RCS-9659_X_Instruction Manual_EN_Domestic General_X_R1.02_(EN_DYBH0319.0086.0003).pdf

  • Upload
    tonybui

  • View
    27

  • Download
    0

Embed Size (px)

Citation preview

  • RCS-9659

    Auto Synchronizer

    Instruction Manual

    NR Electric Co., Ltd.

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. i

    Preface

    Introduction

    This guide and the relevant operating or service manual documentation for the equipment provide

    full information on safe handling, commissioning and testing of this equipment.

    Documentation for equipment ordered from NR Electric Co., Ltd. is dispatched separately from

    manufactured goods and may not be received at the same time. Therefore this guide is provided

    to ensure that printed information normally present on equipment is fully understood by the

    recipient. Before carrying out any work on the equipment the user should be familiar with the contents of this

    manual, and read relevant chapter carefully.

    This chapter describes the safety precautions recommended when using the equipment. Before

    installing and using the equipment, this chapter must be thoroughly read and understood.

    Health and Safety

    The information in this chapter of the equipment documentation is intended to ensure that

    equipment is properly installed and handled in order to maintain it in a safe condition.

    When electrical equipment is in operation, dangerous voltages will be present in certain parts of

    the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger

    personnel and equipment and cause personal injury or physical damage.

    Before working in the terminal strip area, the equipment must be isolated.

    Proper and safe operation of the equipment depends on appropriate shipping and handling,

    proper storage, installation and commissioning, and on careful operation, maintenance and

    servicing. For this reason only qualified personnel may work on or operate the equipment.

    Qualified personnel are individuals who:

    Are familiar with the installation, commissioning, and operation of the equipment and of the

    system to which it is being connected;

    Are able to safely perform switching operations in accordance with accepted safety

    engineering practices and are authorized to energize and de-energize equipment and to

    isolate, ground, and label it;

    Are trained in the care and use of safety apparatus in accordance with safety engineering

    practices;

    Are trained in emergency procedures (first aid).

    Instructions and Warnings

    The following indicators and standard definitions are used:

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. ii

    DANGER means that dearth, severe personal injury, or considerable equipment damage will

    occur if safety precautions are disregarded.

    WARNING means that dearth, severe personal or considerable equipment damage could occur

    if safety precautions are disregarded.

    CAUTION means that light personal injury or equipment damage may occur if safety

    precautions are disregarded. This particularly applies to damage to the device and to

    resulting damage of the protected equipment.

    WARNING!

    The firmware may be upgraded to add new features or enhance/modify existing features, please

    make sure that the version of this manual is compatible with the product in your hand.

    WARNING!

    During operation of electrical equipment, certain parts of these devices are under high voltage.

    Severe personal injury or significant equipment damage could result from improper behavior.

    Only qualified personnel should work on this equipment or in the vicinity of this equipment. The se

    personnel must be familiar with all warnings and service procedures described in this manual, as

    well as safety regulations.

    In particular, the general facility and safety regulations for work with high-voltage equipment must

    be observed. Noncompliance may result in dearth, injury, or significant equipment damage.

    DANGER!

    Never allow the current transformer (CT) secondary circuit connected to this equipment to be

    opened while the primary system is live. Opening the CT circuit will produce a dangerously high

    voltage.

    WARNING!

    Exposed terminals

    Do not touch the exposed terminals of this equipment while the power is on, as the high voltage

    generated is dangerous

    Residual voltage

    Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It

    takes a few seconds for the voltage to discharge.

    CAUTION!

    Earth

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. iii

    The earthing terminal of the equipment must be securely earthed

    Operating environment

    The equipment must only be used within the range of ambient environment detailed in the

    specification and in an environment free of abnormal vibration.

    Ratings

    Before applying AC voltage and current or the DC power supply to the equipment, check that they

    conform to the equipment ratings.

    Printed circuit board

    Do not attach and remove printed circuit boards when DC power to the equipment is on, as this

    may cause the equipment to malfunction.

    External circuit

    When connecting the output contacts of the equipment to an external circuit, carefully check the

    supply voltage used in order to prevent the connected circuit from overheating.

    Connection cable

    Carefully handle the connection cable without applying excessive force.

    Copyright

    Version: R1.02

    P/N: EN_DYBH0319.0086.0003

    Copyright NR 2008. All rights reserved

    We reserve all rights to this document and to the information

    contained herein. Improper use in particular reproduction and

    dissemination to third parties is strictly forbidden except where

    expressly authorized.

    The information in this manual is carefully checked periodically,

    and necessary corrections will be included in future editions. If

    nevertheless any errors are detected, suggestions for correction or

    improvement are greatly appreciated.

    We reserve the rights to make technical improvements without

    notice.

    NR ELECTRIC CO., LTD.

    69 Suyuan Avenue, Jiangning, Nanjing 211102, China

    Tel: 86-25-87178185, Fax: 86-25-87178208

    Website: www.nari -relays.com

    Email: international@nari -relays.com

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. iv

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. v

    Table of Contents

    Preface ........................................................................................................................................ i

    Introduction ......................................................................................................................... i

    Health and Safety ................................................................................................................ i

    Instructions and Warnings .................................................................................................. i

    Table of Contents....................................................................................................................... v

    Chapter 1 Introduction .............................................................................................................. 1

    1.1 Application .................................................................................................................... 1

    1.2 Functions ...................................................................................................................... 1

    1.3 Features ........................................................................................................................ 2

    1.4 Ordering ........................................................................................................................ 2

    Chapter 2 Technical Data .......................................................................................................... 5

    2.1 Electrical Specifications ............................................................................................... 5

    2.1.1 Analog Voltage Input Ratings ............................................................................. 5

    2.1.2 Power supply ...................................................................................................... 5

    2.1.3 Binary input......................................................................................................... 5

    2.1.4 Binary output ...................................................................................................... 5

    2.1.5 Power supply output for Opto-coupler .............................................................. 6

    2.2 Mechanical Specifications............................................................................................ 6

    2.3 Ambient Temperature and Humidity Range ................................................................ 6

    2.4 Rear Communication Port ............................................................................................ 7

    2.5 Type Tests ..................................................................................................................... 8

    2.5.1 Environmental tests ............................................................................................ 8

    2.5.2 Mechanical tests ................................................................................................. 8

    2.5.3 Electrical tests .................................................................................................... 8

    2.5.4 Electromagnetic compatibility ........................................................................... 9

    2.6 Certifications................................................................................................................. 9

    2.7 Functional Specification............................................................................................. 10

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. vi

    2.7.1 Accurate Operating Scope ............................................................................... 10

    2.7.2 Synchronism Check function........................................................................... 10

    Chapter 3 Functional Description ............................................................................................11

    3.1 Synchronizing Modes ..................................................................................................11

    3.1.1 Automatic Synchronizing Mode ........................................................................11

    3.1.2 Semi-automatic Synchronizing Mode .............................................................. 13

    3.1.3 Manual Synchronizing Mode ............................................................................ 16

    3.2 Block Function............................................................................................................ 18

    3.3 Time Synchronization................................................................................................. 18

    Chapter 4 Automatic Supervision........................................................................................... 21

    4.1 General Description .................................................................................................... 21

    4.2 Synchronizer Self-supervision................................................................................... 21

    4.2.1 Hardware Supervision ...................................................................................... 21

    4.2.2 Check Setting .................................................................................................... 21

    4.2.3 Voltage drift Supervision and auto adjustment ............................................... 21

    4.2.4 DSP sampling Supervision............................................................................... 22

    4.2.5 CPU sampling Supervision .............................................................................. 22

    4.2.6 Opto-coupler power Supervision ..................................................................... 22

    4.2.7 Synchronism Point Supervision ...................................................................... 22

    4.2.8 System Voltage Supervision ............................................................................ 22

    4.2.9 Voltage Transformer Supervision VTS ..................................................... 22

    4.2.10 Circuit Breaker Closing Supervision ............................................................. 23

    4.3 Understand the Alarms ............................................................................................... 23

    Chapter 5 Metering and Recording......................................................................................... 25

    5.1 General Description .................................................................................................... 25

    5.2 Metering ...................................................................................................................... 25

    5.3 Binary Input................................................................................................................. 26

    5.4 Recording.................................................................................................................... 26

    5.4.1 General description .......................................................................................... 26

    5.4.2 Event recorder .................................................................................................. 27

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. vii

    5.4.3 Disturbance recorder........................................................................................ 27

    Chapter 6 Hardware Description............................................................................................. 29

    6.1 Overview ..................................................................................................................... 29

    6.2 Plug-in Modules .......................................................................................................... 30

