Upload
tonybui
View
27
Download
0
Tags:
Embed Size (px)
Citation preview
RCS-9659
Auto Synchronizer
Instruction Manual
NR Electric Co., Ltd.
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. i
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR Electric Co., Ltd. is dispatched separately from
manufactured goods and may not be received at the same time. Therefore this guide is provided
to ensure that printed information normally present on equipment is fully understood by the
recipient. Before carrying out any work on the equipment the user should be familiar with the contents of this
manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
Health and Safety
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.
Qualified personnel are individuals who:
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
Are trained in emergency procedures (first aid).
Instructions and Warnings
The following indicators and standard definitions are used:
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. ii
DANGER means that dearth, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means that dearth, severe personal or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. The se
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in dearth, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. iii
The earthing terminal of the equipment must be securely earthed
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Printed circuit board
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Carefully handle the connection cable without applying excessive force.
Copyright
Version: R1.02
P/N: EN_DYBH0319.0086.0003
Copyright NR 2008. All rights reserved
We reserve all rights to this document and to the information
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.
The information in this manual is carefully checked periodically,
and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or
improvement are greatly appreciated.
We reserve the rights to make technical improvements without
notice.
NR ELECTRIC CO., LTD.
69 Suyuan Avenue, Jiangning, Nanjing 211102, China
Tel: 86-25-87178185, Fax: 86-25-87178208
Website: www.nari -relays.com
Email: international@nari -relays.com
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. iv
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. v
Table of Contents
Preface ........................................................................................................................................ i
Introduction ......................................................................................................................... i
Health and Safety ................................................................................................................ i
Instructions and Warnings .................................................................................................. i
Table of Contents....................................................................................................................... v
Chapter 1 Introduction .............................................................................................................. 1
1.1 Application .................................................................................................................... 1
1.2 Functions ...................................................................................................................... 1
1.3 Features ........................................................................................................................ 2
1.4 Ordering ........................................................................................................................ 2
Chapter 2 Technical Data .......................................................................................................... 5
2.1 Electrical Specifications ............................................................................................... 5
2.1.1 Analog Voltage Input Ratings ............................................................................. 5
2.1.2 Power supply ...................................................................................................... 5
2.1.3 Binary input......................................................................................................... 5
2.1.4 Binary output ...................................................................................................... 5
2.1.5 Power supply output for Opto-coupler .............................................................. 6
2.2 Mechanical Specifications............................................................................................ 6
2.3 Ambient Temperature and Humidity Range ................................................................ 6
2.4 Rear Communication Port ............................................................................................ 7
2.5 Type Tests ..................................................................................................................... 8
2.5.1 Environmental tests ............................................................................................ 8
2.5.2 Mechanical tests ................................................................................................. 8
2.5.3 Electrical tests .................................................................................................... 8
2.5.4 Electromagnetic compatibility ........................................................................... 9
2.6 Certifications................................................................................................................. 9
2.7 Functional Specification............................................................................................. 10
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. vi
2.7.1 Accurate Operating Scope ............................................................................... 10
2.7.2 Synchronism Check function........................................................................... 10
Chapter 3 Functional Description ............................................................................................11
3.1 Synchronizing Modes ..................................................................................................11
3.1.1 Automatic Synchronizing Mode ........................................................................11
3.1.2 Semi-automatic Synchronizing Mode .............................................................. 13
3.1.3 Manual Synchronizing Mode ............................................................................ 16
3.2 Block Function............................................................................................................ 18
3.3 Time Synchronization................................................................................................. 18
Chapter 4 Automatic Supervision........................................................................................... 21
4.1 General Description .................................................................................................... 21
4.2 Synchronizer Self-supervision................................................................................... 21
4.2.1 Hardware Supervision ...................................................................................... 21
4.2.2 Check Setting .................................................................................................... 21
4.2.3 Voltage drift Supervision and auto adjustment ............................................... 21
4.2.4 DSP sampling Supervision............................................................................... 22
4.2.5 CPU sampling Supervision .............................................................................. 22
4.2.6 Opto-coupler power Supervision ..................................................................... 22
4.2.7 Synchronism Point Supervision ...................................................................... 22
4.2.8 System Voltage Supervision ............................................................................ 22
4.2.9 Voltage Transformer Supervision VTS ..................................................... 22
4.2.10 Circuit Breaker Closing Supervision ............................................................. 23
4.3 Understand the Alarms ............................................................................................... 23
Chapter 5 Metering and Recording......................................................................................... 25
5.1 General Description .................................................................................................... 25
5.2 Metering ...................................................................................................................... 25
5.3 Binary Input................................................................................................................. 26
5.4 Recording.................................................................................................................... 26
5.4.1 General description .......................................................................................... 26
5.4.2 Event recorder .................................................................................................. 27
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. vii
5.4.3 Disturbance recorder........................................................................................ 27
Chapter 6 Hardware Description............................................................................................. 29
6.1 Overview ..................................................................................................................... 29
6.2 Plug-in Modules .......................................................................................................... 30
6.2.1 DC Module (No.K DC) ....................................................................................... 30
6.2.2 AC Module (No.J AC) ........................................................................................ 31
6.2.3 LFP Module (No.H LFP) .................................................................................... 33
6.2.4 CPU Module (No.G CPU) .................................................................................. 33
6.2.5 COM module (No.F COM) ................................................................................. 34
6.2.6 OPT Module (No.E OPT) ................................................................................... 36
6.2.7 SIG Module (No.C SIG) ..................................................................................... 40
6.2.8 SIG Module (No.B SIG) ..................................................................................... 41
6.2.9 OUT Module (No.n OUT) ................................................................................... 42
Chapter 7 Settings ................................................................................................................... 45
7.1 Equipment Settings .................................................................................................... 45
7.2 Protection Settings ..................................................................................................... 47
7.3 IP address ................................................................................................................... 50
Chapter 8 HMI Operation Introduction ................................................................................... 51
8.1 Overview ..................................................................................................................... 51
8.1.1 Keypad operation.............................................................................................. 52
8.1.2 LED Indicators .................................................................................................. 53
8.1.3 Communication Ports ....................................................................................... 54
8.1.4 TARGET RESET Button .................................................................................... 54
8.2 Understand the HMI Menu Tree .................................................................................. 54
8.2.1 Overview............................................................................................................ 54
8.2.2 VALUES ............................................................................................................. 55
8.2.3 REPORT............................................................................................................. 56
8.2.4 PRINT................................................................................................................. 56
8.2.5 SETTINGS.......................................................................................................... 56
8.2.6 CLOCK............................................................................................................... 57
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. viii
8.2.7 VERSION ........................................................................................................... 57
