity Size

Capacity Size

kW

kW

Capacity Unit

Capacity Unit

Page 25: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 25 of 42

D3020.03.01 Furnaces**

D3020.03.02 Chimneys (&Comb. Air): Furnace*

D3040.01.01 Air Handling Units: Air Distribution** 1958 Gymnasium

4 - Acceptable

4 - Acceptable

2 - Poor

Rating

Rating

Rating

1986

1986

1958

Installed

Installed

Installed

25

30

30

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace Furnaces

Replace Air Handling Unit

Lifecycle Replacement

Failure Replacement

2010

2008

$24,000

$40,000

Low

High

It is in poor condition and is very difficult to service due to itslocation.

Concern:

Replace existing furnaces. Consider using ventilation systemswith hot water heating coils from existing heating system.

Provide new gymnasium ventilation system. Install in existingunused storage room.

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

A Flamemaster EM-235 fresh air furnace is used for locker room ventilation. A Lennox model G14Q3-80-C3 pulse furnace provides heating and ventilation for the gymnasium offices. A Lennox model G14Q5-130 pulse furnace provides heating and ventilation for the upper level multi-purpose room.

ABS flue piping for pulse furnaces. B-vent for fresh air furnace.

The ventilation for the gymnasium is provided by a constant volume custom air handling unit located in the ceiling of astorage area at the southeast corner of the gymnasium. The unit includes a forward curved supply fan, filters, hot waterheating coil, and mixing section. The unit was manufactured by Canadian Blower model 153-C-Lowboy.

4000Capacity Size

L/sCapacity Unit

Page 26: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 26 of 42

D3040.01.01 Air Handling Units: Air Distribution** 1992 CTS

D3040.01.01 Air Handling Units: Air Distribution** 1997 Addition

D3040.01.02 Fans: Air Distribution*

D3040.01.03 Air Cleaning Devices:Air Distribution*

D3040.01.04 Ducts: Air Distribution* Gymnasium

D3040.01.04 Ducts: Air Distribution* - 1997 Addition

5 - Good

5 - Good

5 - Good

4 - Acceptable

4 - Acceptable

5 - Good

Rating

Rating

Rating

Rating

Rating

Rating

1992

1997

1992

1992

1958

1997

Installed

Installed

Installed

Installed

Installed

Installed

30

30

30

30

50

50

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

The ventilation for the CTS area at the south end of the school is provided by a single, constant volume custom air handlingunit. The unit includes a forward curved supply fan, filters, pumped hot water heating coil, and mixing section. Unit isEngineered Air model LM-4-C. There is an Engineered Air model HE-70 direct fired make-up air unit interlocked with the IA dust collection system.

The ventilation for the 1997 Addition and renovation area at the west side of the 1958 main floor corridor is provided by aconstant volume custom air handling unit. The unit includes forward curved supply and return fans, filters, pumped hot waterheating coil, and mixing section. Unit is SSM model HQ-100. Unit serves Library, Computing, Administration and Ancillary.

Return fan from the CTS area is a vertically mounted Carnes plenum fan interlocked with the air handling unit for that area.

Non-recirculating dust collection system in the IA area.

Low velocity ductwork above gymnasium ceiling.

Low velocity ductwork used throughout, concealed in ceiling space.

5000

1700

Capacity Size

Capacity Size

L/s

L/s

Capacity Unit

Capacity Unit

Page 27: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 27 of 42

D3040.01.04 Ducts: Air Distribution* CTS

D3040.01.07 Air Outlets & Inlets:Air Distribution*

D3040.03.01 Hot Water Distribution Systems**

D3040.03.01 Hot Water Distribution Systems** - CTS

5 - Good

4 - Acceptable

4 - Acceptable

5 - Good

Rating

Rating

Rating

Rating

1992

1997

1959

1992

Installed

Installed

Installed

Installed

50

30

40

40

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace Hot Water Distribution

Lifecycle Replacement 2010 $90,000 Low

Replace the hot water distribution system.Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

Low velocity ductwork used throughout. Exposed overhead in the IA area. Concealed in ceiling space of Home Economicsarea.

Ceiling diffusers in the 1992 and 1997 additions.