    6.2.1 DC Module (No.K DC) ....................................................................................... 30

    6.2.2 AC Module (No.J AC) ........................................................................................ 31

    6.2.3 LFP Module (No.H LFP) .................................................................................... 33

    6.2.4 CPU Module (No.G CPU) .................................................................................. 33

    6.2.5 COM module (No.F COM) ................................................................................. 34

    6.2.6 OPT Module (No.E OPT) ................................................................................... 36

    6.2.7 SIG Module (No.C SIG) ..................................................................................... 40

    6.2.8 SIG Module (No.B SIG) ..................................................................................... 41

    6.2.9 OUT Module (No.n OUT) ................................................................................... 42

    Chapter 7 Settings ................................................................................................................... 45

    7.1 Equipment Settings .................................................................................................... 45

    7.2 Protection Settings ..................................................................................................... 47

    7.3 IP address ................................................................................................................... 50

    Chapter 8 HMI Operation Introduction ................................................................................... 51

    8.1 Overview ..................................................................................................................... 51

    8.1.1 Keypad operation.............................................................................................. 52

    8.1.2 LED Indicators .................................................................................................. 53

    8.1.3 Communication Ports ....................................................................................... 54

    8.1.4 TARGET RESET Button .................................................................................... 54

    8.2 Understand the HMI Menu Tree .................................................................................. 54

    8.2.1 Overview............................................................................................................ 54

    8.2.2 VALUES ............................................................................................................. 55

    8.2.3 REPORT............................................................................................................. 56

    8.2.4 PRINT................................................................................................................. 56

    8.2.5 SETTINGS.......................................................................................................... 56

    8.2.6 CLOCK............................................................................................................... 57

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. viii

    8.2.7 VERSION ........................................................................................................... 57

    8.2.8 LANGUAGE ....................................................................................................... 57

    8.3 Understand the LCD Display ...................................................................................... 57

    8.3.1 Main display under normal operation condition ............................................. 57

    8.3.2 Display tripping report...................................................................................... 58

    8.3.3 Display self-supervision report........................................................................ 58

    8.3.4 Display status change of binary input report .................................................. 59

    8.3.5 View the settings............................................................................................... 60

    8.3.6 View Records .................................................................................................... 61

    8.3.7 Printing reports and waveform ........................................................................ 61

    8.4 Input Operation Through Keypad .............................................................................. 62

    8.4.1 Change the Settings ......................................................................................... 62

    8.4.2 Delete Fault Records and Event Records........................................................ 63

    8.4.3 Adjusting Clock................................................................................................. 63

    8.4.4 Check Version ................................................................................................... 64

    Chapter 9 Communications .................................................................................................... 65

    9.1 General Description .................................................................................................... 65

    9.2 Rear Communication Port Information...................................................................... 65

    9.2.1 RS-485 Interface................................................................................................ 65

    9.2.2 Ethernet Interface ............................................................................................. 67

    9.2.3 IEC60870-5-103 Communication ...................................................................... 68

    9.3 IEC60870-5-103 Interface over Serial Port ................................................................. 68

    9.3.1 Physical Connection and Link Layer ............................................................... 68

    9.3.2 Initialization ....................................................................................................... 68

    9.3.3 Time Synchronization ....................................................................................... 69

    9.3.4 Spontaneous Events......................................................................................... 69

    9.3.5 General Interrogation........................................................................................ 70

    9.3.6 General Functions ............................................................................................ 70

    9.3.7 Disturbance Records ........................................................................................ 70

    9.4 IEC60870-5-103 Interface over Ethernet .................................................................... 71

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. ix

    9.5 Messages Description for IEC61850 Protocol........................................................... 71

    9.5.1 Overview............................................................................................................ 71

    9.5.2 Communication profiles ................................................................................... 72

    9.5.3 Server data organization .................................................................................. 73

    9.5.4 Server features and configuration ................................................................... 74

    9.5.5 ACSI conformance ............................................................................................ 77

    Chapter 10 Installation and Commissioning .......................................................................... 81

    10.1 Introduction............................................................................................................... 81

    10.2 Safety Information .................................................................................................... 81

    10.3 Overview.................................................................................................................... 83

    10.4 Unpacking and Checking the Equipment ................................................................ 83

    10.5 Installing the Protective Device ............................................................................... 84

    10.5.1 Overview.......................................................................................................... 84

    10.5.2 Dimensions ..................................................................................................... 84

    10.5.3 Grounding Guidelines .................................................................................... 85

    10.5.4 Cubicle Grounding.......................................................................................... 86

    10.5.5 Ground Connection on the Device................................................................. 86

    10.5.6 Grounding Strips and their Installation ......................................................... 87

    10.5.7 Making the electrical connections ................................................................. 87

    10.5.8 Typical Wiring.................................................................................................. 89

    10.6 Check the External Circuitry .................................................................................... 90

    10.7 Energizing the Equipment ........................................................................................ 91

    10.7.1 Checking front panel LCD display ................................................................. 91

    10.7.2 Setting the date and time................................................................................ 92

    10.7.3 Checking light emitting diodes (LEDs) .......................................................... 92

    10.8 Setting the Protective Device ................................................................................... 92

    10.9 Establishing Connection and Verifying Communication........................................ 93

    10.10 Verifying settings by secondary injection ............................................................. 93

    10.10.1 Commissioning Tools ................................................................................... 93

    10.10.2 Insulation test (if required) ........................................................................... 94

  • RCS-9659 Auto Synchronizer

    NR ELECTRIC CO., LTD. x

    10.10.3 Testing the AC Voltage Inputs ...................................................................... 94

    10.10.4 Testing the Binary Inputs.............................................................................. 95

    10.10.5 Synchronism Function ................................................................................. 96

    10.11 Final Check.............................................................................................................. 96

    Chapter 11 Maintenance .......................................................................................................... 97

    11.1 Appearance Check .................................................................................................... 97

    11.2 Failure Tracing and Repair ....................................................................................... 97

    11.3 Replace Failed Modules............................................................................................ 98

    11.4 Replace Button Battery............................................................................................. 99

    11.5 Cleaning .................................................................................................................... 99

    11.6 Storage ...................................................................................................................... 99

    Chapter 12 Decommissioning and Disposal .........................................................................101

    12.1 Decommissioning ....................................................................................................101

    12.2 Disposal ...................................................................................................................101

    Chapter 13 Manual Version History .......................................................................................103

  • Chapter 1 Introduction

    NR ELECTRIC CO., LTD. 1

    Chapter 1 Introduction

    1.1 Application

    RCS-9659 is a digital synchronizer that determines the proper time to initiate closing of circuit

    breaker to parallel a generator and bus, or to reclose a line. In order to fulfill different application

    requirements, it is equipped with three kinds of synchronizing modes: automatic synchronizing,

    semi-automatic synchronizing and manual synchronizing. By monitoring frequency, voltage and

    phase angle, RCS-9659 provides correction signals to governor of prime mover and voltage

    regulator of generator for voltage matching and frequency matching. With a powerful and large

    capacity, RCS-9659 provides the multi-generator paralleling solution. It can manage up to 10

    circuit breakers synchronism.

    Prime

    mover

    Frequency control

    Voltage control

    Clo

    sin

    g s

    ignal

    Circuit breaker

    Station bus ABC rotation

    Power Grid

    GEN A sineBUS A sineGovernor

    UG1

    UG2

    US1

    US2

    RCS-9659

    VTS FDR25

    Generator

    Regulator

    Figure 1.1-1 Typical Application of RCS-9659

    1.2 Functions

    Automatic synchronizing (25A)

    Semi-automatic synchronizing (25SA

    Manual synchronizing (25M)

    Multi-generator paralleling solution: capability of 10 circuit breakers synchronization. To any

    of the circuit breakers, frequency and voltage regulation can be done separately.

    Remote/local control paralleling mode

    Output of signal contacts

    Output block signal to other equipments

    Receive block signal from other equipments

  • Chapter 1 Introduction

    NR ELECTRIC CO., LTD. 2

    Communicate with substation automation system via serial port on IEC60870-5-103 or

    Ethernet port based on IEC60870-5-103 or IEC61850.

    GPS clock synchronization PPS (pulse per second), PPM (pulse per minute), RS-485

    difference level and IRIG-B synchronization.

    Oscillograph,8 cycles ahead of closing signal and 2 cycles after closing signal.

    1.3 Features

    Based on DSP hardware platform, 14 bits high accuracy A/D converter. DSP performs data

    acquisition, voltage, frequency and phase angle calculations, voltage and frequency

    regulations and synchronism checking task. The breaker can be closed only when the

    synchronism condition is met which is judged by DSP. Hereby, security is enhanced

    significantly.

