NORMATIVIDAD EN LA GESTION DEL ACTIVO TRANSFORMADOR
SEMINARIO INTERNACIONAL DE GESTION DEACTIVOS DE TRANSFORMADORES SIGAT - CIER 2010
I.E. M.Sc. HERNAN DARIO RODRIGUEZ S.
INTRODUCCION
“Large power transformers are the most significant p ortion of the T&D assets, and a major concern to every electric utility” .
Life Cycle Management of Utility Transformer AssetsWilliam H. Bartley P.E. Hartford Steam Boiler Inspection & Insurance Co.
October 10–11, 2002 Salt Lake City, Utah
Deregulation and an increasing competition in elect ricity markets urge energy suppliers to optimize the utilization of their equipment, foc using on technical and cost-effective aspects. As a respond to these requirements utiliti es introduce methods formerly used by aspects. As a respond to these requirements utiliti es introduce methods formerly used by investment managers or insurance companies.
Asset management techniques.Schneider, J. y otros.
International Journal of Electrical Power & Energy Systems,
Volume 28, Issue 9, November 2006.
It is therefore imperative to manage power transfor mers to attain optimum utilization and thereby maximizing the return on investment without lowering their production and availabilility levels ”.
Power Transformer Life Management. L.M.Geldenhuis
18th International Conference on Electricity Distribution –CIRED 2005-
Turin, 6 -9 June 2005
2
ENTORNO DE LAS EMPRESAS ELECTRICAS
EMPRESAS
Usuarios
Empleados y sindicatos
Financiadores
Accionistas
Contratistas yconsultores
3
ELECTRICAS Empleados y sindicatos
Entes reguladores ymarcos regulatoriosde la industria
Proveedores
Accionistas
Normatividadtécnica nacionale internacional
Regulaciones o los estándares mundiales:
ISO 9001:2000 – Sistemas de Gestión de Calidad
ISO 14000:2004 – Sistemas de Gestión Ambiental (basada en la BS 7750, sólo la 14001-Requisitos con orientación para su uso- es certificable)
ENTORNO DE LAS EMPRESAS ELECTRICAS
certificable)
OHSAS 18000:2007 -Sistemas de Gestión de Seguridad y Salud Ocupacional ( basada en la BS 8800) (OHSAS = Occupational Health and SafetyAssessment Series)
ISO 26000:2010 - Guía sobre Responsabilidad Social (no certificable y voluntaria)
PAS 55:2008 – Gestión de Activos(PAS = Publicly Available Specification)
4
A diferencia de las demás, la PAS 55 se estandarizó como una especificacióny está dirigida a:
“Mejorar y garantizar un desarrollo sostenible de los activos (físicos, humanos, financieros, información y social) de forma optimizada a niveles realmente
ENTORNO DE LAS EMPRESAS ELECTRICAS
financieros, información y social) de forma optimizada a niveles realmente requeridos”
Objeto : demostrar a los reguladores y/o accionistas un manejo de sus activos de forma responsable y sustenible en el tiempo. Todo esto planteado en un plan real a lo largo del ciclo de vida de sus activos, sin hipotecarlos a mediano y largo plazos.
Fuente:
Asset Management PAS 55 para una gestión optimizada de los activos certificada
Sojo, Luis. The Woodhouse Partnership Ltd, England
5
La especificación PAS 55 fue desarrollada por el Institute of Asset Management –AMI- en colaboracióncon el British Standards Institute –BSI- y un grannúmero de organizaciones y personas.
ORIGEN DE LA PAS 55
Está dividida en dos partes, así:
� Part 1 – Specification for the optimized management of physical infrastructure assets
� Part 2 – Guidelines for the application of Part 1
6
DEFINICION DE LA GESTIÓN DE ACTIVOS
“Actividades y prácticas coordinadas y sistemáticas a través de las cuales una organización maneja óptima y sostenible sus activos, su desempeño, riesgos y gastos
PAS 55
ACTIVOS: Planta, maquinaria, propiedades, edificios, vehículos y otros ítems dede valor importante para una organización empresarial
7
sostenible sus activos, su desempeño, riesgos y gastos asociados a lo largo de sus ciclos de vida con el propósito de lograr su plan estratégico organizacional”.