Heated water from the main heating boilers is circulated through steel piping to perimeter wall fin radiation, vestibule cabinetunit heaters, unit heaters and unit ventilators. Primary circulating pumps (P-1 and P-2) are Taco base mounted, end suction model FE3007-7 pumps capable of 25.2lps@ 120kPa each. A third Taco base mounted, end suction pump, model FE2506-5.4 pump is used to distribute heatingwater to the reheat coils and radiation in the 1997 addition (11lps@135kPa). Pumps were installed in 2001. The majorityof the piping distribution outside the mechanical room is from the 1958 and 1959 construction.

Bell & Gossett horizontal in-line pumps model 1-1/2AB are used to distribute heating water to perimeter radiation, reheatcoils, and heating coils in the CTS area. There is a 2-way modulating valve for pressure by-pass and a 3-way modulatingvalve for temperature reset control.

Page 28: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 28 of 42

D3040.04.01 Fans: Exhaust**

D3040.04.03 Ducts: Exhaust*

D3040.04.05 Air Outlets and Inlets: Exhaust*

D3050.02 Air Coils**

1 - Critical

4 - Acceptable

4 - Acceptable

5 - Good

Rating

Rating

Rating

Rating

1959

1959

1959

1997

Installed

Installed

Installed

Installed

30

50

30

30

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace Exhaust Fans

Failure Replacement 2007 $80,000 Unassigned

Exhaust fans cannot be operated when the boilers are requiredfor heating because they create a severe negative pressuresituation in the building resulting in back-drafting of the boilers.In order to compensate for this problem, the DDC controlsystem shuts the fans off whenever there is a call for heating inthe building. This means that there is virtually no exhaust fromthe classrooms or the washrooms during the winter months.

Concern:

Replace the exhaust fans with heat recovery ventilation unitssized to provide adequate exhaust and ventilation air for theareas presently served by the existing fans.

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

There are three roof mounted spun aluminum exhaust fans that extract air from the classrooms and washrooms in the1958/59 sections. One fan is used for the 1959 north classrooms. The other two fans serve the east and west sides ofthe 1958 classroom wings. These fans were designed to operate continuously in conjunction with the classroom unitventilators to provide ventilation air for the school.

Low pressure ductwork in corridor ceiling space from each classroom to roof mounted exhaust fans.

400x150 exhaust grilles in corridor wall of classrooms in the 1958 and 1959 sections of the school.

Reheat coils installed in low pressure ductwork to serve 1997 addition.

3

26

Capacity Size

Capacity Size

number

number

Capacity Unit

Capacity Unit

Page 29: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 29 of 42

D3050.05.01 Convectors**

D3050.05.03 Finned Tube Radiation**

D3050.05.06 Unit Heaters**

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1958

1959

1959

Installed

Installed

Installed

40

40

30

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace Convectors (2)

Replace Radiation

Replace 8 Entrance Heaters

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2010

2010

2010

$2,000

$48,000

$5,000

Low

Low

Low

Replace finned tube radiation. (160 meters)Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-07

MAR-07

MAR-07

Two convectors are used to heat the staff room above the stage, adjacent to the gymnasium.

Radiation behind millwork in classrooms. Radiation cabinets in stairwells.

Surface mounted cabinet unit heaters located at entrance. Horizontal unit heaters are used in the mechanical room forcombustion air heating.

2

0

8

Capacity Size

Capacity Size

Capacity Size

number

N/A

number

Capacity Unit

Capacity Unit

Capacity Unit

Page 30: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 30 of 42

D3050.05.07 Unit Ventilators**

D3050.05.08 Radiant Heating (Ceiling & Floor)**

D3060.02.03 Pneumatic and Electric Controls

2 - Poor

5 - Good

4 - Acceptable

Rating

Rating

Rating

1959

1997

2001

Installed

Installed

Installed

30

35

40

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Provide Ventilation System

Indoor Air Quality Upgrade 2007 $126,000 Unassigned

Unit ventilators are not capable of providing adequate fresh airto the classrooms to meet current standards. Associatedexhaust fans are turned off in cold weather so no fresh air isadmitted to the classrooms.

Concern:

Provide new ventilation systems capable of providingacceptable indoor air quality to ASHRAE standards.

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

Nesbitt hot water unit ventilators are used in conjunction with roof mounted exhaust fans to provide tempered ventilation airto the classrooms.

Linear ceiling mounted aluminum radiant panel provides space heating for the 1997 addition areas.