    Frequency tracking technology is adopted. By the aid of that, real-time value of frequency,

    voltage and phase are calculated with high precision on every sampling point.

    The equipment uses an integral front panel and closed cabinet. High and low level signals

    are separated strictly. With well designed software anti-EMI facilities, the equipments

    capability of interference immunity is highly enhanced. Furthermore, its electromagnetic

    radiation also satisfies relevant international standards.

    Flexible communication function

    2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol

    1 RS-485 communication rear ports for clock synchronization

    4 rear Ethernet ports (optional), IEC 61850, or IEC 60870-5-103 over TCP/IP

    Monitoring and Metering

    Event Recorder including 64 reports of status change of binary input, 64 self-supervision

    reports and 256 operating reports.

    Disturbance recorder including 64 fault reports, and 24 waveforms (The file format of

    disturbance recorder is compatible with international COMTRADE file.)

    Friendly Human Machine interface User Interface

    Friendly HMI interface with LCD and 9-button keypad on the front panel.

    1 RS-232 communication faceplate port for testing and setting

    1 RS-232 communication rear ports or RS-485 for printer

    Auxiliary software - RCSPC

    1.4 Ordering

    Equipment type definition

  • Chapter 1 Introduction

    NR ELECTRIC CO., LTD. 3

    Composition of type of varieties of the equipment is as follows:

    RCS-9659 - XX - NN

    num ber of O UT m odule

    type of CO M m odule

    type of the equipm ent

    Figure 1.4-1 Varieties of RCS-9659 Synchronizer

    As illustrated in Figure 1.4-1, type of COM module and number of OUT module are configurable.

    Table 1.4-1 Equipment configuration

    Suffix Possible value Description

    XX

    No COM module is comprised.

    ST RS-485 serial port communication board is equipped. See section

    0.

    SF 100Mbps optical-fiber Ethernet communication board is

    employed. See section 0.

    NT 100Mbps RJ-45 twisted wire Ethernet communication board is fit.

    See section 0.

    NN 110 Number of synchronism output board

    Two options are available for rated secondary current of CT inputs: 1A or 5A.

    Four options are available for rated auxiliary voltage: 250V, 220V, 125V, 110V.

    There are three types of COM module are optional mentioned above.

  • Chapter 1 Introduction

    NR ELECTRIC CO., LTD. 4

  • Chapter 2 Technical Data

    NR ELECTRIC CO., LTD. 5

    Chapter 2 Technical Data

    2.1 Electrical Specifications

    2.1.1 Analog Voltage Input Ratings

    Per IEC 60255-6, IEC 60288

    Rated Voltage 100V/ 3 , 110V/ 3 100V, 110V 200V

    Linear to 100V 173V 230V

    Thermal withstand -continuously -10s -1s

    120V 200V 250V

    120V 200V 250V

    200V 350V 400V

    Burden at rated

  • Chapter 2 Technical Data

    NR ELECTRIC CO., LTD. 6

    Bounce time 1ms 1ms

    Breaking capacity at 250Vdc

    0.4A resistance 0.2A inductive (L/R=40ms)

    0.2A resistance 0.05A inductive (L/R=40ms)

    Durability Loaded contact

    Unloaded contact

    100,000 operations minimum

    10,000,000 operations minimum

    Output mode Potential free contact

    Making capacity >1000W at L/R=40ms

    Max system voltage 250Vac/dc

    Test voltage across open contact

    1000Vac RMS for 1min

    Short duration current 50A for 200ms

    2.1.5 Power supply output for Opto-coupler

    Rated Voltage 24V

    Rated Current 200mA

    Max current 500mA

    2.2 Mechanical Specifications

    Enclosure dimensions (WHD)

    482.6177291 (unit: mm)

    Mounting Way Flush mounted

    Trepanning dimensions (WH)

    450179, M6 screw

    Housing color Silver grey

    Weight per device Approx. 20kg

    Display language English

    Housing material Aluminum

    Location of terminal Rear panel of the device

    Protection class

    Standard Per IEC60529:1989

    Front side IP51 (Flush mounted)

    Other sides IP30

    Rear side, connection terminals

    IP20

    2.3 Ambient Temperature and Humidity Range

    Standard IEC60255-6:1988

    Operating

    temperature -25C to +55C

    Transport and storage temperature range

    -40C to +70C

    Permissible humidity 5%-95%, condensation not permissible

  • Chapter 2 Technical Data

    NR ELECTRIC CO., LTD. 7

    2.4 Rear Communication Port

    Interface for communicating with RTU/SCADA

    RS-485 (EIA)

    Electrical

    Port number 2

    Baud rate 4800~38400bps

    Transmission distance

  • Chapter 2 Technical Data

    NR ELECTRIC CO., LTD. 8

    RS-232 (EIA)

    Prot number 1

    Baud Rate 4800bps~38400bps

    Printer type EPSON 300K printer

    Safety level Isolation to ELV level

    Interface for clock synchronization

    RS-485 (EIA)

    Port number 1

    Transmission distance

  • Chapter 2 Technical Data

    NR ELECTRIC CO., LTD. 9

    Test voltage 5kV, unipolar impulses waveform 1.2/50s,source

    energy 0.5J

    Insulation resistance

    measurements

    Per IEC 60255-5:2000

    Isolation resistance >100M, 500Vdc

    2.5.4 Electromagnetic compatibility

    1MHz burst disturbance test

    Per IEC 60255-22-1 (idt IEC61000-4-12)

    Common mode: class III 2.5KV

    Differential mode: class III 1.0KV

    Electrostatic discharge test

    Per IEC60255-22-2 class IV

    For contact discharge: 8kV

    For air discharge: 15kV

    Radio frequency interference tests

    Per IEC 60255-22-3 class III

    Frequency sweep

    Radiated amplitude-modulated

    10V/m (rms), f=801000MHz

    Spot frequency

    Radiated amplitude-modulated

    10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

    Radiated pulse-modulated

    10V/m (rms), f=900MHz

    Fast transient disturbance tests

    Per IEC 60255-22-4

    Power supply, I/O, Earth: Class IV, 4kV, 2.5 kHz, 5/50ns

    Communication terminals: Class IV, 2kV, 5 kHz, 5/50ns

    Surge immunity test Per IEC 60255-22-5, 1.2/50us class III

    Power supply, AC input, I/O port: 2kV, line to earth; 1kV line to line

    Conducted RF Electromagnetic Disturbance

    Per IEC 60255-22-6

    Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz

    Power Frequency Magnetic Field Immunity

    Per IEC 61000-4-8:1993

    Class 5: 100A/m for 1min, 1000A/m for 3s

    Pulse Magnetic Field

    Immunity

    Per IEC 61000-4-9:1993

    Class 5: 6.4/16s, 1000A/m for 3s

    Damped oscillatory magnetic field immunity

    IEC 61000-4-10:1993

    Class 5: 100kHz & 1MHz100A/m

    2.6 Certifications

  • Chapter 2 Technical Data

    NR ELECTRIC CO., LTD. 10

    ISO9001: 2000

    ISO14001:2004

    OHSAS18001: 1999

    ISO10012:2003

    CMMI L3

    EMC: 89/336/EEC, EN50263:2000

    Products safety(PS): 73/23/EEC, EN61010-1: 2001, EN60950: 2002

    2.7 Functional Specification

    2.7.1 Accurate Operating Scope

    Voltage 0.4V100V

    Frequency 45HZ55HZ

    Time delay 0100S

    df/dt 0.3HZ/S10HZ/S

    2.7.2 Synchronism Check function

    Synchronism points 0~10

    Secondary rated voltage (system and generator)

    57.70100.00V

    Slip frequency 00.5 HZ

    Frequency slip speed 110.00 HZ/S

    Voltage difference 5%30%

    Dead check threshold 5%30%

    Corrected angle between system voltage and generator voltage

    0330

    Pulse wide of adjusting frequency 109999ms

    Period of adjusting frequency 109999ms

    Pulse wide of adjusting voltage 109999ms

    period of adjusting voltage 109999ms

    Pulse wide of closing a breaker 109999ms

    The breaker closing time 20999ms

    Resetting time of checking synchronism 20999s

    Tolerance of voltage setting 3%xsetting

    Tolerance of slip frequency 0.02HZ

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 11

    Chapter 3 Functional Description

    3.1 Synchronizing Modes

    As described in section 1.2, RCS-9659 has three kinds of synchronizing modes. For each mode,

    they have two sub-modes: synchronism checking mode and dead checking mode. Just as the

    name implies, under synchronism checking mode, the circuit breaker is only permitted to be

    closed while all synchronism conditions are met. Dead checking mode allows selection of various

    low bus voltage conditions to enable breaker closing without synchronism check. This provides a

    black start capability for the system. Three kinds of synchronizing modes are comprehensively

    explained in the following sections.

