43
OFFSHORE CABLES NEK 606 INTRODUCTION NEK 606 FLAME RETARDANT NEK 606 FIRE RESISTANT GENERALS Head office: Strada Provinciale, n. 117 20010 BERNATE TICINO (MILANO) - ITALY Phone +39.02.97.25.58.17 a.r. - Fax +39.02.97.25.57.54 www.ccicables.com - E-mail: [email protected]

OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

  • Upload
    dotram

  • View
    232

  • Download
    0

Embed Size (px)

Citation preview

Page 1: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

OFFSHORE CABLESNEK 606

INTRODUCTION NEK 606FLAME RETARDANT

NEK 606FIRE RESISTANT

GENERALS

Head office: Strada Provinciale, n. 11720010 BERNATE TICINO (MILANO) - ITALY

Phone +39.02.97.25.58.17 a.r. - Fax +39.02.97.25.57.54www.ccicables.com - E-mail: [email protected]

Page 2: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

OFFSHORE CABLESNEK 606

GrGroupoup

Page 3: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:
Page 4: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Offshore CablesNEK 606

Dual CompoundHalogen Free - Mud Resistant

(–40 Deg C)

Low SmokeFlame Retardant

Fire Resistant

Type Approvals:

• ABS American Bureau of Shipping• DNV Det Norske Veritas• LRS Lloyd’s Register of Shipping

Page 5: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Type Approvals

ABS DNV

Lloyd’s Register

3

Page 6: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

DUAL COMPOUNDNEK 606 Offshore Cables

The objective of CONTROLCAVI INDUSTRIA was to develop a cable whichwill perform some of the most inhospitable conditions imaginableSaline atmosphere, UV radiation, extremes of temperature, hydrocarbons,oils, drilling fluids and muds while still maintaining the highest levels ofsafety for personnel requiring.High levels of flame retardance with zero emissions of halogens and toxicgases, which can endanger life and the safety of installation.

By developing a sheathing compound which meets the demands of allthese criteria with outstanding fire performance and high level of resistanceto atmospheric and chemical attack, CONTROLCAVI INDUSTRIA can offerowners and operators the perfect solution for the transmission of allelectrical energy, from mV signals to Medium tensions.

The result of this development is a cable with properties far in excess of therequirements stipulated in NEK 606 and associates IEC specifications. Inaddition, the conductors, insulating and sheathing compounds have thefollowing unique properties:

DUAL COMPOUND sheathing which is both halogen free andresistant to drilling fluids, muds and associates environmental conditions.

EASE OF INSTALLATION always an important consideration,for medium to large cross sectional cables, from the conceptual designthrough to the final installation with the unique conductor configuration ofmulti stranded class 2 tinned conductors which have the electricalresistance of “traditional” minimal strand conductors.CONTROLCAVI INDUSTRIA have developed a unique solution whichreduces total installation costs by offering a significant reduction inbending radius and speed of installation.

4

Page 7: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

COLD BEND AND IMPACT (CSA C22.2) –40 Deg Cwith the search of hydrocarbons in ever more inhospitable climates andincreased use of FPSO vessels which can find themselves operating inextremes of temperature from one field to another, all cables manufacturedby CONTROLCAVI INDUSTRIA can be installed and operate attemperatures down to –40 Deg Centigrade.(test witnessed by ABS, DNV and LRS)

HEPR INSULATION in order to increase the insulating properties,and, as a result the current carrying capacity of 0,6/1 kV cables andabove, CONTROLCAVI INDUSTRIA have developed High ModulusEthylene Propylene Rubber (HEPR) compound.This offers superior insulation constant (Ki) and significantly improvedageing performance at higher operating temperatures than the traditional85 Deg C EPR compounds. These results can be seen below on the ARRHENIUSGRAPH obtained by performing the Thermal Endurance Evaluation accordingto IEC 60216, where Temperature Index achieved has been Ti = 114 Deg C(witnessed by ABS, DNV and LRS)

2,66 2,61 2,56 2,51 2,46 2,41 2,36 2,31 2,26 2,21 2,16 2,11100.000

10.000

20.000

1.000

100

100 110 114 120 130 140 150 160 170 180 190 20010

Reciprocal thermodynamic temperature (1000/Deg K)

Tim

e (h

ours

)

Temperature (Deg C)

5

Page 8: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Reference Standards The informations in this catalog apply to materials, constructions, andtesting of power and telecommunication shipboard and offshore cablesaccording to next standards:

IEC 60092-350 Low voltage shipboard power cables.General construction and test requirements.

IEC 60092-351 Insulating materials of shipboard power cables.

IEC 60092-353 Single and multicore non-radial field power cables with extruded solid insulation for rated voltages 1 kV and 3 kV.

IEC 60092.354 Single and three-core power cables with extruded solid insulation for rated voltages 6 kV, 10 kV and 15 kV

IEC 60092-359 Sheathing materials for shipboard power and telecommunication cables.

IEC 60092-375 Shipboard telecommunication cables and radio-frequency cables. General instrumentation, control and telecommunicationcables.

IEC 60331 Fire-resistant characteristics of electric cables

IEC 60332-1 Tests on electric cables under fire conditions.Test on a single vertical insulated wire or cable.

IEC 60332-3 Tests on electric cables under fire conditions.Tests on bunched wires or cables

IEC 60754-1/2 Test on gases evolved during combustion of electric cables.Part 1: Determination of the haogen acid gasPart 2: Determination of the degree of acidity duringthe combustion of materials taken from electric cablesby measuring pH and conductivity.

IEC 61034-1/2 Measurement of smoke density of cables burning under defined conditions.

NEK 606 Cables for offshore installation halogen-free or mud resitant

NVE 1990 FEA-M regulation Regulation for electrical installations - maritime installationsClause 1238 Methodes of earthing and dimensions

CSA C22.2 N° 38-95Thermoset Insulated Wires and Cables - Wiring ProductsClause 6.4.4 Low Temperature Flexibility (- 40 Deg C)Clause 6.4.5 Low Temperature Impact (- 40 Deg C)

6

Page 9: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Manufacturing Program

Halogen Free Mud ResistantFlame Retardant Low temp. –40 Deg CRFOU P1/P8 page 11Power & control, armoured 0,6/1 kV

RFOU(i) S1/S5 page 15Instrumentation, individual screen 250 V

RFOU(c) S2/S6 page 17Instrumentation, common screen 250 V

RFOU P2/P9 page 21Medium Voltage, armoured 3,6/6 kV

RFOU P3/P10 page 23Medium Voltage, armoured 6/10 kV

RFOU P4/P11 page 25Medium Voltage, armoured 8,7/15 kV

Halogen Free Mud ResistantFire Resistant Low temp. –40 Deg C

BFOU P5/P12 page 29Power & control, armoured 0,6/1 kV

BFOU(i) S3/S7 page 33Instrumentation, individual screen 250 V

BFOU(c) S4/S8 page 35Instrumentation, common screen 250 V

7

Page 10: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Cable designationin accordance to NEK 606

R ethylene propylene (HEPR or EPR) insulation halogen free flame retardant

B mica tape + HEPR or EPR insulationfire resistant halogen free flame retardant

F SHF2 thermosetting bedding compoundhalogen free flame retardant

O tinned copper wire braid armour

U SHF2 thermosetting dual compoundHALOGEN FREE & MUD RESISTANT flame retardant - low temperature - 40 Deg C

(C) common screen of copper / polyester tapetinned copper drain wire over assembled pairs / triples

( I ) individual screen of copper / polyester tapetinned copper drain wire over each pair / triple

P1/P8 power & control 0,6 / 1 kVHALOGEN FREE & MUD RESISTANT flame retardant

P2/P9 power medium voltage 3,6 / 6 kVHALOGEN FREE & MUD RESISTANT flame retardant

P3/P10 power medium voltage 6 / 10 kVHALOGEN FREE & MUD RESISTANT flame retardant

P4/P11 power medium voltage 8,7 / 15 kVHALOGEN FREE & MUD RESISTANT flame retardant