Most control actuators are pneumatic. Some on newer systems are electronic. Control air is produced by a Husky tank mounted simplex compressor with an Omega refrigerated air dryer. Line voltage thermostats used on entrance heaters and unit heaters.

28Capacity Size

numberCapacity Unit

Page 31: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 31 of 42

D3060.02.05 Building Systems Controls (BMCS, EMCS)**

D4030.01 Fire Extinguisher, Cabinets and Accessories**

3 - Marginal

4 - Acceptable

Rating

Rating

2001

1997

Installed

Installed

25

30

Design Life

Design Life

MAR-07

MAR-07

Updated

Updated

Revise Controls

Indoor Air Quality Upgrade 2007 $24,000 High

Poor ventilation control results in either severe negativepressurization or poor space ventilation . Zone control forperimeter heating in the 1958/59 areas is very limited.

Concern:

Upgrade zone heating control for classrooms. Revise ventilation control in conjunction with ventilationupgrades.

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

Siemans Apogee BMCS was installed in 2001. Many existing pneumatic actuators have been retained on valves anddampers. Provides basic monitoring and control of building systems. Energy management capabilities are limited becauseof the limitations of the existing mechanical systems.

Fire extinguishers appropriately located in cabinets, fire hose cabinets, and wall hung in service spaces. 5# and 10# ABC

80Capacity Size

pointsCapacity Unit

Page 32: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 32 of 42

D5010.01 Main Electrical Transformers**

D5010.03 Main Electrical Switchboards (Main Distribution)**

D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)**

D5010.07 Motor Control Centers (Motor Control)**

D5010.07.02 Motor Starters and Accessories**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1992

1992

1958

1992

1992

Installed

Installed

Installed

Installed

Installed

40

40

30

30

30

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Install new panels in 1958 and 1959 sections

Lifecycle Replacement 2010 $15,000 Low

Install five new panels in 1958 / 1959 sections.Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

S5 ELECTRICAL

Event:

Type Year Cost Priority

Updated: MAR-07

Pad mounted transformer located at south side of school. Underground to main disconnect in electrical room. Maintained byFortis.

1200 Amp 120/208 volt three phase manufactured by Westinghouse. Main Distribution Panel is 60% full. Digital metershows peak at 300 Amp.

1958 and 1959 sections have Westinghouse original panels. 1992 and 1997 sections have Westinghouse panels. Panelsare 80% full.

200 Amp three phase 208 volt Westinghouse MCC in 1992 section. MCC is 50% full.

Allen Bradley, and Telemecanique starters. Siemens Apogee Automation for boilers control.. Power System 600 by Landis& Gryfor for energy management system.

Page 33: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 33 of 42

D5020.01 Electrical Branch Wiring*

D5020.01.03 Wiring Devices

4 - Acceptable

2 - Poor

Rating

Rating

1958

1958

Installed

Installed

50

0

Design Life

Design Life

MAR-07

MAR-07

Updated

Updated

Replace Electrical Branch Wiring

Add receptacles in classrooms.

Lifecycle Replacement

Program Functional Upgrade

2010

2007

$25,000

$10,800

Low

High

Need more receptacles in classrooms. Extension cords usedto reach equipment.

Concern:

Megger test existing wiring and upgrade as required in the 1958and 1959 sections.

Add 108 new receptacles in school in various classrooms.

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

Wiring is run in conduit.

Majority of the classrooms only have two receptacles.

Consequences of Deferral:Insufficient receptacles to educational tools.

Page 34: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 34 of 42

D5020.02.01 Lighting Accessories (Lighting Controls)*

D5020.02.02.02 Interior Florescent Fixtures**

D5020.02.02.03 Interior Metal Halide Fixture*

D5020.02.03.02 Emergency Lighting Battery Packs**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

1958

2004

2004

1992

Installed

Installed

Installed

Installed

30

30

30

20

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace lighting switches

Lifecycle Replacement 2010 $15,000 Low

Install new low voltage switching in 1958 and 1959 sectionsand connect to energy management system.

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

120 volt switching in classrooms and Gym. Keyed switching in hallways. Westinghouse lighting control panel for stagelighting.

All sections are equipped with surface mounted and recessed fluorescent light fixtures T8 lamps and electronic ballasts.

Metal Halide high bay light fixtures in Gym area.

Emergi-Lite emergency lighting and battery packs located through the school as required.