    3.1.1 Automatic Synchronizing Mode

    When RCS-9659 is configured to work under automatic synchronizing mode, all functions are

    provided automatically. RCS-9659 monitors slip frequency (frequency difference), slip speed,

    voltage difference and phase angle difference issues control signal to adjust frequency and

    voltage of generator for voltage matching and frequency matching, gives close command to the

    breaker at the correct instant.

    As shown the in logic diagram of automatic synchronizing mode Figure 3.1-1, under automatic

    synchronizing mode, there are two sub-modes: synchronism checking mode and dead checking

    mode.

    Setting [En_DeadChk] determines whether RCS-9659 works as synchronism checking

    ([En_DeadChk] is 0) mode or dead checking ([En_DeadChk] is 1) way.

    Procedure of closing circuit breaker under automatic synchronizing mode

    (1) Energize the binary input [BI_AutoSync] manually.

    (2) Issue a synchronism command remotely from a substation automation system or a control

    center.

    (3) RCS-9659 then adjust generator frequency and voltage by sending regulation pulse signals

    to the prime mover governor and the voltage regulator according to predetermined settings

    automatically.

    (4) RCS-9659 will issue a closing command to a circuit breaker automatically when all the

    synchronism parameters are within predetermined limits. The closing logic can also adopt

    contact of sync-check relay to improve security further. Refer to .

    (5) Remotely send a reset command to RCS-9659 to reset operation signals and LED

    CLOSE.

    If the dead checking mode is enabled ([En_DeadChk] is 1), immediate CB closure is enabled if

    the system voltage or generator voltage is less than the setting [V_DeadChk_Sync].

    By the way, the automatic synchronizing mode is suitable for a substation or a power plant where

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 12

    automatic control system is equipped by the aid of which synchronism command can be issued to

    RCS-9659 automatically by substation automation system or energy management system.

    Logic scheme

    Ug

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 13

    [En_SyncRly]: it is the logic setting used to determine that whether the status of contac ts of

    sync-check relay shall be used to back up RCS-9659s operation. Set 1 to adopt normally open

    contact and normally closed contact of sync-check relay.

    [V_Diff_Sync]: it is the permissible voltage difference for synchronism check.

    [f_Diff_Sync]: it is the permissible slip frequrence for synchronism check.

    [df/dt_Sync]: it is the permissible frequrence slip speed difference for synchronism check.

    U_diff: it is the measured voltage difference.

    f_diff: it is the measured slip frequency.

    df/dt: is the measured frequency slip speed.

    phi_dif: it is the measured angle difference.

    Phi_Limit*, V_Limt*: they are constant settings that are unnecessary to modify as it has been

    already set in the program.

    Us: it represents three phase voltages of system side, e.g. Usa, Usb and Usc.

    Ug: it represents three phase voltages of generator side, e.g. Uga, Ugb and Ugc.

    VT Circuit Failure: it is the internal flag indicating that VT circuit failure is detected. If

    [En_DeadChk] and [En_VTS] are set as 1, a detected VT circuit failure will block the CB closing

    command output contact in the dead checking mode.

    Block output: it is the NO contact (i.e. BO_Blk_n) on the OUTn board (n=1,2,,A) of RCS-9659

    operating to block other equipment

    Close CB: it is the NO contact (i.e. BO_Cls_n ) on the module OUTn board (n=1,2,,A) of

    RCS-9659 operating to parallel generator or reclose a line.

    3.1.2 Semi-automatic Synchronizing Mode

    If RCS-9659 is configured to work under semi-automatic synchronizing mode, except that an

    operator has to select wanted circuit breaker to close and to initiate synchronism process manually,

    the other functions are provided automatically just the same as automatic synchronizing mode.

    RCS-9659 monitors slip frequency (frequency difference), slip speed, voltage difference and

    phase angle difference, issues control signal to adjust frequency and voltage of generator for

    voltage matching and frequency matching, gives close command to the breaker at the correct

    instant.

    As shown in the logic diagram of automatic synchronizing mode Figure 3.1-2, under

    semi-automatic synchronizing mode, there are two sub-modes: synchronism checking mode and

    dead checking mode.

    Setting [En_DeadChk] and binary input [BI_ManDeadChk] together determine whether RCS-9659

    works as synchronism checking ([En_DeadChk] is set 0 or [BI_ManDeadChk] is de-energized)

    mode or dead checking ([En_DeadChk] is set 1 and [BI_ManDeadChk] is energized) way. Refer

    to Figure 3.1-2.

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 14

    Procedure of closing circuit breaker under semi-automatic synchronizing mode

    (1) Energize the binary input [BI_SemiSync] (refer to 6.2.6) manually.

    (2) Select the expected circuit breaker by energizing the associated binary input

    [BI_RmtSyncCmd_n]* (n=1,2,,A) manually.

    (3) Initiate a synchronism process by energizing the binary input [BI_TrigSync] manually. After

    the synchronism process has started, de-energize [BI_TrigSync].

    (4) RCS-9659 will adjust generator frequency and voltage by sending regulation pulse signals

    to the prime mover governor and the voltage regulator according to predetermined settings

    automatically.

    (5) RCS-9659 will issue a closing command to a circuit breaker automatically when all the

    synchronism parameters are within predetermined limits. When synchronism checking other

    than dead checking function is used, the closing logic can also adopt the contact of sync-check

    relay to improve security further.

    (6) Remotely or locally send a reset command to RCS-9659 to reset operation signals and LED

    CLOSE.

    (7) De-energize associated binary input [ManualSynCmd.n] (n=1,2,,A) manually.

    If the dead checking mode is enabled ([En_DeadChk] is set 1 and [BI_ManDeadChk] is

    energized), immediate CB closure is enabled if the system voltage or generator voltage is less

    than the setting [V_DeadChk_Sync]. Refer to Figure 3.1-2.

    The semi-automatic synchronizing mode is usually used for locally initiating synchronism process

    or checking the synchronizer RCS-9659.

    Logic scheme

    1Ug

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 15

    [BI_SemiSync]: it is the binary input on terminal E08 used to enable that RCS-9659 works in

    semi-automatic synchronizing mode.

    [BI_ManSynCmd_n]*: it is the binary input on terminal n28 used to select desired circuit breaker to

    be closed.

    [BI_TrigSync]: it is the binary input on terminal E23, by which RCS-9659 is triggered to initiate

    synchronism process.

    [BI_ManDeadChk]: it is the binary input on terminal E10. [BI_ManDeadChk] and [En_DeadChk]

    are together used to enable dead checking mode.

    [BI_ExtBlk]: it is the binary input on terminal E26, by which RCS-9659 can be blocked by an

    external signal from other protection relays.

    [BI_RunState]: it is a binary input on terminal E07 used to configure that RCS-9659 works in

    normal operation mode or works in testing mode.

    [BI_NC_SyncRly]: it is a binary input on terminal E20 used to adopt the status of the normal closed

    contact of sync-check relay.

    [En_DeadChk]: it is the logic setting used to enable RCS-9659 work under dead checking mode.

    [V_DeadChk_Sync]: it is the setting used to judge whether the generator side or the system side is

    dead or live.

    [En_AutoReg]: it is the logic setting used to determine whether to adjust the frequency and voltage

    automatically or not when paralleling a generator. Set 1 to enable the function.

    [En_SyncRly]: it is the logic setting used to determine that whether the status of contacts of

    sync-check relay shall be used to back up RCS-9659s operation. Set 1 to adopt normally open

    contact and normally closed contact of sync-check relay.

    [V_Diff_Sync]: it is the permissible voltage difference for synchronism check.

    [f_Diff_Sync]: it is the permissible slip frequency for synchronism check.

    [df/dt_Sync]: it is the permissible frequency slip speed difference for synchronism check.

    U_dif: is the measured voltage difference.

    f_dif: it is the measured slip frequency.

    df/dt: it is the measured frequency slip speed.

    phi_dif: it is the measured angle difference.

    Phi_Limit*, V_Limt*: they are constant settings that are unnecessary to modify as it has been

    already set in the program.

    Us: it represents three phase voltages of system side, e.g. Usa, Usb and Usc.

    Ug: it represents three phase voltages of generator side, e.g. Uga, Ugb and Ugc.

    VT Circuit Failure: it is the internal flag indicating that VT circuit failure is detected. If

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 16

    [En_DeadChk] and [En_VTS] are set as 1, a detected VT circuit failure will block the CB closing

    command output contact in the dead checking mode.

