Report run on: January 26, 2005 4:32 PM RECAPP Facility Evaluation Report Vauxhall Elementary School B4202A Vauxhall Horizon School Division #67

RECAPP Facility Evaluation Report - Alberta · 2013-05-29 · RECAPP Facility Evaluation Report Vauxhall Elementary School B4202A ... Consideration should be given to upgrading the

Embed Size (px)

Citation preview

Report run on: January 26, 2005 4:32 PM

RECAPP Facility Evaluation Report

Vauxhall Elementary School

B4202AVauxhall

Horizon School Division #67

Report run on: January 26, 2005 4:32 PM Page 2 of 35

B4202ABuilding Id:

Vauxhall Elementary SchoolBuilding Name:

VauxhallLocation:423 - 7 Street N.Address:

0.00Gross Area (sq. m): $6,462,168Replacement Cost:0Construction Year:

Evaluation Date: May 1 2004

J.A Matthews ArchitectEvaluation Company:

Mr. Joe MatthewEvaluator Name:

(403) 320-2722Evaluator Phone:

The original school was constructed in 1952. There was a large addition with a gym added in 1968. In 1971 the gymwas expanded on and an extra classroom added. Since then they added a storage room in 1992, at which time theoriginal 1952 building was modernized. The 1968 and 1971 areas of the school are in poor condition and will requiremodernization.

General Summary:

Structural Summary:The original structure of the 1952 building is a wood framed construction on a cast in place concrete basement. The 1968,1971, and 1992 additions are all slab on grade. The structure of the later additions are generally in good condition, howeverthe structural integrity basement walls of the original 1952 building should be investigated.

Envelope Summary:The overall condition of the 1968, and 1971 envelope is in good condition. The stucco work on the 1952 section is badlydamaged. The roof for the 1952 structure was replaced in 1992 and the rest of the roof was replaced in 2001. Thealuminum framed windows in poor condition and will require replacement. The exterior wood doors are damaged andthere are no barrier free access; these items will have to be addressed in the near future.

Interior Summary:The interior of the 1952 area was modernized in 1992 and with the exception of the windows, carpet and ceiling. Itremains in good condition. The 1968 and 1971 sections are in disrepair, and will require a major modernization. Theflooring, ceiling, and windows are among the largest problems. Millwork, interior doors and paint are also in need ofrepair and or replacement.

Mechanical Summary:Overall, the condition of the mechanical systems is poor. The school is heated by a mixture of hot water heating, gas fired furnaces, and Shelva duct heaters. The furnacessupply air through an underground network of ducts. Low voltage thermostats are provided throughout and a pneumaticcontrols systems operates the hydronic system in the 1952 wing. Major deficiencies with the mechanical system are related to concerns with the underground duct, ventilation capacity,and aging equipment therefore the following recommendations are made. -The underground ductwork should be abandoned and a new network of overhead duct should be installed. -Ventilation units should be provided throughout to provide sufficient quantities of outside air. -The majority of the Shelva duct furnaces are aging and should be replaced with furnaces. -The plumbing pipes are leaking and should be replaced. Consideration should be given to upgrading the entire mechanical heating and ventilation system in all areas, apart fromthe 1952 wing, to a hydronic heating system serving perimeter radiation and air handling units coils for new ventilationunits. This will alleviate all problems regarding aging unit ventilators, outdoor air flow rates, and lack of humidification.The estimated cost of such an upgrade based on $130/m2 would be $300,000.

9.28%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $599,600

Vauxhall - Vauxhall Elementary School (B4202A)

Report run on: January 26, 2005 4:32 PM Page 3 of 35

Electrical Summary:The general condition of the facilities electrical systems is poor. Major electrical upgrades in the life safety, power, lighting, data, and audio / video systems are required to bring thefacility to current day standards. The emergency lighting and to a limited extent the fire alarm system, upgrades areurgently needed for life safety. The power, data, and audio/video systems, while still being functional, seriously limitprogram funtion. The lighting system in general is ineficient and provides a poor quality of light. Other components of the building such as the telephone system, security system, and computer system (data linesand electrical supply) are in adequate condition. Although these systems are not state-of-the-art they are functionaland in good repair.

Vauxhall - Vauxhall Elementary School (B4202A)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Report run on: January 26, 2005 4:32 PM Page 4 of 35

A1030 Slab on Grade*

A2020 Basement Walls*

B1010.01 Floor Structural Frame*(Building Frame)

3

2

4

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

100

0

100

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

Updated

Updated

Updated

Crack in the slab of the 1952 section should bemonitored.

Repair cracks in basement walls

Study

Study

2006

2006

$0

$10,000

Low

Medium

There is crack in the floor slab and a significant slope in thenorth 1952 vestibule.

There are visible cracks in the foundation walls.