ACTIVOS DE INFORMACION
NEGOCIO
Condición, desempeño, actividades, costos, oportunidades
Contexto Vital: Objetivos, políticas, regulación, requerimientos de desempeño, gestión de riesgos
8
ACTIVOS ACTIVOS FISICOS
ACTIVOS FINANCIEROS
RECURSOS HUMANOS
ACTIVOS INTANGIBLES
Ciclos de vida, criterios de inversión, costos de capital, valor de activos.
oportunidadesMotivación, comunicación, responsabilidades, conocimiento, experiencia
Reputación, imagen, restricciones, impacto social
� Cualquier negocio intensivo en activos que tenga gastos importantes, recursos y dependencia del desempeño y los riesgos asociados con el ciclo de vida de los activos.
ALCANCE DE LA GESTION DE ACTIVOS
PAS 55
� Cualquier organización que tenga la intención de invertir en un portafolio importante de activos o su desempeño es vital para la entrega del servicio o producto u otros objetivos del negocio.
� Organizaciones con el requerimiento de responsabilidad pública y que deba demostrar la mejor gestión para el suministro de servicios (p.e.salud, educación, etc.).
9
- Uso y cuidado de los activos- Desempeño a corto y largo plazo- Inversiones de Capital- Costos Operacionales- Riesgos
ALCANCE DE LA GESTIÓN DE ACTIVOS
VIDA UTIL
PAS 55
10
DIMENSIONESDE LA GESTION DE ACTIVOS
- Holística- Sistemática- Sistémica- Basada en el riesgo- Óptima- Sostenible- Integrada
- Estructura organizacional que facilite su implementación con adecuada dirección y liderazgo.
- Conciencia, competencias y Actividades
PAS 55
- Conciencia, competencias y compromiso del personal .
- Información y conocimientos adecuados del aseguramiento de la condición, desempeño, riesgos y costos de los activos y su interrelación.
11
Actividades de los Elementos Habilitadores
Crear/adquirir
ACTIVIDADES DEL CICLO DE VIDA DE LOS ACTIVOS
Renovar/disponerMantenerUtilizar
PAS 55
12
OPTIMIZACION DEL CICLO DE VIDA DE LOS ACTIVOS
SISTEMAS DE GESTION DE ACTIVOS
Actividades de la Gestión del Activo Transformador
ACTIVIDADES
REMPLAZO/ DISPOSICION FINALVIDA UTIL
DEFINICIONES Y ESPECIFICACIONES
FABRICACION Y PRUEBAS
TRANSPORTE, MONTAJE Y PUESTA EN SERVICIO
MONITOREO, ASEGURAMIENTO DE CONDICION, MANTENIMIENTO
Y USO DE VIDA UTIL
FINAL
13
VIDA UTIL
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
¿Para qué son las especificaciones?
Desde el punto de vista del Cliente : para comunicar formal y claramente lo que desea que el fabricante le entr egue.
Desde el punto de vista del fabricante : para ser capaz de ofrecer servicios y productos que entreguen una sol ución satisfactoria (técnica/comercial) al Cliente que le permita mantener la rentabilidad de su negocio.
Desde ambos lados : evitar malentendidos que pueden resultar costosos.
14
Las especificaciones son el campo de entendimiento entre el Cliente y el fabricante
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
Entorno operativo
Tipo de transformador y aplicación, niveles de tensión, con o sin aceite, siliconados o encapsulados (SF6), lugar donde va a ser usado (al aire libre o confinado), temperatura ambiente, sismicidad, condiciones de servicio, altitud sobre el nivel del mar, proyecciones de demanda, ceraunicidad, etc.ceraunicidad, etc.
15
IEEE Std C57.12.80 IEEE Standard Terminology for Power and Distribution Transformers
IEC 60076-1 Power transformers –Part 1:General
IEEE Std C57.12.00 IEEE Standard for Standard General Requirements for Liquid-ImmersedDistribution, Power, and Regulating Transformers
IEEE Std C57.12.01, IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers, Including Those with Solid-Cast and/or Resin Encapsulated Windings
DIN VDE 0532, DIN 42 500-523-524
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
� Guías para especificaciones
Nuestra experiencia y conocimiento.
Información y consultas a los fabricantes.
Estándares Internacionales (IEEE, ANSI, BSI, VDE, DIN EN, ISO, NEC, NEMA, ASTM, NFPA y otras normas dependiendo del país de origen y destino con las respectivas equivalencias).