8.2.8 LANGUAGE ....................................................................................................... 57
8.3 Understand the LCD Display ...................................................................................... 57
8.3.1 Main display under normal operation condition ............................................. 57
8.3.2 Display tripping report...................................................................................... 58
8.3.3 Display self-supervision report........................................................................ 58
8.3.4 Display status change of binary input report .................................................. 59
8.3.5 View the settings............................................................................................... 60
8.3.6 View Records .................................................................................................... 61
8.3.7 Printing reports and waveform ........................................................................ 61
8.4 Input Operation Through Keypad .............................................................................. 62
8.4.1 Change the Settings ......................................................................................... 62
8.4.2 Delete Fault Records and Event Records........................................................ 63
8.4.3 Adjusting Clock................................................................................................. 63
8.4.4 Check Version ................................................................................................... 64
Chapter 9 Communications .................................................................................................... 65
9.1 General Description .................................................................................................... 65
9.2 Rear Communication Port Information...................................................................... 65
9.2.1 RS-485 Interface................................................................................................ 65
9.2.2 Ethernet Interface ............................................................................................. 67
9.2.3 IEC60870-5-103 Communication ...................................................................... 68
9.3 IEC60870-5-103 Interface over Serial Port ................................................................. 68
9.3.1 Physical Connection and Link Layer ............................................................... 68
9.3.2 Initialization ....................................................................................................... 68
9.3.3 Time Synchronization ....................................................................................... 69
9.3.4 Spontaneous Events......................................................................................... 69
9.3.5 General Interrogation........................................................................................ 70
9.3.6 General Functions ............................................................................................ 70
9.3.7 Disturbance Records ........................................................................................ 70
9.4 IEC60870-5-103 Interface over Ethernet .................................................................... 71
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. ix
9.5 Messages Description for IEC61850 Protocol........................................................... 71
9.5.1 Overview............................................................................................................ 71
9.5.2 Communication profiles ................................................................................... 72
9.5.3 Server data organization .................................................................................. 73
9.5.4 Server features and configuration ................................................................... 74
9.5.5 ACSI conformance ............................................................................................ 77
Chapter 10 Installation and Commissioning .......................................................................... 81
10.1 Introduction............................................................................................................... 81
10.2 Safety Information .................................................................................................... 81
10.3 Overview.................................................................................................................... 83
10.4 Unpacking and Checking the Equipment ................................................................ 83
10.5 Installing the Protective Device ............................................................................... 84
10.5.1 Overview.......................................................................................................... 84
10.5.2 Dimensions ..................................................................................................... 84
10.5.3 Grounding Guidelines .................................................................................... 85
10.5.4 Cubicle Grounding.......................................................................................... 86
10.5.5 Ground Connection on the Device................................................................. 86
10.5.6 Grounding Strips and their Installation ......................................................... 87
10.5.7 Making the electrical connections ................................................................. 87
10.5.8 Typical Wiring.................................................................................................. 89
10.6 Check the External Circuitry .................................................................................... 90
10.7 Energizing the Equipment ........................................................................................ 91
10.7.1 Checking front panel LCD display ................................................................. 91
10.7.2 Setting the date and time................................................................................ 92
10.7.3 Checking light emitting diodes (LEDs) .......................................................... 92
10.8 Setting the Protective Device ................................................................................... 92
10.9 Establishing Connection and Verifying Communication........................................ 93
10.10 Verifying settings by secondary injection ............................................................. 93
10.10.1 Commissioning Tools ................................................................................... 93
10.10.2 Insulation test (if required) ........................................................................... 94
RCS-9659 Auto Synchronizer
NR ELECTRIC CO., LTD. x
10.10.3 Testing the AC Voltage Inputs ...................................................................... 94
10.10.4 Testing the Binary Inputs.............................................................................. 95
10.10.5 Synchronism Function ................................................................................. 96
10.11 Final Check.............................................................................................................. 96
Chapter 11 Maintenance .......................................................................................................... 97
11.1 Appearance Check .................................................................................................... 97
11.2 Failure Tracing and Repair ....................................................................................... 97
11.3 Replace Failed Modules............................................................................................ 98
11.4 Replace Button Battery............................................................................................. 99
11.5 Cleaning .................................................................................................................... 99
11.6 Storage ...................................................................................................................... 99
Chapter 12 Decommissioning and Disposal .........................................................................101
12.1 Decommissioning ....................................................................................................101
12.2 Disposal ...................................................................................................................101
Chapter 13 Manual Version History .......................................................................................103
Chapter 1 Introduction
NR ELECTRIC CO., LTD. 1
Chapter 1 Introduction
1.1 Application
RCS-9659 is a digital synchronizer that determines the proper time to initiate closing of circuit
breaker to parallel a generator and bus, or to reclose a line. In order to fulfill different application
requirements, it is equipped with three kinds of synchronizing modes: automatic synchronizing,
semi-automatic synchronizing and manual synchronizing. By monitoring frequency, voltage and
phase angle, RCS-9659 provides correction signals to governor of prime mover and voltage
regulator of generator for voltage matching and frequency matching. With a powerful and large
capacity, RCS-9659 provides the multi-generator paralleling solution. It can manage up to 10
circuit breakers synchronism.
Prime
mover
Frequency control
Voltage control
Clo
sin
g s
ignal
Circuit breaker
Station bus ABC rotation
Power Grid
GEN A sineBUS A sineGovernor
UG1
UG2
US1
US2
RCS-9659
VTS FDR25
Generator
Regulator
Figure 1.1-1 Typical Application of RCS-9659
1.2 Functions
Automatic synchronizing (25A)
Semi-automatic synchronizing (25SA
Manual synchronizing (25M)
Multi-generator paralleling solution: capability of 10 circuit breakers synchronization. To any
of the circuit breakers, frequency and voltage regulation can be done separately.
Remote/local control paralleling mode
Output of signal contacts
Output block signal to other equipments
Receive block signal from other equipments
Chapter 1 Introduction
NR ELECTRIC CO., LTD. 2
Communicate with substation automation system via serial port on IEC60870-5-103 or
Ethernet port based on IEC60870-5-103 or IEC61850.
GPS clock synchronization PPS (pulse per second), PPM (pulse per minute), RS-485
difference level and IRIG-B synchronization.
Oscillograph,8 cycles ahead of closing signal and 2 cycles after closing signal.
1.3 Features
Based on DSP hardware platform, 14 bits high accuracy A/D converter. DSP performs data
acquisition, voltage, frequency and phase angle calculations, voltage and frequency
regulations and synchronism checking task. The breaker can be closed only when the
synchronism condition is met which is judged by DSP. Hereby, security is enhanced
significantly.
Frequency tracking technology is adopted. By the aid of that, real-time value of frequency,
voltage and phase are calculated with high precision on every sampling point.
The equipment uses an integral front panel and closed cabinet. High and low level signals
are separated strictly. With well designed software anti-EMI facilities, the equipments
capability of interference immunity is highly enhanced. Furthermore, its electromagnetic
radiation also satisfies relevant international standards.
Flexible communication function
2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol
1 RS-485 communication rear ports for clock synchronization
4 rear Ethernet ports (optional), IEC 61850, or IEC 60870-5-103 over TCP/IP
Monitoring and Metering
Event Recorder including 64 reports of status change of binary input, 64 self-supervision
reports and 256 operating reports.
Disturbance recorder including 64 fault reports, and 24 waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Friendly Human Machine interface User Interface
Friendly HMI interface with LCD and 9-button keypad on the front panel.
1 RS-232 communication faceplate port for testing and setting
1 RS-232 communication rear ports or RS-485 for printer
Auxiliary software - RCSPC
1.4 Ordering
Equipment type definition
Chapter 1 Introduction
NR ELECTRIC CO., LTD. 3
Composition of type of varieties of the equipment is as follows:
RCS-9659 - XX - NN
num ber of O UT m odule
type of CO M m odule
type of the equipm ent
Figure 1.4-1 Varieties of RCS-9659 Synchronizer
As illustrated in Figure 1.4-1, type of COM module and number of OUT module are configurable.
Table 1.4-1 Equipment configuration
Suffix Possible value Description
XX
No COM module is comprised.
ST RS-485 serial port communication board is equipped. See section
0.
SF 100Mbps optical-fiber Ethernet communication board is
employed. See section 0.
NT 100Mbps RJ-45 twisted wire Ethernet communication board is fit.
See section 0.
NN 110 Number of synchronism output board
Two options are available for rated secondary current of CT inputs: 1A or 5A.
Four options are available for rated auxiliary voltage: 250V, 220V, 125V, 110V.
There are three types of COM module are optional mentioned above.