P5/P12 power & control 0,6 / 1 kVHALOGEN FREE & MUD RESISTANT flame retardant fire resistant

S1/S5 instrumentation individual screen 250 VHALOGEN FREE & MUD RESISTANT flame retardant

S2/S6 instrumentation common screen 250 VHALOGEN FREE & MUD RESISTANT flame retardant fire resistant

S3/S7 instrumentation individual screen 250 VHALOGEN FREE & MUD RESISTANT flame retardant fire resistant

S4/S8 instrumentation common screen 250 VHALOGEN FREE & MUD RESISTANT flame retardant fire resistant

8

Page 11: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

NEK 606

Halogen freeMUD resistant

–40 Deg C

Flame retardant

Page 12: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

IEC 60332.3 Cat. A FLAME RETARDANT TEST

10

Page 13: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

RFOU P1/P8Power & Control 0,6/1 kVHalogen Free & MUD Resistant

(–40 Deg C)

Design and construction IEC 60092-353 Operating temperature 85 Deg C (see page 5)Nominal voltage Uo / U 0,6/1 kVFlame retardancy IEC 60332-1 IEC 60332-3 cat ACorrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact (–40 Deg C) CSA C22.2 No 38-95

1 core off-white (grey)2 cores off-white black3 cores off-white black red4 cores off-white black red blue5 cores and above white & numbered

sheath colour black

Cores Identification

CCI RFOU P1/P8 0,6/1 kV n x s/braid mm2 (–40C) CSA C22.2NEK 606 IEC 60332-3A QA ref metric marking

Sheath Marking

11

1 CONDUCTOR tinned stranded compacted copper IEC 60228 class 2

2 INSULATION halogen free HEPR compoundSEPARATOR (if necessary) halogen free tape

3 BEDDING halogen free SHF2 compound

4 ARMOUR tinned copper wire braidaccording to FEA-M 1238.5

5 OUTER SHEATH SHF2 thermoset dual compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

Page 14: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

RFOU P1/P8

12

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTOR CURRENT SHORTTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE RATING CIRCUIT

DIAMETER THICKNESS (APPROX) AT 20 Deg C AT 45 Deg C RATING[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km] [A] [kA]

1 x 16 1.0 9.4 1.2 13 345 60 1.160 98 2.33

1 x 25 1.2 11.0 1.5 15.5 520 70 0.735 127 3.65

1 x 35 1.2 12.1 1.6 17 650 80 0.530 162 5.11

1 x 50 1.4 13.5 1.6 18.5 830 85 0.391 214 7.30

1 x 70 1.6 16.0 1.7 21 1100 95 0.270 266 10.20

1 x 95 1.6 17.1 1.8 22.5 1370 100 0.195 307 13.90

1 x 120 1.6 18.6 1.9 24 1650 110 0.154 359 17.50

1 x 150 1.8 20.3 2.0 26 2010 115 0.126 406 21.90

1 x 185 2.0 22.4 2.1 28.5 2420 120 0.100 493 27.00

1 x 240 2.2 25.5 2.2 31.5 3070 140 0.076 556 35.00

1 x 300 2.4 28.5 2.3 34.5 3740 155 0.061 672 43.80

2 x 1.5 / 4 1.0 9.5 1.5 13.5 275 60 12.200 17 0.21

2 x 2.5 / 7 1.0 10.3 1.5 15 350 65 7.560 24 0.35

2 x 4 / 7 1.0 11.4 1.5 16 418 75 4.700 40 0.58

2 x 6 / 8 1.0 12.5 1.6 17.5 505 80 3.110 49 0.87

2 x 10 / 10 1.0 13.7 1.6 18.5 625 85 1.840 61 1.46

2 x 16 / 16 1.0 16.3 1.8 22 890 100 1.160 81 2.33

3 x 1.5 / 5 1.0 10.1 1.5 14.5 335 65 12.200 15 0.21

3 x 2.5 / 7 1.0 11.0 1.5 15.5 395 70 7.560 22 0.36

3 x 4 / 7 1.0 12.1 1.5 17 475 75 4.700 27 0.58

3 x 6 / 8 1.0 13.4 1.6 18 585 80 3.110 37 0.87

3 x 10 / 10 1.0 14.6 1.6 19.5 745 90 1.840 56 1.46

3 x 16 / 16 1.0 17.4 1.8 23 1070 105 1.160 69 2.33

3 x 25 / 16 1.2 21.0 1.8 26.5 1505 120 0.735 100 3.65

3 x 35 / 16 1.2 23.4 2.0 29.5 1925 135 0.530 120 5.11

3 x 50 / 25 1.4 26.6 2.2 33 2565 150 0.391 140 7.30

3 x 70 / 35 1.6 32.0 2.4 39.5 3515 180 0.270 179 10.20

3 x 95 / 50 1.6 34.5 2.6 42.5 4520 190 0.195 214 13.90

3 x 120 / 60 1.6 37.9 2.8 46.5 5565 210 0.154 243 17.50

3 x 150 / 75 1.8 46.7 2.8 55 7380 250 0.126 307 21.90

3 x 185 / 95 2.0 51.8 3.0 60 9075 270 0.100 348 27.00

3 x 240 / 120 2.2 53.1 3.2 65 11375 295 0.076 394 33.80

0,6/1 kVNominal dimensional and electrical data

Page 15: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

13

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTOR CURRENT SHORTTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE RATING CIRCUIT

DIAMETER THICKNESS (APPROX) AT 20 Deg C AT 45 Deg C RATING[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km] [A] [kA]

4 x 1.5 / 6 1.0 11.0 1.5 15.5 385 70 12.200 15 0.21

4 x 2.5 / 7 1.0 12.0 1.5 16.5 455 75 7.560 22 0.36

4 x 4 / 8 1.0 13.3 1.5 18 560 80 4.700 27 0.58

4 x 6 / 8 1.0 14.6 1.6 19.5 690 90 3.110 37 0.87

4 x 10 / 10 1.0 16.0 1.6 21 890 95 1.840 56 1.46

4 x 16 / 16 1.0 19.1 1.8 24.5 1295 110 1.160 69 2.33

4 x 25 / 16 1.2 23.1 1.8 28.5 1840 130 0.735 100 3.65

4 x 35 / 16 1.2 25.8 2.0 32 2365 145 0.530 120 5.11

4 x 50 / 25 1.4 29.4 2.2 37.5 3335 170 0.391 140 7.30

4 x 70 / 35 1.6 35.4 2.4 42.5 4430 190 0.270 179 10.20

4 x 95 / 50 1.6 38.1 2.6 46 5630 210 0.195 214 13.90

4 x 120 / 60 1.6 42.0 2.8 50.5 6940 230 0.154 243 17.50

7 x 1,5 / 8 1.0 13.1 1.5 17.5 510 80 12.200 9 0.20

12 x 1,5 / 10 1.0 17.5 1.7 22.5 815 100 12.200 8 0.20

19 x 1,5 / 10 1.0 20.4 1.8 25.5 1095 115 12.200 8 0.20

27 x 1,5 / 11 1.0 24.8 2.0 30.5 1525 140 12.200 7 0.20

37 x 1,5 / 13 1.0 28.0 2.2 34 1930 155 12.200 7 0.20

7 x 2,5 / 8 1.0 14.5 1.5 19.2 630 85 7.560 15 0.36

12 x 2,5 / 11 1.0 19.2 1.7 24.5 1010 110 7.560 12 0.36

19 x 2,5 / 11 1.0 22.7 1.8 28 1390 125 7.560 10 0.36

27 x 2,5 / 16 1.0 27.5 2.0 33.5 1985 150 7.560 8 0.36

37 x 2,5 / 16 1.0 31.1 2.2 39.5 2700 180 7.560 8 0.36

0,6/1 kVNominal dimensional and electrical data

RFOU P1/P8

Page 16: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Instrumentation 250 VHalogen Free & MUD Resistant - Individual Screen

(–40 Deg C)

15

RFOU (i) S1/S5

Design and construction IEC 60092-375 IEC 60092-353 Nominal voltage 250 VOperating temperature 85 Deg CFlame retardancy IEC 60332-1 IEC 60332-3 cat ACorrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact test (–40 Deg C) CSA C22.2 No 38-95