� Otras fuentes de ayuda
CIGRE Working Group 12.15., “Guide for Customers Specifications for Transformers 100MVA and 123kV and above”, Technical Brochure 156, April 2000
ABB, “Transformer Handbook”, ABB Power Technologies Management Ltd, 2010.
16
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
� Evaluación de ofertas
La evaluación de las ofertas deberá incluir todos los aspectos de cumplimiento de la normatividad solicitada. Para la valoración de las diferencias de eficiencias deberá tenerse en cuenta la norma:
IEEE Std C57.120 IEEE Loss Evaluation Guide for Power Transformersand Reactors
� Aspectos a tener en cuenta:
Variación de precios de la energía en el tiempo, tasas de interés paraevaluación, ciclos de carga en el tiempo del transformador.
Presencia de armónicos, costos de mantenimiento, instalaciones, niveles de polución, etc.
17
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
Pruebas en fábrica
Objetivo: verificar, asegurar y documentar que el t ransformador cumplió con los requerimientos de las especificaciones
IEEE Std C57.12.00 IEEE Std C57.12.00 IEEE Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers
ANSI/IEEE C57.12.90 IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers
IEC 60076 Power transformers - Part 1: General
18
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
Pruebas en fábrica
� Pruebas de calentamiento : IEC 60076 Power transformers - Part 2: Temperature rise.
� Pruebas de impulso : IEC 60076 Part 4: Guide to the lightning impulse and � Pruebas de impulso : IEC 60076 Part 4: Guide to the lightning impulse and switching impulse testing - Power transformers and reactors.ANSI/IEEE Std C57.98 Guide forTransformer Impulse Test
Pruebas dieléctricas : IEC 60076 Power transformers - Part 3: Insulation levels, dielectric tests and external clearances in air
� Pruebas de pédidas : IEEE C57.123 IEEE Guide for Transformer Loss Measurement
� Otras pruebas en fábrica : ANSI/IEEE C57.12.90 IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers
19
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
Pruebas en fábrica
Medida de la relación de voltaje y chequeo de la po laridad y el grupo de conexión (measurement of voltage ratio and check of grupo de conexión (measurement of voltage ratio and check of polarity and vector group)
� Resistencia y Factor de potencia del aislamiento
� Medida de la resistencia de los devanados y núcleo (measurementof winding/core resistance)
20
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
Pruebas en fábrica
� Dieléctricas: Prueba de impulso de onda recortada o completa, alta tensión (hi-pot), descargas parciales, voltaje inducido, suicheo, etc.
� Medida de las pérdidas sin carga y corriente de exc itación (measurement of no-load losses and no-load current losses)(measurement of no-load losses and no-load current losses)
� La prueba de calentamiento a ventilación natural o elevación de temperatura (Heat-run test at natural cooling)
� Medida de las pérdidas con carga (measurement of load loss)� Medida del voltaje de la impedancia (measurement of impedance
voltage)� Secuencia cero y otros parámetros� Prueba de cortocircuito (short circuit test)
21
Actividades de la Gestión del Activo Transformador
DEFINICIONES Y ESPECIFICACIONES
Definición de protecciones eléctricas, mecánicas y seguridad física y del personal
� IEEE Std C37.91 IEEE Guide for Protecting Power Transformers� ANSI/IEEE Std-242 IEEE Recommended Practice for Protection and
Coordination of Industrial and Commercial Power Systems-BuffBookCoordination of Industrial and Commercial Power Systems-BuffBook� IEEE Std 142 IEEE Recommended Practice for Grounding of Industrial
and Commercial Power Systems- Green Book� IEEE Std C57.109 -IEEE guide for liquid-immersed transformer through-
fault-current duration� IEEE Std C57.131 IEEE Standard Requirements for Load Tap Changers� IEEE Std C57.19.01 IEEE Standard Performance Characteristics and
Dimensions for Outdoor Apparatus Bushings� NFPA 70 (NEC) y NFPA 70E (Standard for Electrical Safety in the
Workplace)� IEEE 979-1994. IEEE Guide for Substation Fire Protection. � NEMA Standards Publication 250, IEC/EN 60529 (tableros de control)
22
Actividades de la Gestión del Activo TransformadorNormas IEC Normas ANSI/IEEE