Page 35: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 35 of 42

D5020.02.03.03 Exit Signs*

D5020.02.05 Special Purpose Lighting*

D5020.03.01.04 Exterior H.P. Sodium Fixtures*

D5020.03.02 Lighting Accessories: Exterior (Lighting Controls)*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2004

1992

2004

2004

Installed

Installed

Installed

Installed

30

30

30

30

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Connect Exit signs to Emergency Power

Code Repair 2007 $5,000 High

Exit signs will not operate in power outage conditions.Concern:

Connect 25 EXIT signs to DC side of emergency lightingbattery packs.

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

LED exit signs located at required exits.

Spot lights are located in the Gym for stage lighting.

HPS wall packs located around perimeter of school. Pole mounted HPS light fixtures located in parking lot.

Photocell control used to operate exterior lighting.

Page 36: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 36 of 42

D5030.01 Detection and Fire Alarm**

D5030.02.01 Door Answering*

D5030.02.02 Intrusion Detection**

3 - Marginal

4 - Acceptable

3 - Marginal

Rating

Rating

Rating

1986

1992

1985

Installed

Installed

Installed

25

25

25

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace fire alarm system.

Replace security system

Failure Replacement

Program Functional Upgrade

2008

2008

$40,000

$15,000

High

High

Detectors and pull stations are required in 1958 boiler room.Visual signals are not available for the hearing impairedstudents.

Spare parts not available.

Concern:

Concern:

Install new fire alarm system with new detection devices andhorn strobes. Install horn strobe in music room. Install hornstrobe in boiler room.

Replace security system detectors and control panel.

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

Simplex Panel c/w 16 zones, bells, pull stations and smoke and heat detectors.

Main entrance push button buzzer, connected to the energy management system.

Bolt security system in school. DSC 864 control panel. Infrared detectors and door contacts located in various areas of theschool. Keyed door entry tied to security.

Page 37: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 37 of 42

D5030.03 Clock and Program Systems**

D5030.04.01 Telephone Systems**

D5030.04.04 Data Systems**

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1986

1999

1997

Installed

Installed

Installed

25

25

25

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace clock system.

Install telephone handsets and connect to PAsystem.

Lifecycle Replacement

Program Functional Upgrade

2010

2008

$20,000

$35,000

Low

High

Classrooms do not have communication outside the school.Concern:

Install new central master clock and 30 individual clocks inclassrooms, library, main administration office and Gym.

Install extra 35 telephone hand sets in classrooms. Connect topublic address system.

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

120 volt clocks in classrooms and Gym.

Nortel Meridian telephone system. Handsets are located in offices and library only. Four telephone lines and one fax line.

Cat5 cables are installed in conduit and free air in ceiling space. Supernet in school. Four servers by Dell and AB CDD plusMac server. Eleven switches by 3com. Eight Hubble patch panels. Network is 70% full.

Page 38: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 38 of 42

D5030.05 Public Address and Music Systems**

D5030.06 Television Systems*

D5090.01 Uninterruptible Power Supply Systems**

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1999

1997

1999

Installed

Installed

Installed

20

20

30

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Dukane Sound system c/w cd and tape players and radio. It also controls period bells. Intercom switches are located inclassrooms. FM systems are located in most class rooms. TOA900 Sound system is located in Gym.

Portable TV and VHS / DVD units on carts.

Three APC UPS units for servers. APC 500 UPS for telephone equipment. Triplite UPS for Emergency Evacuation Unit inoffice.

Page 39: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 39 of 42

E1020.07 Laboratory Equipment*

E1090 Other Equipment Art

E1090 Other Equipment Industrial Arts

E1090.04 Residential Equipment*

E1090.07 Athletic, Recreational, and Therapeutic Equipment*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

1958

1985

1992

1996

1990

Installed

Installed

Installed

Installed

Installed

25

0

0

25

15

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION

Fume hoods in science classroom and science prep room.

The art room has a kiln.

Industrial arts room has variety of manual and power wood working completed with dust collection system, metal worksequipment, electrical work equipment, small engine equipment, drafting equipment. It also has a darkroom with photoprocessing equipment.

Residential grade freezer and cooler in kitchen. Residential grade refrigerator, dishwasher and microwave oven in staff room. Residential grade refrigerator, range, stove, microwave oven, washer and dryer in home economic room.