CCI RFOU(i) S1/S5 250 V n x p(trp) x s mm2 (–40C) CSA C22.2NEK 606 IEC 60332-3A QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded copper wireIEC 60228 class 2

2 INSULATION halogen free EPR compound

3 INDIVIDUAL SCREEN copper/polyester tapetinned copper drain wire

4 BEDDING halogen free SHF2 compound

5 ARMOUR tinned copper wire braidaccording to IEC 60092.375

6 OUTER SHEATH SHF2 thermoset compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

pair black light bluetriple light blue black brown

(pairs/triples progressively numbered)

Pair/Triple Identification

sheath colour greyblue for intrinsically safe

Page 17: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

RFOU (i) S1/S5

16

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTORTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE

DIAMETER THICKNESS (APPROX) AT 20 Deg C[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km]

1 x 2 x 0.75 0.8 8.0 1.3 11.5 200 70 26.62 x 2 x 0.75 0.8 11.8 1.4 15.5 320 95 26.64 x 2 x 0.75 0.8 14.2 1.5 18.5 475 110 26.67 x 2 x 0.75 0.8 17.0 1.6 21.5 675 125 26.68 x 2 x 0.75 0.8 19.3 1.7 24 750 135 26.6

12 x 2 x 0.75 0.8 22.7 1.9 27.5 1030 160 26.616 x 2 x 0.75 0.8 25.1 2.0 31 1360 180 26.619 x 2 x 0.75 0.8 26.2 2.1 32 1555 195 26.624 x 2 x 0.75 0.8 30.4 2.2 35 2030 225 26.632 x 2 x 0.75 0.8 33.7 2.4 39 2465 245 26.61 x 3 x 0.75 0.8 8.4 1.3 12 215 75 26.62 x 3 x 0.75 0.8 13.1 1.5 17.5 380 105 26.64 x 3 x 0.75 0.8 15.5 1.6 20.5 570 120 26.67 x 3 x 0.75 0.8 19.5 1.7 25 840 145 26.68 x 3 x 0.75 0.8 21.0 1.8 26 940 155 26.6

12 x 3 x 0.75 0.8 25.8 2.0 30.5 1280 180 26.616 x 3 x 0.75 0.8 28.5 2.1 34 1625 200 26.619 x 3 x 0.75 0.8 31.5 2.2 37 1920 230 26.624 x 3 x 0.75 0.8 34.0 2.4 41 2370 240 26.632 x 3 x 0.75 0.8 38.2 2.6 46 3170 280 26.6

1 x 2 x 1 0.8 8.3 1.3 12 215 75 26.62 x 2 x 1 0.8 12.8 1.5 17 355 100 26.64 x 2 x 1 0.8 15.0 1.5 20 510 115 26.67 x 2 x 1 0.8 18.1 1.7 23.5 745 135 26.68 x 2 x 1 0.8 20.5 1.8 25.5 835 145 26.6

12 x 2 x 1 0.8 23.7 1.9 29.5 1130 165 26.616 x 2 x 1 0.8 26.1 2.0 32 1485 190 26.619 x 2 x 1 0.8 27.8 2.1 34 1705 205 26.624 x 2 x 1 0.8 32.2 2.4 38.5 2355 240 26.632 x 2 x 1 0.8 36.5 2.5 44 2790 260 26.61 x 3 x 1 0.8 8.8 1.3 12.5 230 75 26.62 x 3 x 1 0.8 14.0 1.5 18 415 105 26.64 x 3 x 1 0.8 16.0 1.6 21 620 125 26.67 x 3 x 1 0.8 21.2 1.8 26.5 940 150 26.68 x 3 x 1 0.8 22.1 1.9 28 1050 160 26.6

12 x 3 x 1 0.8 27.3 2.0 33.5 1460 190 26.616 x 3 x 1 0.8 29.8 2.2 36 2055 225 26.619 x 3 x 1 0.8 31.5 2.4 38.5 2370 240 26.624 x 3 x 1 0.8 37.0 2.5 45 2810 260 26.632 x 3 x 1 0.8 40.8 2.7 48.5 3550 295 26.6

1 x 2 x 1.5 0.8 9.0 1.3 12.5 240 75 12.22 x 2 x 1.5 0.8 13.8 1.5 18 395 105 12.24 x 2 x 1.5 0.8 16.5 1.6 21.5 595 120 12.27 x 2 x 1.5 0.8 20.0 1.7 24.5 865 145 12.28 x 2 x 1.5 0.8 21.8 1.9 27 980 155 12.2

12 x 2 x 1.5 0.8 26.3 2.0 32 1405 185 12.216 x 2 x 1.5 0.8 28.7 2.2 34.5 1770 205 12.219 x 2 x 1.5 0.8 29.7 2.2 36.5 2270 235 12.224 x 2 x 1.5 0.8 35.1 2.5 41.5 2630 250 12.232 x 2 x 1.5 0.8 37.5 2.6 46 3295 285 12.21 x 3 x 1.5 0.8 9.4 1.3 13 260 80 12.22 x 3 x 1.5 0.8 15.0 1.5 19.5 470 115 12.24 x 3 x 1.5 0.8 18.0 1.6 23.5 720 130 12.27 x 3 x 1.5 0.8 22.9 1.8 28 1100 160 12.28 x 3 x 1.5 0.8 24.0 1.9 29 1235 175 12.2

12 x 3 x 1.5 0.8 29.3 2.2 34.5 1795 205 12.216 x 3 x 1.5 0.8 33.3 2.3 40 2435 240 12.219 x 3 x 1.5 0.8 34.5 2.4 41 2710 250 12.224 x 3 x 1.5 0.8 38.5 2.7 45.5 3380 285 12.232 x 3 x 1.5 0.8 44.0 2.8 52.5 4260 320 12.2

250 VNominal dimensional and electrical data

Page 18: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

17

RFOU (c) S2/S6Instrumentation 250 V

Halogen Free & MUD Resistant - Common Screen(–40 Deg C)

Design and construction IEC 60092-375 IEC 60092-353 Nominal voltage 250 VOperating temperature 85 Deg CFlame retardancy IEC 60332-1 IEC 60332-3 cat ACorrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact test (–40 Deg C) CSA C22.2 No 38-95

CCI RFOU(c) S2/S6 250 V n x p(trp) x s mm2 (–40C) CSA C22.2NEK 606 IEC 60332-3A QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded copper wireIEC 60228 class 2

2 INSULATION halogen free EPR compound

3 COMMON SCREEN copper/polyester tapetinned copper drain wire

4 BEDDING halogen free SHF2 compound

5 ARMOUR tinned copper wire braidaccording to IEC 60092.375

6 OUTER SHEATH SHF2 thermoset compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

pair black light bluetriple light blue black brown

(pairs/triples progressively numbered)

Pair/Triple Identification

sheath colour greyblue for intrinsically safe

Page 19: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

RFOU (c) S2/S6

18

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTORTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE

DIAMETER THICKNESS (APPROX) AT 20 Deg C[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km]

1 x 2 x 0.75 0.8 8.0 1.3 11.5 200 70 26.62 x 2 x 0.75 0.8 11.5 1.4 15.5 315 95 26.64 x 2 x 0.75 0.8 13.8 1.5 18 435 110 26.67 x 2 x 0.75 0.8 16.2 1.6 20.5 590 130 26.68 x 2 x 0.75 0.8 18.3 1.7 22.5 660 135 26.6

12 x 2 x 0.75 0.8 21.3 1.9 26 880 160 26.616 x 2 x 0.75 0.8 24.2 2.0 28.5 1115 185 26.619 x 2 x 0.75 0.8 25.2 2.1 29.5 1300 195 26.624 x 2 x 0.75 0.8 29.1 2.2 33.5 1705 225 26.632 x 2 x 0.75 0.8 32.3 2.4 37.5 2025 245 26.61 x 3 x 0.75 0.8 8.4 1.3 12 215 75 26.62 x 3 x 0.75 0.8 12.9 1.5 17 360 105 26.64 x 3 x 0.75 0.8 15.1 1.6 19.5 505 120 26.67 x 3 x 0.75 0.8 19.1 1.7 24 710 145 26.68 x 3 x 0.75 0.8 20.5 1.8 25 790 155 26.6