Concern:

Concern:

1952 floor slab should be monitored

Cracks in basement walls should be patched to prevent anyfurther damage.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

S1 STRUCTURAL

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1952 - Slab on grade 1968 - Slab on grade 1972 - Slab on grade

1952 - Foundation walls

1952 - Some uneven spots in wood floor

Report run on: January 26, 2005 4:32 PM Page 5 of 35

B1020.01 Roof Structural Frame*

B1020.04 Canopies*

4

4

Rating

Rating

0

0

Installed

Installed

100

50

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Vauxhall - Vauxhall Elementary School (B4202A)

1952 - Wood roof structure 1968 - Laminated wood beams & joists & plywood decking 1972 and 1968 Gym - Laminated wood beams & joists & plywood decking

1952 - Wood structure 1968 - Laminate beam and joists

Report run on: January 26, 2005 4:32 PM Page 6 of 35

B2010.01.02.01 Brick Masonry: Ext. Wall Skin*

B2010.01.02.02 Concrete Block: Ext. Wall Skin*

B2010.01.08 Portland Cement Plaster: Ext. Wall*

B2010.01.11 Joint Sealers (caulking): Ext. Wall*

B2010.03 Exterior Wall Vapor Retarders, Air Barriers, and Insulation*

B2010.06 Exterior Louvers, Grilles, and Screens*

4

4

3

4

4

4

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

75

75

75

20

30

30

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

October 2004

October 2004

October 2004

Updated

Updated

Updated

Updated

Updated

Updated

Repaire stucco

Repair 2006 $18,000 Low

Stucco on 1952 section is damaged and breaking away.Concern:

Replace stucco finish with new stucco.Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

S2 ENVELOPE

Event:

Type Year Cost Priority

Updated: October 8 2004

1968 - Brick face 1972 - Brick face

1992 - Conc. block

1952 - Stucco finish

Install date unknown - Joints have been re-caulked

1952 - Vapour barriers 1968 - Vapoir barrier 1972 - Vapour barrier

1952 - Aluminum louvres and screens

Report run on: January 26, 2005 4:32 PM Page 7 of 35

B2010.09 Exterior Soffits*

B2020.01.01.02 Aluminum Windows*

3

3

Rating

Rating

0

0

Installed

Installed

30

35

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Replace wood soffits

Replace Composite and combination sealed unitsand hardware.

Lifecycle Replacement

Lifecycle Replacement

2006

2006

$7,500

$16,000

Low

Low

Wood soffits around 1972 Gym area are very deteriorated.

Composite and combination sealed units are failing, very wornand hardware not functioning properly.

Concern:

Concern:

Replace wood soffits with an aluminum soffit.

Replace aluminum composite and combination sealed unitswith new units and hardware throughout school.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1952 - Metal soffits 1968 - Metal soffits 1972 - Wood soffits

1952 - Composite and combination sealed units 1968 - Composite and combination sealed units 1972 - Composite and combination sealed units

Report run on: January 26, 2005 4:32 PM Page 8 of 35

B2030.01.10 Wood Entrance Door*

B3010.01 Deck Vapor Retarder and Insulation*

B3010.04.04 Modified Bituminous Membrane Roofing (SBS)*

B3010.08.02 Metal Gutters and Downspouts*

3

4

4

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

20

22

25

30

Design Life

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

October 2004

Updated

Updated

Updated

Updated

Replace wood exterior woord doors.

Lifecycle Replacement 2006 $10,200 Low

Exterior wood doors and hardware are very worn and in poorcondition.

Concern:

Replace exterior wood doors with hollow metal doors. (4 sets ofdouble doors)

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Type Year Cost Priority

Updated: October 8 2004

1952 - Wood exterior entrance doors 1968 - Wood exterior entrance doors 1972 - Wood exterior entrance doors

1994 - Replacement of 1952 roof 2001 - Replacement of 1968 and 1972 area

2001 - Replacement of metal gutters and downspouts

Report run on: January 26, 2005 4:32 PM Page 9 of 35

C1010.01 Interior Fixed Partitions*

C1010.02 Interior Demountable Partitions*

C1010.03 Interior Operable Folding Panel Partitions*

C1010.05 Interior Windows*

4

3

3

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

50

30

30

40

Design Life

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

October 2004

Updated

Updated

Updated

Updated

Replace demountable partitions

Replace accordion partitions.

Lifecycle Replacement

Failure Replacement

2006

2006

$45,500

$7,500

Low

Low

Demountable partitions are in poor condition and do not provideadequate sound barriers

Accordian operable wall between stage and band room is badlydamaged.

Concern:

Concern:

Replace demountable partitions with a fixed framed wall.(Approx. 220 linear metres)

Replace accordian folding partition wall.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

S3 INTERIOR

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1952 - Wood framing 1968 - Concrete block 1972 - Concrete block 1992 - Concrete block

1968 - Demountable partitions

1968 - Accordian operable wall

1968 - Aluminum frame interior windows

Report run on: January 26, 2005 4:32 PM Page 10 of 35

C1020.01 Interior Swinging Doors*

C1020.01 Interior Swinging Doors*

C1020.02 Interior Entrance Doors*

C1030.01 Visual Display Boards*

4

3

3

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

40

40

50

10

Design Life

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

October 2004

Updated

Updated

Updated

Updated

Replace interior swinging doors

Replace interior entrance doors

Lifecycle Replacement

Lifecycle Replacement

2006

2006

$12,000

$8,000

Low

Low

Existing SCWD in the 1968 and 1972 areas are very worn andin poor condition.