Chapter 1 Introduction
NR ELECTRIC CO., LTD. 4
Chapter 2 Technical Data
NR ELECTRIC CO., LTD. 5
Chapter 2 Technical Data
2.1 Electrical Specifications
2.1.1 Analog Voltage Input Ratings
Per IEC 60255-6, IEC 60288
Rated Voltage 100V/ 3 , 110V/ 3 100V, 110V 200V
Linear to 100V 173V 230V
Thermal withstand -continuously -10s -1s
120V 200V 250V
120V 200V 250V
200V 350V 400V
Burden at rated
Chapter 2 Technical Data
NR ELECTRIC CO., LTD. 6
Bounce time 1ms 1ms
Breaking capacity at 250Vdc
0.4A resistance 0.2A inductive (L/R=40ms)
0.2A resistance 0.05A inductive (L/R=40ms)
Durability Loaded contact
Unloaded contact
100,000 operations minimum
10,000,000 operations minimum
Output mode Potential free contact
Making capacity >1000W at L/R=40ms
Max system voltage 250Vac/dc
Test voltage across open contact
1000Vac RMS for 1min
Short duration current 50A for 200ms
2.1.5 Power supply output for Opto-coupler
Rated Voltage 24V
Rated Current 200mA
Max current 500mA
2.2 Mechanical Specifications
Enclosure dimensions (WHD)
482.6177291 (unit: mm)
Mounting Way Flush mounted
Trepanning dimensions (WH)
450179, M6 screw
Housing color Silver grey
Weight per device Approx. 20kg
Display language English
Housing material Aluminum
Location of terminal Rear panel of the device
Protection class
Standard Per IEC60529:1989
Front side IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals
IP20
2.3 Ambient Temperature and Humidity Range
Standard IEC60255-6:1988
Operating
temperature -25C to +55C
Transport and storage temperature range
-40C to +70C
Permissible humidity 5%-95%, condensation not permissible
Chapter 2 Technical Data
NR ELECTRIC CO., LTD. 7
2.4 Rear Communication Port
Interface for communicating with RTU/SCADA
RS-485 (EIA)
Electrical
Port number 2
Baud rate 4800~38400bps
Transmission distance
Chapter 2 Technical Data
NR ELECTRIC CO., LTD. 8
RS-232 (EIA)
Prot number 1
Baud Rate 4800bps~38400bps
Printer type EPSON 300K printer
Safety level Isolation to ELV level
Interface for clock synchronization
RS-485 (EIA)
Port number 1
Transmission distance
Chapter 2 Technical Data
NR ELECTRIC CO., LTD. 9
Test voltage 5kV, unipolar impulses waveform 1.2/50s,source
energy 0.5J
Insulation resistance
measurements
Per IEC 60255-5:2000
Isolation resistance >100M, 500Vdc
2.5.4 Electromagnetic compatibility
1MHz burst disturbance test
Per IEC 60255-22-1 (idt IEC61000-4-12)
Common mode: class III 2.5KV
Differential mode: class III 1.0KV
Electrostatic discharge test
Per IEC60255-22-2 class IV
For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests
Per IEC 60255-22-3 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=801000MHz
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Fast transient disturbance tests
Per IEC 60255-22-4
Power supply, I/O, Earth: Class IV, 4kV, 2.5 kHz, 5/50ns
Communication terminals: Class IV, 2kV, 5 kHz, 5/50ns
Surge immunity test Per IEC 60255-22-5, 1.2/50us class III
Power supply, AC input, I/O port: 2kV, line to earth; 1kV line to line
Conducted RF Electromagnetic Disturbance
Per IEC 60255-22-6
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Power Frequency Magnetic Field Immunity
Per IEC 61000-4-8:1993
Class 5: 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field
Immunity
Per IEC 61000-4-9:1993
Class 5: 6.4/16s, 1000A/m for 3s
Damped oscillatory magnetic field immunity
IEC 61000-4-10:1993
Class 5: 100kHz & 1MHz100A/m
2.6 Certifications
Chapter 2 Technical Data
NR ELECTRIC CO., LTD. 10
ISO9001: 2000
ISO14001:2004
OHSAS18001: 1999
ISO10012:2003
CMMI L3
EMC: 89/336/EEC, EN50263:2000
Products safety(PS): 73/23/EEC, EN61010-1: 2001, EN60950: 2002
2.7 Functional Specification
2.7.1 Accurate Operating Scope
Voltage 0.4V100V
Frequency 45HZ55HZ
Time delay 0100S
df/dt 0.3HZ/S10HZ/S
2.7.2 Synchronism Check function
Synchronism points 0~10
Secondary rated voltage (system and generator)
57.70100.00V
Slip frequency 00.5 HZ
Frequency slip speed 110.00 HZ/S
Voltage difference 5%30%
Dead check threshold 5%30%
Corrected angle between system voltage and generator voltage
0330
Pulse wide of adjusting frequency 109999ms
Period of adjusting frequency 109999ms
Pulse wide of adjusting voltage 109999ms
period of adjusting voltage 109999ms
Pulse wide of closing a breaker 109999ms
The breaker closing time 20999ms
Resetting time of checking synchronism 20999s
Tolerance of voltage setting 3%xsetting
Tolerance of slip frequency 0.02HZ
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 11
Chapter 3 Functional Description
3.1 Synchronizing Modes
As described in section 1.2, RCS-9659 has three kinds of synchronizing modes. For each mode,
they have two sub-modes: synchronism checking mode and dead checking mode. Just as the
name implies, under synchronism checking mode, the circuit breaker is only permitted to be
closed while all synchronism conditions are met. Dead checking mode allows selection of various
low bus voltage conditions to enable breaker closing without synchronism check. This provides a
black start capability for the system. Three kinds of synchronizing modes are comprehensively
explained in the following sections.
3.1.1 Automatic Synchronizing Mode
When RCS-9659 is configured to work under automatic synchronizing mode, all functions are
provided automatically. RCS-9659 monitors slip frequency (frequency difference), slip speed,
voltage difference and phase angle difference issues control signal to adjust frequency and
voltage of generator for voltage matching and frequency matching, gives close command to the
breaker at the correct instant.
As shown the in logic diagram of automatic synchronizing mode Figure 3.1-1, under automatic
synchronizing mode, there are two sub-modes: synchronism checking mode and dead checking
mode.
Setting [En_DeadChk] determines whether RCS-9659 works as synchronism checking
([En_DeadChk] is 0) mode or dead checking ([En_DeadChk] is 1) way.
Procedure of closing circuit breaker under automatic synchronizing mode
(1) Energize the binary input [BI_AutoSync] manually.
(2) Issue a synchronism command remotely from a substation automation system or a control
center.
(3) RCS-9659 then adjust generator frequency and voltage by sending regulation pulse signals
to the prime mover governor and the voltage regulator according to predetermined settings
automatically.
(4) RCS-9659 will issue a closing command to a circuit breaker automatically when all the
synchronism parameters are within predetermined limits. The closing logic can also adopt
contact of sync-check relay to improve security further. Refer to .
(5) Remotely send a reset command to RCS-9659 to reset operation signals and LED
CLOSE.
If the dead checking mode is enabled ([En_DeadChk] is 1), immediate CB closure is enabled if
the system voltage or generator voltage is less than the setting [V_DeadChk_Sync].
By the way, the automatic synchronizing mode is suitable for a substation or a power plant where
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 12
automatic control system is equipped by the aid of which synchronism command can be issued to
RCS-9659 automatically by substation automation system or energy management system.
Logic scheme
Ug
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 13
[En_SyncRly]: it is the logic setting used to determine that whether the status of contac ts of
sync-check relay shall be used to back up RCS-9659s operation. Set 1 to adopt normally open
contact and normally closed contact of sync-check relay.
[V_Diff_Sync]: it is the permissible voltage difference for synchronism check.