12 x 3 x 0.75 0.8 24.2 2.0 29 1040 180 26.616 x 3 x 0.75 0.8 27.2 2.1 32 1355 200 26.619 x 3 x 0.75 0.8 28.9 2.2 34 1715 230 26.624 x 3 x 0.75 0.8 32.8 2.4 38 1960 245 26.632 x 3 x 0.75 0.8 36.3 2.6 42.5 2490 275 26.6

1 x 2 x 1 0.8 8.3 1.3 12 215 75 26.62 x 2 x 1 0.8 12.4 1.5 16.5 345 100 26.64 x 2 x 1 0.8 14.5 1.5 19 475 115 26.67 x 2 x 1 0.8 17.0 1.7 22 670 135 26.68 x 2 x 1 0.8 18.5 1.8 24 745 145 26.6

12 x 2 x 1 0.8 22.5 1.9 27.5 980 165 26.616 x 2 x 1 0.8 24.7 2.0 29 1280 190 26.619 x 2 x 1 0.8 26.1 2.1 31 1455 205 26.624 x 2 x 1 0.8 30.6 2.4 35.5 1940 240 26.632 x 2 x 1 0.8 34.7 2.5 40.5 2355 260 26.61 x 3 x 1 0.8 8.8 1.3 12.5 230 75 26.62 x 3 x 1 0.8 13.5 1.5 17.5 390 110 26.64 x 3 x 1 0.8 15.5 1.6 20 555 125 26.67 x 3 x 1 0.8 20.1 1.8 24.5 805 150 26.68 x 3 x 1 0.8 21.6 1.9 27 895 160 26.6

12 x 3 x 1 0.8 25.9 2.0 31 1210 190 26.616 x 3 x 1 0.8 28.5 2.2 33.5 1715 225 26.619 x 3 x 1 0.8 30.0 2.4 36 1965 240 26.624 x 3 x 1 0.8 34.5 2.5 41.5 2290 260 26.632 x 3 x 1 0.8 38.0 2.7 45 2850 295 26.6

1 x 2 x 1.5 0.8 9.0 1.3 12.5 240 75 12.22 x 2 x 1.5 0.8 13.3 1.5 17.5 390 105 12.24 x 2 x 1.5 0.8 15.5 1.6 20 560 120 12.27 x 2 x 1.5 0.8 19.0 1.7 23 785 145 12.28 x 2 x 1.5 0.8 20.4 1.9 25 885 155 12.2

12 x 2 x 1.5 0.8 24.9 2.0 29.5 1215 185 12.216 x 2 x 1.5 0.8 27.2 2.2 32 1560 205 12.219 x 2 x 1.5 0.8 28.2 2.2 33.5 1930 235 12.224 x 2 x 1.5 0.8 33.1 2.5 38.5 2305 250 12.232 x 2 x 1.5 0.8 33.5 2.6 43 2850 285 12.21 x 3 x 1.5 0.8 9.4 1.3 13 260 80 12.22 x 3 x 1.5 0.8 14.5 1.5 19 445 115 12.24 x 3 x 1.5 0.8 17.0 1.6 22 650 130 12.27 x 3 x 1.5 0.8 21.7 1.8 26 955 160 12.28 x 3 x 1.5 0.8 23.3 1.9 27 1065 175 12.2

12 x 3 x 1.5 0.8 27.8 2.2 32 1535 205 12.216 x 3 x 1.5 0.8 30.8 2.3 36 2080 240 12.219 x 3 x 1.5 0.8 32.7 2.4 38.5 2280 250 12.224 x 3 x 1.5 0.8 37.0 2.7 42.5 2830 285 12.232 x 3 x 1.5 0.8 42.0 2.8 48.5 3515 320 12.2

250 VNominal dimensional and electrical data

Page 20: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

NEK 606

Halogen freeMUD resistant

–40 Deg C

Medium Voltage

Page 21: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

21

RFOU P2/P9Medium Voltage 3,6/6 kVHalogen Free & MUD Resistant

(–40 Deg C)

Design and construction IEC 60092-354 IEC 60502 Nominal voltage Uo/U 3.6/6 kVMaximum rated temperature 85 Deg C (see page 5)Flame retardancy IEC 60332-1 IEC 60332-3 cat ACorrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact (–40 Deg C) CSA C22.2 No 38-95

CCI RFOU P2/P9 3.6/6 kV n x s/braid mm2 (–40C) CSA C22.2NEK 606 IEC 60332-3A QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded compactedcopper IEC 60228 class 2

2 SEMICONDUCTOR halogen free EPR compound

3 INSULATION halogen free HEPR compound

4 SCREEN tinned copper wire braidaccording to NVE FEA-M 1238.5

5 BEDDING halogen free thermosetcompound type SHF2

6 ARMOUR tinned copper wire braid

7 OUTER SHEATH SHF2 thermoset compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

sheath colour red

by coloured or numbered tapes

Cores Identification

Page 22: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

CONSTRUCTION CONDUCTOR DIAMETER UNDER OVERALL WEIGHT BENDING CONDUCTOR CURRENT SHORTDIAMETER OVER ARMOUR DIAMETER (APPROX) RADIUS RESISTANCE RATING CIRCUIT

INSULATION DIAMETER (APPROX) AT 20 Deg C AT 45 Deg C RATING[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km] [A] [kA]

1 x 25 6.1 14.1 18.5 23.5 900 190 0.734 140 3.4

1 x 35 7.2 15.2 20.5 25.5 1170 205 0.529 171 5.0

1 x 50 8.3 16.3 22.5 29 1360 230 0.391 204 7.1

1 x 70 10.3 18.4 25.0 30 1650 240 0.270 257 9.9

1 x 95 11.5 19.6 27.0 32 1960 255 0.195 314 13.5

1 x 120 12.9 21.0 29.0 34 2270 270 0.154 363 17.0

1 x 150 14.3 22.5 30.0 36 2550 290 0.126 410 21.2

1 x 185 16.0 24.2 32.0 38.5 3190 310 0.100 472 26.0

1 x 240 18.3 26.6 34.0 39.5 3715 315 0.076 558 34.5

1 x 300 20.7 29.0 36.0 43.5 4580 350 0.061 640 43.0

3 x 25 6.1 14.1 39.5 45.5 3220 365 0.734 102 3.4

3 x 35 7.2 15.2 43.0 48.5 3820 390 0.53 123 5.0

3 x 50 8.3 16.3 46.5 53 4550 425 0.391 148 7.1

3 x 70 10.3 18.4 49.0 56 5610 450 0.270 185 9.9

3 x 95 11.5 19.6 52.5 61 6880 490 0.195 224 13.5

3 x 120 12.9 21.0 56.0 63.5 7930 510 0.154 259 17.0

3 x 150 14.3 22.5 58.0 67 9390 535 0.126 292 21.2

3 x 185 16.0 24.2 65.0 74 11100 590 0.100 336 26.0

3.6/6 kVNominal dimensional and electrical data

22

RFOU P2/P9

Page 23: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

23

RFOU P3/P10Medium Voltage 6/10 kVHalogen Free & MUD Resistant

(–40 Deg C)

Design and construction IEC 60092-354 IEC 60502 Nominal voltage Uo/U 6/10 kVMaximum rated temperature 85 Deg C (see page 5)Flame retardancy IEC 60332-1 IEC 60332-3 cat ACorrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact (–40 Deg C) CSA C22.2 No 38-95

CCI RFOU P3/P10 6/10 kV n x s/braid mm2 (–40C) CSA C22.2NEK 606 IEC 60332-3A QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded compactedcopper IEC 60228 class 2