    Block output: it is the NO contact (i.e. BO_Blk_n) on the OUTn board (n=1,2,,A) of RCS-9659

    operating to block other equipment

    Close CB: it is the NO contact (i.e. BO_Cls_n ) on the module OUTn board (n=1,2,,A) of

    RCS-9659 operating to parallel generator or reclose a line.

    3.1.3 Manual Synchronizing Mode

    When RCS-9659 is configured to work under manual synchronizing mode, all functions have to be

    performed manually. According to the information provided by the digital frequency and voltage

    meters and synchroscope, the operator controls the speed and voltage of the generator as well as

    the closure of the circuit breaker.

    As shown in the logic diagram of automatic synchronizing mode Figure 3.1-3, under

    semi-automatic synchronizing mode, there are two sub-modes: synchronism checking mode and

    dead checking mode.

    Binary input [BI_ManDeadChk] determines whether RCS-9659 works as synchronism checking

    ([BI_ManDeadChk] is de-energized) mode or dead checking ([BI_ManDeadChk] is energized)

    way.

    Procedure of closing circuit breaker under manual synchronizing mode

    (1) Energize binary input [BI_ManSync] manually.

    (2) Select expected circuit breaker by energizing associated binary input [BI_ManSynCmd_n]

    (n=1,2,,A) manually.

    (3) Initiate a synchronism process by energizing binary input [BI_TrigSync] manually.

    (4) Adjust the generator frequency and voltage based on reading of frequency meter, and

    voltage meter.

    (5) Manually issue a closing command to the circuit breaker at the correct instant based on

    reading of the synchroscope. When synchronism checking other than deadline checking

    function is used, the closing contact can also be in series with the contact of sync-check relay to

    improve security further.

    (6) Locally send a reset command to RCS-9659 to reset operation signals and LED CLOSE.

    Whether the circuit breaker will close or not, it may also depend on the status of the

    [BI_ManDeadChk]. Refer to 6.2.6.

    (7) De-energize the binary input [BI_TrigSync].

    (8) De-energize associated binary input [BI_ManSyncCmd_n]* (n=1,2,,A) manually.

    If Dead checking mode is enabled ([BI_ManDeadChk] is as 1) is energized, immediate CB

    closure is enabled and the operator can issue closing command immediately. Refer to Figure

    3.1-3.

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 17

    The manual synchronizing mode is applicable for an application where there needs manual

    operation. The major drawback is that an operator with enough knowledge to avoid damage to the

    machinery is needed.

    Logic scheme

    [BI_ManSyncCmd_n]*

    [BI_TrigSync]

    [BI_ManSync]

    [BI_NC_SyncRly]

    [BI_ManDeadChk]

    [BI_ManStepUp]

    [BI_RunState]

    [BI_ManStepDown]

    [BI_ManAccel]

    [BI_ExtBlk]

    [BI_ManCls]

    &

    &

    &

    &

    &

    1

    1

    & &

    [BI_ManDecel]

    Block output

    To voltage regulator

    To voltage regulator

    To prime mover governor

    To prime mover governor

    Close CB

    Figure 3.1-3 Logic Diagram of Manual Synchronizing Mode

    Where:

    [BI_ManSync]: it is the binary input on terminal E05 used to enable that RCS-9659 works in

    manual synchronizing mode.

    [BI_ManSyncCmd_n]*: it is the binary input on terminal n28 used to select desired circuit breaker

    to be closed.

    [BI_TrigSync]: it is the binary input on terminal E23, by which RCS-9659 is triggered to initiate

    synchronism process.

    [BI_ManDeadChk]: it is the binary input on terminal E10. [BI_ManDeadChk] and [En_DeadChk]

    are together used to enable Dead checking mode.

    [BI_ManStepUp]: it is the binary input on terminal E09 used to increase the generator voltage.

    [BI_ManStepDown]: it the binary input on terminal E09 used to decrease the generator voltage.

    [BI_ManAccel]: it is the binary input on terminal E09 used to increase the generator frequency.

    [BI_ManDecel]: it is the binary input on terminal E09 used to decrease the generator frequency.

    [BI_ManCls]: it is the binary input on terminal E17, by which RCS-9659 is triggered to issue a

    closing command to circuit breaker.

    [BI_ExtBlk]: it is the binary input on terminal E26, by which RCS-9659 can be blocked by an

    external signal from other protection relays.

    [BI_RunState]: it is a binary input on terminal E07 used to configure that RCS-9659 works in

    normal operation mode or works in testing mode.

    [BI_NC_SyncRly]: it is a binary input on terminal E20 used to adopt the status of the normal closed

    contact of sync-check relay.

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 18

    Block output: it is the NO contact (i.e. BO_Blk_n) on the OUTn board (n=1,2,,A) of RCS-9659

    operating to block other equipment

    Close CB: it is the NO contact (i.e. BO_Cls_n ) on the module OUTn board (n=1,2,,A) of

    RCS-9659 operating to parallel generator or reclose a line.

    3.2 Block Function

    The digital synchronizer can either send block signals to other equipment or be blocked by other

    protection relays (refer to6.2.6, the binary input [BI_ExtBlk]).

    Once the synchronism process has started, two normal open output contacts provided by SIG

    board via terminals C27-C28 and C29-C30 (for automatic or semi-automatic synchronizing mode)

    or terminals B27-B28 and B29-B30 (for manual synchronizing mode) will close to issue block

    signals to other protection relays. Refer to 6.2.7 and 6.2.8.

    3.3 Time Synchronization

    As the equipment Real Time Clock has small drift per day, therefore, in order to have a correct

    time for time tagging of event or report etc., the operator should set its time periodically or it shou ld

    be synchronized by a master clock automatically.

    Time synchronization of RCS-9659 can be done by four means:

    (1) IRIG-B signal input from external clock device via a RS-485 port named GPS pulse

    (2) Differential signal of PPS or PPM from external clock device via a RS-485 port named

    GPS pulse

    (3) PPM or PPS input via binary input [GPS_Pulse] terminal E02 on OPT board E. Refer

    to6.2.6 for detailed description.

    (4) Clock message from substation automation system depending on protocol

    The external clock device receives the synchronization signal from GPS antenna and then sends it

    to RCS-9659 based on IRIG-B standard, as differential signal of PPM or PPS by means of

    so-called synchronization bus. When the differential signal is a PPM input, setting [GPS_Pulse]

    under EQUIP SETTINGS sub-menu should be set as 1, while if the differential signal is a PPS

    input, the setting [GPS_Pulse] should be set as 0. A specific clock synchronization port RS-485

    interface is dedicated for this application. Refer to 0.

    Substation automation system clock synchronization depends on protocol. The clock message is

    directly acquired by RCS-9659 through the substation automation system link. Clock message can

    provide full information for a certain time as a way of year, date, hour, minute and second while

    pulse input lacks these information.

    Therefore, in general applications, clock message is usually combined with PPM or PPS input via

    binary input, or combined with differential signal of PPM or PPS by means of the clock

    synchronization port RS-485 with an accuracy of 1ms.

    Moreover, the user could also set time and data directly using the local human-machine interface

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 19

    (HMI) of the equipment.

    RCS-9659 internal clock will then be adjusted accordingly. When the equipment is synchronized,

    all events in TRIP REPORT, ALM REPORT and BI CHG REPORT and current measurement

    have a time tag with synchronized attribute.

  • Chapter 3 Functional Description

    NR ELECTRIC CO., LTD. 20

  • Chapter 4 Automatic Supervision

    NR ELECTRIC CO., LTD. 21

    Chapter 4 Automatic Supervision

    4.1 General Description

    Though the protection system is in non-operating synchronism state under normal conditions, it is

    waiting for a synchronism checking command and must execute it without fail. When the

    equipment is in energizing process before the LED HEALTHY is on, the equipment needs to be

    checked to ensure no errors. Therefore, the automatic supervision function, which checks the

    health of the synchronizing system when startup and during a normal operation, plays an

    important role.

    The numerical synchronizer based on the microprocessor operations is suitable for implementing

    this automatic supervision function of the synchronizing system.

    In case a fault is detected during initialization when DC power supply is provided to the equipment,

    the equipment will be blocked out, which means the synchronizer is out of service. Before you

    must re-energize the synchronizer or reset CPU module by restarting equipment to make it back

    into service, please find out the cause and inform the factory.

    When a failure is detected by the automatic supervision, it is followed with an LCD message, LED

    indication and alarm contact outputs. At the same time event recording will record the failure alarm

    which can be viewed in event recording report and be printed.