Four basketball backboards and 1 score board in gymnasium.

Page 40: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 40 of 42

E2010.02 Fixed Casework**

E2010.03.01 Blinds**

E2010.03.06 Curtains and Drapes**

F2020.01 Asbestos*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

0

1995

1990

0

Installed

Installed

Installed

Installed

35

30

30

0

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Replace casework.

Lifecycle Replacement 2010 $127,000 Low

Replace the original casework in the 1958 original building andthe 1959 addition. (280.00 linear meter)

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

Event:

Type Year Cost Priority

Updated: MAR-07

Painted and plastic laminated plywood casework throughout. The 1958 and 1959 sections have original casework. (note:Modernized library and administration area in 1997. Upgraded art room in 1998. Modernized 2 science classrooms in 2000).

Venetian blinds throughout.

Stage has curtains and drapes.

The information for 1958 building and 1959, 1985 additions is from the asbestos audit report dated July, 2003. 1992 & 1997 sections - No asbestos audit report.

Page 41: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 41 of 42

K4010.01 Barrier Free Route: Parking to Entrance

K4010.02 Barrier Free Entrances

K4010.03 Barrier Free Interior Circulation

4 - Acceptable

3 - Marginal

2 - Poor

Rating

Rating

Rating

1997

0

0

Installed

Installed

Installed

0

0

0

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Install barier free push padles on entrance doors.

Install elevator and wheel chair lift.

Barrier Free Access Upgrade

Barrier Free Access Upgrade

2007

2007

$5,000

$82,000

High

High

It does not meet current code requirement.

There is no barrier free access to gymnasium, music room and2nd floor.

Concern:

Concern:

Install barrier free paddles on the main entrance doors.

Install a wheel chair lift to gymnasium. ($6,000.00) Install a wheel chair lift to music room. ($6,000.00) Install an elevator to 2nd floor. ($70,000.00)

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (B4023A)

S8 FUNCTIONAL ASSESSMENT

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

It has barrier free route from parking lot to the entrances.

No barrier free push paddles on entrance doors.

1958, 1959, 1997 - No elevator to 2nd floor. 1958 - No chair lift to gymnasium. No chair lift to music room.

Page 42: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 12, 2007 9:31 AM Page 42 of 42

K4010.04 Barrier Free Washrooms

4 - AcceptableRating

1991Installed

0Design Life

MAR-07Updated

Sherwood Park - Sherwood Heights Junior High School (B4023A)

There are barrier free washrooms.

Page 43: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM

RECAPP Facility Evaluation Report

Sherwood Heights Junior High School

S4023Sherwood Park

Page 44: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 2 of 9

S4023Building Id:

Sherwood Heights Junior HighBuilding Name:

Sherwood ParkLocation:Address:

0.00Gross Area (sq. m): $0Replacement Cost:0Construction Year:

Evaluation Date: September 29 2006

Kenneth M. Lee ArchitectEvaluation Company:

Ken LeeEvaluator Name:

The rating for other architectural site work is acceptable. The rating for mechanical site work is acceptable. Pad mounted transformer is located on south side, 1992 installation. 30 car receptacles are rail mounted, controlled byenergy management system in school. Lighting is controlled by photocell. Exterior lighting is done by HPS wall packsand pole mounted HPS light fixtures in the parking area.

General Summary:

Structural Summary:

Envelope Summary:

Interior Summary:

Mechanical Summary:

Electrical Summary:

0%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $51,000

Sherwood Park - Sherwood Heights Junior High School (S4023)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Page 45: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 3 of 9

G2010.02.02 Flexible Pavement Roadway (Asphalt)**

G2010.05 Roadway Curbs and Gutters*

G2020.02.02 Flexible Paving Parking Lots(Asphalt)**

4 - Acceptable

4 - Acceptable

3 - Marginal

Rating

Rating

Rating

2001

0

2001

Installed

Installed

Installed

25

25

10

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Install handicapped stalls.

Repair asphalt pavement.

Barrier Free Access Upgrade

Repair

2007

2007

$2,500

$2,500

High

High

No handicapped parking stalls. It does not meet coderequirement.

Some asphalt pavement is cracking and breaking up in thewest parking lot.

Concern:

Concern:

Install 1 handicapped parking stalls in closed proximity withsignage.

