ETAP Knowledge Base Zig-Zag Grounding Transformer This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2010 by Operation Technology, Inc. All Rights Reserved. © Operation Technology, Inc. Page 1 of 2 ETAPKB Description: Modeling of a Zig-Zag Grounding Transformer Category: Transformer, Zig-Zag Grounding Transformer Type: Modeling Keywords: Zig-Zag Grounding Transformer Operation of a Zig-Zag Grounding Transformer During normal operation the current flowing in the zig-zag transformer is the magnetizing current which is very small compared to the normal operating current and hence is negligible Under a line to ground fault the current flowing to the ground through the zig-zag transformer is equal to the rated neutral current, if 100% line to neutral voltage is applied ETAP Representation A zig-zag grounding transformer can be represented in ETAP by a R / Δ transformer with Δ side bus open: Notes : Td is a R / Δ connected transformer with a voltage ratio of 1 and Bus2 is a Dummy Bus. There is nothing connected to Bus2 except the transformer Td. Zig-Zag Transformer ETAP Representation of Zig-Zag Transformer

modelado de un transformador en delta abierto

  • Upload
    yradyh

  • View
    48

  • Download
    5

Embed Size (px)

DESCRIPTION

guia practica de entrenamiento para el programa ETAP, que muestra como realizar la simulación de un transformador en ZIG ZAG (delta abierto)

Citation preview

Page 1: modelado de un transformador en delta abierto

ETAP Knowledge Base

Zig-Zag Grounding Transformer

This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2010 by Operation Technology, Inc. All Rights Reserved. © Operation Technology, Inc. Page 1 of 2 ETAPKB

Description: Modeling of a Zig-Zag Grounding Transformer Category: Transformer, Zig-Zag Grounding Transformer Type: Modeling Keywords: Zig-Zag Grounding Transformer Operation of a Zig-Zag Grounding Transformer

• During normal operation the current flowing in the zig-zag transformer is the magnetizing

current which is very small compared to the normal operating current and hence is negligible

• Under a line to ground fault the current flowing to the ground through the zig-zag

transformer is equal to the rated neutral current, if 100% line to neutral voltage is applied ETAP Representation

A zig-zag grounding transformer can be represented in ETAP by a R / Δ transformer with

Δ side bus open:

Notes: • Td is a R / Δ connected transformer with a voltage ratio of 1 and Bus2 is a Dummy Bus. • There is nothing connected to Bus2 except the transformer Td.

Zig-Zag Transformer

ETAP Representation of Zig-Zag Transformer

Page 2: modelado de un transformador en delta abierto

ETAP Knowledge Base

Zig-Zag Grounding Transformer

This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2010 by Operation Technology, Inc. All Rights Reserved. © Operation Technology, Inc. Page 2 of 2 ETAPKB

Equivalent Parameters The parameters of transformer Td are calculated as follows: Let the zig-zag transformer have the following rating:

MVAzz

Line) to(Line kVzz Current) (Ground , zzIg

%100=Zzz

Therefore, the equivalent parameters of the transformer Td will be:

MVAzzMVA = kVzzkVprim =

kVzzkV =sec

%100,310003100 2 =×

×××

×=prim

Td kVMVA

zzIgkVzzZ