60076-1, 2000 Power Transformers Part 1, GeneralC57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code
60076-2, 1993 Power Transformers Part 2, Temperature RiseC57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code
60076-3, 2000Power Transformers Part 3, Insulation levels, dielectric tests and external clearances in air
C57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code
60076-4, 2002
Power transformers Part 4:Guide to the lightning impulse andswitching impulse testing –Power transformers and reactors C57.98-1993 Impulse Test Guide
60076-5, 2006Power transformers - Part 5: Ability to withstand short circuit
C57.12.00-2006 and C57.12.90-2006 General Requirements and Test Code
60076-6, 1997 ReactorsC57.16, C57.21, IEEE 1277, C57.32 Various
Power transformers - Part 7: Loading guide for oil-
23
Fuente:H. Jin Sim;TF Chairman IEEE/IEC Cross Reference - Transformers Committee Oct. 2008
60076-7, 2005Power transformers - Part 7: Loading guide for oil-immersed power transformers C57.91-1995 Loading Guide
60076-8, 1997 Power transformers - Part 8: Application guide C57.105-1978 Application Guide
60076-10, 2005Power transformers - Part 10: Determination of sound levels C57.12.90-2006 Test Code
60076-10-1, 2005Power transformers - Part 10-1: Determination of sound levels - Application guide
60076-13, 2006Power transformers - Part 13: Self-protected liquid-filled transformers
60076-14, 2004
Power transformers - Part 14: Design and application of liquid-immersed power transformers using high-temperature insulation materials IEEE Std 1276-1997
Guide for the Application of High-Temperature Insulation Materials in Liquid-Immersed Power Transformers
60214-1, 2003Tap-changers - Part 1: Performance requirements and test methods C57.131-1995 IEEE Standard Requirements for Load Tap Changers
60214-2, 2004 Tap-changers - Part 2: Application guide
60296, 2003Fluids for electrotechnical applications - Unused mineral insulating oils for transformers and switchgear C57.106-2006 Oil Guide
60616, 1978 Terminal and tapping markings for power transformers C57.12.70-2000IEEE Standard Terminal Markings and Connections for Distribution and Power Transformers
60599, 1999? Gas Guide C57.104-1991 Gas Guide60076-2, Annex D (CD now) Gas Guide during Factory Thermal Tests PC57.130 Gas Guide during Factory Thermal Tests
TRANSPORTE
Actividades de la Gestión del Activo Transformador
24
Fuente:Betancourt, E; Hernández, C. PowerTransformer Manufacturer´s Experience withTransportation Mishandling. WeidmannDiagnostic Solutions 7th AnnualConference. New Orleans, L.A. Sept. 15-17 2008
TRANSPORTE
Actividades de la Gestión del Activo Transformador
Referencias
ANSI/IEEE PC 57.150. Guide for the Transportation of Transformers and Reactors Rated 10.000 kVA and Larger.
T.Lundquist, E.Schweiger, M.Silvestre, W.Hoffman. Transportation
25
T.Lundquist, E.Schweiger, M.Silvestre, W.Hoffman. TransportationIssues of Power Transformers , IEEE TC Meeting, San Diego, CA, 2004.
Transformer Logistics Monitoring Key to Customer Satisfaction. http://www.masplantiz.com
Normas de transporte fluvial, aéreo y vial en cada país.
Regímenes aduaneros nacionales
Normas INCOTERMS (International Commercial Terms) - 2010
TRANSPORTE
Actividades de la Gestión del Activo Transformador
Proveedor Cliente
26
TRANSPORTE
Actividades de la Gestión del Activo Transformador
Durante el transporte si un transformador experimenta choques mecánicos, y más que los sugeridos niveles “g” los siguientes daños pueden ocurrir:
� Deformación/desplazamiento de los devanados/núcleo
27
� Deformación/desplazamiento de los devanados/núcleo
� Desgaste del aislamiento por fricción que causaráfallas en funcionamiento
� Vibraciones mecánicas que desajustan las sujecionesmecánicas que llevan a colapsar el devanado durantefallas eléctricas
� Compromiso de los espacios entre las partes activas y eltanque
.
TRANSPORTE
Actividades de la Gestión del Activo Transformador
Casos de impactos por tipo de transporte :
1. Durante los procesos de carga, descarga y amarre . De baja ocurrenciapero con alto potencial de impacto (fallas en mecanismos de alce, caída), Los eventos de choque estarán entre 2.5g y 10g en la banda de 2-20 Hz.
28
Los eventos de choque estarán entre 2.5g y 10g en la banda de 2-20 Hz.