2 SEMICONDUCTOR halogen free EPR compound

3 INSULATION halogen free HEPR compound

4 SCREEN tinned copper wire braidaccording to NVE FEA-M 1238.5

5 BEDDING halogen free thermosetcompound type SHF2

6 ARMOUR tinned copper wire braid

7 OUTER SHEATH SHF2 thermoset compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

sheath colour red

by coloured or numbered tapes

Cores Identification

Page 24: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

CONSTRUCTION CONDUCTOR DIAMETER UNDER OVERALL WEIGHT BENDING CONDUCTOR CURRENT SHORTDIAMETER OVER ARMOUR DIAMETER (APPROX) RADIUS RESISTANCE RATING CIRCUIT

INSULATION DIAMETER (APPROX) AT 20 Deg C AT 45 Deg C RATING[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km] [A] [kA]

1 x 25 6.1 15.4 21.0 25.5 950 205 0.734 140 3.4

1 x 35 7.2 16.5 22.5 27.5 1190 220 0.529 172 5.0

1 x 50 8.3 17.6 23.5 31 1400 240 0.391 204 7.1

1 x 70 10.3 19.6 25.0 31.5 1740 250 0.270 255 9.9

1 x 95 11.5 20.8 27.0 33 2080 260 0.195 313 13.5

1 x 120 12.9 22.2 29.0 35 2390 280 0.154 361 17.0

1 x 150 14.3 23.6 30.5 37 2790 295 0.126 409 21.2

1 x 185 16.0 25.3 32.5 39 3360 310 0.100 472 26.0

1 x 240 18.3 27.6 35.0 41.5 3930 330 0.076 555 34.5

1 x 300 20.7 30.0 37.5 46.5 4800 370 0.061 637 43.0

3 x 25 6.1 15.4 41.5 47 3390 375 0.735 111 3.4

3 x 35 7.2 16.5 44.5 50.5 4100 405 0.530 133 5.0

3 x 50 8.3 17.6 48.5 55 4780 440 0.391 159 7.1

3 x 70 10.3 19.6 51.0 58 5920 465 0.270 198 9.9

3 x 95 11.5 20.8 54.0 63.5 7190 510 0.195 293 13.5

3 x 120 12.9 22.2 59.0 66.5 8340 530 0.154 275 17.0

3 x 150 14.3 23.6 62.0 70 9750 560 0.126 307 21.2

3 x 185 16.0 25.3 67.0 77 11720 615 0.100 351 26.0

6/10 kVNominal dimensional and electrical data

24

RFOU P3/P10

Page 25: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

25

RFOU P4/P11Medium Voltage 8,7/15 kV

Halogen Free & MUD Resistant(–40 Deg C)

Design and construction IEC 60092-354 IEC 60502 Nominal voltage Uo/U 8.7/15 kVMaximum rated temperature 85 Deg C (see page 5)Flame retardancy IEC 60332-1 IEC 60332-3 cat ACorrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact test (–40 Deg C) CSA C22.2 No 38-95

CCI RFOU P4/P11 8.7/15 kV n x s/braid mm2 (–40C) CSA C22.2NEK 606 IEC 60332-3A QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded compactedcopper IEC 60228 class 2

2 SEMICONDUCTOR halogen free EPR compound

3 INSULATION halogen free HEPR compound

4 SCREEN tinned copper wire braidaccording to NVE FEA-M 1238.5

5 BEDDING halogen free thermosetcompound type SHF2

6 ARMOUR tinned copper wire braid

7 OUTER SHEATH SHF2 thermoset compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

sheath colour red

by coloured or numbered tapes

Cores Identification

Page 26: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

26

CONSTRUCTION CONDUCTOR DIAMETER UNDER OVERALL WEIGHT BENDING CONDUCTOR CURRENT SHORTDIAMETER OVER ARMOUR DIAMETER (APPROX) RADIUS RESISTANCE RATING CIRCUIT

INSULATION DIAMETER (APPROX) AT 20 Deg C AT 45 Deg C RATING[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km] [A] [kA]

1 x 25 6.1 18.1 22.5 28 1280 225 0.734 138 3.4

1 x 35 7.2 19.2 24.0 30 1420 240 0.529 167 5.0

1 x 50 8.3 20.3 25.5 33 1630 265 0.391 201 7.1

1 x 70 10.3 22.3 28.0 34.5 1950 275 0.270 252 9.9

1 x 95 11.5 23.5 29.0 36 2260 290 0.195 307 13.5

1 x 120 12.9 24.9 30.5 37.5 2580 300 0.154 354 17.0

1 x 150 14.3 26.3 32.0 39.5 3090 315 0.126 402 21.2

1 x 185 16.0 28.0 33.5 41 3580 330 0.100 460 26.0

1 x 240 18.3 30.3 37.0 44 4450 350 0.076 551 34.5

1 x 300 20.7 32.7 40.0 48 5180 385 0.061 625 43.0

3 x 25 6.1 18.1 45.0 53 4270 425 0.735 110 3.4

3 x 35 7.2 19.2 48.0 56 4890 450 0.530 134 5.0

3 x 50 8.3 20.3 51.5 59 5650 470 0.391 159 7.1

3 x 70 10.3 22.3 54.5 64 6850 510 0.270 198 9.9

3 x 95 11.5 23.5 59.0 68.5 8110 550 0.195 239 13.5

3 x 120 12.9 24.9 63.0 72 9750 575 0.154 275 17.0

3 x 150 14.3 26.3 67.0 76.5 10900 610 0.126 351 21.2

8,7/15 kVNominal dimensional and electrical data

RFOU P4/P11

Page 27: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

NEK 606

Halogen freeMUD resistant

–40 Deg C

Fire resistant

Page 28: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

IEC 60331 FIRE RESISTANT TEST

28

Page 29: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

BFOU P5/P12Power & Control 0,6/1 kVHalogen Free & MUD Resistant

(–40 Deg C)

Design and construction IEC 60092-353 Operating temperature 85 Deg C (see page 5)Nominal voltage Uo / U 0.6/1 kVFlame retardancy IEC 60332-1 IEC 60332-3 cat AFire resistance IEC 60331Corrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact (–40 Deg C) CSA C22.2 No 38-95

1 core off-white (grey)2 cores off-white black3 cores off-white black red4 cores off-white black red blue5 cores and above white & numbered

sheath colour black

Cores Identification

CCI BFOU P5/P12 0.6/1 kV n x s/braid mm2 (–40C) CSA C22.2NEK 606 IEC 60331 QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded compacted copper IEC 60228 class 2

2 INSULATION mica tape +halogen free HEPR compound

SEPARATOR (if necessary) halogen free tape

3 BEDDING halogen free SHF2 compound

4 ARMOUR tinned copper wire braidaccording to FEA-M 1238.5

5 OUTER SHEATH SHF2 thermoset dual compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

29

Page 30: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

30

BFOU P5/P12

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTOR CURRENT SHORTTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE RATING CIRCUIT

DIAMETER THICKNESS (APPROX) AT 20 Deg C AT 45 Deg C RATING[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km] [A] [kA]