Repair the asphalt pavement in the west parking lot. (120.00sq.m.)

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (S4023)

S7 SITE

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

One roadway (asphalt) from Fir Street to the west parking lot. Two roadways (asphalt) from Fir Street to the east parking lot.

Concrete curbs and gutters at roadway from Fir Street to the west parking lot. The east parking lot has 2 roadways from FirStreet and the west roadway to this parking lot has concrete curb and gutter on the west side.

Asphalt paved west parking lot for 20 stalls. The asphalt pavement is in acceptable condition. Asphalt paved east parking lot for 42 stalls. Some asphalt pavement iscracking and breaking up. Require marked handicapped stalls in close proximity with signage.

Page 46: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 4 of 9

G2020.05 Parking Lot Curbs and Gutters*

G2020.06 Parking Lot Appurtenances

G2020.06.03 Parking Lot Signs*

3 - Marginal

5 - Good

2 - Poor

Rating

Rating

Rating

1990

0

0

Installed

Installed

Installed

25

0

25

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Replace concrete curbs.

Install parking lot signs.

Failure Replacement

Program Functional Upgrade

2007

2007

$6,000

$2,500

Unassigned

High

The west parking lot has broken concrete curbs,

No parking lot signs for staff and visitors parking stalls.

Concern:

Concern:

Replace the broken concrete curbs in the west parking lot.(30.00sq.m.)

Install metal parking lot signs for staff and visitors parkingstalls. (6 signs)

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (S4023)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

Concrete curbs and gutters in west parking lot. The west parking lot has broken concrete curbs.

Steel guard rails on steel posts in the west and east parking lots.

No parking lot signs for staff and visitors parking stalls.

Page 47: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 5 of 9

G2020.06.04 Pavement Markings*

G2030.02.02 Asphalt Pedestrain Pavement**

2 - Poor

3 - Marginal

Rating

Rating

0

2001

Installed

Installed

25

10

Design Life

Design Life

MAR-07

MAR-07

Updated

Updated

Install pavement markings for stalls.

Repave asphalt pavement.

Program Functional Upgrade

Repair

2007

2007

$2,500

$10,000

Unassigned

High

No pavement markings for parking stalls in west parking lot andeast parking lot.

The asphalt pavement on the north side of the west wing of the1958 original building is cracking and breaking up in a numberof areas.

Concern:

Concern:

Install pavement markings for parking stalls in west parking lotand east parking lot.

Re-pave the asphalt pavement on the north side of the westwing of the 1958 original building. (415.00 sq.m.)

Recommendation:

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (S4023)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-07

MAR-07

No pavement markings for parking stalls in west parking lot and east parking lot.

The asphalt pavement at the southwest portion of the school site is in acceptable condition. (Note: This asphalt pavement isan outdoor play area with 6 basketball backboards on steel posts.) The asphalt pavement at the south entrance of the gymnasium of the 1958 original building is in acceptable condition. The asphalt pavement on the south side of the school is in acceptable condition. The asphalt pavement on the east side of the school for bicycle racksis in acceptable condition. The asphalt pavement on the north side of the west wing of the 1958 original building is cracking and breaking up in anumber of areas.

Page 48: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 6 of 9

G2030.04 Rigid Pedestrian Pavement (Concrete)**

G2030.06 Exterior Steps and Ramps*

G2040.02 Fences and Gates**

3 - Marginal

4 - Acceptable

5 - Good

Rating

Rating

Rating

1997

1958

1990

Installed

Installed

Installed

15

15

30

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Rerplace concrete sidewalks.

Failure Replacement 2007 $32,500 High

Some concrete sidewalks cracked and are a tripping hazard.Concern:

Replace east concrete sidewalks, concrete sidewalk at theeast side of the west parking lot and some concrete sidewalksat the main entrance of the school. (230.00 sq.m.)