2. A bordo del transporte terrestre . Impactos longitudinales (frenados) y verticales debido al esatdo de la carretera. La aceleración estará entre 1.0g y 1.0 g en la banda de 3-350 Hz.
3. A bordo un barco . Rodamiento, lanzamiento. Vibraciones de frecuencia bajas que repiten en períodos regulares. La aceleración es de 0.3 a 0.8 g en la banda de 2-30 Hz.
4. A bordo de un tren . Los transformadores están sujetos a impactos en el eje longitudinal por de cambio de carril y vertical debido a las uniones de los rieles. La aceleración de 0.5 a 1.0 g en la banda de 2-500 Hz pero durante maniobras de la aceleración de operación hasta 4.0g en la banda de 2-20 Hz.
TRANSPORTE
Actividades de la Gestión del Activo Transformador
PREPARACION PARA ENVIO PREPARACION PARA RECIBO
• Realizar prueba FRA • Verificar registradores de Impacto
Preparación para envío y recibo
29
• Desensamble del transformador • Prueba de contenido de humedad (Dew Point)
• Presurización del transformador (aire seco, nitrógeno)
• Inspección de daños físicos
• Instalación registradores de Impacto (A/D) • Medidas de aislamiento
• Empacar las partes para envío • Prueba de respuesta en frecuencia
Actividades para la Gestión del Activo Transformado r
ESTRATEGIAS DEL MANTENIMIENTO
RCMMantenimiento Basado en Confiablidad�Lista de prioridades
CBMMantenimiento basado en
condición
Con
side
rado
30
Con
dici
ón
TBMMantenimiento Basado en Tiempo
�Inspecciones y mantenimiento a intervalos de tiempo fijos
CMMantenimiento Correctivo
�No hay inspección ni mantenimiento hasta que el equipo falle
�Lista de prioridades�Conexión entre condición y efecto de la falla�Gestión de riesgos
condición�Monitoreo continuo u ocasional�Mantenimiento cuando sea necesarioC
onsi
dera
doN
o C
onsi
dera
do
Importancia
No Considerada Considerada
Actividades para la Gestión del Activo Transformado r
31
Monitoreo y Aseguramiento de Condición
Desarrollo de planes de mantenimiento
Envejecimiento, estado y final de vida útil
Actividades de la Gestión del Activo Transformador
Monitoreo de Condición y Aseguramiento de Condición
Tiene que ver con la aplicación y desarrollo de métodos y equipos que están involucrados en el monitoreo de una condición de un parámetro en un transformador. Se concentra más en la detección de fallas incipientes.
Puede ser dividido en seis categorías principales:
- Monitoreo de los puntos calientes. IEEE Std C57.134, C57.115, IEEE Std 1538- Monitoreo de la vibración de paredes y devanados. IEEE Std C57.131, CIGRE
SC 12 WG 12.05- Monitoreo de gases disueltos y furanos. IEEE Std C57.104, IEC 60599- Monitoreo de descargas parciales. IEEE Std C57.113- Monitoreo de movimiento y deformaciones de los dev anados . IEEE PC57.149
A Guide to Frequency Response Analysis in Oil-immersed Transformers- Niveles de ruido. IEEE Std C57.136
32
Actividades de la Gestión del Activo Transformador
Deformaciones y Niveles de Descargas Vibración de cuba Gases disueltos Monitoreo de
Parámetros de Monitoreo de Condición
33
Análisis térmico
Análisis de Vibraciones
Análisis de gases disueltos
Análisis de Descargas parciales
Análisis de respuesta en frecuencia (FRA)
Aseguramiento de Condición
Fuente: Abu-Elanien; Salama. Asset Management Techniques forTransformers. Electric Power Systems Research. 2010.