Interior entrance doors are damaged and in poor condition.

Concern:

Concern:

Replace doors with new SCWD and hardware. (23 doors)

Replace the existing interior entrance doors with new hollowmetal doors. (4 doors)

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1991 - Replacement of 1952 interior doors

1968 - Interior SCWD 1972 - Interior SCWD

1968 - Interior SCWD 1972 - Interior SCWD

Chalkboards

Report run on: January 26, 2005 4:32 PM Page 11 of 35

C1030.02 Fabricated Compartments(Toilets/Showers)*

C1030.08 Interior Identifying Devices*

3

3

Rating

Rating

0

0

Installed

Installed

20

20

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Replace 1952 area toilet partitions

Replace and add new signage throughout school

Lifecycle Replacement

Program FunctionalUpgrade

2006

2006

$9,300

$1,000

Low

Low

Toilet partitions in the 1952 section are damaged

There is minimal signage throughout the 1952,1968,1972sections.

Concern:

Concern:

Replace existing toilet partitions in the 1952 area with new pre-fabricated partitions

Replace signs throughout school

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1952 - Floor mounted metal toilet partitions 1992 - Replacement of 1968 toilet partitions

1952 - Plastic signage for rooms

Report run on: January 26, 2005 4:32 PM Page 12 of 35

C1030.12 Storage Shelving*

C1030.14 Toilet, Bath, and Laundry Accessories*

C2010 Stair Construction (Including Ramps)*

3

4

3

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

20

20

100

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

Updated

Updated

Updated

Replace library shelving.

Replace framed stairs.

Lifecycle Replacement

Lifecycle Replacement

2006

2006

$6,000

$10,000

Low

Medium

Library shelving is gouged and splitting

Framed stairs in 1952 to 1968 area and the stairs at the 1952vestibules are in poor condition.

Concern:

Concern:

Replace shelving with new millwork.

Replace framed stairs with new framed construction.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1968 Library - Plywood shelving

1991 - Replacement of 1952 washroom accessories 1992 - Replacement of 1968 washroom accessories

1952 - Wood frame construction 1968 - Wood frame construction

Report run on: January 26, 2005 4:32 PM Page 13 of 35

C2020.05 Resilient Stair Finishes*

C3010.01 Concrete Wall Finishes*

3

3

Rating

Rating

0

0

Installed

Installed

20

100

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Replace stair treads

Re-paint concrete block walls

Failure Replacement

Preventative Maintenance

2006

2006

$1,700

$34,000

Low

Low

Treads on framed stairs are damaged and very worn.

Paint is worn and chipped off.

Concern:

Concern:

Replace treads with new rubber stair treads.

Re-paint concrete walls in 1968 and 1972 sections. (approx.5612 m2)

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1952 - Stair treads

1968 - Painted concrete block 1972 - Painted concrete block

Report run on: January 26, 2005 4:32 PM Page 14 of 35

C3010.04 Gypsum Board Wall Finishes*

C3010.06 Tile Wall Finishes*

C3020.01 Concrete Floor Finishes*

3

3

4

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

40

50

20

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

Updated

Updated

Updated

Re-paint walls

Replace porcelain tile dados

Preventative Maintenance

Repair

2006

2006

$27,000

$32,500

Low

Low

Paint is chipped and worn away.

Porcelain tile is cracked and in poor condition

Concern:

Concern:

Re-paint gypsum board walls throughout school. (approx. 4453m2)

Replace porcelain tile dados. (Approx. 260 m2)

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1991 - Repainting of gypsum board walls

1952 - Porcelain tile dados 1992 - Porcelain tile dados

1972 - Painted concrete floors

Report run on: January 26, 2005 4:32 PM Page 15 of 35

C3020.02 Tile Floor Finishes*

C3020.03 Terrazzo Floor Finishes*

C3020.04 Wood Flooring*

C3020.07 Resilient Flooring*

3

4

3

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

30

75

10

20

Design Life

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

October 2004

Updated

Updated

Updated

Updated

Replace ceramic tile flooring in washrooms

Re-finish hardwood flooring

Lifecycle Replacement

Preventative Maintenance

2006

2006

$21,000

$7,000

Low

Low

Ceramic tile floors are cracked substantially.

Hardwood flooring is gouged and very worn

Concern:

Concern:

Replace ceramic tile flooring with new tile. (Approx. 165 m2)

Re-finish existing hardwood flooring to a better condition.(approx. 90m2)

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1952 - Ceramic floor tile 1992 - Replacement of 1968 tile flooring

1968 - Vestibules

1968 - Stage

1968 - Marmoleum

Report run on: January 26, 2005 4:32 PM Page 16 of 35

C3020.07.01 Resilient Tile Flooring

C3020.08 Carpet Flooring*

3

3

Rating

Rating

0

0

Installed

Installed

0

10

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Replace vinyl tile flooring in 1968 gym.