    4.2 Synchronizer Self-supervision

    4.2.1 Hardware Supervision

    The DSP, RAM, ROM chips on CPU module are monitored to ensure whether they are damaged

    or have errors. If any one of them is detected damaged or having error, the equipment will be

    blocked and issue the alarm [Alm_RAM] and [Alm_ROM]. At the same time the HEALTHY LED

    being extinguished and the ALARM LED being lit.

    4.2.2 Check Setting

    RCS-9659 series has 10 setting groups protection settings for 10 synchronism points respectively.

    The settings of each synchronism point setting are checked to ensure they are reasonable. If the

    settings are checked error in DSP chip and CPU chip, an alarm [Alm_Setting] and [Alm_EEPROM]

    are issued respectively. Meanwhile, LED HEALTH is extinguished and LED ALARM is lit on.

    If these 10 setting groups are not all set, when the protective device is provided with DC power

    supply first, an alarm [Alm_InvalidGrp] will be issued. If the secondary rated current of CT (I2n) in

    equipment parameters is changed and the protection settings is not confirmed or some settings in

    protection settings exceed setting range, the alarm [Alm_InvalidGrp] will be issued. At the same

    time the HEALTHY LED is extinguished and the ALARM LED being lit.

    4.2.3 Voltage drift Supervision and auto adjustment

    Zero point of voltage may drift influenced by variation of temperature or other environment factors.

  • Chapter 4 Automatic Supervision

    NR ELECTRIC CO., LTD. 22

    The equipment continually automatically traces the drift and adjusts it to normal value.

    4.2.4 DSP sampling Supervision

    AC sampling of DSP chip is monitored and if the samples are detected to be wrong, an alarm

    [Alm_Smpl_DSP] will be issued and the equipment will be blocked. At the same time the

    HEALTHY LED is extinguished and the ALARM LED being lit.

    4.2.5 CPU sampling Supervision

    The synchronizer compares the CPU sampling and DSP sampling. In normal condition, the

    sampling should be the same for a certain AC input. If a sampling in CPU is detected to be

    different largely with that in DSP, the alarm signal [Alm_Smpl_CPU] will be issued and the

    synchronizer will be blocked. At the same time the HEALTHY LED is extinguished and the

    ALARM LED being lit.

    4.2.6 Opto-coupler power Supervision

    Positive power supply of opto-coupler is continually monitored. If an error or damage has occurred,

    the alarm [Alm_Pwr_Opto] will be issued with ALARM LED being lit, but the equipment will not

    be blocked.

    4.2.7 Synchronism Point Supervision

    In the manual synchronizing mode, if two or more synchronism points are selected (i.e. two or

    more binary inputs [BI_ManSyncCmd_n]* are energized at the same time, n=1, 2, , A) or no

    synchronism point is selected (i.e. no binary input [BI_ManSyncCmd_n]* is energized, n=1, 2, ,

    A) by an operator, but a synchronizing process is triggered by energizing the binary input

    [BI_TrigSync], then the alarm signal [Alm_SyncPoint] will be issued with the ALARM LED being

    lit, and the synchronizing function is blocked temporarily at the same time.

    After the binary inputs of other synchronism points are de-energized and only one binary input of

    synchronism point is kept being energized, then the alarm signal will reset with the ALARM LED

    being extinguished. The synchronism checking of the point still can be carried out if the

    synchronizer doesnt reset.

    4.2.8 System Voltage Supervision

    If the logic setting [En_DeadChk] is set as 0 and the system or generator voltage is tool low (less

    than [V_DeadChk_Syn]) during a synchronism process (i.e. a synchronism process is triggered

    manually or remotely), then the alarm signal [Alm_UV_Sys] will be issued with the ALARM LED

    being lit, and synchronizing function is blocked temporarily at the same time.

    After the system or generator voltage returns to a normal condition, the alarm signal will rest with

    the ALARM LED being extinguished. The synchronism checking still can be carried out if the

    synchronizer doesnt reset.

    4.2.9 Voltage Transformer Supervision VTS

    If the logic setting [En_VTS] are set as 1 and the negative sequence voltage of the generator

  • Chapter 4 Automatic Supervision

    NR ELECTRIC CO., LTD. 23

    side or system side is more than 8V, then the alarm signal [Alm_VTS] will be issued with the

    ALARM LED being lit. If the logic setting [En_DeadChk] is set as 1 at the same time, the

    synchronizing function is blocked temporarily.

    After the generator or system voltage returns to a normal condition, the alarm signal will rest with

    the ALARM LED being extinguished. The synchronism checking still can be carried out if the

    synchronizer doesnt reset.

    4.2.10 Circuit Breaker Closing Supervision

    After a closing pulse to close a circuit breaker is issued by the synchronizer, the alarm signal

    [Alm_Fail_Cls] will be issued if the auxiliary contact of the circuit breaker doesnt return a signal

    (i.e. the binary input [BI_AuxContact] is energized), which means the circuit breaker is failed to be

    closed.

    4.3 Understand the Alarms

    The hardware circuits and operation conditions of the equipment are self-supervised continuously.

    If any abnormal condition is detected, information or report will be displayed and a corresponding

    alarm will be issued.

    A common abnormality may block a certain number of functions while the other functions can still

    work. However, if serious hardware failure or abnormality were detected, all functions will be

    blocked and the LED HEALTHY will be extinguished and blocking signal will be given by the

    corresponding contacts outputs BO_Fail. The synchronizer equipment then cannot work normally

    and maintenance is required to eliminate the failure.

    NOTE: If the synchronizer is blocked or alarm signal is sent during operation, please do

    find out its reason with the help of self-diagnose record. If the reason can not be found at

    site, please notice the factory NR. Please do not simply press button TARGET RESET

    on the protection panel or re-power on the equipment.

    Table 4.3-1 Repairmen suggestion for alarms information

    No. Alarm Message Meaning Description

    1 Alm_RAM CPU module RAM is damaged.

    2 Alm_ROM CPU module ROM is damaged.

    3 Alm_EEPROM Invalid settings in any setting group

    4 Alm_InvalidGrp Invalid settings in active setting group

    5 Alm_Smpl_CPU CPU chip sample differs too much from DSP sampling

    6 Alm_Smpl_DSP DSP chip is damaged or DSP sampling is wrong

    7 Alm_Setting Settings in active group are found error after setting check in DSP chip

    When No.1~No.7 above alarm messages are displayed on the LCD, the LED HEALTHY is extinguished and the LED ALARM is it. At the same time the synchronizer equipment is blocked.

    8 Alm_Pwr_Opto Loss of opto-coupler power supply.

  • Chapter 4 Automatic Supervision

    NR ELECTRIC CO., LTD. 24

    No. Alarm Message Meaning Description

    9 Alm_SyncPoint Two or more synchronism points are selected or no synchronism point is selected by the operator.

    10 Alm_UV_Sys System voltage is too low.

    11 Alm_VTS The secondary circuit of the voltage transformer of system or generator is abnormal.

    12 Alm_Fail_Cls A circuit breaker is failed to close.

    When the No.8~No.12 above alarm messages are issued on the LCD, the LED HEALTHY is still on, and the LED ALARM is lit. No.8 and No.9 alarm signals can result in blocking synchronizing process and please refer to the sections 4.2.7 and 4.2.8 respectively for details.

    Handling suggestion

    1. Inform manufacturer for maintenance.(No.1~No.7)

    2. Check the power supply in the OPT module. (No.8)

    3. Check whether two or more synchronism points are selected or no synchronism point is

    selected on the SCP (Synchronization Control Panel). (No.9)

    4. Check the sample value, the setting, and the corresponding VT secondary circuit of the

    system voltage. (No.10)

    5. Check the sample value, and the corresponding VT secondary circuit. (No.11)

    6. Check whether the circuit breaker is failed to close, and if it has been closed, please check the

    auxiliary contact of the circuit breaker and the corresponding binary input of the contact.

    (No.12)

  • Chapter 5 Metering and Recording

    NR ELECTRIC CO., LTD. 25

    Chapter 5 Metering and Recording

    5.1 General Description

    The synchronizer also provides some auxiliary functions, such as real-time data metering, binary

    input status recording, event and disturbance recording, etc. All these make the synchronizer meet

    the demands of the modern power grid requirements.

    5.2 Metering

    RCS-9659 performs continuous measurement of the analogue input quantities. The measurement

    data shown below is displayed on the LCD of the synchronizer front panel or on the local or remote

    PC.

    Equipment samples 24 points per cycle. Calculate the RMS value in each interval and LCD will be

    updated every 0.5 second. The following system quantities are displayed in RMS values of the

    secondary side of CT and VT. This device has double CPU system (i.e. CPU and MON module),

    so the sampled values of both modules will be displayed on LCD through different access menu.