Recommendation:

Sherwood Park - Sherwood Heights Junior High School (S4023)

Event:

Type Year Cost Priority

Updated: MAR-07

At the north side of the school, a concrete sidewalk from Fir Street to the concrete pavement in front of the main entrance.Concrete sidewalks from this concrete pavement to the west parking lot and to an entrance of the west wing of the 1958original building. Some sidewalks are cracking and breaking up and needs replacement.. (Note: One sidewalk has aconcrete ramp to the west parking lot.) The concrete sidewalk at the east side of the west parking lot also needsreplacement. The concrete pavement in front of the north entrance to the gymnasium is acceptable. At the east side of the school, a concrete sidewalk from Fir Street to the concrete pavement of the east entrance of the1959 addition. A east concrete sidewalk from this concrete pavement on the east side of the school to the south concretesidewalk on the south side of the school. The concrete of this east sidewalk has a lot of cracks and needs replacement. At the south side of the school, the south concrete sidewalk to entrances at the south end of the school. A concretepavement has a concrete sculpture for skate boards. There is a concrete sidewalk connecting 2 concrete sidewalks from Fir Street to the school at the north side of the school.(Note:This concrete sidewalk is on the north side of the 1959 addition.)

A steel exterior stair south of the west wing of the 1958 original building. A concrete ramp in the concrete walkway from the west parking lot to the concrete pavement in front of the main entrance.

A steel guard post gate at the south side of the east parking lot. A steel guard post gate at the south side of the westparking lot. Chain link fences for the asphalt paved outdoor play area south of the west wing of the 1958 original building.

Page 49: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 7 of 9

G2040.03 Athletic and Recreational Surfaces**

G2040.05 Site and Street Furnishings*

G2040.06 Exterior Signs*

G2040.08 Flagpoles*

G2040.11 Retaining Walls*

G2050.04 Lawns and Grasses*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

5 - Good

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

2001

1996

1959

1985

1958

1980

Installed

Installed

Installed

Installed

Installed

Installed

25

15

25

30

50

15

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (S4023)

An asphalt paved outdoor play area with 6 basketball backboards on steel posts at the southwest portion of the school site.A concrete sculpture on concrete pavement for skate boards and an asphalt paved outdoor play area on the south side ofthe school. The school uses the athletic and recreational facilities in the adjacent City's community park. These facilities are childrenplayground, volleyball court, soccer field, football field and basketball courts.

Wood benches in the asphalt paved outdoor play area at the southwest side of the school. Wood benches on the southlawn. Wood panic tables with benches on the east lawn.

A school name sign on the north exterior wall facing Fir Street. A free standing wood sign on the north lawn facing FirStreet.

One flagpole on a north lawn at main entrance.

Concrete retaining walls south of the west wing of the 1958 original building.

Lawns on 4 sides of the school.

Page 50: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 8 of 9

G2050.05 Trees, Plants and Ground Covers*

G3010.02 Site Domestic Water Distribution*

G3010.03 Site Fire Protection Water Distribution*

G3020.01 Sanitary Sewage Collection*

G3030.01 Storm Water Collection*

G3060.01 Gas Distribution*

G4010.02 Electrical Power Distribution Lines*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

1980

1958

1958

1958

1958

2001

1992

Installed

Installed

Installed

Installed

Installed

Installed

Installed

10

50

50

50

50

50

50

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (S4023)

Trees and plants on the north lawns. Trees on the south lawn.

100 mm domestic water from municipal service enters mechanical room adjacent to the main entrance.

Fire hydrants on Fir Street.

A 150 mm sanitary line ties into the municipal sewer service north of the property below Fir Street.

There are catch basins in the parking areas. Storm water from the building is connected to the municipal drainage systemin the street.

The medium pressure gas service connects into the utility main and runs underground to the point of entry outside the mainmechanical room adjacent to the main entrance of the building.

Underground feeders from pad mounted transformer to main distribution panel and main disconnect.

Page 51: RECAPP Facility Evaluation Report - … · RECAPP Facility Evaluation Report ... 1997 additions have grade beam on concrete pile foundation. ... 1200 Amp 120/208 volt three phase

Report run on: March 15, 2007 2:43 PM Page 9 of 9

G4010.03 Electrical Power Distribution Equipment*

G4010.04 Car Plugs-ins*

G4020.01 Area Lighting*

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

1992

1992

2004

Installed

Installed

Installed

50

25

25

Design Life

Design Life

Design Life

MAR-07

MAR-07

MAR-07

Updated

Updated

Updated

Sherwood Park - Sherwood Heights Junior High School (S4023)

Pad mounted transformer located at south side of school. Maintained by Fortis.

30 car receptacles rail mounted. Receptacles are controlled by the main energy system of the school.

HPS wall packs located around perimeter of school. Pole mounted HPS light fixtures located in parking area.