Replace vinyl tile flooring in 1968 section.

Replace carpet

Failure Replacement

Failure Replacement

Lifecycle Replacement

2006

2006

2006

$7,300

$7,600

$23,000

Low

Low

Low

VCT in Gym is in poor condition.

Vinyl tile flooring in 1968 area is damaged and very worn.

Carpet in 1968 section is in very poor condition, pulling up andripped. 1992 carpet is getting very worn, and in rough condition.

Concern:

Concern:

Concern:

Remove VCT in Gym in preparation for new sports flooring.(160m2)

Replace vinyl tile flooring with a resilient sheet flooring in 1968section. (200 m2)

Replace carpet with a sheet vinyl flooring. (Approx. 765 m2)

Recommendation:

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

October 8 2004

October 8 2004

October 8 2004

1991 - Replacement of 1952 flooring with VCT 1968 - Vinyl flooring

1968 - Original carpet 1991 - Replacement of flooring in 1952 section

Report run on: January 26, 2005 4:32 PM Page 17 of 35

C3030.04 Gypsum Board Ceiling Finishes*

C3030.06 Acoustic Ceiling Treatment (Susp.T-Bar)*

3

3

Rating

Rating

0

0

Installed

Installed

50

15

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Repaint gypsum board ceilings.

Replace suspended t-bar

Preventative Maintenance

Preventative Maintenance

2006

2006

$7,600

$7,100

Low

Low

Paint on ceilings has become stained and faded. Peeling inareas.

T-bar in 1952 wing is damaged.

Concern:

Concern:

Repaint gypsum board ceilings throughout

Replace t-bar with new acoustical t-bar grid and panels.(Approx. 2135 m2)

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1968 - Painted Gypsum Board ceiling 1972 - Painted Gypsum Board ceiling 1992 - Repainting of gypsum board ceiling

1992 - T-bar installed in 1952 area

Report run on: January 26, 2005 4:32 PM Page 18 of 35

C3030.09 Other Ceiling Finishes*

2Rating

0Installed

0Design Life

October 2004Updated

Replace tentest ceiling tile

Failure Replacement 2006 $42,100 Low

Tentest tile is damaged and some tiles are missing. Libraryarea has the most damage. (Please refer to photo)

Concern:

Replace tentest tile with a suspended t-bar system. (Approx.1830 m 2) Abatement cost to be determined after hazardousmaterial s audit.

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Type Year Cost Priority

Updated: October 8 2004

1968 - Tentest tile 1972 - Tentest tile

Report run on: January 26, 2005 4:32 PM Page 19 of 35

D2010.01 Water Closets*.1952 wing

D2010.01 Water Closets*.1968 wing

D2010.02 Urinals*.1952 wing

D2010.02 Urinals*.1968 wing

D2010.03 Lavatories*.1952 wing

D2010.03 Lavatories*.1968 wing

D2010.04 Sinks*.1952 wing

D2010.04 Sinks*.1968

4

4

4

4

4

4

4

4

Rating

Rating

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

Installed

Installed

30

30

30

30

30

30

30

30

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Vauxhall - Vauxhall Elementary School (B4202A)

S4 MECHANICAL

1984

1992

1984

1992

1984

1992

1984

1992

Report run on: January 26, 2005 4:32 PM Page 20 of 35

D2010.08 Drinking Fountains / Coolers*.1952 wing

D2010.08 Drinking Fountains / Coolers*.1968 wing

D2020.01.01 Pipes and Tubes: Domestic Water*

D2020.02.06 Domestic Water Heaters*

4

4

3

3

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

30

30

40

20

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Repair plumbing pipes.

Replace domestic water heaters.

Repair

Lifecycle Replacement

2005

2005

$48,000

$8,000

Low

Low

Plumbing pipes and fittings have been leaking and type M thinwall copper has been used in some areas.

Domestic water heaters have passed their life expectancy.

Concern:

Concern:

Replace plumbing pipes and fittings in select locations whereleaks have been known to occur. Pricing based on 20%square footage of school and unit cost of $60/m2.

Replace 2 domestic water heaters.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

September 24 2004

September 24 2004

1984

1992

Copper piping and fittings leaking.

2 domestic water heaters, 1 in 1952 wing and 1 in 1968 wing. Unit in 1952 wing is a State domestic water heater located inboiler room, 66 kW heating input, 284 L capacity. Both units are past their life expectancy.

Report run on: January 26, 2005 4:32 PM Page 21 of 35

D2030.01 Waste and Vent Piping*

D2040.01 Rain Water Drainage Piping Systems*

D3020.02.01 Heating Boilers and Accessories: H.W.*

D3020.02.02 Chimneys (&Comb. Air): H.W. Boiler*

D3020.02.03 Water Treatment: H. W. Boiler*

3

4

4

4

4

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

50

50

30

30

30

Design Life

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Updated

Replace sanitary services.