[f_Diff_Sync]: it is the permissible slip frequrence for synchronism check.
[df/dt_Sync]: it is the permissible frequrence slip speed difference for synchronism check.
U_diff: it is the measured voltage difference.
f_diff: it is the measured slip frequency.
df/dt: is the measured frequency slip speed.
phi_dif: it is the measured angle difference.
Phi_Limit*, V_Limt*: they are constant settings that are unnecessary to modify as it has been
already set in the program.
Us: it represents three phase voltages of system side, e.g. Usa, Usb and Usc.
Ug: it represents three phase voltages of generator side, e.g. Uga, Ugb and Ugc.
VT Circuit Failure: it is the internal flag indicating that VT circuit failure is detected. If
[En_DeadChk] and [En_VTS] are set as 1, a detected VT circuit failure will block the CB closing
command output contact in the dead checking mode.
Block output: it is the NO contact (i.e. BO_Blk_n) on the OUTn board (n=1,2,,A) of RCS-9659
operating to block other equipment
Close CB: it is the NO contact (i.e. BO_Cls_n ) on the module OUTn board (n=1,2,,A) of
RCS-9659 operating to parallel generator or reclose a line.
3.1.2 Semi-automatic Synchronizing Mode
If RCS-9659 is configured to work under semi-automatic synchronizing mode, except that an
operator has to select wanted circuit breaker to close and to initiate synchronism process manually,
the other functions are provided automatically just the same as automatic synchronizing mode.
RCS-9659 monitors slip frequency (frequency difference), slip speed, voltage difference and
phase angle difference, issues control signal to adjust frequency and voltage of generator for
voltage matching and frequency matching, gives close command to the breaker at the correct
instant.
As shown in the logic diagram of automatic synchronizing mode Figure 3.1-2, under
semi-automatic synchronizing mode, there are two sub-modes: synchronism checking mode and
dead checking mode.
Setting [En_DeadChk] and binary input [BI_ManDeadChk] together determine whether RCS-9659
works as synchronism checking ([En_DeadChk] is set 0 or [BI_ManDeadChk] is de-energized)
mode or dead checking ([En_DeadChk] is set 1 and [BI_ManDeadChk] is energized) way. Refer
to Figure 3.1-2.
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 14
Procedure of closing circuit breaker under semi-automatic synchronizing mode
(1) Energize the binary input [BI_SemiSync] (refer to 6.2.6) manually.
(2) Select the expected circuit breaker by energizing the associated binary input
[BI_RmtSyncCmd_n]* (n=1,2,,A) manually.
(3) Initiate a synchronism process by energizing the binary input [BI_TrigSync] manually. After
the synchronism process has started, de-energize [BI_TrigSync].
(4) RCS-9659 will adjust generator frequency and voltage by sending regulation pulse signals
to the prime mover governor and the voltage regulator according to predetermined settings
automatically.
(5) RCS-9659 will issue a closing command to a circuit breaker automatically when all the
synchronism parameters are within predetermined limits. When synchronism checking other
than dead checking function is used, the closing logic can also adopt the contact of sync-check
relay to improve security further.
(6) Remotely or locally send a reset command to RCS-9659 to reset operation signals and LED
CLOSE.
(7) De-energize associated binary input [ManualSynCmd.n] (n=1,2,,A) manually.
If the dead checking mode is enabled ([En_DeadChk] is set 1 and [BI_ManDeadChk] is
energized), immediate CB closure is enabled if the system voltage or generator voltage is less
than the setting [V_DeadChk_Sync]. Refer to Figure 3.1-2.
The semi-automatic synchronizing mode is usually used for locally initiating synchronism process
or checking the synchronizer RCS-9659.
Logic scheme
1Ug
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 15
[BI_SemiSync]: it is the binary input on terminal E08 used to enable that RCS-9659 works in
semi-automatic synchronizing mode.
[BI_ManSynCmd_n]*: it is the binary input on terminal n28 used to select desired circuit breaker to
be closed.
[BI_TrigSync]: it is the binary input on terminal E23, by which RCS-9659 is triggered to initiate
synchronism process.
[BI_ManDeadChk]: it is the binary input on terminal E10. [BI_ManDeadChk] and [En_DeadChk]
are together used to enable dead checking mode.
[BI_ExtBlk]: it is the binary input on terminal E26, by which RCS-9659 can be blocked by an
external signal from other protection relays.
[BI_RunState]: it is a binary input on terminal E07 used to configure that RCS-9659 works in
normal operation mode or works in testing mode.
[BI_NC_SyncRly]: it is a binary input on terminal E20 used to adopt the status of the normal closed
contact of sync-check relay.
[En_DeadChk]: it is the logic setting used to enable RCS-9659 work under dead checking mode.
[V_DeadChk_Sync]: it is the setting used to judge whether the generator side or the system side is
dead or live.
[En_AutoReg]: it is the logic setting used to determine whether to adjust the frequency and voltage
automatically or not when paralleling a generator. Set 1 to enable the function.
[En_SyncRly]: it is the logic setting used to determine that whether the status of contacts of
sync-check relay shall be used to back up RCS-9659s operation. Set 1 to adopt normally open
contact and normally closed contact of sync-check relay.
[V_Diff_Sync]: it is the permissible voltage difference for synchronism check.
[f_Diff_Sync]: it is the permissible slip frequency for synchronism check.
[df/dt_Sync]: it is the permissible frequency slip speed difference for synchronism check.
U_dif: is the measured voltage difference.
f_dif: it is the measured slip frequency.
df/dt: it is the measured frequency slip speed.
phi_dif: it is the measured angle difference.
Phi_Limit*, V_Limt*: they are constant settings that are unnecessary to modify as it has been
already set in the program.
Us: it represents three phase voltages of system side, e.g. Usa, Usb and Usc.
Ug: it represents three phase voltages of generator side, e.g. Uga, Ugb and Ugc.
VT Circuit Failure: it is the internal flag indicating that VT circuit failure is detected. If
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 16
[En_DeadChk] and [En_VTS] are set as 1, a detected VT circuit failure will block the CB closing
command output contact in the dead checking mode.
Block output: it is the NO contact (i.e. BO_Blk_n) on the OUTn board (n=1,2,,A) of RCS-9659
operating to block other equipment
Close CB: it is the NO contact (i.e. BO_Cls_n ) on the module OUTn board (n=1,2,,A) of
RCS-9659 operating to parallel generator or reclose a line.
3.1.3 Manual Synchronizing Mode
When RCS-9659 is configured to work under manual synchronizing mode, all functions have to be
performed manually. According to the information provided by the digital frequency and voltage
meters and synchroscope, the operator controls the speed and voltage of the generator as well as
the closure of the circuit breaker.
As shown in the logic diagram of automatic synchronizing mode Figure 3.1-3, under
semi-automatic synchronizing mode, there are two sub-modes: synchronism checking mode and
dead checking mode.
Binary input [BI_ManDeadChk] determines whether RCS-9659 works as synchronism checking
([BI_ManDeadChk] is de-energized) mode or dead checking ([BI_ManDeadChk] is energized)
way.
Procedure of closing circuit breaker under manual synchronizing mode
(1) Energize binary input [BI_ManSync] manually.
(2) Select expected circuit breaker by energizing associated binary input [BI_ManSynCmd_n]
(n=1,2,,A) manually.
(3) Initiate a synchronism process by energizing binary input [BI_TrigSync] manually.
(4) Adjust the generator frequency and voltage based on reading of frequency meter, and
voltage meter.
(5) Manually issue a closing command to the circuit breaker at the correct instant based on
reading of the synchroscope. When synchronism checking other than deadline checking
function is used, the closing contact can also be in series with the contact of sync-check relay to
improve security further.