    NOTE: Ie and In mentioned in following sections are units. Ie is secondary rated current of

    transformer and In is secondary rated current of CT.

    Table 5.2-1 Measured values in MON module

    No. Value Meaning Unit

    1 Ua_S A-phase voltage of system side V

    2 Ub_S B-phase voltage of system side V

    3 Uc_S C-phase voltage of system side V

    4 Ua_G A-phase voltage of generator side V

    5 Ub_G B-phase voltage of generator side V

    6 Uc_G C-phase voltage of generator side V

    7 Udif Voltage difference. It equals to UGa - USa V

    8 F_S System frequency (USa) Hz

    9 F_G Generator frequency (UGa) Hz

    10 Fdif Frequency difference. It equals to F_S - F_G Hz

    11 Facc Delta of Facc. It equals to dif /dt Hz/s

    12 Pdif The advance angle of the system voltage leading the generator

    voltage.

    13 Tcls Actual breaker closing time measured by RCS-9659 s

    Path VALUES -> MEASUREMENT

  • Chapter 5 Metering and Recording

    NR ELECTRIC CO., LTD. 26

    Table 5.2-2 Relevant quantities of differential protection

    No. Value Meaning Unit

    1 (Ua_Ub)_S Phase angle between Ua_S and Ub_S

    2 (Ub-Uc)_S Phase angle between Ub_S and Uc_S

    3 (Uc-Ua)_S Phase angle between Uc_Sand Ua_S

    4 (Ua-Ub)_G Phase angle between Ua_G and Ub_G

    5 (Ub-Uc)_G Phase angle between Ub_G and Uc_G

    6 (Uc-Ua)_G Phase angle between Uc_G and Ua_G

    7 (US-UG)_a Phase angle between Ua_S and Ua_G

    Path VALUES -> PHASE ANGLE

    5.3 Binary Input

    All the binary input changes are recorded in the synchronizer, and can be displayed on LCD locally

    printed or sent to automation system of substation via communication channel.

    Table 5.3-1 Binary input status list

    No. Value Meaning

    1 BI_AutoSync Binary input of enabling automatic synchronizing mode.

    2 BI_SemiSync Binary input of enabling semi-automatic synchronizing mode.

    3 BI_ManSync Binary input of enabling manual synchronizing mode.

    4 BI_RunState Binary input of selecting running mode of the synchronizer.

    5 BI_NC_SyncRly Binary input of the normally closed contact of the sync-check relay.

    6 BI_NO_SyncRly Binary input of the normally open contact of the sync-check relay.

    7 BI_Resv Reserved binary input.

    8 BI_ManDeadChk Binary input of enabling the dead checking of the manual

    synchronizing mode.

    9 BI_AuxContact Binary input of auxiliary contact of a circuit breaker to be closed.

    10 BI_TrigSync Binary input of manual triggering synchronism process.

    11 BI_ExtBlk Binary input of external blocking signal.

    12 BI_ManCls Binary input of manual closing signal.

    13 BI_Pulse_GPS Binary input of GPS synchronizing pulse.

    14 BI_Print Binary input of printing.

    15 BI_BlkComm Binary input of blocking communication.

    16 BI_RstTarg Binary input of resetting signal.

    Path VALUES->BI STATE

    5.4 Recording

    5.4.1 General description

    The RCS-9659 series provides the following recording functions:

  • Chapter 5 Metering and Recording

    NR ELECTRIC CO., LTD. 27

    Event recorder

    Disturbance recorder

    These records are displayed on the LCD of the synchronizer front panel or on the local or remote

    PC. Navigate the menu to view the report through LCD screen.

    5.4.2 Event recorder

    Event recorder includes self-supervision report, status change of binary input report and operating

    report. The equipment can store 64 records of each kind for self-supervision report and status

    change of binary input report in non-volatile memory.

    1. Self-supervision report

    The equipment is under automatic supervision all the time. If there are any failure or abnormal

    condition detected, such as, chip damaged, VT circuit failure and so on , it will be logged as an

    event.

    2. Status change of binary input report

    When there is binary input is energized or de-energized, i.e., its state has changed from 0 to 1

    or from 1 to 0, it will be logged as an event r.

    3. Tripping reports

    When a synchronizing process is triggered and a circuit breaker is closed, than a report

    [Op_Clsed_CB] will be recorded as an event.

    5.4.3 Disturbance recorder

    RCS-9659 can save 24 pieces of waveforms of synchronizing operations. If a new synchronizing

    operation occurs when 24 waveform records have been stored, the waveform of the first type of

    fault report will be overwritten, and then the latest waveform record will overwrite the oldest one if

    another new fault waveform is generated again. The synchronizer stores actual samples that are

    taken at a rate of 24 samples per cycle. Besides the voltage waveform, binary inputs state and

    measurement magnitudes are all recorded.

    There are the following two ways to initiate RCS-9659s oscillographic process to records 8 cycles

    waveforms before the initiating time and 2 cycles after the initiating time.

    (1) Being initiated by the binary input [BI_AuxContact]

    If the logic setting [En_AuxContact] is set as 1, oscillographic process will be initiated to record

    waveforms when [BI_AuxContact] rises from 0 to 1, i.e. the time when breaker is closed.

    (2) Being initiated by a time delay [t_Cls_CB]

    If the logic setting [En_AuxContact] is set as 0, oscillographic process will be initiated to record

    waveforms after a delay (i.e. setting [t_Cls_CB]), and the delay timer begins to time since

    RCS-659 issuing a closing command to circuit breaker.

  • Chapter 5 Metering and Recording

    NR ELECTRIC CO., LTD. 28

  • Chapter 6 Hardware Description

    NR ELECTRIC CO., LTD. 29

    Chapter 6 Hardware Description

    6.1 Overview

    Modular structured digital synchronizer RCS-9659 is IEC 4U high and 19 wide and adopts an

    integral faceplate.

    Front panel and rear panel are shown in Figure 6.1-1 respectively.

    RCS974AGTRANSFORMER AUXILIARY RELAY

    HEALTHY

    ALARM

    SYNC

    f

    U

    CLOSE

    TARGET RESET

    AUTO SYNCHRONIZER

    NANJING NARI-RELAYS ELECTRIC CO., LTD

    RCS9659

    f

    U

    Figure 6.1-1 Front Panel of RCS-9659

    OUTDC220V AC LPF CPU COM SIGSIGOPT OUT OUT OUTOUT OUT OUTOUT OUT OUT

    K

    DC

    J

    AC

    F

    COM

    1

    OUT

    2

    OUT

    3

    OUT

    4

    OUT

    5

    OUT

    6

    OUT

    7

    OUT

    8

    OUT

    9

    OUT

    A

    OUT

    B

    SIG

    C

    SIG

    E

    OPT

    G

    CPU

    H

    LFP

    No.

    Module

    Figure 6.1-2 Rear View of RCS-9659

    The digital synchronizer RCS -9659 comprises 8 plug-in modules as described in follow sections.

    RCS-9659 comprises the following 18 plug-in modules. Figure 6.1-2 is rear view of the equipment

    and shows disposition of these modules.

    Table 6.1-1 Hardware configuration

  • Chapter 6 Hardware Description

    NR ELECTRIC CO., LTD. 30

    No. Module Description

    1 OUT Synchronism operating module

    2 OUT Synchronism operating module (optional)

    3 OUT Synchronism operating module (optional)

    4 OUT Synchronism operating module (optional)

    5 OUT Synchronism operating module (optional)

    6 OUT Synchronism operating module (optional)

    7 OUT Synchronism operating module (optional)

    8 OUT Synchronism operating module (optional)

    9 OUT Synchronism operating module (optional)

    A OUT Synchronism operating module (optional)

    B SIG Signal output module

    C SIG Signal output module

    E OPT Binary input opto-coupler module

    F COM Communication module

    G CPU Control nucleus of the equipment

    H LFP Low-pass filter

    J AC AC current and voltage input module

    K DC DC power supply module

    No.1~No.A OUT modules are configured according to the requirement of the applied-specific

    project.

    6.2 Plug-in Modules

    6.2.1 DC Module (No.K DC)

    DC power supply (250V/220V/125V/110 V) shall be connected to terminals K01(+) and K02 (-).

    Through interference filter and power switch on the rear, DC/DC converter converts the DC power

    supply to three voltage class +5V, 12V and +24V to supply to other modules of the equipment.

    Terminal K04 (+) and terminal K05 (-) output 24V as power supply of OPT. Terminal K06 is surge

    ground. The following figure shows rear view and connections of DC power supply module.