Lifecycle Replacement 2005 $15,000 Low

Both sanitary services have been plugging and have likelydeteriorated.

Concern:

Replace both sanitary services.Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Type Year Cost Priority

Updated: September 24 2004

Cast iron piping. 2 sanitary services, 1 for the 1952 wing and 1 for the 1968 wing.

Downspouts connect into common sewer below grade and connect to Town storm sewer.

1990 - 4 hydrotherm hot water boilers heat 1952 wing with a total heating capacity of 562 kW.

Report run on: January 26, 2005 4:32 PM Page 22 of 35

D3020.03.01 Furnaces*

D3040.01.01 Air Handling Units: Air Distribution*.1952 wing

D3040.01.01 Air Handling Units: Air Distribution*.1968 wing

3

4

2

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

25

30

30

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

Updated

Updated

Updated

Replace 4 furnaces.

Provide 2 ventilation units.

Lifecycle Replacement

Indoor Air Quality Upgrade

2005

2004

$16,000

$43,200

Low

Low

The 2 furnaces serving the gymnasium and the 2 serving the1968 wing have reached their life expectancy.

The furnaces and Shelva duct units are not capable of providingsufficient quantities of outside air.

Concern:

Concern:

Replace total of 4 furnaces with new furnaces withapproximately 50kW heating capacity.

Provide 2 gas fired ventilation units in addition to the newfurnaces along with ductwork to provide sufficient quantities ofoutside air for the occupant load. Units should includehumidification section. Cost includes electrical work.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

September 24 2004

September 24 2004

2 flamemaster furnaces heat the gymnasium. 2 Flamemaster furnaces in the 1968 wing electrical room heat that portion ofthe school. One addition furnace serves North side entrance foyers.

1990 - Engineered Air LM-10C unit with hot water coil delivers 5900 L/s of ventilation in the 1952 wing.

Shelva duct heaters and furnaces are not capable of providing sufficient quantities of outside air.

Report run on: January 26, 2005 4:32 PM Page 23 of 35

D3040.01.04 Ducts: Air Distribution*

D3040.03.01 Hot Water Distribution Systems*

D3040.04.01 Fans*: Exhaust

D3040.04.01 Fans*: Exhaust.Lan Room

2

4

4

3

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

50

0

30

30

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Install new ventilation ducts.

Add exhaust fan in LAN room.

Indoor Air Quality Upgrade

Indoor Air Quality Upgrade

2004

2005

$43,000

$1,500

High

Low

The condition of the underground ductwork is suspect due tothe history of ground water problems in the area. There may bea potential for mold in the ductwork. Furthermore, floor grillesin the gymnasium protrude from the floor and create a safetyhazard.

The temperature in the LAN room is too high.

Concern:

Concern:

Abandon all underground ducts and provide a new network ofoverhead duct. Fill in the abandoned underground duct withconcrete. Modify the furnaces as required to accommodate thedirection of air flow.

Install an exhaust fan in the LAN room c/w roof curb.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

September 24 2004

September 24 2004

Underground ductwork in 1968 addition is damaged due to ground water.

1990 - 2 Bell & Gossette pumps deliver hot water to the building zones.

No exhaust fan in LAN Room.

Report run on: January 26, 2005 4:32 PM Page 24 of 35

D3050.01.01 Computer Room Air Conditioning Units*

D3050.03 Humidifiers*

D3050.05.07 Unit Ventilators*

D3060.02.02 Pneumatic Controls*

4

3

3

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

30

25

30

40

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Provide humidification.

Replace Shelva duct heaters.

Code Upgrade

Lifecycle Replacement

2004

2005

$0

$28,000

Low

Low

There is no humidification.

The shelva duct heaters have reached their life expectancy andrequire replacement. The chimney vents are deteriorating.

Concern:

Concern:

Provide humidification sections in the 2 new ventilation units.Cost included in D3040.01.01.

If no mechanical upgrade/modernization is planned for, replace4 Shelva duct heaters with horizontal discharge uprightfurnaces c/w new chimney vent.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

September 24 2004

September 24 2004

Evaporative type cooling unit.

No humidification.

4 unit ventilators in the north end of the 1968 addition serve the perimeter classrooms.

Pneumatic compressor and controls for HVAC systems in the 1952 wing.

Report run on: January 26, 2005 4:32 PM Page 25 of 35

D3060.02.05 Building Systems Controls(BMCS, EMCS)*

D4020 Standpipes*

D4030.01 Fire Extinguisher, Cabinets and Accessories*

4

4

4

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

25

50

30

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

Updated

Updated

Updated

Vauxhall - Vauxhall Elementary School (B4202A)

CSI BMCS management system in 1952 wing. 1968 wing uses original thermostats without any energy managementsystem

Fire standpipe system in 1968 wing.

Fire extinguishers throughout.