(6) Locally send a reset command to RCS-9659 to reset operation signals and LED CLOSE.
Whether the circuit breaker will close or not, it may also depend on the status of the
[BI_ManDeadChk]. Refer to 6.2.6.
(7) De-energize the binary input [BI_TrigSync].
(8) De-energize associated binary input [BI_ManSyncCmd_n]* (n=1,2,,A) manually.
If Dead checking mode is enabled ([BI_ManDeadChk] is as 1) is energized, immediate CB
closure is enabled and the operator can issue closing command immediately. Refer to Figure
3.1-3.
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 17
The manual synchronizing mode is applicable for an application where there needs manual
operation. The major drawback is that an operator with enough knowledge to avoid damage to the
machinery is needed.
Logic scheme
[BI_ManSyncCmd_n]*
[BI_TrigSync]
[BI_ManSync]
[BI_NC_SyncRly]
[BI_ManDeadChk]
[BI_ManStepUp]
[BI_RunState]
[BI_ManStepDown]
[BI_ManAccel]
[BI_ExtBlk]
[BI_ManCls]
&
&
&
&
&
1
1
& &
[BI_ManDecel]
Block output
To voltage regulator
To voltage regulator
To prime mover governor
To prime mover governor
Close CB
Figure 3.1-3 Logic Diagram of Manual Synchronizing Mode
Where:
[BI_ManSync]: it is the binary input on terminal E05 used to enable that RCS-9659 works in
manual synchronizing mode.
[BI_ManSyncCmd_n]*: it is the binary input on terminal n28 used to select desired circuit breaker
to be closed.
[BI_TrigSync]: it is the binary input on terminal E23, by which RCS-9659 is triggered to initiate
synchronism process.
[BI_ManDeadChk]: it is the binary input on terminal E10. [BI_ManDeadChk] and [En_DeadChk]
are together used to enable Dead checking mode.
[BI_ManStepUp]: it is the binary input on terminal E09 used to increase the generator voltage.
[BI_ManStepDown]: it the binary input on terminal E09 used to decrease the generator voltage.
[BI_ManAccel]: it is the binary input on terminal E09 used to increase the generator frequency.
[BI_ManDecel]: it is the binary input on terminal E09 used to decrease the generator frequency.
[BI_ManCls]: it is the binary input on terminal E17, by which RCS-9659 is triggered to issue a
closing command to circuit breaker.
[BI_ExtBlk]: it is the binary input on terminal E26, by which RCS-9659 can be blocked by an
external signal from other protection relays.
[BI_RunState]: it is a binary input on terminal E07 used to configure that RCS-9659 works in
normal operation mode or works in testing mode.
[BI_NC_SyncRly]: it is a binary input on terminal E20 used to adopt the status of the normal closed
contact of sync-check relay.
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 18
Block output: it is the NO contact (i.e. BO_Blk_n) on the OUTn board (n=1,2,,A) of RCS-9659
operating to block other equipment
Close CB: it is the NO contact (i.e. BO_Cls_n ) on the module OUTn board (n=1,2,,A) of
RCS-9659 operating to parallel generator or reclose a line.
3.2 Block Function
The digital synchronizer can either send block signals to other equipment or be blocked by other
protection relays (refer to6.2.6, the binary input [BI_ExtBlk]).
Once the synchronism process has started, two normal open output contacts provided by SIG
board via terminals C27-C28 and C29-C30 (for automatic or semi-automatic synchronizing mode)
or terminals B27-B28 and B29-B30 (for manual synchronizing mode) will close to issue block
signals to other protection relays. Refer to 6.2.7 and 6.2.8.
3.3 Time Synchronization
As the equipment Real Time Clock has small drift per day, therefore, in order to have a correct
time for time tagging of event or report etc., the operator should set its time periodically or it shou ld
be synchronized by a master clock automatically.
Time synchronization of RCS-9659 can be done by four means:
(1) IRIG-B signal input from external clock device via a RS-485 port named GPS pulse
(2) Differential signal of PPS or PPM from external clock device via a RS-485 port named
GPS pulse
(3) PPM or PPS input via binary input [GPS_Pulse] terminal E02 on OPT board E. Refer
to6.2.6 for detailed description.
(4) Clock message from substation automation system depending on protocol
The external clock device receives the synchronization signal from GPS antenna and then sends it
to RCS-9659 based on IRIG-B standard, as differential signal of PPM or PPS by means of
so-called synchronization bus. When the differential signal is a PPM input, setting [GPS_Pulse]
under EQUIP SETTINGS sub-menu should be set as 1, while if the differential signal is a PPS
input, the setting [GPS_Pulse] should be set as 0. A specific clock synchronization port RS-485
interface is dedicated for this application. Refer to 0.
Substation automation system clock synchronization depends on protocol. The clock message is
directly acquired by RCS-9659 through the substation automation system link. Clock message can
provide full information for a certain time as a way of year, date, hour, minute and second while
pulse input lacks these information.
Therefore, in general applications, clock message is usually combined with PPM or PPS input via
binary input, or combined with differential signal of PPM or PPS by means of the clock
synchronization port RS-485 with an accuracy of 1ms.
Moreover, the user could also set time and data directly using the local human-machine interface
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 19
(HMI) of the equipment.
RCS-9659 internal clock will then be adjusted accordingly. When the equipment is synchronized,
all events in TRIP REPORT, ALM REPORT and BI CHG REPORT and current measurement
have a time tag with synchronized attribute.
Chapter 3 Functional Description
NR ELECTRIC CO., LTD. 20
Chapter 4 Automatic Supervision
NR ELECTRIC CO., LTD. 21
Chapter 4 Automatic Supervision
4.1 General Description
Though the protection system is in non-operating synchronism state under normal conditions, it is
waiting for a synchronism checking command and must execute it without fail. When the
equipment is in energizing process before the LED HEALTHY is on, the equipment needs to be
checked to ensure no errors. Therefore, the automatic supervision function, which checks the
health of the synchronizing system when startup and during a normal operation, plays an
important role.
The numerical synchronizer based on the microprocessor operations is suitable for implementing
this automatic supervision function of the synchronizing system.
In case a fault is detected during initialization when DC power supply is provided to the equipment,
the equipment will be blocked out, which means the synchronizer is out of service. Before you
must re-energize the synchronizer or reset CPU module by restarting equipment to make it back
into service, please find out the cause and inform the factory.
When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication and alarm contact outputs. At the same time event recording will record the failure alarm
which can be viewed in event recording report and be printed.
4.2 Synchronizer Self-supervision
4.2.1 Hardware Supervision
The DSP, RAM, ROM chips on CPU module are monitored to ensure whether they are damaged
or have errors. If any one of them is detected damaged or having error, the equipment will be
blocked and issue the alarm [Alm_RAM] and [Alm_ROM]. At the same time the HEALTHY LED
being extinguished and the ALARM LED being lit.
4.2.2 Check Setting
RCS-9659 series has 10 setting groups protection settings for 10 synchronism points respectively.
The settings of each synchronism point setting are checked to ensure they are reasonable. If the
settings are checked error in DSP chip and CPU chip, an alarm [Alm_Setting] and [Alm_EEPROM]
are issued respectively. Meanwhile, LED HEALTH is extinguished and LED ALARM is lit on.
If these 10 setting groups are not all set, when the protective device is provided with DC power
supply first, an alarm [Alm_InvalidGrp] will be issued. If the secondary rated current of CT (I2n) in
equipment parameters is changed and the protection settings is not confirmed or some settings in
protection settings exceed setting range, the alarm [Alm_InvalidGrp] will be issued. At the same
time the HEALTHY LED is extinguished and the ALARM LED being lit.
4.2.3 Voltage drift Supervision and auto adjustment
Zero point of voltage may drift influenced by variation of temperature or other environment factors.