1 x 16 1.0 10.0 1.2 13.5 365 60 1.160 104 2.33

1 x 25 1.2 11.6 1.5 16.5 545 75 0.735 139 3.65

1 x 35 1.2 12.7 1.6 17.5 675 80 0.530 168 5.11

1 x 50 1.4 14.1 1.6 19 860 85 0.391 208 7.30

1 x 70 1.6 16.6 1.7 21.5 1130 95 0.270 261 10.20

1 x 95 1.6 17.8 1.8 23 1400 105 0.195 319 13.90

1 x 120 1.6 19.2 1.9 24.5 1690 110 0.154 371 17.50

1 x 150 1.8 21.0 2.0 26.5 2050 120 0.126 423 21.90

1 x 185 2.0 23.1 2.1 29 2460 130 0.100 480 27.00

1 x 240 2.2 26.2 2.2 32.5 3115 145 0.076 568 35.00

1 x 300 2.4 29.0 2.3 35.5 3960 160 0.061 649 43.80

2 x 1.5 / 4 1.0 10.7 1.5 15 325 70 12.200 19 0.21

2 x 2.5 / 7 1.0 11.5 1.5 16 400 75 7.560 27 0.35

2 x 4 / 7 1.0 12.6 1.5 17 470 80 4.700 37 0.58

2 x 6 / 8 1.0 13.7 1.6 18.5 560 85 3.110 47 0.87

2 x 10 / 10 1.0 14.9 1.6 20 685 90 1.840 66 1.46

2 x 16 / 16 1.0 17.5 1.8 23 960 105 1.160 89 2.33

3 x 1.5 / 5 1.0 11.4 1.5 16 400 70 12.200 16 0.21

3 x 2.5 / 7 1.0 12.2 1.5 17 450 75 7.560 23 0.36

3 x 4 / 7 1.0 13.4 1.5 18 535 80 4.700 31 0.58

3 x 6 / 8 1.0 14.6 1.6 19.5 645 90 3.110 39 0.87

3 x 10 / 10 1.0 15.9 1.6 21 810 95 1.840 54 1.46

3 x 16 / 16 1.0 18.7 1.8 24.5 1155 110 1.160 73 2.33

3 x 25 / 16 1.2 22.4 1.8 28 1600 125 0.735 97 3.65

3 x 35 / 16 1.2 24.7 2.0 30.5 2025 140 0.530 118 5.11

3 x 50 / 25 1.4 28.0 2.2 34.5 2675 155 0.391 146 7.30

3 x 70 / 35 1.6 33.4 2.4 40.5 3705 180 0.270 183 10.20

3 x 95 / 50 1.6 35.8 2.6 44 4760 200 0.195 223 13.90

3 x 120 / 60 1.6 39.4 2.8 48 5735 215 0.154 259 17.50

3 x 150 / 75 1.8 48.4 2.8 57 7700 255 0.126 296 21.90

3 x 185 / 95 2.0 53.5 3.0 62 9480 280 0.100 337 27.00

3 x 240 / 120 2.2 55.0 3.2 67.5 11750 305 0.076 398 33.80

0,6/1 kVNominal dimensional and electrical data

Page 31: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

31

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTOR CURRENT SHORTTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE RATING CIRCUIT

DIAMETER THICKNESS (APPROX) AT 20 Deg C AT 45 Deg C RATING[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km] [A] [kA]

4 x 1.5 / 6 1.0 12.4 1.5 17 450 75 12.200 16 0.21

4 x 2.5 / 7 1.0 13.4 1.5 18 525 80 7.560 23 0.36

4 x 4 / 8 1.0 14.7 1.5 19.5 625 90 4.700 31 0.58

4 x 6 / 8 1.0 16.1 1.6 21 765 95 3.110 39 0.87

4 x 10 / 10 1.0 17.5 1.6 22.5 970 100 1.840 54 1.46

4 x 16 / 16 1.0 20.6 1.8 26 1395 115 1.160 73 2.33

4 x 25 / 16 1.2 24.6 1.8 30 1950 135 0.735 97 3.65

4 x 35 / 16 1.2 27.3 2.0 33.5 2485 150 0.530 118 5.11

4 x 50 / 25 1.4 30.9 2.2 39 3480 175 0.391 146 7.30

4 x 70 / 35 1.6 36.9 2.4 44 4585 200 0.270 183 10.20

4 x 95 / 50 1.6 39.6 2.6 47.5 5800 215 0.195 223 13.90

4 x 120 / 60 1.6 43.6 2.8 52 7145 235 0.154 259 17.50

7 x 1.5 / 8 1.0 14.9 1.5 19.5 600 90 12.200 12 0.21

12 x 1.5 / 10 1.0 20.0 1.7 25 935 110 12.200 10 0.21

19 x 1.5 / 10 1.0 23.4 1.8 28.5 1240 130 12.200 9 0.21

27 x 1.5 / 11 1.0 28.5 2.0 36 1895 160 12.200 8 0.21

37 x 1.5 / 13 1.0 32.2 2.2 39 2395 175 12.200 8 0.21

7 x 2.5 / 8 1.0 16.3 1.5 21 725 95 7.560 17 0.36

12 x 2.5 / 11 1.0 21.6 1.7 26.5 1175 120 7.560 13 0.36

19 x 2.5 / 11 1.0 25.7 1.8 31 1615 140 7.560 12 0.36

27 x 2.5 / 16 1.0 31.2 2.0 39 2495 175 7.560 10 0.36

37 x 2.5 / 16 1.0 35.3 2.2 43 3150 195 7.560 10 0.36

0,6/1 kVNominal dimensional and electrical data

BFOU P5/P12

Page 32: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Instrumentation 250 VHalogen Free & MUD Resistant - Individual Screen

(–40 Deg C)

33

BFOU (i) S3/S7

Design and construction IEC 60092-375 IEC 60092-353 Nominal voltage 250 VMaximum rated temperature 85 Deg CFlame retardancy IEC 60332-1 IEC 60332-3 cat AFire resistance IEC 60331Corrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact test (–40 Deg C) CSA C22.2 No 38-95

CCI BFOU(i) S3/S7 250 V n x p(trp) x s mm2 (–40C) CSA C22.2NEK 606 IEC 60331 QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded copper wireIEC 60228 class 2

2 INSULATION mica tape +halogen free EPR compound

3 INDIVIDUAL SCREEN copper/polyester tapetinned copper drain wire

4 BEDDING halogen free SHF2 compound

5 ARMOUR tinned copper wire braidaccording to IEC 60092.375

6 OUTER SHEATH SHF2 thermoset compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

pair black light bluetriple light blue black brown

(pairs/triples progressively numbered)

Pair/Triple Identification

sheath colour greyblue for intrinsically safe

Page 33: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

34

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTORTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE

DIAMETER THICKNESS (APPROX) AT 20 Deg C[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km]

1 x 2 x 0.75 0.8 8.4 1.3 12 215 75 26.62 x 2 x 0.75 0.8 13.1 1.4 17 360 100 26.64 x 2 x 0.75 0.8 15.4 1.5 20 530 120 26.67 x 2 x 0.75 0.8 18.6 1.6 23 760 140 26.68 x 2 x 0.75 0.8 20.7 1.7 26 855 150 26.6

12 x 2 x 0.75 0.8 23.9 1.9 30 1165 175 26.616 x 2 x 0.75 0.8 27.2 2.0 33.5 1535 200 26.619 x 2 x 0.75 0.8 28.5 2.1 36.5 1925 225 26.624 x 2 x 0.75 0.8 33.0 2.2 40 2300 250 26.632 x 2 x 0.75 0.8 36.0 2.4 45 2800 270 26.61 x 3 x 0.75 0.8 9.0 1.3 12.5 235 75 26.62 x 3 x 0.75 0.8 14.4 1.5 19.5 430 110 26.64 x 3 x 0.75 0.8 17.5 1.6 22 645 130 26.67 x 3 x 0.75 0.8 21.4 1.7 26.5 960 155 26.68 x 3 x 0.75 0.8 23.5 1.8 28.5 1075 170 26.6

12 x 3 x 0.75 0.8 27.5 2.0 33 1465 195 26.616 x 3 x 0.75 0.8 30.7 2.1 36.5 2000 235 26.619 x 3 x 0.75 0.8 32.5 2.2 39.5 2335 240 26.624 x 3 x 0.75 0.8 37.3 2.4 46 2820 270 26.632 x 3 x 0.75 0.8 41.5 2.6 51.5 3640 310 26.6

1 x 2 x 1 0.8 9.1 1.3 13 240 75 26.62 x 2 x 1 0.8 14.0 1.5 19 405 110 26.64 x 2 x 1 0.8 16.3 1.5 21.5 590 125 26.67 x 2 x 1 0.8 19.2 1.7 25 865 150 26.68 x 2 x 1 0.8 21.5 1.8 27.5 965 160 26.6