Report run on: January 26, 2005 4:32 PM Page 26 of 35

D5010.03 Main Electrical Switchboards (Main Distribution)*

D5010.03 Main Electrical Switchboards (Main Distribution)*

D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)*

3

4

3

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

40

40

30

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

Updated

Updated

Updated

Upgrade to existing electrical service

Replace existing branch circuit panelboards

Lifecycle Replacement

Code Repair

2006

2006

$25,000

$24,000

Low

Low

Existing service small for the size of the school and will notaccommodate any large mechanical upgrade. The switch gearis past its life expectancy and should not be reused in anyfashion if it is upgraded.

When additional devices are added panels will be insufficientlysized for the number of circuits required, and in several casessome panel feeders would also be to small.

Concern:

Concern:

Install larger service and new current distribution panel.Installation should only occur when the mechanical systemsare upgraded, and other additional equipment is required.

Replace existing panels to accommodate addition wiringdevices and other loads.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

S5 ELECTRICAL

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 7 2004

October 7 2004

300 Amp, 120/208 Volt, 3 phase, 4 wire underground. Service switch gear past life expectancy antiquated.

TVSS is installed at main service and is in good condition.

Distribution system and panels are well maintained however there is no spare capacity, and are very poorly labeled.

Report run on: January 26, 2005 4:32 PM Page 27 of 35

D5010.07 Motor Control Centers (Motor Control)*

D5020.01 Electrical Branch Wiring*

D5020.02.02.02 Interior Florescent Fixtures*

4

3

3

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

25

50

0

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

Updated

Updated

Updated

Add / Replace wiring devices

Upgrade Existing Lighting

Program FunctionalUpgrade

Energy Efficiency Upgrade

2006

2005

$22,000

$65,000

Low

Low

1968 portion of the building devices are past life expectancy,and higher maintenance costs are going to be incurred. Alsowhere there are large spaces between receptacles or poorlyplaced switches, this greatly effects functionality.

Existing lights are inefficient and have higher operating costs.

Concern:

Concern:

Add 2 or 3 new receptacles in all classrooms depending onclassrom layout, and replace all existing devices in 1968portion.

Replace existing fixtures with energy efficient T-8 Fixtures

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 7 2004

October 7 2004

1992 - 2 section motor control center with spare capacity installed in 1992.

1968 - Entire facility is short on the quantity of outlets. 1968 portion of the building devices are past life expectancy.

1992 - corridors illuminated with 2x4 recessed fluorescents. Excessive use of surface mounted 1x4 wrap type fluorescents.

Report run on: January 26, 2005 4:32 PM Page 28 of 35

D5020.02.02.05 Mercury Vapour Interior Fixtures*

D5020.02.03 Emergency Lighting*

3

1

Rating

Rating

0

0

Installed

Installed

0

20

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Upgrade Existing Gym Lighting

Upgrade Emergency Lighting

Energy Efficiency Upgrade

Code Repair

2006

2004

$11,000

$13,000

Low

High

Existing lights are not very energy efficient and provide a poorquality of light.

Several emergency packs are not functioning properly.

Concern:

Concern:

Replace existing Mercury Vapor fixtures with T-5 Fluorescentlight fixtures.

Replace failing emergency packs and add 6 new units toimprove lighting for egress.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 7 2004

October 7 2004

Gym lighting is 400 watt mercury vapor high bay fixtures.

Some battery packs installed in corridors not functioning. 2000 - Generator removed and current system is battery packsand emergency heads.

Report run on: January 26, 2005 4:32 PM Page 29 of 35

D5020.02.03.03 Exit Signs

D5020.03.01.01 Exterior Incandescent Fixtures*

D5030.01 Detection and Alarm Fire Alarm*

1

2

2

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

0

0

25

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

Updated

Updated

Updated

Upgrade Existing Exit Signs

Replace exterior fixtures

Fire Alarm System Upgrade

Code Repair

Lifecycle Replacement

Code Upgrade

2004

2004

2004

$8,000

$7,500

$19,000

High

Medium

Medium

Some exit signs are very dim and should be replaced with LEDexit signs

Limited vision at night.

Fire Alarm system old and there are no visual alarm devices.

Concern:

Concern:

Concern:

Replace exit signs with 12 new LED exit signs.

Replace existing fixtures with 6 new HID lighting.

Replace system with new addressable Fire Alarm system.

Recommendation:

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

October 7 2004

October 7 2004

October 7 2004

Existing exits lights are poorly lit and past life expectancy.

Exterior fixtures are antiquated and inefficient and provide very poor light.

Edwards 2280 analog Fire Alarm System with annunciator at front entrance. System is adequate but becoming obsolete.Installation of devices will warrant upgrade during renovations.

Report run on: January 26, 2005 4:32 PM Page 30 of 35

D5030.02.02 Intrusion Detection*

D5030.04.01 Telephone Systems*

D5030.04.02 Paging Systems*

D5030.04.04 Data Systems*

4

5

3

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

25

15

15

15

Design Life

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

October 2004

Updated

Updated

Updated

Updated

Expand Functionality of Paging System

Program FunctionalUpgrade

2005 $8,000 Low

Current system does incorporate any call back function, thismeans the system is not very functional.