Chapter 4 Automatic Supervision
NR ELECTRIC CO., LTD. 22
The equipment continually automatically traces the drift and adjusts it to normal value.
4.2.4 DSP sampling Supervision
AC sampling of DSP chip is monitored and if the samples are detected to be wrong, an alarm
[Alm_Smpl_DSP] will be issued and the equipment will be blocked. At the same time the
HEALTHY LED is extinguished and the ALARM LED being lit.
4.2.5 CPU sampling Supervision
The synchronizer compares the CPU sampling and DSP sampling. In normal condition, the
sampling should be the same for a certain AC input. If a sampling in CPU is detected to be
different largely with that in DSP, the alarm signal [Alm_Smpl_CPU] will be issued and the
synchronizer will be blocked. At the same time the HEALTHY LED is extinguished and the
ALARM LED being lit.
4.2.6 Opto-coupler power Supervision
Positive power supply of opto-coupler is continually monitored. If an error or damage has occurred,
the alarm [Alm_Pwr_Opto] will be issued with ALARM LED being lit, but the equipment will not
be blocked.
4.2.7 Synchronism Point Supervision
In the manual synchronizing mode, if two or more synchronism points are selected (i.e. two or
more binary inputs [BI_ManSyncCmd_n]* are energized at the same time, n=1, 2, , A) or no
synchronism point is selected (i.e. no binary input [BI_ManSyncCmd_n]* is energized, n=1, 2, ,
A) by an operator, but a synchronizing process is triggered by energizing the binary input
[BI_TrigSync], then the alarm signal [Alm_SyncPoint] will be issued with the ALARM LED being
lit, and the synchronizing function is blocked temporarily at the same time.
After the binary inputs of other synchronism points are de-energized and only one binary input of
synchronism point is kept being energized, then the alarm signal will reset with the ALARM LED
being extinguished. The synchronism checking of the point still can be carried out if the
synchronizer doesnt reset.
4.2.8 System Voltage Supervision
If the logic setting [En_DeadChk] is set as 0 and the system or generator voltage is tool low (less
than [V_DeadChk_Syn]) during a synchronism process (i.e. a synchronism process is triggered
manually or remotely), then the alarm signal [Alm_UV_Sys] will be issued with the ALARM LED
being lit, and synchronizing function is blocked temporarily at the same time.
After the system or generator voltage returns to a normal condition, the alarm signal will rest with
the ALARM LED being extinguished. The synchronism checking still can be carried out if the
synchronizer doesnt reset.
4.2.9 Voltage Transformer Supervision VTS
If the logic setting [En_VTS] are set as 1 and the negative sequence voltage of the generator
Chapter 4 Automatic Supervision
NR ELECTRIC CO., LTD. 23
side or system side is more than 8V, then the alarm signal [Alm_VTS] will be issued with the
ALARM LED being lit. If the logic setting [En_DeadChk] is set as 1 at the same time, the
synchronizing function is blocked temporarily.
After the generator or system voltage returns to a normal condition, the alarm signal will rest with
the ALARM LED being extinguished. The synchronism checking still can be carried out if the
synchronizer doesnt reset.
4.2.10 Circuit Breaker Closing Supervision
After a closing pulse to close a circuit breaker is issued by the synchronizer, the alarm signal
[Alm_Fail_Cls] will be issued if the auxiliary contact of the circuit breaker doesnt return a signal
(i.e. the binary input [BI_AuxContact] is energized), which means the circuit breaker is failed to be
closed.
4.3 Understand the Alarms
The hardware circuits and operation conditions of the equipment are self-supervised continuously.
If any abnormal condition is detected, information or report will be displayed and a corresponding
alarm will be issued.
A common abnormality may block a certain number of functions while the other functions can still
work. However, if serious hardware failure or abnormality were detected, all functions will be
blocked and the LED HEALTHY will be extinguished and blocking signal will be given by the
corresponding contacts outputs BO_Fail. The synchronizer equipment then cannot work normally
and maintenance is required to eliminate the failure.
NOTE: If the synchronizer is blocked or alarm signal is sent during operation, please do
find out its reason with the help of self-diagnose record. If the reason can not be found at
site, please notice the factory NR. Please do not simply press button TARGET RESET
on the protection panel or re-power on the equipment.
Table 4.3-1 Repairmen suggestion for alarms information
No. Alarm Message Meaning Description
1 Alm_RAM CPU module RAM is damaged.
2 Alm_ROM CPU module ROM is damaged.
3 Alm_EEPROM Invalid settings in any setting group
4 Alm_InvalidGrp Invalid settings in active setting group
5 Alm_Smpl_CPU CPU chip sample differs too much from DSP sampling
6 Alm_Smpl_DSP DSP chip is damaged or DSP sampling is wrong
7 Alm_Setting Settings in active group are found error after setting check in DSP chip
When No.1~No.7 above alarm messages are displayed on the LCD, the LED HEALTHY is extinguished and the LED ALARM is it. At the same time the synchronizer equipment is blocked.
8 Alm_Pwr_Opto Loss of opto-coupler power supply.
Chapter 4 Automatic Supervision
NR ELECTRIC CO., LTD. 24
No. Alarm Message Meaning Description
9 Alm_SyncPoint Two or more synchronism points are selected or no synchronism point is selected by the operator.
10 Alm_UV_Sys System voltage is too low.
11 Alm_VTS The secondary circuit of the voltage transformer of system or generator is abnormal.
12 Alm_Fail_Cls A circuit breaker is failed to close.
When the No.8~No.12 above alarm messages are issued on the LCD, the LED HEALTHY is still on, and the LED ALARM is lit. No.8 and No.9 alarm signals can result in blocking synchronizing process and please refer to the sections 4.2.7 and 4.2.8 respectively for details.
Handling suggestion
1. Inform manufacturer for maintenance.(No.1~No.7)
2. Check the power supply in the OPT module. (No.8)
3. Check whether two or more synchronism points are selected or no synchronism point is
selected on the SCP (Synchronization Control Panel). (No.9)
4. Check the sample value, the setting, and the corresponding VT secondary circuit of the
system voltage. (No.10)
5. Check the sample value, and the corresponding VT secondary circuit. (No.11)
6. Check whether the circuit breaker is failed to close, and if it has been closed, please check the
auxiliary contact of the circuit breaker and the corresponding binary input of the contact.
(No.12)
Chapter 5 Metering and Recording
NR ELECTRIC CO., LTD. 25
Chapter 5 Metering and Recording
5.1 General Description
The synchronizer also provides some auxiliary functions, such as real-time data metering, binary
input status recording, event and disturbance recording, etc. All these make the synchronizer meet
the demands of the modern power grid requirements.
5.2 Metering
RCS-9659 performs continuous measurement of the analogue input quantities. The measurement
data shown below is displayed on the LCD of the synchronizer front panel or on the local or remote
PC.
Equipment samples 24 points per cycle. Calculate the RMS value in each interval and LCD will be
updated every 0.5 second. The following system quantities are displayed in RMS values of the
secondary side of CT and VT. This device has double CPU system (i.e. CPU and MON module),
so the sampled values of both modules will be displayed on LCD through different access menu.
NOTE: Ie and In mentioned in following sections are units. Ie is secondary rated current of
transformer and In is secondary rated current of CT.
Table 5.2-1 Measured values in MON module
No. Value Meaning Unit
1 Ua_S A-phase voltage of system side V
2 Ub_S B-phase voltage of system side V
3 Uc_S C-phase voltage of system side V
4 Ua_G A-phase voltage of generator side V
5 Ub_G B-phase voltage of generator side V
6 Uc_G C-phase voltage of generator side V
7 Udif Voltage difference. It equals to UGa - USa V
8 F_S System frequency (USa) Hz
9 F_G Generator frequency (UGa) Hz
10 Fdif Frequency difference. It equals to F_S - F_G Hz
11 Facc Delta of Facc. It equals to dif /dt Hz/s
12 Pdif The advance angle of the system voltage leading the generator
voltage.