12 x 2 x 1 0.8 26.0 1.9 32 1410 185 26.616 x 2 x 1 0.8 27.8 2.0 34.5 1890 225 26.619 x 2 x 1 0.8 30.0 2.1 37.5 2155 240 26.624 x 2 x 1 0.8 34.5 2.4 41.5 2680 260 26.632 x 2 x 1 0.8 38.0 2.5 46 3245 295 26.61 x 3 x 1 0.8 9.6 1.3 13.5 260 80 26.62 x 3 x 1 0.8 15.5 1.5 19.5 475 120 26.64 x 3 x 1 0.8 18.3 1.6 24 720 135 26.67 x 3 x 1 0.8 23.5 1.8 28 1095 170 26.68 x 3 x 1 0.8 25.0 1.9 31 1230 180 26.6

12 x 3 x 1 0.8 29.5 2.0 36 1875 220 26.616 x 3 x 1 0.8 32.5 2.2 40 2230 240 26.619 x 3 x 1 0.8 33.8 2.4 43.5 2735 260 26.624 x 3 x 1 0.8 39.9 2.5 48 3300 290 26.632 x 3 x 1 0.8 44.0 2.7 53 4180 330 26.6

1 x 2 x 1.5 0.8 9.7 1.3 13.5 260 80 12.22 x 2 x 1.5 0.8 14.6 1.5 19 450 115 12.24 x 2 x 1.5 0.8 18.0 1.6 23 675 135 12.27 x 2 x 1.5 0.8 21.5 1.7 27 985 160 12.28 x 2 x 1.5 0.8 24.0 1.9 30.5 1120 170 12.2

12 x 2 x 1.5 0.8 27.9 2.0 34 1605 205 12.216 x 2 x 1.5 0.8 31.0 2.2 37 2055 240 12.219 x 2 x 1.5 0.8 34.0 2.2 41 2420 250 12.224 x 2 x 1.5 0.8 37.8 2.5 46 3020 280 12.232 x 2 x 1.5 0.8 44.0 2.6 52 3960 315 12.21 x 3 x 1.5 0.8 10.2 1.3 14 285 85 12.22 x 3 x 1.5 0.8 16.5 1.5 21 535 125 12.24 x 3 x 1.5 0.8 20.0 1.6 24.5 830 145 12.27 x 3 x 1.5 0.8 24.5 1.8 29 1270 180 12.28 x 3 x 1.5 0.8 27.0 1.9 32 1425 190 12.2

12 x 3 x 1.5 0.8 31.5 2.2 38 2255 230 12.216 x 3 x 1.5 0.8 36.5 2.3 43 2730 260 12.219 x 3 x 1.5 0.8 37.5 2.4 46 3140 280 12.224 x 3 x 1.5 0.8 42.5 2.7 51 3915 315 12.232 x 3 x 1.5 0.8 47.0 2.8 56 4945 355 12.2

250 VNominal dimensional and electrical data

BFOU (i) S3/S7

Page 34: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

35

Instrumentation 250 VHalogen Free & MUD Resistant - Common Screen

(–40 Deg C)

BFOU (c) S4/S8

Design and construction IEC 60092-375 IEC 60092-353 Nominal voltage 250 VMaximum rated temperature 85 Deg CFlame retardancy IEC 60332-1 IEC 60332-3 cat AFire resistance IEC 60331Corrosivity IEC 60754-1 IEC 60754-2Smoke density IEC 61034-2MUD resistance NEK 606Cold bend and impact test (–40 Deg C) CSA C22.2 No 38-95

CCI BFOU(c) S4/S8 250 V n x p(trp) x s mm2 (–40C) CSA C22.2NEK 606 IEC 60331 QA ref metric marking

Sheath Marking

1 CONDUCTOR tinned stranded copper wireIEC 60228 class 2

2 INSULATION mica tape +halogen free EPR compound

3 COMMON SCREEN copper/polyester tapetinned copper drain wire

4 BEDDING halogen free SHF2 compound

5 ARMOUR tinned copper wire braidaccording to IEC 60092.375

6 OUTER SHEATH SHF2 thermoset compoundhalogen free & MUD resistantlow temperature (–40 Deg C)

Construction Data

pair black light bluetriple light blue black brown

(pairs/triples progressively numbered)

Pair/Triple Identification

sheath colour greyblue for intrinsically safe

Page 35: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

36

CONSTRUCTION INSULATION UNDER OUTER OVERALL WEIGHT BENDING CONDUCTORTHICKNESS ARMOUR SHEATH DIAMETER (APPROX) RADIUS RESISTANCE

DIAMETER THICKNESS (APPROX) AT 20 Deg C[mm2] [mm] [mm] [mm] [mm] [kg / km] [mm] [Ω / km]

1 x 2 x 0.75 0.8 8.4 1.3 12 215 75 26.62 x 2 x 0.75 0.8 13.0 1.4 16.5 360 105 26.64 x 2 x 0.75 0.8 15.0 1.5 19.5 505 120 26.67 x 2 x 0.75 0.8 17.3 1.6 22 700 140 26.68 x 2 x 0.75 0.8 19.9 1.7 25 780 150 26.6

12 x 2 x 0.75 0.8 23.2 1.9 28.5 1040 180 26.616 x 2 x 0.75 0.8 25.3 2.0 32 1360 205 26.619 x 2 x 0.75 0.8 26.3 2.1 33 1715 230 26.624 x 2 x 0.75 0.8 30.5 2.2 37.5 1850 240 26.632 x 2 x 0.75 0.8 34.2 2.4 40 2415 275 26.61 x 3 x 0.75 0.8 9.0 1.3 12.5 235 75 26.62 x 3 x 0.75 0.8 14.1 1.5 18.5 410 115 26.64 x 3 x 0.75 0.8 16.5 1.6 21 580 130 26.67 x 3 x 0.75 0.8 21.3 1.7 25 830 160 26.68 x 3 x 0.75 0.8 22.3 1.8 27.5 925 170 26.6

12 x 3 x 0.75 0.8 26.5 2.0 31.5 1230 200 26.616 x 3 x 0.75 0.8 28.5 2.1 34 1785 240 26.619 x 3 x 0.75 0.8 31.5 2.2 37 1845 245 26.624 x 3 x 0.75 0.8 35.8 2.4 42.5 2320 275 26.632 x 3 x 0.75 0.8 39.1 2.6 45.5 2960 315 26.6

1 x 2 x 1 0.8 9.1 1.3 13 240 75 26.62 x 2 x 1 0.8 14.0 1.5 18 405 110 26.64 x 2 x 1 0.8 15.5 1.5 20 565 130 26.67 x 2 x 1 0.8 18.5 1.7 23.5 805 150 26.68 x 2 x 1 0.8 21.0 1.8 26 890 160 26.6

12 x 2 x 1 0.8 25.1 1.9 30 1185 190 26.616 x 2 x 1 0.8 26.5 2.0 32 1720 230 26.619 x 2 x 1 0.8 28.5 2.1 35 1950 245 26.624 x 2 x 1 0.8 33.1 2.4 38.5 2265 265 26.632 x 2 x 1 0.8 36.5 2.5 43 2870 300 26.61 x 3 x 1 0.8 9.6 1.3 13.5 260 80 26.62 x 3 x 1 0.8 15.0 1.5 18.5 455 120 26.64 x 3 x 1 0.8 17.5 1.6 23 665 140 26.67 x 3 x 1 0.8 22.5 1.8 24.5 965 170 26.68 x 3 x 1 0.8 23.5 1.9 29.5 1075 185 26.6

12 x 3 x 1 0.8 28.5 2.0 34 1635 225 26.616 x 3 x 1 0.8 30.5 2.2 36 1895 245 26.619 x 3 x 1 0.8 32.6 2.4 39.5 2180 265 26.624 x 3 x 1 0.8 38.0 2.5 44.5 2780 300 26.632 x 3 x 1 0.8 42.0 2.7 49.5 3470 335 26.6

1 x 2 x 1.5 0.8 9.7 1.3 13.5 260 80 12.22 x 2 x 1.5 0.8 14.0 1.5 18.5 450 120 12.24 x 2 x 1.5 0.8 16.8 1.6 21.5 655 135 12.27 x 2 x 1.5 0.8 20.1 1.7 25 930 160 12.28 x 2 x 1.5 0.8 23.1 1.9 28.5 1045 175 12.2