Concern:

Expand current system by installing additional wiring anddevices to create individual call back.

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Type Year Cost Priority

Updated: October 7 2004

Motion sensors only.

2000 - Telephone system in place, only 6 lines coming into school.

Speakers are installed in corridors and classrooms. The phone system reaches to several common areas in the facility. Toallow call back, system could be expanded.

Network cabling is Cat 5 and installed in conduit. Super Net fibre optic installed in 2004. LAN distribution equipment isinstalled in storage room.

Report run on: January 26, 2005 4:32 PM Page 31 of 35

D5030.06 Television Systems*

3Rating

0Installed

0Design Life

October 2004Updated

Upgrade Existing Television System

Program FunctionalUpgrade

2005 $26,000 Low

Existing system is lacking in functionality and the ability to usenew media, such as smart boards.

Concern:

Install new multimedia system throughout the school.Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Type Year Cost Priority

Updated: October 7 2004

TV cabling and multimedia system is a suggested upgrade due to the current minimal installation.

Report run on: January 26, 2005 4:32 PM Page 32 of 35

E1090.07 Athletic, Recreational, and Therapeutic Equipment*

E2010.02.05 Educational Facility Casework*

3

3

Rating

Rating

0

0

Installed

Installed

15

0

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Replace existing basketball backstops

Install millwork along perimeter of room.

Lifecycle Replacement

Program FunctionalUpgrade

2006

2006

$5,000

$35,000

Low

Low

Backstops are in poor condition.

There is not adaquate storage shelving in 6 classrooms.

Concern:

Concern:

Replace backstops with two new fixed backstops and 2motorized.

Install perimeter millwork. (Approx. 91 m)

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1968 - Basketball backstops

1968 - No perimeter shelving 1991 - Replacement of 1952 millwork

Report run on: January 26, 2005 4:32 PM Page 33 of 35

E2010.02.07 Kitchen Casework*

E2010.02.08 Laboratory Casework*

E2010.03.01 Blinds*

3

3

3

Rating

Rating

Rating

0

0

0

Installed

Installed

Installed

0

0

10

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

Updated

Updated

Updated

Replace staff room kitchen millwork.

Replace science lab perimeter casework

Install new window coverings

Lifecycle Replacement

Lifecycle Replacement

Failure Replacement

2006

2006

2006

$3,000

$5,200

$1,000

Low

Low

Low

Staff room millwork is very worn.

Science lab case work is very worn and in poor workingcondition.

Blinds built into windows are broken and do not functionproperly.

Concern:

Concern:

Concern:

Replace existing kitchen casework with new millwork.

Replace science lab casework with new millwork.

Replace the built in type blinds for a wall hanging blind

Recommendation:

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

October 8 2004

October 8 2004

October 8 2004

1968 - Staff room kitchenette

1972 - Science lab

1968 - Built in-window blinds

Report run on: January 26, 2005 4:32 PM Page 34 of 35

E2020 Moveable Furnishings*

F2020 Hazardous Components Abatement

3

3

Rating

Rating

0

0

Installed

Installed

20

0

Design Life

Design Life

October 2004

October 2004

Updated

Updated

Replace existing teacher and student desks andchairs

Conduct a hazardous materials audit.

Lifecycle Replacement

Hazardous MaterialsAbatement

2006

2006

$20,000

$5,000

Low

Medium

Furnishings for students and teachers are very worn anddistressed.

Possibility of asbestos in tentest tile, unit ventilators, andtentest ceiling tile located in the 1968 section.

Concern:

Concern:

Replace student and teacher desks and chairs. (200 desks andchairs to be replaced)

A thorough abatement should be conducted to identify possiblehazardous materials in the different building components.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1952, 1968, 1972 - Student and faculty furnishings

1968 - 12 x 12 flooring tile, Unit Ventilators, tentest ceiling tile

Report run on: January 26, 2005 4:32 PM Page 35 of 35

K4010.01 Barrier Free Route: Parking to Entrance

K4010.02 Barrier Free Entrances

K4010.03 Barrier Free Interior Circulation

K4010.04 Barrier Free Washrooms

4

2

3

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

0

0

0

0

Design Life

Design Life

Design Life

Design Life

October 2004

October 2004

October 2004

October 2004

Updated

Updated

Updated

Updated

Add an automatic door.

Add lift to stairs in 1952 section.

Barrier Free AccessUpgrade

Barrier Free AccessUpgrade

2006

2006

$5,000

$12,000

Medium

Low

There is currently no automatic door opener for barrier freeaccess at the main entrance of either of the school sections.

There is no barrier free access from the upper floor of the 1952section and grade level or basement level.

Concern:

Concern:

Install an automatic door opener at main entrance of school.

Install a wheel chair lift to stairs.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (B4202A)

S8 FUNCTIONAL ASSESSMENT

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

October 8 2004

October 8 2004

1968 - Level ground from parking area to school entrance.

1968, 1952 - No barrier free access

Currently no access from 1968 section to lower level of 1952 section. Add lift to provide access to lower level.