13 Tcls Actual breaker closing time measured by RCS-9659 s
Path VALUES -> MEASUREMENT
Chapter 5 Metering and Recording
NR ELECTRIC CO., LTD. 26
Table 5.2-2 Relevant quantities of differential protection
No. Value Meaning Unit
1 (Ua_Ub)_S Phase angle between Ua_S and Ub_S
2 (Ub-Uc)_S Phase angle between Ub_S and Uc_S
3 (Uc-Ua)_S Phase angle between Uc_Sand Ua_S
4 (Ua-Ub)_G Phase angle between Ua_G and Ub_G
5 (Ub-Uc)_G Phase angle between Ub_G and Uc_G
6 (Uc-Ua)_G Phase angle between Uc_G and Ua_G
7 (US-UG)_a Phase angle between Ua_S and Ua_G
Path VALUES -> PHASE ANGLE
5.3 Binary Input
All the binary input changes are recorded in the synchronizer, and can be displayed on LCD locally
printed or sent to automation system of substation via communication channel.
Table 5.3-1 Binary input status list
No. Value Meaning
1 BI_AutoSync Binary input of enabling automatic synchronizing mode.
2 BI_SemiSync Binary input of enabling semi-automatic synchronizing mode.
3 BI_ManSync Binary input of enabling manual synchronizing mode.
4 BI_RunState Binary input of selecting running mode of the synchronizer.
5 BI_NC_SyncRly Binary input of the normally closed contact of the sync-check relay.
6 BI_NO_SyncRly Binary input of the normally open contact of the sync-check relay.
7 BI_Resv Reserved binary input.
8 BI_ManDeadChk Binary input of enabling the dead checking of the manual
synchronizing mode.
9 BI_AuxContact Binary input of auxiliary contact of a circuit breaker to be closed.
10 BI_TrigSync Binary input of manual triggering synchronism process.
11 BI_ExtBlk Binary input of external blocking signal.
12 BI_ManCls Binary input of manual closing signal.
13 BI_Pulse_GPS Binary input of GPS synchronizing pulse.
14 BI_Print Binary input of printing.
15 BI_BlkComm Binary input of blocking communication.
16 BI_RstTarg Binary input of resetting signal.
Path VALUES->BI STATE
5.4 Recording
5.4.1 General description
The RCS-9659 series provides the following recording functions:
Chapter 5 Metering and Recording
NR ELECTRIC CO., LTD. 27
Event recorder
Disturbance recorder
These records are displayed on the LCD of the synchronizer front panel or on the local or remote
PC. Navigate the menu to view the report through LCD screen.
5.4.2 Event recorder
Event recorder includes self-supervision report, status change of binary input report and operating
report. The equipment can store 64 records of each kind for self-supervision report and status
change of binary input report in non-volatile memory.
1. Self-supervision report
The equipment is under automatic supervision all the time. If there are any failure or abnormal
condition detected, such as, chip damaged, VT circuit failure and so on , it will be logged as an
event.
2. Status change of binary input report
When there is binary input is energized or de-energized, i.e., its state has changed from 0 to 1
or from 1 to 0, it will be logged as an event r.
3. Tripping reports
When a synchronizing process is triggered and a circuit breaker is closed, than a report
[Op_Clsed_CB] will be recorded as an event.
5.4.3 Disturbance recorder
RCS-9659 can save 24 pieces of waveforms of synchronizing operations. If a new synchronizing
operation occurs when 24 waveform records have been stored, the waveform of the first type of
fault report will be overwritten, and then the latest waveform record will overwrite the oldest one if
another new fault waveform is generated again. The synchronizer stores actual samples that are
taken at a rate of 24 samples per cycle. Besides the voltage waveform, binary inputs state and
measurement magnitudes are all recorded.
There are the following two ways to initiate RCS-9659s oscillographic process to records 8 cycles
waveforms before the initiating time and 2 cycles after the initiating time.
(1) Being initiated by the binary input [BI_AuxContact]
If the logic setting [En_AuxContact] is set as 1, oscillographic process will be initiated to record
waveforms when [BI_AuxContact] rises from 0 to 1, i.e. the time when breaker is closed.
(2) Being initiated by a time delay [t_Cls_CB]
If the logic setting [En_AuxContact] is set as 0, oscillographic process will be initiated to record
waveforms after a delay (i.e. setting [t_Cls_CB]), and the delay timer begins to time since
RCS-659 issuing a closing command to circuit breaker.
Chapter 5 Metering and Recording
NR ELECTRIC CO., LTD. 28
Chapter 6 Hardware Description
NR ELECTRIC CO., LTD. 29
Chapter 6 Hardware Description
6.1 Overview
Modular structured digital synchronizer RCS-9659 is IEC 4U high and 19 wide and adopts an
integral faceplate.
Front panel and rear panel are shown in Figure 6.1-1 respectively.
RCS974AGTRANSFORMER AUXILIARY RELAY
HEALTHY
ALARM
SYNC
f
U
CLOSE
TARGET RESET
AUTO SYNCHRONIZER
NANJING NARI-RELAYS ELECTRIC CO., LTD
RCS9659
f
U
Figure 6.1-1 Front Panel of RCS-9659
OUTDC220V AC LPF CPU COM SIGSIGOPT OUT OUT OUTOUT OUT OUTOUT OUT OUT
K
DC
J
AC
F
COM
1
OUT
2
OUT
3
OUT
4
OUT
5
OUT
6
OUT
7
OUT
8
OUT
9
OUT
A
OUT
B
SIG
C
SIG
E
OPT
G
CPU
H
LFP
No.
Module
Figure 6.1-2 Rear View of RCS-9659
The digital synchronizer RCS -9659 comprises 8 plug-in modules as described in follow sections.
RCS-9659 comprises the following 18 plug-in modules. Figure 6.1-2 is rear view of the equipment
and shows disposition of these modules.
Table 6.1-1 Hardware configuration
Chapter 6 Hardware Description
NR ELECTRIC CO., LTD. 30
No. Module Description
1 OUT Synchronism operating module
2 OUT Synchronism operating module (optional)
3 OUT Synchronism operating module (optional)
4 OUT Synchronism operating module (optional)
5 OUT Synchronism operating module (optional)
6 OUT Synchronism operating module (optional)
7 OUT Synchronism operating module (optional)
8 OUT Synchronism operating module (optional)
9 OUT Synchronism operating module (optional)
A OUT Synchronism operating module (optional)
B SIG Signal output module
C SIG Signal output module
E OPT Binary input opto-coupler module
F COM Communication module
G CPU Control nucleus of the equipment
H LFP Low-pass filter
J AC AC current and voltage input module
K DC DC power supply module
No.1~No.A OUT modules are configured according to the requirement of the applied-specific
project.
6.2 Plug-in Modules
6.2.1 DC Module (No.K DC)
DC power supply (250V/220V/125V/110 V) shall be connected to terminals K01(+) and K02 (-).
Through interference filter and power switch on the rear, DC/DC converter converts the DC power
supply to three voltage class +5V, 12V and +24V to supply to other modules of the equipment.
Terminal K04 (+) and terminal K05 (-) output 24V as power supply of OPT. Terminal K06 is surge
ground. The following figure shows rear view and connections of DC power supply module.