  • Chapter 6 Hardware Description

    NR ELECTRIC CO., LTD. 31

    102

    101

    104

    105

    106

    To other

    modules To 24V OPT module

    Ground

    From DC power supply

    DC/DC

    5V

    12V

    24V

    Inte

    rfere

    nce filt

    er

    101

    102

    103

    104

    105

    GND

    DC

    1

    106

    Pwr +

    Pwr -

    Opto L -

    Opto L +

    +

    Figure 6.2-1 Rear View and Connections of DC Module

    WARNINGIt is only permitted to withdraw or insert the DC module or some other

    modules when the auxiliary power is switched off.

    6.2.2 AC Module (No.J AC)

    Figure 6.2-2 shows rear view and typical connections of AC module.

  • Chapter 6 Hardware Description

    NR ELECTRIC CO., LTD. 32

    A

    B

    C

    To LPF

    52G

    n01

    n02

    n03

    n04

    n28(26)

    n05

    n06

    n07

    n08

    from other OUT boardBUS

    J05

    J09

    J13

    J01

    To LPF

    n09

    n10

    n11

    n12

    n13

    n14

    n15

    n16

    from other OUT board

    J21

    J25

    J29

    J17

    AC

    J01

    Syste

    m V

    oltage Input

    J02

    J03 J04

    J05 J06

    J07 J08

    J09 J10

    J11 J12

    J13 J14

    J15 J16

    J17 J18

    J19 J20

    J21 J22

    J23 J24

    J25 J26

    J27 J28

    J29 J30 Genera

    tor

    Voltage Input

    OUT board AC board

    Syste

    m V

    oltage Input

    Genera

    tor

    Voltage Input

    Ub_S

    Uc_S

    Ua_S

    Un_S

    Ua_G

    Ub_G

    Uc_G

    Un_G

    Figure 6.2-2 Rear View and Typical Connections of AC Module

    Both generator voltage and bus voltage on both sides of the breaker are inputted together, and

    have a nominal rating of 100V or 100V/3V at 50/60Hz. As illustrated in Figure 6.2-2, secondary

    voltage from voltage transformer (VT) on both sides of circuit breaker first enters into OUT board,

    then passes a selective switchover circuit (remotely or locally controlled by terminal n26 (n28)).

    After that, only one group of system voltage and generator voltage comes into No.J, the AC board.

    Small VTs built in AC board provide isolation and converts the secondary voltage from VT to a

    synchronizer acceptable level and then transfer it to LPF board for filtering. Following the low-pass

    filter circuits, the analog signals enter into well-designed precise phase detecting circuit and high

    accurate A/D converter. Then DSP will calculate the voltage, frequency and phase angle and

    check the synchronism conditions independently. If RCS-9659 is configured to work as

    synchronism checking mode, the breaker can be closed only when synchronism conditions are

    met which is judged by DSP. The AC signal flow graph is proposed in Figure 6.2-3.

  • Chapter 6 Hardware Description

    NR ELECTRIC CO., LTD. 33

    AC

    board

    LPF

    board

    CPU

    board

    OUT

    board

    52

    GP

    ow

    er

    Gri

    d

    BU

    S

    Figure 6.2-3 AC Signal Flow Graph

    Furthermore, there is an earthing terminal on AC board. It shall be connected to station ground

    grid.

    NOTESince RCS-9659 calculates synchronism conditions according the voltages

    inputted via channels Ua_S and Ua_G, these two channels must be led with appropriate

    voltages.

    DANGERNever allow the VT secondary circuit connected to the AC board or OUT board

    to be short circuit while the primary system is live. Short the VT circuit will produce a

    dangerously strong current.

    6.2.3 LFP Module (No.H LFP)

    This module is used to filter high frequency disturbance from the AC signal, regulate the input level

    and provide an interface between the equipment and dedicated test instrument HELP-90A

    developed by NR.

    From module AC

    From HELP-90AMeasurement in DSP Low-pass filterAdder

    Figure 6.2-4 Block Diagram of LFP Module

    6.2.4 CPU Module (No.G CPU)

    Module CPU, control nucleus of the equipment, comprises monolithic micro controller CPU and

    digital signal processor DSP. CPU finishes the following functions:

    1 General fault detection

  • Chapter 6 Hardware Description

    NR ELECTRIC CO., LTD. 34

    2 Event recorder and disturbance recorder (could be printed via serial port)

    3 Print and communication with HMI

    4 Communication with the host of SCADA system of the substation

    DSP finishes the following functions:

    5 Algorithm and logic of protection

    Sampling rate of the equipment is 24 points per cycle. Parallel real time data is calculated for

    algorithm and logic of protection at every sampling point. Hence, very high inherent reliability and

    security are ensured.

    6.2.5 COM module (No.F COM)

    Module COM performs connection between the equipment and the SCADA system or RTU. Three

    types are available.

    To SAS

    To SAS

    To GPS for clock synchronism

    To printer or controller

    Type 5A

    COM

    7

    8

    9

    1

    2

    3

    4

    5

    6

    10

    11

    12

    RS-485 1A

    RS-485 1B

    Printer RX

    Printer TX

    Printer Ground

    RS-485 1GND

    RS-485 2A

    RS-485 2B

    RS-485 2GND

    RS-485 A

    RS-485 B

    RS-485 GND

    PORT 1 PORT 2 PORT 3 PORT 4

    Type

    Physical Layer

    RS-485 RS-485 RS-485 RS-485/RS-232

    Twisted pair wire Twisted pair wireTwisted pair wire Twisted pair wire

    Figure 6.2-5 Rear view of type A and external connections of COM module

    Optic Fibre

    Optic Fibre

    To printer or controller

    To GPS for clock synchronism

    To SAS

    To SAS

    RS-485 A

    RS-485 B

    RS-485 GND

    Printer RX

    Printer TX

    Printer Ground

    1

    2

    3

    4

    5

    6

    Op.Fib.RX1

    Op.Fib.TX1

    Op.Fib.RX2

    Op.Fib.TX2

    Type 5B

    COM

    TX

    TX

    RX

    RX

    PORT 1 PORT 2 PORT 3 PORT 4

    Type

    Physical Layer

    RS-485 RS-485 RS-485 RS-485/RS-232

    Optic fibre Twisted pair wireOptic fibre Twisted pair wire

    Figure 6.2-6 Rear view of type B and external connections of COM module

  • Chapter 6 Hardware Description

    NR ELECTRIC CO., LTD. 35

    To GPS for clock synchronism

    To printer or controller

    1

    2

    3

    4

    5

    6

    7

    8

    9

    RS-485A

    RS-485B

    RS-485GND

    RS-485A

    RS-485B

    RS-485GND

    Printer RX

    Printer TX

    Printer Ground

    To SAS

    To SAS

    To SAS

    To SAS

    To SAS

    Ethernet 1

    10/100 TX

    Ethernet 4

    10/100 TX

    Ethernet 3

    10/100 TX

    Ethernet 2

    10/100 TX

    Type 5E

    COM

    PORT 1 PORT 2 PORT 3 PORT 4

    Type

    Physical Layer

    Ethernet Ethernet Ethernet RS-485

    Twisted pair

    wire

    Twisted pair

    wire

    Twisted pair

    wire

    Twisted pair

    wire

    PORT 5

    RS-485/

    RS-232

    Twisted pair

    wire

    PORT 6 PORT 7

    Ethernet RS-485

    Twisted pair

    wire

    Twisted pair

    wire

    Figure 6.2-7 Rear view of type E and external connections of COM module

    All ports used to communicate with SAS support IEC60870-5-103 protocol, moreover, Ethernet

    port in COM modules of type 5E also supports IEC61850. From Figure 6.2-5 to Figure 6.2-7 shows

    rear view of these types and their external connections.

    All types are equipped with a RS-485 port for receiving second pulse signal (PPS-pulse per

    second) from GPS and a port for printer. Printer port could be configured as RS-232 or RS-485 by

    setting corresponding jumpers on the PCB (RS-232 default). If logic setting [En_Net_Print] is set to

    1, printer port must be set as RS-485. Transmission rate of printer port can be set by the setting

    [Printer_Baud] and should be the same with baud rate of the printer.

    NOTE: For the port used to printer or controller, it can be configured as RS-485 or RS-232

    by setting corresponding jumper of module COM. The port is configured as RS-232 by

    shorting PIN 1 and PIN 2 and as RS-485 by shorting PIN 2 and PIN 3. As shown in Figure

    6.2-8

    PIN 1 PIN 2 PIN 3

    RS-232RS-485

    Figure 6.2-8 Print Port Configuration

    There are three options to finish time synchronization:

    1 Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact

    2 Receiving PPS, PPM and I