1992 - Replacement of 1962 washrooms barrier free access added at this time

Report run on: January 28, 2005 3:39 PM Page 2 of 6

S4202Building Id:

Vauxhall Elementary SchoolBuilding Name:

VauxhallLocation:Address:

0.00Gross Area (sq. m): $0Replacement Cost:0Construction Year:

Evaluation Date: May 1 2004

J.A Matthew Architect Ltd.Evaluation Company:

Mr. Joe MatthewEvaluator Name:

(403) 320-2722Evaluator Phone:

Overall the site is in reasonable condition. SIte is landscaped some gravel play areas and asphalt basketball court.There should be an investigation into the site surface drainage. Car plug ins and new site lighting is recommended.Cracked sidewalks should be replaced and a new free standing sign installed.

General Summary:

Structural Summary:

Envelope Summary:

Interior Summary:

Mechanical Summary:

Electrical Summary:

0%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $50,000

Vauxhall - Vauxhall Elementary School (S4202)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Report run on: January 28, 2005 3:39 PM Page 3 of 6

G1030.04 Slope Protection and Erosion Control

G2010.02.01 Aggregate Roadway (Gravel)*

G2020.02.01 Aggregate Parking Lots (Gravel)*

G2030.04 Rigid Pedestrian Pavement (Concrete)*

2

4

4

3

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

0

10

10

0

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Re-grade site and create an on site stom systemand drywell.

Replace concrete sidewalk

Study

Lifecycle Replacement

2006

2006

$60,000

$20,000

Low

Low

Heavy rain causes water to seep into basement. There is notadaquate drainage away from the school.

Concrete sidewalk is cracked and has sunk in some areas.

Concern:

Concern:

Re-grade site around school to an on site storm system whereit can be carried to a dry well on site.

Replace exisitng side walk with a new one sloped away fromschool.

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (S4202)

S7 SITE

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

September 24 2004

September 24 2004

1952, 1968 - Drainage away from school

1968 - Gravel roadway

1968 - Gravel parking

1968 - Original sidewalks

Report run on: January 28, 2005 3:39 PM Page 4 of 6

G2040.03 Athletic and Recreational Surfaces*

G2040.06 Exterior Signs*

G2040.08 Flagpoles*

G2050.01 Irrigation Systems*

4

3

3

4

Rating

Rating

Rating

Rating

0

0

0

0

Installed

Installed

Installed

Installed

0

0

0

0

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Sign is difficult to see from parking lot

Replace flag pole

Program FunctionalUpgrade

Lifecycle Replacement

2006

2006

$1,500

$2,000

Low

Low

The sign is hiddedn under the canopy, very difficult to see fromroadway or parking area.

Flag pole is very worn, and is in poor condition.

Concern:

Concern:

A free standing sign should be installed beside main entrancesidewalk.

Replace with a new flag pole and base

Recommendation:

Recommendation:

Vauxhall - Vauxhall Elementary School (S4202)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

September 24 2004

September 24 2004

1968 - Asphalt basketball court Landscaped soccer and playing fields.

1968 - Individual aluminum letters above main entrance

1968 - Flag pole

1952, 1968 - Hose bibs. Minimum coverage

Report run on: January 28, 2005 3:39 PM Page 5 of 6

G2050.04 Lawns and Grasses*

G2050.05 Trees, Plants and Ground Covers*

G3010.02 Site Domestic Water Distribution*

G3020.01.01 Sanitary Piping

G3030.02 Storm Water Piping*

G4010.02 Electrical Power Distribution Lines*

G4010.04 Car Plugs-ins*

4

4

4

4

4

4

3

Rating

Rating

Rating

Rating

Rating

Rating

Rating

0

0

0

0

0

0

0

Installed

Installed

Installed

Installed

Installed

Installed

Installed

0

0

0

0

40

0

0

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

September 2004

September 2004

September 2004

September 2004

September 2004

September 2004

September 2004

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Adding Car Plug-ins

Maintenance 2004 $20,000 N/A

Add 10 parking pedistals off temperature controlled circuitsRecommendation:

Vauxhall - Vauxhall Elementary School (S4202)

Event:

Type Year Cost Priority

Updated: September 24 2004

1952, 1968 - Lawns

1952, 1968 - Trees

2 Municipal services provide good pressure, volume & quality.

Municipal sanitary system.

Rainwater leaders collect to common storm sewer and connects into Town system.

Electrical service is a 300A 120/208V underground service.

No car plugs present but required

Report run on: January 28, 2005 3:39 PM Page 6 of 6

G4020 Site Lighting

2Rating

0Installed

0Design Life

September 2004Updated

Add exterior lighting

Maintenance 2004 $8,000 N/A

Add 4 new exterior metal halide fixture to the exterior of theschool and replace several existing fixtures

Recommendation:

Vauxhall - Vauxhall Elementary School (S4202)

Event:

Type Year Cost Priority

Updated: September 24 2004

Installation date unknown. 3-4 wall packs and some incandescent down lights installed.