Ultrasonido
Deformaciones y movimiento de devanados
Niveles de ruido
Descargas parciales
Vibración de cuba y devanados
Gases disueltos en el aceite
Monitoreo de puntos calientes
Actividades de la Gestión del Activo Transformador
34Importancia de los métodos de diagnóstico
Fuente:Zhang, X; Gockenbach, EAsset-Management of TransformersBased on Condition Monitoring andStandard DiagnosisIEEE Electrical Insulation Magazine July/August 2008 — Vol. 24, No.4
Actividades de la Gestión del Activo Transformador
Técnicas más usadas en el análisis de gases disueltos
� Triángulo de Duval� IEEE C57.104, Limites, tasas y TDCG� Método de los gases claves
35
� Método de los gases claves� Razones de Dörnenburg� Razones de Roger� IEC 60599 Razones y Límites� Análisis de tendencias� Huella digital (Fingerprints)� Análisis por sistemas expertos� DGA Bujes (IEC 61464)
Discusión de los distintos métodos:N.A. Muhamad, B.T. Phung, T.R. Blackburn, K.X Lai. Comparative Study and Analysis of DGA Methods for Transformer Mineral Oil . PowerTech 2007
Actividades de la Gestión del Activo Transformador
COMPONENTEMÉTODO DE
DIAGNÓSTICOEN LÍNEA
FUERA DE LÍNEA
LABORATORIO OBSERVACIONES
Envejecimiento aceite X Rutinaria
DGA X Rutinaria
Medida de resistencia XDespués de
indicación (DGA)
XDespués de
Estrategia de diagnóstico
36
Partes activas
Medida Impedancia XDespués de
indicación (DGA)
Descargas Parciales XDespués de Cortocircuito
FRA XDespués de Cortocircuito
Análisis furanos XAseguramiento
condiciónGrado de
PolimerizaciónX
Aseguramiento condición
Bujes
Tang δ/ Capacitancia X Rutinaria
DGA XAseguramiento
condición
Descargas Parciales XAseguramiento
condición
Cambiador de tomasInspección suiche X Rutinaria
Medida torque XAseguramiento
condición
Asset managementtechniques. Schneider, J. y otros. International Journal of ElectricalPower & EnergySystems, Volume28, Issue 9, November 2006.
ENSAYOS BÁSICOS
• Rigidez dieléctrica ASTM D 1816• Tensión interfacial ASTM D 2285• Número de neutralización (acidez orgánica) ASTM D 974• Contenido de inhibidor de oxidación (para aceites inhibidos) IEC 60666• Contaminación con agua ASTM D 1533
Existe gran número de ensayos para los aceites dieléctricos pero con los siguientes se considera suficiente para determinar su estado y comportamiento futuro:
37
• Contaminación con agua ASTM D 1533• Gases disueltos IEC 60567 / 60599
ENSAYOS COMPLEMENTARIOS
• Color, aspecto ASTM D 1500 / VDE 0370• Sustancias polares ASTM D 1902• Punto de inflamación ASTM D 3• Punto de escurrimiento ASTM D 97• Lodos IEC 60422• Densidad ASTM D 1298• Viscosidad. ASTM D 445• Tangente delta, factor de disipación dieléctrica ASTM D 927• Contaminantes sólidos ISO 4406• Residuo carbonoso ASTM D 189• Cenizas ASTM D 482
Fuente: Lantos, E. Mantenimiento Proactivo en transformadores. Reliability World 2006-Sudamérica
EXTENSIÓN DE LA VIDA ÚTIL
Métodos de extensión de la vida útil:
� Tratamiento/cambio del aceite� Remplazo de los bujes� Cambio de los contactos del cambiador de tomas� Secado de partes activas� Reparación después de falla
38
Los procedimientos de reparación en sitio requieren de una inspección exacta, identificando la falla y que sea accesible y mediante métodos ya probados y riesgos calculados; de lo contrario es mejor llevar a la fábrica o al proveedor del servicio.
IEEE Std. C57.140 IEEE Guide for the Evaluation and Reconditioning of Liquid Immersed Power Transformers.ANSI/IEEE C57-125 IEEE Guide for Failure Investigation Documentation and Analysis for PowerTransformers and Shunt ReactorsAn Analysis of Transformer Failures, Part 1-2 — Caus es, Prevention and Maximum Service Life By William H. Bartley, P.E. Hartford Steam Boiler CIGRE-WG 12-05: An international survey on failures in large power transformers in service , Electra No.88 1983
FINAL DE LA VIDA ÚTIL
Un transformador llega al final de su vida útil por dos razones básicas:
� Decisión de reemplazo � Falla definitiva� Falla catastrófica (incendio)
39
GESTIÓN DE RESIDUOS PELIGROSOS
� Manejo y disposición final de PCB´s (C12H10-nCln, n>2) (ANSI/IEEE 799 -IEEE Guide for Handling and Disposal of Transformer Grade Insulating Liquids Containing PCBs
� Disposición de residuos de los mantenimientos� Disposición final de transformadores remplazados� Disposición final de transformadores fallados� Reciclaje