Chapter 6 Hardware Description
NR ELECTRIC CO., LTD. 31
102
101
104
105
106
To other
modules To 24V OPT module
Ground
From DC power supply
DC/DC
5V
12V
24V
Inte
rfere
nce filt
er
101
102
103
104
105
GND
DC
1
106
Pwr +
Pwr -
Opto L -
Opto L +
+
Figure 6.2-1 Rear View and Connections of DC Module
WARNINGIt is only permitted to withdraw or insert the DC module or some other
modules when the auxiliary power is switched off.
6.2.2 AC Module (No.J AC)
Figure 6.2-2 shows rear view and typical connections of AC module.
Chapter 6 Hardware Description
NR ELECTRIC CO., LTD. 32
A
B
C
To LPF
52G
n01
n02
n03
n04
n28(26)
n05
n06
n07
n08
from other OUT boardBUS
J05
J09
J13
J01
To LPF
n09
n10
n11
n12
n13
n14
n15
n16
from other OUT board
J21
J25
J29
J17
AC
J01
Syste
m V
oltage Input
J02
J03 J04
J05 J06
J07 J08
J09 J10
J11 J12
J13 J14
J15 J16
J17 J18
J19 J20
J21 J22
J23 J24
J25 J26
J27 J28
J29 J30 Genera
tor
Voltage Input
OUT board AC board
Syste
m V
oltage Input
Genera
tor
Voltage Input
Ub_S
Uc_S
Ua_S
Un_S
Ua_G
Ub_G
Uc_G
Un_G
Figure 6.2-2 Rear View and Typical Connections of AC Module
Both generator voltage and bus voltage on both sides of the breaker are inputted together, and
have a nominal rating of 100V or 100V/3V at 50/60Hz. As illustrated in Figure 6.2-2, secondary
voltage from voltage transformer (VT) on both sides of circuit breaker first enters into OUT board,
then passes a selective switchover circuit (remotely or locally controlled by terminal n26 (n28)).
After that, only one group of system voltage and generator voltage comes into No.J, the AC board.
Small VTs built in AC board provide isolation and converts the secondary voltage from VT to a
synchronizer acceptable level and then transfer it to LPF board for filtering. Following the low-pass
filter circuits, the analog signals enter into well-designed precise phase detecting circuit and high
accurate A/D converter. Then DSP will calculate the voltage, frequency and phase angle and
check the synchronism conditions independently. If RCS-9659 is configured to work as
synchronism checking mode, the breaker can be closed only when synchronism conditions are
met which is judged by DSP. The AC signal flow graph is proposed in Figure 6.2-3.
Chapter 6 Hardware Description
NR ELECTRIC CO., LTD. 33
AC
board
LPF
board
CPU
board
OUT
board
52
GP
ow
er
Gri
d
BU
S
Figure 6.2-3 AC Signal Flow Graph
Furthermore, there is an earthing terminal on AC board. It shall be connected to station ground
grid.
NOTESince RCS-9659 calculates synchronism conditions according the voltages
inputted via channels Ua_S and Ua_G, these two channels must be led with appropriate
voltages.
DANGERNever allow the VT secondary circuit connected to the AC board or OUT board
to be short circuit while the primary system is live. Short the VT circuit will produce a
dangerously strong current.
6.2.3 LFP Module (No.H LFP)
This module is used to filter high frequency disturbance from the AC signal, regulate the input level
and provide an interface between the equipment and dedicated test instrument HELP-90A
developed by NR.
From module AC
From HELP-90AMeasurement in DSP Low-pass filterAdder
Figure 6.2-4 Block Diagram of LFP Module
6.2.4 CPU Module (No.G CPU)
Module CPU, control nucleus of the equipment, comprises monolithic micro controller CPU and
digital signal processor DSP. CPU finishes the following functions:
1 General fault detection
Chapter 6 Hardware Description
NR ELECTRIC CO., LTD. 34
2 Event recorder and disturbance recorder (could be printed via serial port)
3 Print and communication with HMI
4 Communication with the host of SCADA system of the substation
DSP finishes the following functions:
5 Algorithm and logic of protection
Sampling rate of the equipment is 24 points per cycle. Parallel real time data is calculated for
algorithm and logic of protection at every sampling point. Hence, very high inherent reliability and
security are ensured.
6.2.5 COM module (No.F COM)
Module COM performs connection between the equipment and the SCADA system or RTU. Three
types are available.
To SAS
To SAS
To GPS for clock synchronism
To printer or controller
Type 5A
COM
7
8
9
1
2
3
4
5
6
10
11
12
RS-485 1A
RS-485 1B
Printer RX
Printer TX
Printer Ground
RS-485 1GND
RS-485 2A
RS-485 2B
RS-485 2GND
RS-485 A
RS-485 B
RS-485 GND
PORT 1 PORT 2 PORT 3 PORT 4
Type
Physical Layer
RS-485 RS-485 RS-485 RS-485/RS-232
Twisted pair wire Twisted pair wireTwisted pair wire Twisted pair wire
Figure 6.2-5 Rear view of type A and external connections of COM module
Optic Fibre
Optic Fibre
To printer or controller
To GPS for clock synchronism
To SAS
To SAS
RS-485 A
RS-485 B
RS-485 GND
Printer RX
Printer TX
Printer Ground
1
2
3
4
5
6
Op.Fib.RX1
Op.Fib.TX1
Op.Fib.RX2
Op.Fib.TX2
Type 5B
COM
TX
TX
RX
RX
PORT 1 PORT 2 PORT 3 PORT 4
Type
Physical Layer
RS-485 RS-485 RS-485 RS-485/RS-232
Optic fibre Twisted pair wireOptic fibre Twisted pair wire
Figure 6.2-6 Rear view of type B and external connections of COM module
Chapter 6 Hardware Description
NR ELECTRIC CO., LTD. 35
To GPS for clock synchronism
To printer or controller
1
2
3
4
5
6
7
8
9
RS-485A
RS-485B
RS-485GND
RS-485A
RS-485B
RS-485GND
Printer RX
Printer TX
Printer Ground
To SAS
To SAS
To SAS
To SAS
To SAS
Ethernet 1
10/100 TX
Ethernet 4
10/100 TX
Ethernet 3
10/100 TX
Ethernet 2
10/100 TX
Type 5E
COM
PORT 1 PORT 2 PORT 3 PORT 4
Type
Physical Layer
Ethernet Ethernet Ethernet RS-485
Twisted pair
wire
Twisted pair
wire
Twisted pair
wire
Twisted pair
wire
PORT 5
RS-485/
RS-232
Twisted pair
wire
PORT 6 PORT 7
Ethernet RS-485
Twisted pair
wire
Twisted pair
wire
Figure 6.2-7 Rear view of type E and external connections of COM module
All ports used to communicate with SAS support IEC60870-5-103 protocol, moreover, Ethernet
port in COM modules of type 5E also supports IEC61850. From Figure 6.2-5 to Figure 6.2-7 shows
rear view of these types and their external connections.
All types are equipped with a RS-485 port for receiving second pulse signal (PPS-pulse per
second) from GPS and a port for printer. Printer port could be configured as RS-232 or RS-485 by
setting corresponding jumpers on the PCB (RS-232 default). If logic setting [En_Net_Print] is set to
1, printer port must be set as RS-485. Transmission rate of printer port can be set by the setting
[Printer_Baud] and should be the same with baud rate of the printer.
NOTE: For the port used to printer or controller, it can be configured as RS-485 or RS-232
by setting corresponding jumper of module COM. The port is configured as RS-232 by
shorting PIN 1 and PIN 2 and as RS-485 by shorting PIN 2 and PIN 3. As shown in Figure
6.2-8
PIN 1 PIN 2 PIN 3
RS-232RS-485
Figure 6.2-8 Print Port Configuration
There are three options to finish time synchronization:
1 Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact
2 Receiving PPS, PPM and I