12 x 2 x 1.5 0.8 26.4 2.0 31.5 1390 210 12.216 x 2 x 1.5 0.8 29.1 2.2 34.5 1780 235 12.219 x 2 x 1.5 0.8 30.5 2.2 36 2215 255 12.224 x 2 x 1.5 0.8 35.5 2.5 42 2750 285 12.232 x 2 x 1.5 0.8 39.0 2.6 45.5 3415 320 12.21 x 3 x 1.5 0.8 10.2 1.3 14 285 85 12.22 x 3 x 1.5 0.8 15.5 1.5 20 515 130 12.24 x 3 x 1.5 0.8 18.5 1.6 22.5 765 150 12.27 x 3 x 1.5 0.8 23.5 1.8 27 1130 185 12.28 x 3 x 1.5 0.8 25.5 1.9 30 1300 195 12.2

12 x 3 x 1.5 0.8 30.6 2.2 35.5 2000 235 12.216 x 3 x 1.5 0.8 34.0 2.3 39.5 2380 265 12.219 x 3 x 1.5 0.8 35.5 2.4 41.5 2715 286 12.224 x 3 x 1.5 0.8 40.8 2.7 47 3370 320 12.232 x 3 x 1.5 0.8 46.0 2.8 52.5 4200 360 12.2

250 VNominal dimensional and electrical data

BFOU (c) S4/S8

Page 36: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

Generals

Page 37: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

GeneralsSome parameters affecting operational chacteristics of the cablesmentioned in this catalog

CONDUCTOR RESISTANCEIt is the most important parameter of the conductor sizing related to:ρ conductor resistivity [Ω / mm 2/m]l conductor length [km]A cross area [mm 2]t temperature [Deg C]f frequency [Hz]

For low frequencies, conductor resistance is equal to DC condition.

R = ρ • l / A [Ω]

Temperature influence is calculated as:

Rt = R20 (234,5 + t) / 254,5 [Ω]

where:Rt conductor resistance [Ω]R20 conductor resistance at 20 Deg C [Ω]t conductor temperature [Deg C]Conductor resistance increases with frequency.

INSULATION RESISTANCEIt’s a peculiar characteristic of the insulation material.An higher value of insulation resistance means larger insulating capacityof the insulation.The "insulation resistance constant Ki" is calculated from the measuredinsulation resistance by the following formula:

Ki = l • R • 10-11 / (log10D / d) [MΩ • km]

where:R measured insulation resistance [Ω]l length if the cable [m]D outer diameter of the insulation [mm]d inner diameter of the insulation [mm]

39

Page 38: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

REACTANCEIn a cable operating in a.c. it is related mainly to axial distance betweenconductors.For 2 - 3 - 4 conductors the reactance per phase could be calculated as:

X = 2 • π • f • L • I [Ω]

f frequency [Hz]L Induction [H/m]l core length [m]L Induction Is calculates as follows:

L = 0,2 [(ln 2a / d) + 0.25] • 10-6 [H/m]

a distance between cores [mm]d core diameter [mm]

MEDIUM VOLTAGE CABLES - REACTANCE

IMPEDANCEZ = √ (R2 + X2) [Ω]

R resistance [Ω]X reactance [Ω]

40

CROSS SECTION SINGLE CORE [Ω/km] THREE CORES [Ω/km]

[mm2] 50 Hz 60 Hz 50 Hz 60 Hz

25 0.147 0.177 0.119 0.14335 0.145 0.174 0.116 0.13950 0.137 0.165 0.108 0.13070 0.130 0.156 0.102 0.12295 0.118 0.142 0.097 0.116

120 0.114 0.137 0.095 0.114150 0.108 0.130 0.092 0.110185 0.107 0.129 0.089 0.107240 0.106 0.127 — —300 0.086 0.103 — —

Page 39: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

MUTUAL CAPACITANCELow mutual capacitance causes small distorsion of the signal.Digital signal transmissions are sensible to this features. Is affected by:- type of conductor construction (increasing of conductor size means

larger capacitance)- insulation thickness (inversely proportional)

ATTENUATIONIt is defined as the decreasing, in signal amplitude, over the total length ofthe cable. Its value increases with the frequency increasing.Minimizing the attenuation means long distance transmission withoutamplification and no distorsions.

INTERFERENCESAre defined as all the noises influencing the signal transmission.They are produced internally the cable (i.e. cross talk) and externally (i.e.power equipments or HF generators).Both can be reduced by using suitable screenings.

INSTRUMENTATION AND TELECOMMUNICATION CABLESELECTRICAL CHARACTERISTICS

41

INDUCTANCEMUTUAL CAPACITANCE LOOP

SIZE (approx)max (approx) RESISTANCE

[mm2][mH/km]

[nF/km] max (approx)

individual screen common screen [Ω/km]

0.75 0.72 < 100 < 95 50.41.0 0.69 < 110 < 100 37.11.5 0.66 < 120 < 110 24.2

Page 40: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

CURRENT DETERMINATION according to power and voltageIn case of three-phase systems, determination of the current Intensityrelated to power and voltage can be easily calculated by using:

I = 722 kW / V I = 578 kVA / V I = 531 HP / V

where

I = current intensity [A]V = rated voltage [V]kW = power(cos ϕ = 0.8) [kW]kVA = power [kVA] HP = horse power [HP]

VOLTAGE DROP (up to 1 kV)

∆V = K • I • L / 1000 [V]

I rated current [A]L electric line length [m]K see following table

nominal K

size 2 cores 3 cores 3 cores (three-foil format.)

[mm2] cos ϕ =1 cos ϕ = 0.8 cos ϕ =1 cos ϕ = 0.8 cos ϕ =1 cos ϕ = 0.8

1.0 45.00 36.10 39.00 31.30 38.30 30.801.5 30.20 24.30 26.10 21.00 25.70 20.702.5 18.20 14.70 15.70 12.70 15.40 12.504.0 11.40 9.210 9.850 7.980 9.650 7.8706.0 7.560 6.160 6.540 5.340 6.420 5.280

10.0 4.550 3.730 3.940 3.240 3.870 3.22016.0 2.870 2.390 2.480 2.070 2.440 2.07025.0 1.810 1.550 1.570 1.340 1.540 1.34035.0 1.310 1.140 1.130 0.988 1.110 0.99350.0 0.967 0.866 0.838 0.750 0.820 0.76070.0 0.669 0.624 0.579 0.541 0.568 0.55595.0 0.484 0.476 0.419 0.412 0.410 0.428

120.0 0.383 0.394 0.332 0.342 0.325 0.358150.0 0.314 0.341 0.272 0.295 0.265 0.308185.0 0.251 0.289 0.217 0.250 0.213 0.265240.0 0.193 0.245 0.167 0.212 0.163 0.224300.0 0.156 0.215 0.135 0.186 0.132 0.198

42

Page 41: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

US / METRIC CROSS SECTION CONVERSION TABLE

43

Metric Standard metric

AWG (U.S.) cross-section cross-section(mm2) (mm2)

20 0.519 0.7518 0.823 116 1.31 1.514 2.08 2.512 3.31 410 5.26 68 8.37 106 13.30 164 21.15 252 33.62 351 42.41 50

1/0 53.49 702/0 67.23 703/0 85.01 954/0 107.2 120— — —— — —

Metric Standard metric

MCM (U.S.) cross-section cross-section(mm2) (mm2)

250 126.7 150300 152.0 150350 177.3 185400 202.7 185450 228.0 240500 253.4 300550 278.7 300600 304.0 300650 329.4 300700 354.7 400750 380.0 400800 405.4 400850 430.7 400900 456.0 500950 481.4 5001000 506.7 5001250 633.4 630

Page 42: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

CCI - NEK 606 Offshore Cables - REV 0 11.00

All data mentioned in the catalogue may be subject to continuous revision and improved at any time

Page 43: OFFSHORE CABLES NEK 606 - Infoklikk.no€¦ · Offshore Cables NEK 606 Dual Compound Halogen Free - Mud Resistant (–40 Deg C) Low Smoke Flame Retardant Fire Resistant Type Approvals:

GrGroup